Loading...
HomeMy WebLinkAboutFS PLANS - 23-00277 - BYUI Romney - RemodelWhen a system modification affects more than 20 sprinklers, the new portion should be isolated and tested at not less than 200 psi for 2 hours. (NFPA 13, 29.7.1.1) When backflow prevention devices are installed on existing systems, hydraulic analysis shall be completed. (NFPA 13, 29.1.3) No RED on plans Leave room in the bottom right corner for stamp. IDAHO STATE FIRE MARSHAL'S OFFICE FIRE SPRINKLER PLAN REVIEW ACCEPTED 09/12/2023WITH COMMEN T S IDAHO STATE FIRE MARSHAL'S OFFICE FIRE SPRINKLER PLAN REVIEW ACCEPTED 09/12/2023WITH COMMEN T S