HomeMy WebLinkAboutFS PLANS - 23-00277 - BYUI Romney - RemodelWhen a system modification affects more than 20 sprinklers,
the new portion should be isolated and tested at not less than
200 psi for 2 hours. (NFPA 13, 29.7.1.1)
When backflow prevention devices are installed on existing
systems, hydraulic analysis shall be completed. (NFPA 13,
29.1.3)
No RED on plans
Leave room in the bottom right corner for stamp.
IDAHO STATE FIRE MARSHAL'S OFFICE
FIRE SPRINKLER PLAN REVIEW
ACCEPTED