PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS
PLANS RECEIVED: August 30, 2023 APPROVED: September 12,
2023
REVIEWED BY: Rory Winch, Fire Plans Examiner
PROJECT: BYU-I Romney Building TI
STREET ADDRESS: 525 S Center CITY: Rexburg
AHJ: Madison Fire Department
SPRINKLER CONTRACTOR: 3-D Fire Protection
6312 S. Burgraff Way
Idaho Falls, ID 83401
IDAHO LICENSE: FPSC-008
CONTACT NAME: Jason Blatter
jason.blatter@3dfire.us
PHONE NO: (208) 881-5439
SYSTEM DESIGNED BY: Jason Blatter
jason.blatter@3dfire.us
PHONE NO: (208) 881-5439
TYPE OF SYSTEM: NFPA 13/Wet HEAD COUNT: 103
TOTAL SYSTEMS: 1 OCCUPANCY CLASSIFICATION: Office
CONSTRUCTION TYPE: AREA SQUARE FOOTAGE:
SCOPE OF WORK: RELOCATE FIRE SPRINKLERS TO ACCOMMODATE A NEW CEILING
LAYOUT. EXISTING FIRE SPRINKLER SYSTEM IS HYDRAULICALLY
DESIGNED TO PROTECT A HAZARD CLASSIFICATION. NO CHANGES
TO HAZARD CLASSIFICATION WILL OCCUR AS PART OF THIS TENANT
IMPROVEMENT. EXISTING FIRE SPRINKLER RISERS, MAINS AND BRANCH LINES WILL
REMAIN AND WILL BE USED TO SUPPLY RELOCATED FIRE SPRINKLERS. EXISTING FIRE
SYSTEM HAS ALREADY BEEN HYDRAULICALLY PROVEN TO PROTECT THE HAZARD
CLASSIFICATION PRESENT.
PLAN REVIEW COMMENTS: Approved with comments
1. When a system modification affects more than 20 sprinklers, the new portion should be
isolated and tested at not less than 200 psi for 2 hours. (NFPA 13, 29.7.1.1)
2. When backflow prevention devices are installed on existing systems, hydraulic analysis
shall be completed. (NFPA 13, 29.1.3)
3. No RED on plans
4. Leave room in the bottom right corner for stamp.
Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or
Rules, International Fire Code, NFPA Standards or any other applicable criteria.
It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s
Office and its personnel does not take any responsibility for the back flow device.