Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 23-00277
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
G000 Stamp Cody Jones : Building Open 1 Approved - Building Inspector
G002 Free Text Cody Jones : Building Open 3 D
G002 Note Cody Jones : Building Open 3 Exit Lighting and Exit Signs comply with IBC 1008 & 1013
G000 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector
EG0.0 Stamp Alex Owens : Electrical Open 74 Approved - Electrical Inspector
EG0.0 Free Text Alex Owens : Electrical Open 74 All electrical work to comply with 2017 NEC
Commercial - Remodel
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
b y u i d a h o p r o j e c t # : 002294
4/28/2023
G000
COVER
SHEET
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
Romney 2023 Remodel
Bid Set - 04/28/2023
owner
company
address 1
salt lake city, ut 84101
(801) 000-0000
contact:
architect
method studio
360 w aspen ave
salt lake city, ut 84101
(801) 532-4422
contact:
civil
company
address 1
salt lake city, ut 84101
(801) 000-0000
contact:
structural
company
address 1
salt lake city, ut 84101
(801) 000-0000
contact:
mechanical
company
address 1
salt lake city, ut 84101
(801) 000-0000
contact:
electrical
company
address 1
salt lake city, ut 84101
(801) 000-0000
contact:
MATERIAL LEGEND
EARTH (EXISTING)
EARTH (BACKFILL)
DRAINAGE FILL
COMPACTED FILL
CONCRETE
CAST-IN-PLACE
CONCRETE
PRECAST
BRICK
CONCRETE MASONRY
UNIT
GROUT
STEEL
ALUMINUM
CONTINUOUS WOOD
SHEATHING
INTERMITTENT WOOD
BLOCKING
WOOD FINISH
HARDBOARD
PARTICLE BOARD
BATT INSULATION
LOOSE FILL INSULATION
RIGID INSULATION
FIRE SPRAY
GYPSUM BOARD
ARCHITECTURE SYMBOLS
A102
SHEET TYPE
DISCIPLINE
SHEET NUMBER SEQUENCE
?
XX
000x
F1
R1
101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF
THE ARCHITECTURAL WOODWORK STANDARDS
(AWS) FOR A FULL DESCRIPTION OF CASEWORK
TYPES
100' - 0"
MAIN LEVEL
LEVEL NAME
LEVEL ELEVATION
AE000
1 Ref
1
Re
f
1 Ref
1
Re
f
AE000
1 Ref
1
Re
f
1 Ref
1
Re
f
SHEET NUMBER
POSITION ON SHEET
SHEET NUMBER
POSITION ON SHEET
DRAWING NUMBER
VIEW NAME
DRAWING SCALE
ORIGINAL SOURCE OF DETAIL
SIMA1
A526.a
SIMA1
A526.a
POSITION ON SHEET
SHEET NUMBER
SHEET NUMBER
VIEW DIRECTION
POSITION ON SHEET
A1
AE101
SIM
A1
AE101
SIM
A1
AE101
SIM
VIEW DIRECTION
POSITION ON SHEET
SHEET NUMBER
ROOM NUMBER
ROOM AREA
01A
SIGN TYPE
SIGN NUMBER
VIEW DIRECTION
POSITION ON SHEET
SHEET NUMBER
1 DELTA MARKER
10' - 0"
HEIGHT OF ELEMENT
C1 10' - 0"
CEILING TYPE
CEILING HEIGHT
1 2
A
B
A1 STARTS AT UPPER LEFT CORNER;
NUMBERS ARE VERTICAL GRIDS AND LETTERS
ARE HORIZONTAL GRIDS (EXCLUDES LETTERS "I"
AND "O")
Room name
101
F
B
W
F
CP
T
-
0
1
?
ROOM NAME
ROOM NUMBER
WALL FINISH
BASE FINISH
FLOOR FINISH
WALL,BASE, OR FLOOR
MATERIAL FINISH CODE
ARROWS REPRESENT EXTENT OF SCOPE
REFER TO FINISH LEGEND
WC-01
00.00
ROOM NAME
101
150 SF
KEYNOTE TAG
CURTAIN WALL TAG
DOOR TAG
FLOOR TAG
ROOF TAG
WALL TAGS
REVISION CLOUD
A1 VIEW NAME
1/8" = 1'-0" (REF: A1/A101)
CORE MATERIAL (SEE LEGEND)
LAYERS (SEE LEGEND)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
1 SA6 a
SA6 a SEE WALL TYPE SHEET(S) FOR LEGEND
ADD ALTERNATE LIST
1. ROLLER WINDOW SHADES IN BIO-CHEMISTRY LAB 272.
2. SNORKELS IN BIO-CHEMISTRY LAB 272, INCLUDING DUCTS TO SNORKELS
3. CONDUIT AND WIRING TO ROOF FROM THE PHYSICS LAB 52 TO AN ANTENNA INSTALLED ON THE ROOF.
4. ACOUSTIC FOAM ON THE WALLS AND CEILING OF THE ACOUSTICS LAB 52B.
5. ALL DEIONIZED WATER SPOUTS/FAUCETS, INCLUDING PIPING TO SPOUTS/FAUCETS.
6. LIGHT FIXTURE RAIL AND ACCORDION ARM IN PHOTO STUDIO 51.
7. ADDITIONAL HAIR LIGHT IN PHOTO STUDIO 51.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
b y u i d a h o p r o j e c t # : 002294
4/28/2023
G001
INDEX,
GENERAL
NOTES,
LEGENDS
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
ABBREVIATION SCHEDULE
Abbrev.Description
0
# NUMBER OR POUND
& AND
2:1 SL 2 HORIZONTAL TO 1 VERTICAL SLOPE
@ AT
[ CHANNEL
± PLUS MINUS
≤ LESS THAN OR EQUAL TO
≥ GREATER THAN OR EQUAL TO
A
AB ANCHOR BOLT
AC APSHALTIC CONCRETE
ACST ACOUSTIC
AD AREA DRAIN
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ALUM ALUMINUM
ARCH ARCHITECTURAL, ARCHITECT, ARCHITECTURE
ASPH ASPHALT
B
B BASELINE
B BOTTOM
BEJ BRICK EXPANSION JOINT
BLDG BUILDING
BLK BLOCK
BM BEAM
BO BOARD
BRG BEARING
BSMT BASEMENT
C
C&G CURB & GUTTER
CAP CAPACITY
CEM CEMENT
CFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED
CG CORNER GUARD
CIP CAST IN PLACE, CAST IRON PIPE
CIR CIRCULATING
CJ CONTROL JOINT
CL CENTERLINE
CL CENTERLINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNITS
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CPT CARPET
CSK COUNTERSUNK
CT CERAMIC TILE
CTR CENTER
D
D DEPTH
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DS DOWNSPOUT
DWG DRAWING
E
E EAST
E/P EDGE OF PAVEMENT
EA EACH
EL ELEVATION
ELECT ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXP EXPANSION
EXP JT EXPANSION JOINT
EXT EXTERIOR
F
F.V. FIELD VERIFY
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FFE FINISHED FLOOR ELEVATION
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIN FINISH
FLR FLOOR
FR FRAME
FTG FOOTING
FXTR FIXTURE
G
G GROUND
GA GA
GALV GALVANIZED
GL GLASS
GR GRADE
GRD GROUND
GWB GYPSUM WALL BOARD
H
HB HOSE BIBB
HC HANDICAPPED
HDW HARDWARE
HGT HEIGHT
HORZ HORIZONTAL
HR HOUR
GENERAL NOTES - MISCELLANEOUS
1 THE PROJECT MANUAL, UNDER SEPARATE COVER, IS AN INTEGRAL PART OF THESE CONSTRUCTION DRAWINGS.
2 PLANS, SECTIONS, ELEVATIONS, DETAILS AND DIMENSIONS LABELED "TYPICAL" SHALL APPLY TO ALL SITUATIONS
OCCURRING THAT ARE THE SAME OR SIMILAR TO THOSE SPECIFICALLY KEYED ON THE DRAWINGS.
3 ALL WORK, MATERIALS, AND METHODS SHALL BE IN CONFORMANCE WITH THE CODES, ORDINANCES AND REGULATIONS
OF ALL GOVERNMENTAL AGENCIES HAVING JURISDICTION AT THE PROJECT LOCATION.
4 UNLESS OTHERWISE INDICATED IN THE CONSTRUCTION DOCUMENTS AS BEING NOT IN CONTRACT (N.I.C.) OR EXISTING,
ALL ITEMS, MATERIALS AND INSTALLATION OF SAME ARE PART OF THE CONTRACT AS DEFINED BY THE CONSTRUCTION
DOCUMENTS. THE CONTRACTOR SHALL PROVIDE AND INSTALL ALL ACCESSORIES, COMPONENTS AND ASSEMBLIES
REQUIRED FOR THE WORK DEPICTED OR SPECIFIED.
5 CONTRACTORS ARE RESPONSIBLE FOR ALL WORK REGARDLESS OF THE LOCATION OF THE INFORMATION ON THE
DOCUMENTS.
6 KEEP SITE CLEAN AND CLEAR OF DEBRIS AND IN ORDERLY CONDITION THAT DOES NOT DETRACT FROM THE
SURROUNDING SITE AND REPAIR ANY DAMAGE CAUSED BY WORK OF THE CONTRACT.
7 ALL DIMENSIONS ARE TO THE FACE OF METAL OR WOOD STUD FRAMED WALLS AND TO THE FACE OF CONCRETE AND
MASONRY WALLS AS SHOWN, UNLESS NOTED OTHERWISE.
8 INSTALL SEALANT AT EXTERIOR SIDE OF ALL JOINTS, SEAMS, CONNECTIONS OR OPENINGS WHICH WOULD ALLOW
WATER OR AIR INFILTRATION EXCEPT AS NOTED OTHERWISE. SEALANT COLOR TO MATCH ADJACENT SURFACE. COLOR
REQUIRES ARCHITECTS APPROVAL.
9 DOOR OPENINGS IN FRAME CONSTRUCTION WHICH ARE NOT DIMENSIONED ARE EITHER CENTERED IN THE WALL, FACE
OF JAMB OR LOCATED 4" FROM THE FACE OF STUD TO THE FINISHED JAMB.
10 ALL SPECIAL ACCESSIBLE FACILITIES SHALL BE IDENTIFIED WITH APPROVED SIGNAGE.
11 THE CONTRACTOR IS RESPONSIBLE FOR PRODUCING A WEATHER TIGHT BUILDING, DETAILS AND OMISSIONS TO
DRAWINGS NOTWITHSTANDING. ALL DRAWING CONFLICTS WHICH MAY NOT ALLOW A WEATHERTIGHT CONDITION SHALL
BE BROUGHT TO THE ATTENTION OF THE ARCHITECT.
12 DISCREPANCIES BETWEEN ACTUAL CONDITIONS AND PLANS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT.
CONTRACTOR SHALL SUBMIT SPECIFIC DISCREPANCIES FOR ARCHITECT REVIEW.
13 PROVIDE FULL METAL BACKING PLATE (16 GAUGE X 6" HIGH SECURED TO 3 STUDS MIN.) OR WOOD BLOCKING AS
REQUIRED TO SECURELY ANCHOR ALL WALL MOUNTED EQUIPMENT (CABINETS, TOILET ROOM ACCESSORIES,
HARDWARE, ETC.). BLOCKING SHALL PROVIDE A RIGID CONNECTION CAPABLE OF SUPPORTING DESIGN LOADS. PROVIDE
A 16 GAUGE X 6" STL. STUD/TRACK SECURED TO 2 STUDS TO SECURELY SUPPORT ALL WALL STOPS (DOOR BUMPER).
14 COORDINATE WITH ALL TRADES, SIZES AND LOCATIONS OF ALL OPENINGS FOR MECHANICAL, PLUMBING, AND
ELECTRICAL EQUIPMENT, EQUIPMENT PADS OR BASES, AS WELL AS ELECTRIC POWER, WATER, AND DRAIN
INSTALLATIONS, BEFORE PROCEEDING WITH WORK. CONTRACTOR SHALL PROVIDE COORDINATION DRAWINGS FOR
PROPER PLACEMENT OF ALL TRADES' WORK. ANY CONCERNS, SPACE LIMITATIONS, OR STRUCTURAL CONFLICTS, SHALL
BE BROUGHT TO THE ATTENTION OF THE ARCHITECT. A REASONABLE RESPONSE TIME SHALL BE ALLOWED AS NOTED IN
THE SPECIFICATIONS.
15 ALL FLOOR OR WALL OPENINGS REQUIRED FOR PIPES, DUCTS, CONDUITS,ETC. SHALL BE SEALED IN AN APPROVED
MANNER.
16 FIRE SPRINKLER DESIGN TO BE DONE BY A CERTIFIED SUB-CONTRACTOR AND WILL REQUIRE APPROVALS BY THE CITY,
AND STATE FIRE MARSHALS. APPROVALS BY THE FIRE MARSHAL ARE TO BE OBTAINED BY THE CONTRACTOR PRIOR TO
SUBMITTAL TO ARCHITECT. SUBMITTAL TO THE ARCHITECT ALSO INDICATES THAT THE CONTRACTOR HAS REVIEWED AND
COORDINATED FIRE-SPRINKLER PIPING LOCATIONS WITH ALL TRADES.
17 ROOMS ENCLOSED WITH RATED WALLS REQUIRE RATED DOORS. ANY DUCTS PASSING THROUGH WALLS REQUIRE FIRE
DAMPERS AND OR FIRE/SMOKE DAMPERS. ANY CONDUIT OR PIPING REQUIRES RATED SEALANT AT JOINTS.
18 GENERAL STRUCTURAL NOTES GOVERN TYPICAL CONDITIONS WHETHER OR NOT SPECIFICALLY DETAILED OR NOTED.
19 IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE AND LOCATE ELECTRICAL, DATA, AND PHONE RECEPTACLES,
SWITCHES, ETC. TO AVOID CASEWORK, DOORS, ETC.
20 THE DRAWINGS AND SPECIFICATIONS INDICATE THE GENERAL SCOPE OF THE PROJECT IN TERMS OF THE
ARCHITECTURAL AND STRUCTURAL DESIGN CONCEPT. THE DI MENSIONS OF THE BUILDING, THE TYPE OF STRUCTURAL,
MECHANICAL, ELECTRICAL, AND UTILITY SYSTEMS AND MAJOR ARCHITECTURAL ELEMENTS OF CONSTRUCTION AS
"SCOPE" DOCUMENTS.
21 THE DRAWINGS AND SPECIFICATIONS DO NOT NECESSARIL Y INDICATE OR DESCRIBE ALL WORK REQUIRED FOR THE FULL
PERFORMANCE AND COMPLETION OF THE WORK. CONTRACTS SHALL BE LET ON THE BASIS OF SUCH DOCUMENTS, WITH
THE UNDERSTANDING THAT THE CONTRACTOR IS TO FURNISH ALL ITEMS REQUIRED FOR PROPER COMPLETION OF THE
WORK WITHOUT ADJUSTMENT TO CONTRACT PRICE. IT IS INTENDED THAT THE WORK TO BE OF SOUND AND QUALITY
CONSTRUCTION AND THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE INCLUSION OF ADEQUATE AMOUNTS
TO COVER INSTALLATION OF ALL ITEMS INDICATED, DESCRIBED, OR REASONABLY IMPLIED.
DRAWING INDEX
GENERAL
G000 COVER SHEET
G001 INDEX, GENERAL NOTES, LEGENDS
G002 CODE ANALYSIS
G003 CODE ANALYSIS & PLANS - LEVEL 00
G004 CODE ANALYSIS & PLANS - LEVEL 01
G005 CODE ANALYSIS & PLANS - LEVEL 02
G011 ADA GUIDELINES
G015 CODE REQUIRED SIGNAGE & DETAILS
ARCHITECTURAL DEMOLITION
D100 LEVEL 00 DEMO PLAN
D101 LEVEL 01 DEMO PLAN
D102 LEVEL 02 DEMO PLAN
D130 LEVEL 00 DEMO RCP PLAN
D131 LEVEL 01 DEMO RCP PLAN
D132 LEVEL 02 DEMO RCP PLAN
ARCHITECTURAL
A100 LEVEL 00 FLOOR PLAN
A101 LEVEL 01 FLOOR PLAN
A102 LEVEL 02 FLOOR PLAN
A120 LEVEL 00 DIMENSION PLAN
A121 LEVEL 01 DIMENSION PLAN
A122 LEVEL 02 DIMENSION PLAN
A130 LEVEL 00 RCP PLAN
A131 LEVEL 01 RCP PLAN
A132 LEVEL 02 RCP PLAN
A411A ENLARGED PLANS AND INTERIOR ELEVATIONS
A411B INTERIOR ELEVATIONS
A412 ENLARGED PLANS AND INTERIOR ELEVATIONS
A413 ENLARGED PLANS AND INTERIOR ELEVATIONS
A414 INTERIOR ELEVATIONS
A415 RESTROOM ENLARGED PLANS AND INTERIOR ELEVATIONS
A501 WALL ASSEMBLIES - INTERIOR
A514 CEILING DETAILS
A571 INTERIOR DETAILS
A581 CASEWORK DETAILS
A601 DOOR & WINDOW TYPES AND SCHEDULE
A700 LEVEL 00 FINISH PLANS
A701 LEVEL 01 FINISH PLANS
A702 LEVEL 02 FINISH PLANS
A710 FINISH SCHEDULES, ACCESSORY SCHEDULES
A900 LEVEL 00 FURNITURE PLAN
A901 LEVEL 01 FURNITURE PLAN
A902 LEVEL 02 FURNITURE PLAN
A910 EQUIPMENT & FURNITURE PLANS & SCHEDULE
A911 EQUIPMENT & FURNITURE PLANS & SCHEDULES
ABBREVIATION SCHEDULE
Abbrev.Description
HW HOT WATER
I
ID INSIDE DIAMETER
IE INVERT ELEVATION
INSUL INSULATION
INT INTERIOR
INTX INTERSECTION
INV INVERT
J
JB JUNCTION BOX
JCT JUNCTION
JST JOIST
JT JOINT
L
L ANGLE
L LENGTH
LC LENGTH OF CURVE
LDC LEAD COVERED
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT LIGHT
M
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MET METAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MTD MOUNTED
MTG MOUNTING
MULL MULLION
MWP MEMBRANE WATERPROOFING
N
N NORTH
NA NOT APPLICABLE
NE NORTHEAST
NEC NATIONAL ELECTRIC CODE
NEUT NEUTRAL
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
NW NIORTHWEST
O
OA OUTSIDE AIR
OA OUTSIDE AIR
OC ON CENTER
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
OPP OPPOSITE
OVHD OVERHEAD
P
PI POINT IF INTERSECTION
PL PLATE
PLAS PLASTER
PLYWD PLYWOOD
PNL PANEL
PNT PAINT
PRELIM PRELIMINARY
PRESS PRESSURE
PRIM PRIMARY
PRTN PARTITION
PT POINT, POINT OF TANGENT
Q
QT QUARRY TILE
R
R RADIUS
RA RETURN AIR
RB RESILIENT VINYL BASE
RCP REINFORCED CONCRETE PIPE
RD ROOF DRAIN
RECP RECEPTACLE
REINF REINFORCEMENT
REQD REQUIRED
REV REVISION
RF ROOF
RFLCP REFLECTIVE CEILING PLAN
RM ROOM
RVT RESILIENT VINYL TILE
S
S SOUTH
SCH SCHEDULE
SD STORM DRAIN
SE SOUTHEAST
SECT SECTION
SHT SHEET
SIM SIMILIAR
SL SLOPE
SPEC SPECIFICATION
SQ SQUARE
STL STEEL
SUSP SUSPENDED
T
T TOP
T&B TOP AND BOTTOM
TEL TELEPHONE
TEMP TEMPORARY
TERM TERMINAL
THK THICK/THICKNESS
THRSLD THRESHOLD
TO TOP OF
TOS TOP OF STEEL, TOP OF SLAB
TOW TOP OF WALL
TYP TYPICAL
U
UNO UNLESS NOTED OTHERWISE
V
VCT VINYL COMPOSITION TILE
VENT VENTILIATING
VERT VERTICAL
VEST VESTIBULE
VWC VINYL WALL COVERING
W
W WIDTH, WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WIDTH
WT WEIGHT
WWF WELDED WIRE FABRIC
X
X TRANSFORMER
MECHANICAL
M-001 MECHANICAL SCHEDULES AND SYMBOL LEGEND
MD100 LEVEL 01 MECHANICAL DEMOLITION PLAN
MD102 LEVEL 02 MECHANICAL DEMOLITION PLAN
MD200 LEVEL 00 MECHANICAL PIPING DEMOLITION PLAN
MD202 LEVEL 02 MECHANCIAL PIPING DEMOLTION PLAN
MH100 LEVEL 00 MECHANICAL REMODEL PLAN
MH102 LEVEL 02 MECHANICAL REMODEL PLAN
MH501 MECHANICAL DETAILS
MH502 MECHANICAL DETAILS
MP200 LEVEL 00 MECHANICAL PIPING REMODEL PLAN
MP202 LEVEL 02 MECHANICAL PIPING REMODEL PLAN
MP501 MECHANICAL PIPING DETAILS
FIRE PROTECTION
FD100 LEVEL 00 FIRE PROTECTION DEMOLITION PLAN
FD101 LEVEL 01 FIRE PROTECTION DEMOLITION PLAN
FD102 LEVEL 02 FIRE PROTECTION DEMOLITION PLAN
FP100 LEVEL 00 FIRE PROTECTION REMODEL PLAN
FP101 LEVEL 01 FIRE PROTECTION REMODEL PLAN
FP102 LEVEL 02 FIRE PROTECTION REMODEL PLAN
ELECTRICAL
EG0.0 ELECTRICAL SYMBOLS & DETAILS
ED1.0 LEVEL 00 EXISTING POWER PLAN
ED1.1 LEVEL 00 EXISTING LIGHTING PLAN
ED1.2 LEVEL 01 EXISTING PLAN
ED2.2 LEVEL 02 EXISTING ELECTRICAL PLAN
EE1.0 LEVEL 00 LIGHTING PLAN
EE2.0 LEVEL 00 ELECTRICAL PLAN
EE2.1 LEVEL 01 ELECTRICAL PLAN
EE2.2 LEVEL 02 ELECTRICAL PLAN
EE3.0 PANEL SCHEDULES
STRUCTURAL
SE-001 GENERAL NOTES
SE-101 LEVEL 01 FRAMING PLAN
SE-102 ROOF FRAMING PLAN
SE-501 DETAILS
PLUMBING
P-001 PLUMBING SCHEDULES AND SYMBOL LEGEND
PD100 LEVLE 00 PLUMBING DEMOLITION PLAN
PD101 LEVLE 01 PLUMBING DEMOLITION PLAN
PD102 LEVLE 02 PLUMBING DEMOLITION PLAN
PD401 ENLARGED LEVEL 00 PLUMBING DEMOLITION PLAN
PD402 ENLARGED PLUMBING DEMOLITION PLANS
PL100 LEVEL 00 PLUMBING MODEL PLAN
PL101 LEVEL 01 PLUMBING REMODEL PLAN
PL102 LEVEL 02 PLUBMING REMODEL PLAN
PL401 ENLARGED LEVEL 00 PLUMBING REMODEL PLAN - WASTE & VENT
PL402 ENLARGED LEVEL 00 PLUMBING REMODEL PLAN - WATER & GAS
PL403 ENLARGED PLUMBING REMODEL PLANS
PL404 ENLARGED PLUMBING REMODEL PLANS
PL501 PLUMBING DETAILS
CODE ANALYSIS
APPLICABLE CODES
YEAR YEAR
INTERNATIONAL BUILDING CODE
INTERNATIONAL MECHANICAL CODE
INTERNATIONAL PLUMBING CODE
INTERNATIONAL FIRE CODE
INTERNATIONAL ENERGY
CONSERVATION CODE
NATIONAL ELECTRICAL CODE
UNIFORM CODE FOR
BUILDING CONSERVATION
ADA ACCESSIBILITY
GUIDELINES
A. OCCUPANCY AND GROUP:
CHANGE IN USE: YES
SPECIAL USE AND OCCUPANCY (e.g. HIGH RISE, COVERED MALL):
MIXED OCCUPANCY: YES
B. SEISMIC DESIGN CATEGORY:DESIGN WIND SPEED (mph):
C. TYPE OF CONSTRUCTION (CIRCLE ONE):
I
A
V
B
I
B
II
A
II
B
III
A
III
B
IV
HT
V
A
D. FIRE RESISTANCE RATING REQUIREMENTS FOR THE EXTERIOR WALLS BASED ON THE FIRE
SEPARATION DISTANCE (IN HOURS):
NORTH EAST SOUTH WEST
E. MIXED OCCUPANCIES: NON-SEPARATED USES:
F. SPRINKLERS:
REQUIRED: PROVIDED: TYPE OF SPRINKLER SYSTEM:
G. NUMBER OF STORIES: BUILDING HEIGHT:
H. ACTUAL AREA (Aa) PER FLOOR (SF, SEE AREA SCHEDULE):
I. TABULAR AREA (At):
J. AREA MODIFICATIONS:
K. FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS)
L. DESIGN OCCUPANT LOAD:
EXIT WIDTH REQUIRED (inches): EXIT WIDTH PROVIDED:
M. MINIMUM NUMBER OF REQUIRED PLUMBING FACILITIES:
(SEE "PLUMBING CODE CALCULATION" SCHEDULE & "PROVIDED PLUMBING FIXTURE
SCHEDULE")
FOOTNOTES:
1) IN CASE OF CONFLICT WITH THE U.S. DEPARTMENT OF JUSTICE FEDERAL REGISTERS PARTS I
THROUGH V - ADA GUIDELINES AND SPECIFIC REFERENCE TO THE INTERNATIONAL BUILDING
CODE ACCESSIBILITY CHAPTERS, THE MORE RESTRICTIVE REQUIREMENT SHALL GOVERN.
2) ADDITIONAL CODE INFORMATION SHALL BE PROVIDED AT THE DISCRETION OF THE BUILDING
OFFICIAL FOR COMPLEX BUILDINGS. INCLUDING, BUT NOT LIMITED TO:
a) HIGH RISE REQUIREMENTS
b) ATRIUMS
c) PERFORMANCE BASED CRITERIA
d) MEANS OF EGRESS ANALYSIS
e) FIRE ASSEMBLY LOCATOR SHEET
f) EXTERIOR AND INTERIOR ACCESSIBILITY ROUTE
g) FIRE STOPPING, INCLUDING TESTED DESIGN NUMBER
NO NO
a) Aa = At + (NS x If)
c) SUM OF THE RATIO CALCULATIONS FOR MIXED OCCUPANCIES:
ACTUAL AREA / ALLOWWABLE AREA ≤ 1
b)If = [F/P - 0.25 ] W/30
ELEMENT HOURS ASSEMBLY
LISTING
Primary Structural Frame
Bearing Walls -Exterior
Bearing Walls -Interior
Nonbearing Walls/Partitions -Interior
Nonbearing Walls/Partitions -Exterior
Floor construction and associated secondary members
Roof construction and associated secondary members
Exterior Doors & Windows
Shaft Enclosures
Fire Walls
Fire Partitions
Smoke Partitions
Fire Barriers
Yes Yes
262"
SINGLE OCCUPANCY ONE STORY
2018 2017
2009
2018
2018
2015
2018
C 112
Yes
(EXISTING)
3 57' - 6"
0.00 SF
9' - 0"
[ 0' / 0' - 0.25 ] 0' / 30
0 + ( 0 x
-
-
-
-
-
-
-
-
-
NONE
NONE
NONE
EXISTING
NONE
0.00 SF / 0.00 SF =
1310
(EXISTING - INCLUDING OBSERVATORY)
(ONLY A PORTION OF LEVLE 1 IS BEING REMODELED - APPROXIMATLEY 4,200 SF REMODEL)
UNCHANGED
(PLUS OBSERVATORY)
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
G002
CODE
ANALYSIS
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
OCCUPANT LOAD SCHEDULE - NEW
ROOM # ROOM NAME
OCCUPANCY USE AREA (SF)
LOAD
FACTOR OCCUPANT LOAD
LEVEL 00
0-H VESTIBULE NON-OCCUPIED - Restrooms/Corridors/Shafts 120 SF 0 0
50 CLASSROOM EDUCATIONAL (Classroom) 744 SF 20 NET 38
51 PHOTO STUDIO EDUCATIONAL (Shops, Vocational) 983 SF 50 NET 20
51A STORAGE MECHANICAL & STORAGE USE 141 SF 300 GROSS 1
51B CHANGING LOCKER ROOM 50 SF 50 GROSS 2
52 PHYSICS LAB EDUCATIONAL (Shops, Vocational) 946 SF 50 NET 19
52A OPTICS LAB EDUCATIONAL (Shops, Vocational) 118 SF 50 NET 3
52B ACOUSTICS STUDIO EDUCATIONAL (Shops, Vocational) 114 SF 50 NET 3
52C STORAGE MECHANICAL & STORAGE USE 163 SF 300 GROSS 1
55 OFFICE BUSINESS AREAS 120 SF 150 GROSS 1
57 OFFICE BUSINESS AREAS 120 SF 150 GROSS 1
59 COMPUTER LAB EDUCATIONAL (Classroom) 908 SF 20 NET 46
59A EQUIP / CHECK OUT EDUCATIONAL (Shops, Vocational)169 SF 50 NET 4
59B STORAGE MECHANICAL & STORAGE USE 121 SF 300 GROSS 1
59C VESTIBULE NON-OCCUPIED - Restrooms/Corridors/Shafts 26 SF 0 0
59D DARK ROOM EDUCATIONAL (Shops, Vocational) 286 SF 50 NET 6
59E FILM EDUCATIONAL (Shops, Vocational) 33 SF 50 NET 1
64 WOMEN'S RM NON-OCCUPIED - Restrooms/Corridors/Shafts 153 SF 0 0
66 MEN'S RM NON-OCCUPIED - Restrooms/Corridors/Shafts 155 SF 0 0
68 CUST RM MECHANICAL & STORAGE USE 47 SF 300 GROSS 1
O-A VESTIBULE NON-OCCUPIED - Restrooms/Corridors/Shafts 145 SF 0 0
O-C HALLWAY NON-OCCUPIED - Restrooms/Corridors/Shafts 1,169 SF 0 0
O-Q PIPE CHASE NON-OCCUPIED - Restrooms/Corridors/Shafts 47 SF 0 0
6,878 SF 148
LEVEL 01
132 WOMEN'S RM NON-OCCUPIED - Restrooms/Corridors/Shafts 131 SF 0 0
134 MEN'S RM NON-OCCUPIED - Restrooms/Corridors/Shafts 133 SF 0 0
136 UNISEX RM NON-OCCUPIED - Restrooms/Corridors/Shafts 47 SF 0 0
158 PHYSICAL GEOLOGY ROOM EDUCATIONAL (Shops, Vocational) 1,104 SF 50 NET 23
1,415 SF 23
LEVEL 02
220 WOMEN'S ROOM NON-OCCUPIED - Restrooms/Corridors/Shafts 132 SF 0 0
226 MEN'S ROOM NON-OCCUPIED - Restrooms/Corridors/Shafts 135 SF 0 0
272 BIO-CHEMISTRY LAB EDUCATIONAL (Shops, Vocational)1,553 SF 50 NET 32
1,819 SF 32
FULL BUILDING OCCUPANCY (FOR REFERENCE)
LEVEL OCC. CLEAR OPEN.
LEVEL 00 -168 OCC. 34"
LEVEL 01 -470 OCC. 94"
LEVEL 02 -672 OCC. 135"
ALL -1310 OCC. 263"
* OCCUPANCY INCLUDED IN THIS SCHEDULE REFLECT REVISED SPACES ONLY. EXISTING SPACES NIC TO REMAIN UNCHANGED
D
367.49 SF
Occ: 2
STORAGE
18
203.92 SF
Occ: 2
CUST OFFICE
16
93.46 SF
Occ: 1
CUSTODIAL LAUNDRY
RM
14
155.06 SF
Occ: 0
MEN'S RM
66
153.38 SF
Occ: 0
WOMEN'S RM
64
1,063.91 SF
Occ: 4
MECHANICAL ROOM
69
2,001.07 SF
Occ: 7
MECHANICAL RM
10
144.77 SF
Occ: 0
VESTIBULE
O-A
74.83 SF
Occ: 1
MECH RM
12
1,168.61 SF
Occ: 0
HALLWAY
O-C
39.98 SF
Occ: 1
STORAGE
63
95.91 SF
Occ: 0
STAIRWELL
O-B
47.38 SF
Occ: 0
ELEVATOR
O-D
33.51 SF
Occ: 1
MECH RM
67
47.38 SF
Occ: 1
CUST RM
68
56.50 SF
Occ: 0
STAIRWELL
0-F
95.45 SF
Occ: 1
STORAGE
20
56.19 SF
Occ: 0
ELEVATOR
0-K
123.30 SF
Occ: 0
ELEC VAULT
80
118.84 SF
Occ: 0
HALLWAY
0-N
COMPACT FILL
COMPACT FILL
COMPACT FILL
CRAWL SPACE
PIPE TUNNEL
PIPE TUNNEL
PI
P
E
T
U
N
N
E
L
CRAWL SPACE
PIPE TUNNEL
PIPE TUNNEL
PIPE TUNNEL
COMPACT FILL
EXTERIOR
MECHANICAL
ENCLOSURE
743.64 SF
Occ: 38
CLASSROOM
50
286.12 SF
Occ: 6
DARK ROOM
59D
907.94 SF
Occ: 46
COMPUTER LAB
59
982.93 SF
Occ: 20
PHOTO STUDIO
51
26.11 SF
Occ: 0
VESTIBULE
59C
120.23 SF
Occ: 1
OFFICE
57
168.63 SF
Occ: 4
EQUIP / CHECK OUT
59A
120.83 SF
Occ: 1
STORAGE
59B
120.23 SF
Occ: 1
OFFICE
55
33.38 SF
Occ: 1
FILM
59E
113.99 SF
Occ: 3
ACOUSTICS STUDIO
52B
140.75 SF
Occ: 1
STORAGE
51A
50.10 SF
Occ: 2
CHANGING
51B 120.02 SF
Occ: 0
VESTIBULE
0-H
117.92 SF
Occ: 3
OPTICS LAB
52A
945.77 SF
Occ: 19
PHYSICS LAB
52
163.10 SF
Occ: 1
STORAGE
52C
FIRE RISER ROOM
569.42 SF
Occ: 12
PLANRTARIUM RM
107
88.92 SF
Occ: 0
LIGHT TRAP
I-Y
FE
1
FE
2
CPE 64 FT
CPE 65 FT
CP
E
8
1
F
T
TD 50FT TD 72 FT
TD
4
9
F
T
CP
E
5
6
F
T
CPE 47 FT
OCC.
Req.
Prov.
19"
216"
95
OCC.
Req.
Prov.
12.2"
36"
61
OCC.
Req.
Prov.
2.4"
36"
12
DI
AG.
DI
ST
.
=
5
0
'
28' > 15' 4" (1/3 DIAG. DIST.)
DIAG. DIST. = 50'40'> 8' 4" (1/3 DIAG. DIST.)
DIAG. DIST. = 60'
2 8 ' 7 " > 2 0 ' (1 /3 D I A G . D I S T .)
EXISTING TO REMAIN UNCHANGED
BUSINESS USE OCCUPANCY
150 GSF PER OCC.
CLASSROOM USE OCCUPANCY
20 NET PER OCC.
(LAB) USE OCCUPANCY
50 GSF PER OCC.
ACCESSORY STORAGE AREAS, MECHANICAL
EQUIPMENT AREAS 300 GSF PER OCC.
OCCUPANCY LOAD AND EXIT REQUIREMENTS (table 1004.5)
Level 00
a. Business area = 2,155@150 = 15 occ
b. Education shops & vocational = 2,469@50 = 50 occ
c. Education Classroom area = 1,797@20 = 90 occ
d. Storage area = 1,554@300 = 6 occ
161 occ
Level 01 (Geology Room)
a. Education Classroom area = 1,126@20 = 57 occ
Level 02 (Bio Chemistry Lab)
a. Education shops & vocational = 1,577@50 = 32 occ
Note: The areas where occupancy is determined above is only in areas where
there is redesign. All other occupancies in existing areas that are not being
redesigned will remain the same.
GRAPHIC LEGEND
OCC.
Req.
Prov.
30"
DOOR
36"
150
OCC.
Req.
Prov.
25.5"
STAIR
44"
85
REQUIRED AND PROVIDED DOOR OPENING SIZE (IN INCHES) BASED
OFF NUMBER OF EXITING OCCUPANTS
REQUIRED AND PROVIDED STAIR WIDTH SIZE (IN INCHES) BASED
OFF NUMBER OF EXITING OCCUPANTS
FIRE EXTINGUISHER SURFACE MOUNTED ON WALL HOOK; 75' RADIUS
FIRE EXTINGUISHER IN RECESSED CABINET; 75' RADIUS
COMMON PATH OF EGRESS (CPE)
TRAVEL DISTANCE (TD)
POINT AT WHICH A CHOICE OF TWO EXITS BECOME AVAILABLE
25 TRAVEL PATH OCCUPANTS & DIRECTION OF TRAVEL
NOTES:
a. SEE SHEET SERIES A500 FOR ADDITIONAL WALL TYPE INFORMATION AND UL LISTINGS
b. SEE G000 SHEET SERIES FOR ADDITIONAL CODE INFORMATION
REMOTE POINT
FIRE RATING OF OPENING (IN MINUTES)
ADDITIONAL INFORMATION PROVIDED IN A600 SERIES
FE
1
FE
2
120
1 HOUR RATING
2 HOUR RATING
3 HOUR RATING
1
1 2
1 2 3
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
G003
CODE
ANALYSIS &
PLANS -
LEVEL 00
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 00 CODE PLAN
PLANRTARIUM RM
107
LIGHT TRAP
I-Y
HAZ. STORAGE
167
HAZ. STORAGE
166
ROCK LABORATORY
164
MEN'S T.R.
162
WOMEN'S T.R.
160
PIPE CHASE
I-Q
HALLWAY
1-T
LAB PREP ROOM
161
ELEVATOR
1-M
CUST.
147
STAIRWELL
1-P
1,103.85 SF
Occ: 23
PHYSICAL GEOLOGY
ROOM
158
PHYSICAL SCIENCE DISPLAY
ROOM
156
SEISMOGRAPH ROOM
154
RESOURCE ROOM
150A
AUTO TUTORIAL ROOM
171
STORAGE
171A
LABORATORY RM
179
OFFICE
175
OFFICE
176
OFFICE
180
OFFICE
182
OFFICE
184
STORAGE RM
133
LECTURE HALL
172
SHOP RM
133A
PHYSICS CLASSROOM
105
OFFICE
112
OFFICE
114
OFFICE
116
OFFICE
118
OFFICE
118A
ADVANCED LAB
126
LECTURE HALL
127
LAB STORAGE RM
126A
ADVANCED LAB
128
ADVANCED LAB RM
129
LABORATORY
141
OFFICE
150
OFFICE
148
OFFICE
146
OFFICE
144
WOMEN'S RM
132
MEN'S RM
134
PHYSICS LECTURE HALL
131
LECTURE HALL
145 PREP/STORAGE RM
143
OFFICE
110
OFFICE
186
MINEROLOGY LAB
149
HALLWAY
I-N
HALLWAY
I-L
HALLWAY
I-G
HALLWAY
I-K
HALLWAY
I-F
HALLWAY
I-W
HALLWAY
I-D
UNISEX RM
136
STORAGE
172A
STORAGE
131A
VESTIBULE
I-A
STAIRWELL
I-C
STAIRWELL
I-B
OFFICE
142
HALLWAY
1-U
STAIRWELL
1-V
BDF
138
STAIRWELL
1-S
STAIRWELL
1-H
STAIRWELL
1-E
ELEVATOR
1-J
C P E 1 0 9 F T
84 3/8"
47 5/8"
68 3/4"
68 1/2"
BUSINESS USE OCCUPANCY
150 GSF PER OCC.
CLASSROOM USE OCCUPANCY
20 NET PER OCC.
(LAB) USE OCCUPANCY
50 GSF PER OCC.
ACCESSORY STORAGE AREAS, MECHANICAL
EQUIPMENT AREAS 300 GSF PER OCC.
OCCUPANCY LOAD AND EXIT REQUIREMENTS (table 1004.5)
Level 00
a. Business area = 2,155@150 = 15 occ
b. Education shops & vocational = 2,469@50 = 50 occ
c. Education Classroom area = 1,797@20 = 90 occ
d. Storage area = 1,554@300 = 6 occ
161 occ
Level 01 (Geology Room)
a. Education Classroom area = 1,126@20 = 57 occ
Level 02 (Bio Chemistry Lab)
a. Education shops & vocational = 1,577@50 = 32 occ
Note: The areas where occupancy is determined above is only in areas where
there is redesign. All other occupancies in existing areas that are not being
redesigned will remain the same.
GRAPHIC LEGEND
OCC.
Req.
Prov.
30"
DOOR
36"
150
OCC.
Req.
Prov.
25.5"
STAIR
44"
85
REQUIRED AND PROVIDED DOOR OPENING SIZE (IN INCHES) BASED
OFF NUMBER OF EXITING OCCUPANTS
REQUIRED AND PROVIDED STAIR WIDTH SIZE (IN INCHES) BASED
OFF NUMBER OF EXITING OCCUPANTS
FIRE EXTINGUISHER SURFACE MOUNTED ON WALL HOOK; 75' RADIUS
FIRE EXTINGUISHER IN RECESSED CABINET; 75' RADIUS
COMMON PATH OF EGRESS (CPE)
TRAVEL DISTANCE (TD)
POINT AT WHICH A CHOICE OF TWO EXITS BECOME AVAILABLE
25 TRAVEL PATH OCCUPANTS & DIRECTION OF TRAVEL
NOTES:
a. SEE SHEET SERIES A500 FOR ADDITIONAL WALL TYPE INFORMATION AND UL LISTINGS
b. SEE G000 SHEET SERIES FOR ADDITIONAL CODE INFORMATION
REMOTE POINT
FIRE RATING OF OPENING (IN MINUTES)
ADDITIONAL INFORMATION PROVIDED IN A600 SERIES
FE
1
FE
2
120
1 HOUR RATING
2 HOUR RATING
3 HOUR RATING
1
1 2
1 2 3
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
G004
CODE
ANALYSIS &
PLANS -
LEVEL 01
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 01 CODE PLAN
238.90 SF
Occ: 1
INSTRUMENT RM
203A
743.72 SF
Occ: 3
CHEMISTRY STOCK RM
213
77.85 SF
Occ: 1
OFFICE
213A
578.04 SF
Occ: 29
CLASSROOM
270
591.12 SF
Occ: 30
CLASSROOM
268
176.21 SF
Occ: 0
MEN'S RM
266
169.03 SF
Occ: 0
WOMEN'S RM
264
168.23 SF
Occ: 2
OFFICE
252
91.19 SF
Occ: 1
OFFICE
253
112.74 SF
Occ: 1
OFFICE
250
113.69 SF
Occ: 1
OFFICE
248
115.58 SF
Occ: 1
OFFICE
246
162.37 SF
Occ: 2
OFFICE
244
155.24 SF
Occ: 2
OFFICE
242
91.02 SF
Occ: 1
OFFICE
240
119.78 SF
Occ: 1
OFFICE
238
175.90 SF
Occ: 2
WORK ROOM
243
115.88 SF
Occ: 1
OFFICE
236
115.88 SF
Occ: 1
OFFICE
234
104.40 SF
Occ: 1
OFFICE
239
101.04 SF
Occ: 1
OFFICE
237
131.23 SF
Occ: 1
OFFICE
235
127.46 SF
Occ: 1
OFFICE
233
119.78 SF
Occ: 1
OFFICE
232
808.75 SF
Occ: 41
CLASSROOM
255
1,400.29 SF
Occ: 71
CLASSROOM
277
111.42 SF
Occ: 1
OFFICE
259
120.51 SF
Occ: 1
OFFICE
261
120.51 SF
Occ: 1
OFFICE
263
122.69 SF
Occ: 1
OFFICE
265
134.52 SF
Occ: 0
MEN'S ROOM
226
131.91 SF
Occ: 0
WOMEN'S ROOM
220
1,852.48 SF
Occ: 38
GENERAL CHEM LAB
282
154.74 SF
Occ: 1
CHEM STOCK RM
282A
100.38 SF
Occ: 1
OFFICE
286
100.03 SF
Occ: 1
OFFICE
285
159.31 SF
Occ: 2
OFFICE
289
99.34 SF
Occ: 1
OFFICE
290
99.39 SF
Occ: 1
OFFICE
291
81.91 SF
Occ: 1
OFFICE
292
82.69 SF
Occ: 1
OFFICE
294
89.46 SF
Occ: 1
OFFICE
296
94.79 SF
Occ: 1
OFFICE
298 376.59 SF
Occ: 8
CHEMISTRY LAB
204
1,151.54 SF
Occ: 24
CHEMISTRY LAB
214
1,957.19 SF
Occ: 40
CHEMISTRY LAB
210
408.29 SF
Occ: 9
CHEMISTRY PREP RM
281
566.79 SF
Occ: 29
CLASSROOM
276
71.08 SF
Occ: 1
CUST RM
267
106.94 SF
Occ: 1
BDF RM
280 54.80 SF
Occ: 1
CUST RM
228
226.66 SF
Occ: 1
INSTRUMENT RM
203B
692.97 SF
Occ: 35
CLASSROOM
229
742.99 SF
Occ: 38
CLASSROOM
279
773.91 SF
Occ: 39
CLASSROOM
297
775.67 SF
Occ: 39
CLASSROOM
299
1,701.03 SF
Occ: 35
CHEMISTRY LAB
203
57.66 SF
Occ: 1
STORAGE
258
100.28 SF
Occ: 1
STORAGE RM
277A
114.50 SF
Occ: 1
WORK ROOM
287A
155.95 SF
Occ: 2
SEC/ RECEP RM
287
407.04 SF
Occ: 0
HALLWAY
2-U
549.72 SF
Occ: 0
HALLWAY
2-D
898.24 SF
Occ: 0
HALLWAY
2-F
396.45 SF
Occ: 0
HALLWAY
2-S
631.22 SF
Occ: 0
LOUNGE
2-V
255.18 SF
Occ: 0
HALLWAY
2-J
1,320.13 SF
Occ: 0
HALLWAY
2-M
483.03 SF
Occ: 4
SECRETARY/RECEPTION
RM
230
268.74 SF
Occ: 0
HALLWAY
2-K
790.30 SF
Occ: 40
CLASSROOM
260
786.38 SF
Occ: 40
CLASSROOM
262 85.53 SF
Occ: 0
HALLWAY
2-L
36.96 SF
Occ: 1
CUST STOR
216149.28 SF
Occ: 0
STAIRWELL
2-H
57.50 SF
Occ: 0
ELEVATOR
2-G148.55 SF
Occ: 0
STAIRWELL
2-T
1,431.99 SF
Occ: 0
HALLWAY
2-B
191.53 SF
Occ: 0
STAIRWELL
2-A
188.96 SF
Occ: 0
STAIRWELL
2-C
1,552.91 SF
Occ: 32
BIO-CHEMISTRY LAB
272
FE
2 CPE 73 FT
TD 74 FT
45"
80 1/2"
41 1/4"
FE
2
BUSINESS USE OCCUPANCY
150 GSF PER OCC.
CLASSROOM USE OCCUPANCY
20 NET PER OCC.
(LAB) USE OCCUPANCY
50 GSF PER OCC.
ACCESSORY STORAGE AREAS, MECHANICAL
EQUIPMENT AREAS 300 GSF PER OCC.
OCCUPANCY LOAD AND EXIT REQUIREMENTS (table 1004.5)
Level 00
a. Business area = 2,155@150 = 15 occ
b. Education shops & vocational = 2,469@50 = 50 occ
c. Education Classroom area = 1,797@20 = 90 occ
d. Storage area = 1,554@300 = 6 occ
161 occ
Level 01 (Geology Room)
a. Education Classroom area = 1,126@20 = 57 occ
Level 02 (Bio Chemistry Lab)
a. Education shops & vocational = 1,577@50 = 32 occ
Note: The areas where occupancy is determined above is only in areas where
there is redesign. All other occupancies in existing areas that are not being
redesigned will remain the same.
GRAPHIC LEGEND
OCC.
Req.
Prov.
30"
DOOR
36"
150
OCC.
Req.
Prov.
25.5"
STAIR
44"
85
REQUIRED AND PROVIDED DOOR OPENING SIZE (IN INCHES) BASED
OFF NUMBER OF EXITING OCCUPANTS
REQUIRED AND PROVIDED STAIR WIDTH SIZE (IN INCHES) BASED
OFF NUMBER OF EXITING OCCUPANTS
FIRE EXTINGUISHER SURFACE MOUNTED ON WALL HOOK; 75' RADIUS
FIRE EXTINGUISHER IN RECESSED CABINET; 75' RADIUS
COMMON PATH OF EGRESS (CPE)
TRAVEL DISTANCE (TD)
POINT AT WHICH A CHOICE OF TWO EXITS BECOME AVAILABLE
25 TRAVEL PATH OCCUPANTS & DIRECTION OF TRAVEL
NOTES:
a. SEE SHEET SERIES A500 FOR ADDITIONAL WALL TYPE INFORMATION AND UL LISTINGS
b. SEE G000 SHEET SERIES FOR ADDITIONAL CODE INFORMATION
REMOTE POINT
FIRE RATING OF OPENING (IN MINUTES)
ADDITIONAL INFORMATION PROVIDED IN A600 SERIES
FE
1
FE
2
120
1 HOUR RATING
2 HOUR RATING
3 HOUR RATING
1
1 2
1 2 3
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
G005
CODE
ANALYSIS &
PLANS -
LEVEL 02
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 02 CODE PLAN
MIRROR SOAP DISPENSER PAPER TOWEL
DISPENSER
TOILET PAPER HOLDER SANITARY NAPKIN
DISPOSAL
SANITARY NAPKIN
DISPENSER
BABY CHANGING
STATION
TOILET SEAT COVERS
DISPENSER
WASTE RECEPTACLE FIRE
EXTINGUISHER
CABINET
HAND DRYER
TO
R
E
F
L
E
C
T
I
V
E
SU
R
F
A
C
E
TO
D
I
S
P
E
N
S
E
R
TO
D
I
S
P
E
N
S
E
R
/
H
A
N
D
L
E
TO
O
P
E
N
,
F
L
A
T
SU
R
F
A
C
E
O
F
B
E
D
NOTES:
1. WHERE SHOWN, 48" MAX HEIGHT SHALL BE MEASURED FROM FLOOR TO ANY HIGHEST OPERABLE PART
2. PROVIDE BLOCKING FOR ALL EQUIPMENT PER MANUFACTURER'S WRITTEN INSTRUCTIONS
3' - 4" MAX
3' - 6"
4' - 0" MAX
15" MIN
2' - 0"
2' - 6"4' - 0" MAX
2' - 10"
4' - 0" MAX
TO TOP OF OPENING
4' - 0" MAX
4' - 0" MAX
4' - 0"
TO
D
I
S
P
E
N
S
E
R
/
H
A
N
D
L
E
4' - 0" MAX
TRASH CHUTE DOOR
1' - 2"
1' - 0"
3'-2" MIN
4' - 0" MAX
TOWEL BARS
LOCKER CONTROLS
15" MIN - 48" MAX
TO TOP OF ACCESSIBLE
ACCESSIBLE
LOCKER
FIRE CABINET CUPS COAT HOOKS
TOP LOCKER SHELF:
46" MAX. AFF
BOT. LOCKER SHELF:
15" MIN. AFF
NON ACCESSIBLE
LOCKER
2x4 TOP EDGE MID RAIL
4x4 POSTS 4'-0" O.C.
2x6 CROSS ROOF SUPPORTS 4'-0"
O.C.
3/4" CDX PLYWOOD
1/2" CDX PLYWOOD SHEATHING
NAILED TO 2x4 RAILS
2x4 MID AND BOTTOM RAIL
2x4 TOP RAIL
2x4 TOP EDGE MID RAIL
8' - 5"
4x4 POSTS 4'-0" O.C.
2x6 CROSS ROOF SUPPORTS
4'-0" O.C.
3/4" CDX PLYWOOD
1/2" CDX PLYWOOD SHEATHING
NAILED TO 2x4 RAILS
2x4 MID AND BOTTOM RAIL
2x4 TOP RAIL
4' - 0"
9' - 0"
2' - 6" MIN
4' - 0" MIN
2' - 0"2' - 0"
CR
PU
SH
TO
OP
EN
4' - 0" MAX
ELEVATIONPLAN
5' - 7" MIN
5' - 8" MIN
3' - 0" MIN
5' - 0" MIN
1' - 4" MIN 3' - 0" MIN 1' - 4" MIN
2' - 0" MIN
0' - 10" MAX
OVERLAP OF KNEE AND TOE
5' - 0" MIN
2' - 1" MAX
OVERLAP OF KNEE AND TOE
0' - 8" MIN
0' - 8" MIN
CIRCULAR TURNING SPACE -
NEW BUILDINGS
CIRCULAR TURNING SPACE -
EXISTING BUILDINGS
T-SHAPED TURNING SPACE -
NEW BUILDINGS - OPTION 1
5' - 4" MIN
3' - 2" MIN
5' - 0" MIN
0' - 11" MIN 3' - 6" MIN 0' - 11" MIN
1' - 10" MIN
T-SHAPED TURNING SPACE -
NEW BUILDINGS - OPTION 2
5' - 4" MIN
3' - 4" MIN
5' - 0" MIN
1' - 0" MIN 3' - 4" MIN 1' - 0" MIN
1' - 8" MIN
T-SHAPED TURNING SPACE -
NEW BUILDINGS - OPTION 3
ARM
BASE
BASE
ARM
T-SHAPED TURNING SPACE -
NEW BUILDINGS - OVERLAP
UNOBSTRUCTED FORWARD REACH OBSTRUCTED FORWARD REACH UNOBSTRUCTED SIDE REACH OBSTRUCTED HIGH SIDE REACH
15
M
I
N
38
0
48
M
A
X
12
2
0
48
M
A
X
12
2
0
44
M
A
X
11
2
0
>20-25 MAX
510-635
20 MAX
510
(a)(b)
10 MAX
255
12
2
0
48
M
A
X
15
M
I
N
38
0
10 MAX
255
12
2
0
48
M
A
X
34
M
A
X
86
5
34
M
A
X
86
5
46
M
A
X
11
7
0
> 10-24 MAX
255-610
(a)(b)
430 - 635
17 - 25
760
2' - 6" min
(b)
plan(a)
elevation
430 - 635
17 - 25
760
30 min
(b)
planFIG 306.2
TOE CLEARANCE
230
9
150
6 max
(a)
elevation FIG 306.3
KNEE CLEARANCE
230
9 min
280
11 min
685
27 min
SIZE OF CLEAR FLOOR SPACE
2' - 6" MIN
EXISTING BLDGS - 48" MIN
NEW BLDGS - 4' - 4" MIN
3' - 0" MIN
X > 2' - 0"
X > 1' - 3"
5' - 0" MIN
POSITION OF CLEAR FLOOR SPACE
FORWARD
POSITION OF CLEAR FLOOR SPACE
PARALLEL
MANEUVERING CLEARANCE IN AN ALCOVE
PARALLEL APPROACH
MANEUVERING CLEARANCE IN AN ALCOVE
FORWARD APPROACH
PUSH SIDE
4' - 10" MIN.
MIN.
1' - 0"
12" MIN. IF DOOR
HAS LATCH AND
CLOSER 12" MIN. IF DOOR
HAS LATCH AND
CLOSER
MIN.
1' - 0"
MIN.
2' - 8"
4' - 0" MIN.
FRONT APPROACHHINGE APPROACH
5' - 0" MIN.
3' - 6" MIN.
LATCH APPROACH
SWINGING DOORS SWINGING DOORS
3' - 6" MIN.
SWINGING DOORS STANDARD HARDWARE DOOR PROVIDED WITH CLOSER & LATCH
22" MIN.5' - 0" MIN.
4' - 0" MIN.
1' - 6" MIN.
4' - 0" MIN.
4' - 0" MIN.
1' - 0" MIN.
8" MAX2' - 0" MIN.4' - 6" MIN.
5' - 0" MIN.
3' - 0" MIN.
3' - 6" MIN.
1' - 10" MIN.
3' - 6" MIN.
1' - 6" MIN.
5' - 0" MIN.
8" MAX
1
2
MAX.
1/2"
MAX.
1/4"
1/4" - 1/2"
1
2
LEVEL CHANGE IN FLOOR SURFACE CARPET ON FLOOR SURFACES
MAX.
0' - 0 1/2"
ALL TRANSITIONS SHALL COMPLY WITH
2009 ICC A117.1 SECTIONS 302 AND 303
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
G011
ADA
GUIDELINES
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/2" = 1'-0"D1 TYPICAL MOUNTING HEIGHTS
1/2" = 1'-0"C5 TYPICAL PEDESTRIAN PROTECTION CORRIDOR
1/2" = 1'-0"E6 CARD READER VIEW
3/8" = 1'-0"E1 (ANSI 304) TURNING SPACE
3/8" = 1'-0"C1 (ANSI 308) REACH RANGES
3/8" = 1'-0"A4 (ANSI 604) TOE / KNEE CLEARANCE
3/8" = 1'-0"A1 (ANSI 305) CLEAR FLOOR SPACE
1/4" = 1'-0"B1 (ANSI 404) DOORS AND DOORWAYS
12" = 1'-0"B4 ACCESSIBLE FLOOR TRANSITIONS
BRAILLE AREA, TYP
0' - 2"
OR AS REQ'D
0' - 8" ±
NOTE:
-COLOR AS SELECTED BY ARCHITECT
-CHARACTER SIZE AND BRAILLE
LOCATION PER ANSI A117.1, CH. 7
EXIT SIGN
SIGN
60" MAX
48" MIN
ACTIVE LEAF INACTIVE LEAF ACTIVE LEAF ACTIVE LEAF
SIGN HEIGHT ABOVE THE FLOOR. TACTILE CHARACTERS SHALL BE 48 INCHES
MINIMUM ABOVE THE FLOOR. MEASURED TO THE BASELINE OF THE LOWEST TACTILE
CHARACTER AND 60 INCHES MAXIMUM ABOVE THE FLOOR. MEASURED TO THE
BASELINE OF THE HIGHEST TACTILE CHARACTER. (ICC/ANSI 703.3.10)
SIGN LOCATION. WHERE A TACTILE SIGN IS PROVIDED AT A DOOR. THE SIGN
SHALL BE ALONGSIDE THE DOOR AT THE LATCH SIDE. WHERE A TACTILE SIGN IS
PROVIDED AT DOUBLE DOORS WITH ONE ACTIVE LEAF. THE SIGN SHALL BE
LOCATED ON THE INACTIVE LEAF. WHERE A TACTILE SIGN IS PROVIDED AT DOUBLE
DOORS WITH TWO ACTIVE LEAVES. THE SIGN SHALL BE TO THE RIGHT OF THE
RIGHT HAND DOOR. WHERE THERE IS NO WALL SPACE ON THE LATCH SIDE OF A
SINGLE DOOR, OR TO THE RIGHT SIDE OF DOUBLE DOORS. SIGNS SHALL BE ON
THE NEAREST ADJACENT WALL. SIGNS SHALL BE ON THE NEAREST SHALL BE
LOCATED SO THAT A CLEAR FLOOR AREA 18 INCHES MINIMUM BUY 18 INCHES
MINIMUM, CENTERED ON THE TACTILE CHARACTERS, IS PROVIDED BEYOND THE
ARC OF THE ANY DOOR SWING BETWEEN THE CLOSED POSITION AND 45 DEGREE
OPEN POSITION. (ICC/ANSI 703.311)
SIGNAGE LOCATIONS
WALL CONSTRUCTION
ACCESSORY MOUNTED
OVER FINISHED WALL
GYPSUM BOARD
NOTE:
1. TYPICAL BLOCKING REQUIRED
BEHIND WALL MOUNTED
ACCESSORIES AND EQUIPMENT
(OPTION 1) 20 GA x 6" FLAT STEEL
BLOCKING. ATTACH W SELF TAPPING
PAN HEAD SCREWS
(OPTION 3) SISTER 16 GA. STL.
STUD ATTACH FIXTURE TO
SISTER STUD W/ SELF
TAPPING SCREWS OR
ANCHORS
(OPTION 2) INLAID FIRE
RETARDANT WOOD
BLOCKING (COMPLY WITH
IBC 2006 2303.2)
STUDS SHOWN @ 16" O.C. SEE WALL TYPES
FOUNTAIN
20 GA x 6" FLAT STEEL
BLOCKING
20 GA x 6" FLAT STEEL
BLOCKING
16 GA SUPPORT STUD
FOR STL. ANGLE
BRACING
WATER
COOLER/
FOUNTAIN
PROVIDE FULL VERTICAL BLOCKING AT
CENTERLINE OF URINAL
NAPKIN
TAMPON
HAND DRYER
20 GA x 6" FLAT STEEL
BLOCKING
TYPICAL BLOCKING DETAILS
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
G015
CODE
REQUIRED
SIGNAGE &
DETAILS
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
STORAGE
18
CUST OFFICE
16
CUSTODIAL LAUNDRY RM
14
MEN'S RM
66
WOMEN'S RM
64
MECHANICAL ROOM
69
MECHANICAL RM
10
VESTIBULE
O-A
MECH RM
12
HALLWAY
O-C
STORAGE
63
STAIRWELL
O-B
PIPE CHASE
O-Q
ELEVATOR
O-D
MECH RM
67
STAIRWELL
0-F
STORAGE
20 ELEVATOR
0-K
ELEC VAULT
80
HALLWAY
0-N
COMPACT FILL
COMPACT FILL
COMPACT FILL
CRAWL SPACE
PIPE TUNNEL
PIPE TUNNEL
PI
P
E
T
U
N
N
E
L
CRAWL SPACE
PIPE TUNNEL
PIPE TUNNEL
PIPE TUNNEL
COMPACT FILL
EXTERIOR
MECHANICAL
ENCLOSURE
02.01
02.06
02.0202.02
02.02
02.03
02.04
02.06 02.06
02.07
02.08
02.08
02.09
02.10
02.11
02.12
02.13
02.14
02.15
02.15
02.16
02.16
02.17
02.1802.18
02.19
02.19
02.20
02.20
02.05
02.2102.21
02.21
02.21
02.21
TYP
02.21
02.21
02.16
02.16 02.21
02.22
02.06
02.06
02.46
02.49
OFFICE WORK RM
LAB OFFICE
STUDIO STOR STORAGE
B ROOM C ROOM D ROOM E ROOM F ROOM G ROOM
K ROOM H ROOM
PHOTO STUDIO RMCONFERENCE ROOM
OFFICE
BLACK AND WHITE PRINTING
COMMON PHOTO LAB
DRESS RM
OFFICE
OFFICE
HALLWAY
LIGHT TRAP
HALLWAY/STAIRWELL
A BOOTH B BOOTH C BOOTH D BOOTH E BOOTH
CUST
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
EXISTING DOOR TO BE DEMOLISHED
REMOVE EXISTING FLOORING AND PREP FOR FLOOR FOR NEW
FLOORING. RE: FINISH PLANS FOR NEW FLOORING.
INTERIOR PARTITION DACMU/MASONRY WALLS TO BE DEMOLISHED -
PROTECT FLOORS AND SURROUNDING AREAS FROM DAMAGE
AREAS THAT ARE N.I.C.
SAWCUT AND REMOVE 2'-6" WIDE SECTIONS OF EXISTING CONCRETE
AS HATCHED AND INDICATED FOR NEW ELECTRICAL AND PLUMBING.
RE: ELECTRICAL AND PLUBMING PLANS FOR COORDINATION.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
D100
LEVEL 00
DEMO PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set1/8" = 1'-0"A1 LEVEL 00 DEMOLITION PLAN
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE WILL BE REMOVED BY OWNER PRIOR TO CONSTRUCTION.
11 EXISTING ITEMS ON WALLS, SUCH AS CLOCKS, PAPER TOWEL DISPENSERS, WHITE BOARDS, TVS, COAT RACKS, ETC. TO
BE REMOVED BY OWNER PRIOR TO CONSTRUCTION.
12 ALL EXISTING CMU WALLS HAVE EXISTING THICKENED SLABS UNDERNEATH THEM. BE AWARE WHEN CUTTING NEW
TRENCHES FOR PLUMBING AND UNDERGROUND POWER.
13 ADDITIONAL INTERIOR WALLS AND OTHER ITEMS NOT GRAPHICALLY REPRESENTED ON THIS SHEET MAY REQURIE
DEMOLITION, CONDUCT A SITE SURVEY TO DETERMINE THE FULL EXTENT OF INTERIOR DEMOLITION WORK.
14 NOTE: BYUI - IT IS CURRENTLY THE PLAN THAT EVERYTHING THAT IS DASHED IN RED WILL BE DEMOLISHED AND
REMOVED. IF THERE IS ANYTHING THAT NEEDS TO BE RE-USED OR SAVED, PLEASE LET METHOD STUDIO KNOW.
KEYED NOTES
02.01 SAW CUT OPENING IN EXISTING CMU FOR NEW DOORS. RE: FLOOR PLANS, DOOR SCHEDULE, AND STRUCTURAL
DRAWINGS FOR NEW OPENING.
02.02 REMOVE EXISTING TECH STATION, PROJECTOR, PROJECTOR SCREEN, AND SPEAKERS. RETURN TO OWNER
02.03 SALVAGE EXISTING COAT RACKS FOR REINSTALLATION BY CONTRACTOR IN NEW OFFICES
02.04 EXISTING STRUCTURAL CMU WALL TO REMAIN, RE: STRUCTURAL FOR REINFORCEMENT TO NEW OPENINGS.
02.05 REMOVE AND DISPOSE OF EXISTING FIRE CABINET. RE: FLOOR PLANS AND ELEVATIONS FOR NEW CABINET.
02.06 SAWCUT AND REMOVE 2'-6" WIDE SECTIONS OF EXISTING CONCRETE AS HATCHED AND INDICATED FOR NEW
ELECTRICAL AND PLUMBING. RE: ELECTRICAL AND PLUBMING PLANS FOR COORDINATION.
02.07 REMOVE EXISTING FIRE CABINET. PATCH AND REPAIR TO MATCH EXISTING WALL.
02.08 REPLACE DOOR AND DOOR HARDWARE. EXISTING HM FRAME TO REMAIN AND REVISED AND AND REPAIRED AS
NEEDED FOR NEW HARDWARE. RE: FLOOR PLAN, DOOR SCHEDULE AND HARDWARE SPECIFICATIONS.
02.09 REMOVE EXISTING RECESSED CYCLOROMA CURVED WALL. PATCH AND REPAIR FLOORING FOR NEW FLOORING
FINISH.
02.10 REMOVE AND DISPOSE OF EXISTING LOCKERS.
02.11 REMOVE EXISTING DOUBLE DOORS AND INFILL WITH CMU WALL TO MAINTAIN 2 HOUR RATING OF MECHANICAL
ROOM AND SHAFT WITHIN THE ROOM.
02.12 REMOVE EXISTING HOSE REAL CABINET AND INFILL WITH CMU WALL TO MAINTAIN 2 HOUR RATING OF MECHANICAL
ROOM AND SHAFT.
02.13 REMOVE AND RELOCATE CUSTODIAL CLOSET. RE: FLOOR PLAN.
02.14 CAREFULLY REMOVE STRUCTURAL CMU WALL PER STRUCTURAL DRAWINGS.
02.15 SAW CUT MASONRY TO FLOOR DECK. PREP FOR NEW FINISH. RE: FINISH PLANS
02.16 REMOVE AND DISPOSE OF PHOTO PROCESSING SINKS, TYPICAL.
02.17 EXISTING DRYING RACKS TO BE REMOVED AND RETURNED TO OWNER.
02.18 EXISTING FLOOR DRAINS TO REMAIN. RE: PLUBMING.
02.19 EXISTING FLOOR DRAIN TO BE CAPPED AND FLOOR LEVELED AND PREPPED FOR NEW FINISHED FLOOR. RE:
FINISH PLANS.
02.20 DEMO EXISTING ELECTRICAL PANELS, RE: ELECTRICAL.
02.21 REMOVE AND DISPOSE OF EXISTING COUNTERTOPS AND CABINETRY.
02.22 EXISTING WALL TILE TO REMAIN AND PROTECTED DURING CONSTRUCTION
02.46 REMOVE FLOOR BOX. PATCH AND REPAIR. RE: ELECTRICAL.
02.49 REMOVE AND SALVAGE CURTAINS AND CEILING TRACKS FOR RE-USE.
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
PLANRTARIUM RM
107
LIGHT TRAP
I-Y
HAZ. STORAGE
167
HAZ. STORAGE
166
ROCK LABORATORY
164
MEN'S T.R.
162
WOMEN'S T.R.
160
PIPE CHASE
I-Q
HALLWAY
1-T
LAB PREP ROOM
161
ELEVATOR
1-M
CUST.
147
STAIRWELL
1-P PHYSICAL GEOLOGY ROOM
158
PHYSICAL SCIENCE DISPLAY
ROOM
156
SEISMOGRAPH ROOM
154
RESOURCE ROOM
150A
AUTO TUTORIAL ROOM
171
STORAGE
171A
LABORATORY RM
179
OFFICE
175
OFFICE
176
OFFICE
180
OFFICE
182
OFFICE
184
STORAGE RM
133
LECTURE HALL
172
SHOP RM
133A
PHYSICS CLASSROOM
105
OFFICE
112
OFFICE
114
OFFICE
116
OFFICE
118
OFFICE
118A
ADVANCED LAB
126
LECTURE HALL
127
LAB STORAGE RM
126A
ADVANCED LAB
128
ADVANCED LAB RM
129
LABORATORY
141
OFFICE
150
OFFICE
148
OFFICE
146
OFFICE
144
WOMEN'S RM
132
MEN'S RM
134
PHYSICS LECTURE HALL
131
LECTURE HALL
145 PREP/STORAGE RM
143
OFFICE
110
OFFICE
186
MINEROLOGY LAB
149
HALLWAY
I-N
HALLWAY
I-L
HALLWAY
I-G
HALLWAY
I-K
HALLWAY
I-F
HALLWAY
I-W
HALLWAY
I-D
UNISEX RM
136
STORAGE
172A
STORAGE
131A
VESTIBULE
I-A
STAIRWELL
I-C
STAIRWELL
I-B
OFFICE
142
HALLWAY
1-U
STAIRWELL
1-V
BDF
138
STAIRWELL
1-S
STAIRWELL
1-H
STAIRWELL
1-E
ELEVATOR
1-J
02.2402.2402.24
02.23 TYP
02.23 TYP02.23 TYP
02.25
02.25
02.25
02.21
02.21
02.26 TYP
TYP
02.27
02.30 TYP
02.29
02.28
02.52
02.52
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
EXISTING DOOR TO BE DEMOLISHED
REMOVE EXISTING FLOORING AND PREP FOR FLOOR FOR NEW
FLOORING. RE: FINISH PLANS FOR NEW FLOORING.
INTERIOR PARTITION DACMU/MASONRY WALLS TO BE DEMOLISHED -
PROTECT FLOORS AND SURROUNDING AREAS FROM DAMAGE
AREAS THAT ARE N.I.C.
SAWCUT AND REMOVE 2'-6" WIDE SECTIONS OF EXISTING CONCRETE
AS HATCHED AND INDICATED FOR NEW ELECTRICAL AND PLUMBING.
RE: ELECTRICAL AND PLUBMING PLANS FOR COORDINATION.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
D101
LEVEL 01
DEMO PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 01 DEMOLITION PLAN
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE WILL BE REMOVED BY OWNER PRIOR TO CONSTRUCTION.
11 EXISTING ITEMS ON WALLS, SUCH AS CLOCKS, PAPER TOWEL DISPENSERS, WHITE BOARDS, TVS, COAT RACKS, ETC. TO
BE REMOVED BY OWNER PRIOR TO CONSTRUCTION.
12 ALL EXISTING CMU WALLS HAVE EXISTING THICKENED SLABS UNDERNEATH THEM. BE AWARE WHEN CUTTING NEW
TRENCHES FOR PLUMBING AND UNDERGROUND POWER.
13 ADDITIONAL INTERIOR WALLS AND OTHER ITEMS NOT GRAPHICALLY REPRESENTED ON THIS SHEET MAY REQURIE
DEMOLITION, CONDUCT A SITE SURVEY TO DETERMINE THE FULL EXTENT OF INTERIOR DEMOLITION WORK.
14 NOTE: BYUI - IT IS CURRENTLY THE PLAN THAT EVERYTHING THAT IS DASHED IN RED WILL BE DEMOLISHED AND
REMOVED. IF THERE IS ANYTHING THAT NEEDS TO BE RE-USED OR SAVED, PLEASE LET METHOD STUDIO KNOW.
KEYED NOTES
02.21 REMOVE AND DISPOSE OF EXISTING COUNTERTOPS AND CABINETRY.
02.23 REMOVE ALL WALL TILE WITHIN RESTROOM.PREP WALLS FOR NEW FINISH. RE: FLOOR AND FINISH PLANS FOR
NEW WALL FINISH.
02.24 REPLACE ALL PLUMBING FIXTURES, PARTITIONS, DISPENSERS, MIRRORS, GRAB BARS, ETC. RE: ENLARGED FLOOR
PLANS AND PLUMBING DRAWINGS.
02.25 PARTIAL DEMO EXISTING WALL AS NEED TO REPLACE PLUMBING AND INSULATION IN WALLS. RE: PLUMBING.
02.26 RETURN CHAIRS TO OWNER FOR RE-USE.
02.27 EXISTING UPPER CABINETS TO REMAIN AND TO BE PROTECTED DURING CONSTRUCTION.
02.28 EXISTING PAPER TOWEL DISPENSER TO REMAIN AND TO BE PROTECTED DURING CONSTRUCTION.
02.29 SINK, FAUCET AND DEIONIZED WATER FAUCET TO BE DEMOLISHED AND REPLACED. RE: PLUMBING
02.30 EXISTING VCT FLOORING TO REMIAN AND TO BE PROTECTED DURING CONSTRUCTION. CLEAN AND RESTORE
EXISTING VCT THAT IS UNDER THE CASEWORK TO BE REMOVED. IF VCT CANNOT BE CLEANED AND RESTORED,
REPLACE VCT PER FINISH SCHEDULE.
02.52 EXISTING CASEWORK TO REMAIN.
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
INSTRUMENT RM
203A
CHEMISTRY STOCK RM
213
OFFICE
213A
CLASSROOM
270
CLASSROOM
268
MEN'S RM
266
WOMEN'S RM
264
OFFICE
252
OFFICE
253
OFFICE
250
OFFICE
248
OFFICE
246 OFFICE
244
OFFICE
242
OFFICE
240
OFFICE
238
WORK ROOM
243
OFFICE
236
OFFICE
234
OFFICE
239
OFFICE
237
OFFICE
235
OFFICE
233
OFFICE
232
CLASSROOM
255
CLASSROOM
277
OFFICE
259
OFFICE
261
OFFICE
263
OFFICE
265
MEN'S ROOM
226
WOMEN'S ROOM
220
GENERAL CHEM LAB
282
CHEM STOCK RM
282A
OFFICE
286
OFFICE
285
OFFICE
289 OFFICE
290
OFFICE
291
OFFICE
292
OFFICE
294
OFFICE
296
OFFICE
298
CHEMISTRY LAB
204
CHEMISTRY LAB
214
CHEMISTRY LAB
210
CHEMISTRY PREP RM
281
CLASSROOM
276
CUST RM
267
BDF RM
280
CUST RM
228
INSTRUMENT RM
203B
CLASSROOM
229
CLASSROOM
279
CLASSROOM
297 CLASSROOM
299
CHEMISTRY LAB
203
STORAGE
258
STORAGE RM
277A
WORK ROOM
287A
SEC/ RECEP RM
287
HALLWAY
2-U HALLWAY
2-D
HALLWAY
2-F
HALLWAY
2-S
LOUNGE
2-V
HALLWAY
2-J
HALLWAY
2-M
SECRETARY/RECEPTION RM
230
HALLWAY
2-K
CLASSROOM
260
CLASSROOM
262
HALLWAY
2-L
CUST STOR
216
STAIRWELL
2-HELEVATOR
2-G
STAIRWELL
2-T
HALLWAY
2-B
STAIRWELL
2-A
STAIRWELL
2-C
02.24
02.25
02.23 TYP
02.24
02.25
02.23
02.25
TYP
02.31
02.32
02.33
02.33
02.34
02.35
02.36
02.45
02.37
02.38
02.39
02.40
02.40
02.41
02.41
02.41
02.42
02.43
02.44
02.55 02.55
02.21
21.03
ADVANCED PHYSICS LAB
CHEM LAB RM
OFFICE
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
EXISTING DOOR TO BE DEMOLISHED
REMOVE EXISTING FLOORING AND PREP FOR FLOOR FOR NEW
FLOORING. RE: FINISH PLANS FOR NEW FLOORING.
INTERIOR PARTITION DACMU/MASONRY WALLS TO BE DEMOLISHED -
PROTECT FLOORS AND SURROUNDING AREAS FROM DAMAGE
AREAS THAT ARE N.I.C.
SAWCUT AND REMOVE 2'-6" WIDE SECTIONS OF EXISTING CONCRETE
AS HATCHED AND INDICATED FOR NEW ELECTRICAL AND PLUMBING.
RE: ELECTRICAL AND PLUBMING PLANS FOR COORDINATION.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
D102
LEVEL 02
DEMO PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 02 DEMOLITION PLAN
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE WILL BE REMOVED BY OWNER PRIOR TO CONSTRUCTION.
11 EXISTING ITEMS ON WALLS, SUCH AS CLOCKS, PAPER TOWEL DISPENSERS, WHITE BOARDS, TVS, COAT RACKS, ETC. TO
BE REMOVED BY OWNER PRIOR TO CONSTRUCTION.
12 ALL EXISTING CMU WALLS HAVE EXISTING THICKENED SLABS UNDERNEATH THEM. BE AWARE WHEN CUTTING NEW
TRENCHES FOR PLUMBING AND UNDERGROUND POWER.
13 ADDITIONAL INTERIOR WALLS AND OTHER ITEMS NOT GRAPHICALLY REPRESENTED ON THIS SHEET MAY REQURIE
DEMOLITION, CONDUCT A SITE SURVEY TO DETERMINE THE FULL EXTENT OF INTERIOR DEMOLITION WORK.
14 NOTE: BYUI - IT IS CURRENTLY THE PLAN THAT EVERYTHING THAT IS DASHED IN RED WILL BE DEMOLISHED AND
REMOVED. IF THERE IS ANYTHING THAT NEEDS TO BE RE-USED OR SAVED, PLEASE LET METHOD STUDIO KNOW.
KEYED NOTES
02.21 REMOVE AND DISPOSE OF EXISTING COUNTERTOPS AND CABINETRY.
02.23 REMOVE ALL WALL TILE WITHIN RESTROOM.PREP WALLS FOR NEW FINISH. RE: FLOOR AND FINISH PLANS FOR
NEW WALL FINISH.
02.24 REPLACE ALL PLUMBING FIXTURES, PARTITIONS, DISPENSERS, MIRRORS, GRAB BARS, ETC. RE: ENLARGED FLOOR
PLANS AND PLUMBING DRAWINGS.
02.25 PARTIAL DEMO EXISTING WALL AS NEED TO REPLACE PLUMBING AND INSULATION IN WALLS. RE: PLUMBING.
02.31 REMOVE AND RETURN EXISTING HOOD AND EQUIPMENT TO OWNER.
02.32 REMOVE EXTERIOR FUROUT WALL AND BLACK COVERING ON EXISTING WINDOW. PREP FOR WINDOW SILL AND
NEW FINISHES. RE: FLOOR AND FINISH PLAN.
02.33 REMOVE AND RETURN EXISTING SHELVING TO OWNERS.
02.34 REMOVE EXISTING HOSE REAL CABINET AND INFILL DRYWALL, PATCH AND PAINT TO MATCH EXISTING ADJACENT
WALL.
02.35 DEMO EXISTING WALL TILE. PATCH AND REPAIR WALL FOR NEW FINISHES. SEE FINISH PLAN.
02.36 REMOVE GYP BOARD AS NEEDED TO PROVIDE BLOCKING AS NEEDED FOR WHITE BOARD, TANK SUPPORT AND
TECH STATION.
02.37 PROVIDE OPENING IN EXISTING WALL FOR A NEW DOOR. RE: FLOOR PLANS AND DOOR SCHEDULE.
02.38 REMOVE AND DISPOSE OF EXISTING SINK. REMOVE EXISTING SOLID SURFACE COUNTER TOP TO NEAREST SEAM
AND PREP FOR REPLACEMENT.
02.39 REMOVE AND DISPOSE OF EXISTING CUP SINK. CUT HOLE FOR NEW SINK IN EXISTING SOLID SURFACE.
COORDINATE WITH NEW SINK DIMENSIONS. RE: PLUMBING.
02.40 EXISTING AIR AND GAS LINES TO REMAIN.
02.41 EXISTING CUP SINK AND FAUCET TO REMAIN.
02.42 EXISTING COUNTERTOP AND UNDERCOUNTER CABINETS TO REMAIN.
02.43 EXISTING UPPER SHELVING TO REMAIN.
02.44 EXISTING FUME HOODS TO BE RELOCATED TO ROOM 272. RE: MECHANICAL AND FLOOR PLAN.
02.45 REMOVE, PROTECT AND RE-USE EXISTING DOOR AND FRAME FOR NEW DOOR LOCATION.
02.55 REMOVE EXISTING DOOR.
21.03 SALVAGE FIRE BLANKET AND FIRE EXTINGUISHER FOR REUSE
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
COMPACT FILL
COMPACT FILL
COMPACT FILL
CRAWL SPACE
PIPE TUNNEL
PIPE TUNNEL
PI
P
E
T
U
N
N
E
L
CRAWL SPACE
PIPE TUNNEL
PIPE TUNNEL
PIPE TUNNEL
COMPACT FILL
EXTERIOR
MECHANICAL
ENCLOSURE
02.02
02.51 02.51
02.48
02.50
02.49
02.51
OFFICE WORK RM
LAB OFFICE
STUDIO STOR STORAGE
B ROOM C ROOM D ROOM E ROOM F ROOM G ROOM
K ROOM H ROOM
PHOTO STUDIO RMCONFERENCE ROOM
OFFICE
BLACK AND WHITE PRINTING
COMMON PHOTO LAB
DRESS RM
OFFICE
OFFICE
HALLWAY
LIGHT TRAP
HALLWAY/STAIRWELL
A BOOTH B BOOTH C BOOTH D BOOTH E BOOTH
CUST
MECHANICAL ROOM
CUST RM
MECH RM ELEVATOR
VESTIBULE
HALLWAY
WOMEN'S RM
PIPE CHASE
MEN'S RM
HALLWAY
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
ACT CEILING TO BE DEMOLISHED
INTERIOR PARTITION NON-REINFORCED CMU/MASONRY WALLS TO BE
DEMOLISHED - PROTECT FLOORS AND SURROUNDING AREAS FROM
DAMAGE
N.I.C.
GYP. BOARD CEILING TO BE DEMOLISHED
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
D130
LEVEL 00
DEMO RCP
PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 00 REFLECTED CEILING DEMO PLAN
KEYED NOTES
02.02 REMOVE EXISTING TECH STATION, PROJECTOR, PROJECTOR SCREEN, AND SPEAKERS. RETURN TO OWNER
02.48 REMOVE EXISTING DARK ROOM LIGHT AND RETURN TO OWNER FOR RE-USE.
02.49 REMOVE AND SALVAGE CURTAINS AND CEILING TRACKS FOR RE-USE.
02.50 REMOVE AND RE-INSTALL POWER PAPER ROLLER, RE: FLOOR AND ELECTRICAL PLANS.
02.51 DEMOLISH TRACK LIGHTING.
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE WILL BE REMOVED BY OWNER PRIOR TO CONSTRUCTION.
11 EXISTING ITEMS ON WALLS, SUCH AS CLOCKS, PAPER TOWEL DISPENSERS, WHITE BOARDS, TVS, COAT RACKS, ETC. TO
BE REMOVED BY OWNER PRIOR TO CONSTRUCTION.
12 ALL EXISTING CMU WALLS HAVE EXISTING THICKENED SLABS UNDERNEATH THEM. BE AWARE WHEN CUTTING NEW
TRENCHES FOR PLUMBING AND UNDERGROUND POWER.
13 ADDITIONAL INTERIOR WALLS AND OTHER ITEMS NOT GRAPHICALLY REPRESENTED ON THIS SHEET MAY REQURIE
DEMOLITION, CONDUCT A SITE SURVEY TO DETERMINE THE FULL EXTENT OF INTERIOR DEMOLITION WORK.
14 NOTE: BYUI - IT IS CURRENTLY THE PLAN THAT EVERYTHING THAT IS DASHED IN RED WILL BE DEMOLISHED AND
REMOVED. IF THERE IS ANYTHING THAT NEEDS TO BE RE-USED OR SAVED, PLEASE LET METHOD STUDIO KNOW.
C
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
PLANRTARIUM RM
107
LIGHT TRAP
I-Y
HAZ. STORAGE
167
HAZ. STORAGE
166
ROCK LABORATORY
164
MEN'S T.R.
162
WOMEN'S T.R.
160
PIPE CHASE
I-Q
HALLWAY
1-T
LAB PREP ROOM
161
ELEVATOR
1-M
CUST.
147
STAIRWELL
1-P
PHYSICAL GEOLOGY ROOM
158
PHYSICAL SCIENCE DISPLAY
ROOM
156
SEISMOGRAPH ROOM
154
RESOURCE ROOM
150A
AUTO TUTORIAL ROOM
171
STORAGE
171A
LABORATORY RM
179
OFFICE
175
OFFICE
176
OFFICE
180
OFFICE
182
OFFICE
184
STORAGE RM
133
LECTURE HALL
172
SHOP RM
133A
PHYSICS CLASSROOM
105
OFFICE
112
OFFICE
114
OFFICE
116
OFFICE
118
OFFICE
118A
ADVANCED LAB
126
LECTURE HALL
127
LAB STORAGE RM
126A
ADVANCED LAB
128
ADVANCED LAB RM
129
LABORATORY
141
OFFICE
150
OFFICE
148
OFFICE
146
OFFICE
144
WOMEN'S RM
132
MEN'S RM
134
PHYSICS LECTURE HALL
131
LECTURE HALL
145 PREP/STORAGE RM
143
OFFICE
110
OFFICE
186
MINEROLOGY LAB
149
HALLWAY
I-N
HALLWAY
I-L
HALLWAY
I-G
HALLWAY
I-K
HALLWAY
I-F
HALLWAY
I-W
HALLWAY
I-D
UNISEX RM
136
STORAGE
172A
STORAGE
131A
VESTIBULE
I-A
STAIRWELL
I-C
STAIRWELL
I-B
OFFICE
142
HALLWAY
1-U
STAIRWELL
1-V
BDF
138
STAIRWELL
1-S
STAIRWELL
1-H
STAIRWELL
1-E
ELEVATOR
1-J
LOADING DOCK
ENTRANCE
02.5302.53
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
ACT CEILING TO BE DEMOLISHED
INTERIOR PARTITION NON-REINFORCED CMU/MASONRY WALLS TO BE
DEMOLISHED - PROTECT FLOORS AND SURROUNDING AREAS FROM
DAMAGE
N.I.C.
GYP. BOARD CEILING TO BE DEMOLISHED
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
D131
LEVEL 01
DEMO RCP
PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 01 REFLECTED CEILING DEMO PLAN
KEYED NOTES
02.53 CEILINGS IN RESTROOMS WILL BE REMOVED AND REPLACED AS NEEDED TO REPLACE PLUMBING PIPES.
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE WILL BE REMOVED BY OWNER PRIOR TO CONSTRUCTION.
11 EXISTING ITEMS ON WALLS, SUCH AS CLOCKS, PAPER TOWEL DISPENSERS, WHITE BOARDS, TVS, COAT RACKS, ETC. TO
BE REMOVED BY OWNER PRIOR TO CONSTRUCTION.
12 ALL EXISTING CMU WALLS HAVE EXISTING THICKENED SLABS UNDERNEATH THEM. BE AWARE WHEN CUTTING NEW
TRENCHES FOR PLUMBING AND UNDERGROUND POWER.
13 ADDITIONAL INTERIOR WALLS AND OTHER ITEMS NOT GRAPHICALLY REPRESENTED ON THIS SHEET MAY REQURIE
DEMOLITION, CONDUCT A SITE SURVEY TO DETERMINE THE FULL EXTENT OF INTERIOR DEMOLITION WORK.
14 NOTE: BYUI - IT IS CURRENTLY THE PLAN THAT EVERYTHING THAT IS DASHED IN RED WILL BE DEMOLISHED AND
REMOVED. IF THERE IS ANYTHING THAT NEEDS TO BE RE-USED OR SAVED, PLEASE LET METHOD STUDIO KNOW.
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
INSTRUMENT RM
203A
CHEMISTRY STOCK RM
213
OFFICE
213A
CLASSROOM
270
CLASSROOM
268
MEN'S RM
266
WOMEN'S RM
264
OFFICE
252
OFFICE
253
OFFICE
250
OFFICE
248
OFFICE
246 OFFICE
244
OFFICE
242
OFFICE
240
OFFICE
238
WORK ROOM
243
OFFICE
236
OFFICE
234
OFFICE
239
OFFICE
237
OFFICE
235
OFFICE
233
OFFICE
232
CLASSROOM
255
CLASSROOM
277
OFFICE
259
OFFICE
261
OFFICE
263
OFFICE
265
MEN'S ROOM
226
WOMEN'S ROOM
220
GENERAL CHEM LAB
282
CHEM STOCK RM
282A
OFFICE
286
OFFICE
285
OFFICE
289 OFFICE
290
OFFICE
291
OFFICE
292
OFFICE
294
OFFICE
296
OFFICE
298
CHEMISTRY LAB
204
CHEMISTRY LAB
214
CHEMISTRY LAB
210
CHEMISTRY PREP RM
281
CLASSROOM
276
CUST RM
267
BDF RM
280
CUST RM
228
INSTRUMENT RM
203B
CLASSROOM
229
CLASSROOM
279
CLASSROOM
297 CLASSROOM
299
CHEMISTRY LAB
203
STORAGE
258
STORAGE RM
277A
WORK ROOM
287A
SEC/ RECEP RM
287
HALLWAY
2-U HALLWAY
2-D
HALLWAY
2-F
HALLWAY
2-S
LOUNGE
2-V
HALLWAY
2-J
HALLWAY
2-M
SECRETARY/RECEPTION RM
230
HALLWAY
2-K
CLASSROOM
260
CLASSROOM
262
HALLWAY
2-L
CUST STOR
216
STAIRWELL
2-HELEVATOR
2-G
STAIRWELL
2-T
HALLWAY
2-B
STAIRWELL
2-A
STAIRWELL
2-C
A
1
B
C
D
E
F
GH
J
K
L
MN
P
2 3 4 5 6 7 8
02.53
02.56
TYP
02.32
ADVANCED PHYSICS LAB CHEM LAB RM
OFFICE
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
ACT CEILING TO BE DEMOLISHED
INTERIOR PARTITION NON-REINFORCED CMU/MASONRY WALLS TO BE
DEMOLISHED - PROTECT FLOORS AND SURROUNDING AREAS FROM
DAMAGE
N.I.C.
GYP. BOARD CEILING TO BE DEMOLISHED
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
D132
LEVEL 02
DEMO RCP
PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 02 REFLECTED CEILING DEMO PLAN
KEYED NOTES
02.32 REMOVE EXTERIOR FUROUT WALL AND BLACK COVERING ON EXISTING WINDOW. PREP FOR WINDOW SILL AND
NEW FINISHES. RE: FLOOR AND FINISH PLAN.
02.53 CEILINGS IN RESTROOMS WILL BE REMOVED AND REPLACED AS NEEDED TO REPLACE PLUMBING PIPES.
02.56 REMOVE EXISTING LIGHTING.
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE WILL BE REMOVED BY OWNER PRIOR TO CONSTRUCTION.
11 EXISTING ITEMS ON WALLS, SUCH AS CLOCKS, PAPER TOWEL DISPENSERS, WHITE BOARDS, TVS, COAT RACKS, ETC. TO
BE REMOVED BY OWNER PRIOR TO CONSTRUCTION.
12 ALL EXISTING CMU WALLS HAVE EXISTING THICKENED SLABS UNDERNEATH THEM. BE AWARE WHEN CUTTING NEW
TRENCHES FOR PLUMBING AND UNDERGROUND POWER.
13 ADDITIONAL INTERIOR WALLS AND OTHER ITEMS NOT GRAPHICALLY REPRESENTED ON THIS SHEET MAY REQURIE
DEMOLITION, CONDUCT A SITE SURVEY TO DETERMINE THE FULL EXTENT OF INTERIOR DEMOLITION WORK.
14 NOTE: BYUI - IT IS CURRENTLY THE PLAN THAT EVERYTHING THAT IS DASHED IN RED WILL BE DEMOLISHED AND
REMOVED. IF THERE IS ANYTHING THAT NEEDS TO BE RE-USED OR SAVED, PLEASE LET METHOD STUDIO KNOW.
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
COMPACT FILL
PLANRTARIUM RM
107
LIGHT TRAP
I-Y
STORAGE
18
CUST OFFICE
16
CUSTODIAL LAUNDRY RM
14
MEN'S RM
66
WOMEN'S RM
64
MECHANICAL ROOM
69
MECHANICAL RM
10
VESTIBULE
O-A
MECH RM
12
HALLWAY
O-C
STORAGE
63
STAIRWELL
O-B
PIPE CHASE
O-Q
ELEVATOR
O-D
MECH RM
67
CUST RM
68
STAIRWELL
0-F
STORAGE
20 ELEVATOR
0-K
ELEC VAULT
80
COMPACT FILL
COMPACT FILL
CRAWL SPACE
PIPE TUNNEL
PIPE TUNNEL
PI
P
E
T
U
N
N
E
L
HALLWAY
0-N
CRAWL SPACE
PIPE TUNNEL
PIPE TUNNEL
PIPE TUNNEL
COMPACT FILL
EXTERIOR
MECHANICAL
ENCLOSURE
DARK ROOM
59D
COMPUTER LAB
59
PHOTO STUDIO
51
VESTIBULE
59C
OFFICE
57
EQUIP / CHECK OUT
59A
STORAGE
59B
OFFICE
55
FILM
59E
ACOUSTICS STUDIO
52B
STORAGE
51A
CHANGING
51B
VESTIBULE
0-H
OPTICS LAB
52A
PHYSICS LAB
52
STORAGE
52C
CLASSROOM
50
2'
-
0
"
3' - 0"
2'
-
0
"
ROOF LINE ABOVE
SOFFIT LINE ABOVE
2' - 0"
A414 D2
A411A
A1
A412
1
A414E4
D1
E1
E2
A414
C1
68
69
52B
52A
50
55
51A
59.1
59A.1
51B
52.1
59.2
59A.2
59D
51.1
51.2
57
52C
59E
59C
0-H
52.2
F3
A414B1
B2
A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
B. DO NOT SCALE THE DRAWINGS
C. ALL EXPOSED INTERIOR COLUMNS TO BE PAINTED WITH INTUMESCENT PAINT
D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
E. SEE G000 SHEET SERIES FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
INSTALLED
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
K. VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES AE400. CONTRACTOR TO VERIFY AND MAXIMIZE
CEILING HEIGHT IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
L. ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION
OF THE DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE
CENTERED ARE CORRECTLY CENTERED BETWEEN THE SOFFITS.
M. SEMI-FLUSH LIGHT FIXTURE TO BE CENTERED OVER UNIT KITCHEN ISLANDS & CENTERED WITHIN FIXED
DINING ROOMS AT UNITS. SEE AE400 UNIT SHEET SERIES FOR LOCATIONS.
N. DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE
LENGTH OF WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD.
ASSUME CENTERED IN FACE OF JAMB UNLESS NOTED OTHERWISE.
O. ALL PANEL MOLDING TO HAVE MITERED CORNERS AND CONSISTENT MOUNTING HEIGHT AND SPACING
WITHIN THE SAME SPACE.
GENERAL NOTES
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A100
LEVEL 00
FLOOR PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 00 FLOOR PLAN
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
PLANRTARIUM RM
107
LIGHT TRAP
I-Y
HAZ. STORAGE
167
HAZ. STORAGE
166
ROCK LABORATORY
164
MEN'S T.R.
162
WOMEN'S T.R.
160
PIPE CHASE
I-Q
HALLWAY
1-T
LAB PREP ROOM
161
ELEVATOR
1-M
CUST.
147
STAIRWELL
1-P
1,104 SF
PHYSICAL GEOLOGY ROOM
158
PHYSICAL SCIENCE DISPLAY
ROOM
156
SEISMOGRAPH ROOM
154
RESOURCE ROOM
150A
AUTO TUTORIAL ROOM
171
STORAGE
171A
LABORATORY RM
179
OFFICE
175
OFFICE
176
OFFICE
180
OFFICE
182
OFFICE
184
STORAGE RM
133
LECTURE HALL
172
SHOP RM
133A
PHYSICS CLASSROOM
105
OFFICE
112
OFFICE
114
OFFICE
116
OFFICE
118
OFFICE
118A
ADVANCED LAB
126
LECTURE HALL
127
LAB STORAGE RM
126A
ADVANCED LAB
128
ADVANCED LAB RM
129
LABORATORY
141
OFFICE
150
OFFICE
148
OFFICE
146
OFFICE
144
WOMEN'S RM
132
MEN'S RM
134
PHYSICS LECTURE HALL
131
LECTURE HALL
145 PREP/STORAGE RM
143
OFFICE
110
OFFICE
186
MINEROLOGY LAB
149
HALLWAY
I-N
HALLWAY
I-L
HALLWAY
I-G
HALLWAY
I-K
HALLWAY
I-F
HALLWAY
I-W
HALLWAY
I-D
UNISEX RM
136
STORAGE
172A
STORAGE
131A
VESTIBULE
I-A
STAIRWELL
I-C
STAIRWELL
I-B
OFFICE
142
HALLWAY
1-U
STAIRWELL
1-V
BDF
138
STAIRWELL
1-S
STAIRWELL
1-H
STAIRWELL
1-E
ELEVATOR
1-J
A415
A1
A201D1
A201
B1
A201 A1
A414
D3
26.1426.1426.14
02.5202.52 02.52
6.06
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A101
LEVEL 01
FLOOR PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set1/8" = 1'-0"A1 LEVEL 01 FLOOR PLAN
GENERAL NOTES - FLOOR PLAN
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE THE DRAWINGS
3 ALL EXPOSED INTERIOR COLUMNS TO BE PAINTED WITH INTUMESCENT PAINT
4 ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
5 SEE G000 SERIES SHEETS FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
6 COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER INSTALLED
7 SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
8 SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
9 SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
10 SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
11 VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES A400. CONTRACTOR TO VERIFY AND MAXIMIZE CEILING HEIGHT IN
ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
12 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
13 SEMI-FLUSH LIGHT FIXTURE TO BE CENTERED OVER UNIT KITCHEN ISLANDS & CENTERED WITHIN FIXED DINING ROOMS
AT UNITS. SEE A400's UNIT SHEET SERIES FOR LOCATIONS
14 DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE LENGTH OF
WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD. ASSUME CENTERED IN FACE
OF JAMB UNLESS NOTED OTHERWISE
KEYED NOTES
02.52 EXISTING CASEWORK TO REMAIN.
6.06 CUT COUNTERTOP AROUND COLUMN. FEILD VERIFY.
26.14 ALL NEW STALLS, FIXTURES AND PLUMBING TO BE REPLACED TO MATCH EXISTING LAYOUT. RE: ELEVATIONS AND
FINSIH PLANS FOR NEW FINISHES.
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
INSTRUMENT RM
203A
CHEMISTRY STOCK RM
213
OFFICE
213A
CLASSROOM
270
CLASSROOM
268
MEN'S RM
266
WOMEN'S RM
264
OFFICE
252
OFFICE
253
OFFICE
250
OFFICE
248
OFFICE
246 OFFICE
244
OFFICE
242
OFFICE
240
OFFICE
238
WORK ROOM
243
OFFICE
236
OFFICE
234
OFFICE
239
OFFICE
237
OFFICE
235
OFFICE
233
OFFICE
232
CLASSROOM
255
CLASSROOM
277
OFFICE
259
OFFICE
261
OFFICE
263
OFFICE
265
MEN'S ROOM
226
WOMEN'S ROOM
220
GENERAL CHEM LAB
282
CHEM STOCK RM
282A
OFFICE
286
OFFICE
285
OFFICE
289 OFFICE
290
OFFICE
291
OFFICE
292
OFFICE
294
OFFICE
296
OFFICE
298
CHEMISTRY LAB
204
CHEMISTRY LAB
214
CHEMISTRY LAB
210
CHEMISTRY PREP RM
281
CLASSROOM
276
CUST RM
267
BDF RM
280
CUST RM
228
INSTRUMENT RM
203B
CLASSROOM
229
CLASSROOM
279
CLASSROOM
297 CLASSROOM
299
CHEMISTRY LAB
203
STORAGE
258
STORAGE RM
277A
WORK ROOM
287A
SEC/ RECEP RM
287
HALLWAY
2-U HALLWAY
2-D
HALLWAY
2-F
HALLWAY
2-S
LOUNGE
2-V
HALLWAY
2-J
HALLWAY
2-M
SECRETARY/RECEPTION RM
230
HALLWAY
2-K
CLASSROOM
260
CLASSROOM
262
HALLWAY
2-L
CUST STOR
216
STAIRWELL
2-HELEVATOR
2-G
STAIRWELL
2-T
HALLWAY
2-B
STAIRWELL
2-A
STAIRWELL
2-C
A415
A3
1,553 SF
BIO-CHEMISTRY LAB
272
272
276
A413
1
SF1
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A102
LEVEL 02
FLOOR PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"(REF: A1/A201)A1 LEVEL 02 FLOOR PLAN
GENERAL NOTES - FLOOR PLAN
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE THE DRAWINGS
3 ALL EXPOSED INTERIOR COLUMNS TO BE PAINTED WITH INTUMESCENT PAINT
4 ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
5 SEE G000 SERIES SHEETS FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
6 COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER INSTALLED
7 SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
8 SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
9 SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
10 SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
11 VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES A400. CONTRACTOR TO VERIFY AND MAXIMIZE CEILING HEIGHT IN
ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
12 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
13 SEMI-FLUSH LIGHT FIXTURE TO BE CENTERED OVER UNIT KITCHEN ISLANDS & CENTERED WITHIN FIXED DINING ROOMS
AT UNITS. SEE A400's UNIT SHEET SERIES FOR LOCATIONS
14 DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE LENGTH OF
WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD. ASSUME CENTERED IN FACE
OF JAMB UNLESS NOTED OTHERWISE
F
F F
CR
CR
FF
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
STORAGE
18
CUST OFFICE
16
CUSTODIAL LAUNDRY RM
14
MEN'S RM
66
WOMEN'S RM
64
MECHANICAL ROOM
69
MECHANICAL RM
10
VESTIBULE
O-A
MECH RM
12
HALLWAY
O-C
STORAGE
63
STAIRWELL
O-BPIPE CHASE
O-Q
ELEVATOR
O-D
MECH RM
67
47 SF
CUST RM
68
STAIRWELL
0-F
STORAGE
20 ELEVATOR
0-K
ELEC VAULT
80
HALLWAY
0-N
COMPACT FILL
COMPACT FILL
COMPACT FILL
CRAWL SPACE
PIPE TUNNEL
PIPE TUNNEL
PI
P
E
T
U
N
N
E
L
CRAWL SPACE
PIPE TUNNEL
PIPE TUNNEL
PIPE TUNNEL
COMPACT FILL
EXTERIOR
MECHANICAL
ENCLOSURE
LIGHT TRAP
I-Y
PLANRTARIUM RM
107
5' - 5"21' - 3 13/16"5' - 5"14' - 4 3/4"10' - 5"10' - 5"10' - 5"6' - 4"
10
'
-
9
1
/
2
"
11
'
-
1
"
8'
-
5
"
12
'
-
5
"
19
'
-
0
1
/
2
"
4'
-
3
1
/
2
"
744 SF
CLASSROOM
50
286 SF
DARK ROOM
59D
908 SF
COMPUTER LAB
59
983 SF
PHOTO STUDIO
51
26 SF
VESTIBULE
59C
120 SF
OFFICE
57
169 SF
EQUIP / CHECK OUT
59A
121 SF
STORAGE
59B
120 SF
OFFICE
55
33 SF
FILM
59E
114 SF
ACOUSTICS STUDIO
52B
141 SF
STORAGE
51A
50 SF
CHANGING
51B
120 SF
VESTIBULE
0-H
118 SF
OPTICS LAB
52A
946 SF
PHYSICS LAB
52
163 SF
STORAGE
52C
14' - 10"5' - 0"
3'
-
0
"
22
'
-
6
"
11 1/4"1'-11 1/4"
11' - 10"
24' - 1 1/2"
5' - 6"6' - 11"26' - 4"9' - 9 3/8"
3'
-
1
"
SF6 b SA
4
b
SA4 b
SA4 a
SA4 a SB
4
a
SB4 a
SB
4
a
SF
6
b
SA6 a SA
4
a
SB
3
a
SB3 a SA
4
a
SA
4
a
SA
4
a
SB3 aSA
4
a
SA
4
a
SB4 a
SA
4
b
SA
4
bSA4b
SA
4
bSA
4
a
SG4 b
SA
4
b
SA4 a
SA
4
a
SA4 a
SA6 a
SA
4
a
SA4 b
SA
4
b
SB
3
a
SB3 a
SB
3
a
SA6 a
SB3 a
SA
4
b
SA4 b
SB
6
a
SA
4
a
SB
4
a
CD
6
SH
2
b
SB1 a
SB3 a
SA
4
b
SA4 b
SB3 aSB4a
SA4 a
SA
6
a
0' - 9"
3'
-
1
1
/
2
"
5'
-
5
"
SA4 a
SA4 a
7'
-
6
1
/
2
"
21
'
-
8
"
2'
-
6
"
0' - 2 1/2"6' - 0"
8'
-
1
0
"
7"
SB1 a
SB1 a
CD
6
CD
6
SH2 b
SB
3
b
SG
4
b
MIN
3'-0"
CLEAR
4'-9"
ALIGN
4"
8
3
/
4
"
8
1
/
4
"
7 1/8"
A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
B. DO NOT SCALE THE DRAWINGS
C. ALL EXPOSED INTERIOR COLUMNS TO BE PAINTED WITH INTUMESCENT PAINT
D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
E. SEE G000 SHEET SERIES FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
INSTALLED
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
K. VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES AE400. CONTRACTOR TO VERIFY AND MAXIMIZE
CEILING HEIGHT IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
L. ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION
OF THE DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE
CENTERED ARE CORRECTLY CENTERED BETWEEN THE SOFFITS.
M. SEMI-FLUSH LIGHT FIXTURE TO BE CENTERED OVER UNIT KITCHEN ISLANDS & CENTERED WITHIN FIXED
DINING ROOMS AT UNITS. SEE AE400 UNIT SHEET SERIES FOR LOCATIONS.
N. DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE
LENGTH OF WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD.
ASSUME CENTERED IN FACE OF JAMB UNLESS NOTED OTHERWISE.
O. ALL PANEL MOLDING TO HAVE MITERED CORNERS AND CONSISTENT MOUNTING HEIGHT AND SPACING
WITHIN THE SAME SPACE.
GENERAL NOTES
LEGEND: INT. PARTITION HEAD CONDITIONS
TYPICAL PARTITION FLOOR TO FLOOR/CEILING/ROOF
1-HR FIRE RATED PARTITION
2-HR FIRE RATED PARTITION
b - ACOUSTIC PARTITION
a - PARTITION EXTENDS FROM FLOOR TO 6" ABOVE CEILING
WALL TYPE HEAD CONDITION LEGEND
IF NULL = TYPICAL PARTITION FLOOR TO FLOOR/CEILING/ROOF
a = PARTITION EXTEND FROM FLOOR TO 6" ABOVE CEILING
b = ACOUSTIC PARTITION
NON-FIRE RATED WALL TAG (description)
SA6a
CORE MATERIAL (SEE LEGEND)
LAYERS (SEE LEGEND)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
FIRE RATED WALL TAG (description)
FIRE RATING (IF APPLICABLE)
1SA6a
CORE MATERIAL (SEE LEGEND BELOW)
LAYERS (REF PARTITIONS SHEET)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
C = CONCRETE WALLS, MASONRY
S = STEEL STUDS
CORE MATERIAL LEGEND
CORE SIZE LEGEND
STEEL STUDS
1 =A7/8"
2 = 1 5/8"
3 = 2 1/2"
4 = 3 5/8"
5 =
6 = 6"
8 = 8"
SUPERSCRIPT NOTES -
A - HAT CHANNEL FURRING IN LIEU OF METAL STUD
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A120
LEVEL 00
DIMENSION
PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set1/8" = 1'-0"A1 LEVEL 00 DIMENSION PLAN
DN
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
PLANRTARIUM RM
107
LIGHT TRAP
I-Y
HAZ. STORAGE
167
HAZ. STORAGE
166
ROCK LABORATORY
164 MEN'S T.R.
162
WOMEN'S T.R.
160
PIPE CHASE
I-Q
HALLWAY
1-T
LAB PREP ROOM
161
ELEVATOR
1-M
CUST.
147
STAIRWELL
1-P
PHYSICAL GEOLOGY ROOM
158
PHYSICAL SCIENCE DISPLAY
ROOM
156
SEISMOGRAPH ROOM
154
RESOURCE ROOM
150A
AUTO TUTORIAL ROOM
171
STORAGE
171A
LABORATORY RM
179
OFFICE
175
OFFICE
176
OFFICE
180
OFFICE
182
OFFICE
184
STORAGE RM
133
LECTURE HALL
172
SHOP RM
133A
PHYSICS CLASSROOM
105
OFFICE
112
OFFICE
114
OFFICE
116
OFFICE
118
OFFICE
118A
ADVANCED LAB
126
LECTURE HALL
127
LAB STORAGE RM
126A
ADVANCED LAB
128
ADVANCED LAB RM
129
LABORATORY
141
OFFICE
150
OFFICE
148
OFFICE
146
OFFICE
144
WOMEN'S RM
132
MEN'S RM
134
PHYSICS LECTURE HALL
131
LECTURE HALL
145 PREP/STORAGE RM
143
OFFICE
110
OFFICE
186
MINEROLOGY LAB
149
HALLWAY
I-N
HALLWAY
I-L
HALLWAY
I-G
HALLWAY
I-K
HALLWAY
I-F
HALLWAY
I-W
HALLWAY
I-D
UNISEX RM
136
STORAGE
172A
STORAGE
131A
VESTIBULE
I-A
STAIRWELL
I-C
STAIRWELL
I-B
OFFICE
142
HALLWAY
1-U
STAIRWELL
1-V
BDF
138
STAIRWELL
1-S
STAIRWELL
1-H
STAIRWELL
1-E
ELEVATOR
1-J
14'-1 1/4"6'-3 5/8"14'-1 1/2"5/8"
A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
B. DO NOT SCALE THE DRAWINGS
C. ALL EXPOSED INTERIOR COLUMNS TO BE PAINTED WITH INTUMESCENT PAINT
D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
E. SEE G000 SHEET SERIES FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
INSTALLED
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
K. VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES AE400. CONTRACTOR TO VERIFY AND MAXIMIZE
CEILING HEIGHT IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
L. ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION
OF THE DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE
CENTERED ARE CORRECTLY CENTERED BETWEEN THE SOFFITS.
M. SEMI-FLUSH LIGHT FIXTURE TO BE CENTERED OVER UNIT KITCHEN ISLANDS & CENTERED WITHIN FIXED
DINING ROOMS AT UNITS. SEE AE400 UNIT SHEET SERIES FOR LOCATIONS.
N. DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE
LENGTH OF WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD.
ASSUME CENTERED IN FACE OF JAMB UNLESS NOTED OTHERWISE.
O. ALL PANEL MOLDING TO HAVE MITERED CORNERS AND CONSISTENT MOUNTING HEIGHT AND SPACING
WITHIN THE SAME SPACE.
GENERAL NOTES
LEGEND: INT. PARTITION HEAD CONDITIONS
TYPICAL PARTITION FLOOR TO FLOOR/CEILING/ROOF
1-HR FIRE RATED PARTITION
2-HR FIRE RATED PARTITION
b - ACOUSTIC PARTITION
a - PARTITION EXTENDS FROM FLOOR TO 6" ABOVE CEILING
WALL TYPE HEAD CONDITION LEGEND
IF NULL = TYPICAL PARTITION FLOOR TO FLOOR/CEILING/ROOF
a = PARTITION EXTEND FROM FLOOR TO 6" ABOVE CEILING
b = ACOUSTIC PARTITION
NON-FIRE RATED WALL TAG (description)
SA6a
CORE MATERIAL (SEE LEGEND)
LAYERS (SEE LEGEND)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
FIRE RATED WALL TAG (description)
FIRE RATING (IF APPLICABLE)
1SA6a
CORE MATERIAL (SEE LEGEND BELOW)
LAYERS (REF PARTITIONS SHEET)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
C = CONCRETE WALLS, MASONRY
S = STEEL STUDS
CORE MATERIAL LEGEND
CORE SIZE LEGEND
STEEL STUDS
1 =A7/8"
2 = 1 5/8"
3 = 2 1/2"
4 = 3 5/8"
5 =
6 = 6"
8 = 8"
SUPERSCRIPT NOTES -
A - HAT CHANNEL FURRING IN LIEU OF METAL STUD
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A121
LEVEL 01
DIMENSION
PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 01 DIMENSION PLAN
F
F
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
INSTRUMENT RM
203A
CHEMISTRY STOCK RM
213
OFFICE
213A
CLASSROOM
270
CLASSROOM
268
MEN'S RM
266
WOMEN'S RM
264
OFFICE
252
OFFICE
253
OFFICE
250
OFFICE
248
OFFICE
246 OFFICE
244
OFFICE
242
OFFICE
240
OFFICE
238
WORK ROOM
243
OFFICE
236
OFFICE
234
OFFICE
239
OFFICE
237
OFFICE
235
OFFICE
233
OFFICE
232
CLASSROOM
255
CLASSROOM
277
OFFICE
259
OFFICE
261
OFFICE
263
OFFICE
265
MEN'S ROOM
226
WOMEN'S ROOM
220
GENERAL CHEM LAB
282
CHEM STOCK RM
282A
OFFICE
286
OFFICE
285
OFFICE
289 OFFICE
290
OFFICE
291
OFFICE
292
OFFICE
294
OFFICE
296
OFFICE
298
CHEMISTRY LAB
204
CHEMISTRY LAB
214
CHEMISTRY LAB
210
CHEMISTRY PREP RM
281
CLASSROOM
276
CUST RM
267
BDF RM
280
CUST RM
228
INSTRUMENT RM
203B
CLASSROOM
229
CLASSROOM
279
CLASSROOM
297 CLASSROOM
299
CHEMISTRY LAB
203
STORAGE
258
STORAGE RM
277A
WORK ROOM
287A
SEC/ RECEP RM
287
HALLWAY
2-U HALLWAY
2-D
HALLWAY
2-F
HALLWAY
2-S
LOUNGE
2-V
HALLWAY
2-J
HALLWAY
2-M
SECRETARY/RECEPTION RM
230
HALLWAY
2-K
CLASSROOM
260
CLASSROOM
262
HALLWAY
2-L
CUST STOR
216
STAIRWELL
2-HELEVATOR
2-G
STAIRWELL
2-T
HALLWAY
2-B
STAIRWELL
2-A
STAIRWELL
2-C
1,553 SF
BIO-CHEMISTRY LAB
272
ALIGN
2'
-
8
"
11
'
-
2
1
/
2
"
3' - 1"
3' - 0"
5' - 1"
0'
-
4
"
5'
-
1
0
"
F
.
V
.
5'
-
6
"
2
3
/
8
"
15
'
-
5
"
SB4 a 4' - 5 7/8"
8' - 3"
9
5
/
8
"
SA6 a
SA
4
b
SA4 b
SB4 a
3'
-
0
"
0' - 2 1/8"
0' - 8"
SB
3
b
SB
4
b
SA6
SB
3
a
A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
B. DO NOT SCALE THE DRAWINGS
C. ALL EXPOSED INTERIOR COLUMNS TO BE PAINTED WITH INTUMESCENT PAINT
D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
E. SEE G000 SHEET SERIES FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
INSTALLED
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
K. VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES AE400. CONTRACTOR TO VERIFY AND MAXIMIZE
CEILING HEIGHT IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
L. ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION
OF THE DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE
CENTERED ARE CORRECTLY CENTERED BETWEEN THE SOFFITS.
M. SEMI-FLUSH LIGHT FIXTURE TO BE CENTERED OVER UNIT KITCHEN ISLANDS & CENTERED WITHIN FIXED
DINING ROOMS AT UNITS. SEE AE400 UNIT SHEET SERIES FOR LOCATIONS.
N. DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE
LENGTH OF WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD.
ASSUME CENTERED IN FACE OF JAMB UNLESS NOTED OTHERWISE.
O. ALL PANEL MOLDING TO HAVE MITERED CORNERS AND CONSISTENT MOUNTING HEIGHT AND SPACING
WITHIN THE SAME SPACE.
GENERAL NOTES
LEGEND: INT. PARTITION HEAD CONDITIONS
TYPICAL PARTITION FLOOR TO FLOOR/CEILING/ROOF
1-HR FIRE RATED PARTITION
2-HR FIRE RATED PARTITION
b - ACOUSTIC PARTITION
a - PARTITION EXTENDS FROM FLOOR TO 6" ABOVE CEILING
WALL TYPE HEAD CONDITION LEGEND
IF NULL = TYPICAL PARTITION FLOOR TO FLOOR/CEILING/ROOF
a = PARTITION EXTEND FROM FLOOR TO 6" ABOVE CEILING
b = ACOUSTIC PARTITION
NON-FIRE RATED WALL TAG (description)
SA6a
CORE MATERIAL (SEE LEGEND)
LAYERS (SEE LEGEND)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
FIRE RATED WALL TAG (description)
FIRE RATING (IF APPLICABLE)
1SA6a
CORE MATERIAL (SEE LEGEND BELOW)
LAYERS (REF PARTITIONS SHEET)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
C = CONCRETE WALLS, MASONRY
S = STEEL STUDS
CORE MATERIAL LEGEND
CORE SIZE LEGEND
STEEL STUDS
1 =A7/8"
2 = 1 5/8"
3 = 2 1/2"
4 = 3 5/8"
5 =
6 = 6"
8 = 8"
SUPERSCRIPT NOTES -
A - HAT CHANNEL FURRING IN LIEU OF METAL STUD
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A122
LEVEL 02
DIMENSION
PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 02 DIMENSION PLAN
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
PLANRTARIUM RM
107
LIGHT TRAP
I-Y
STORAGE
18
CUST OFFICE
16
CUSTODIAL LAUNDRY RM
14
MEN'S RM
66
WOMEN'S RM
64
MECHANICAL ROOM
69
MECHANICAL RM
10
VESTIBULE
O-A
MECH RM
12
HALLWAY
O-C
STORAGE
63
STAIRWELL
O-B
PIPE CHASE
O-Q
ELEVATOR
O-D
MECH RM
67
CUST RM
68
STAIRWELL
0-F
STORAGE
20
ELEVATOR
0-K
ELEC VAULT
80
HALLWAY
0-N
COMPACT FILL
COMPACT FILL
COMPACT FILL
CRAWL SPACE
PIPE TUNNEL
PIPE TUNNEL
PI
P
E
T
U
N
N
E
L
CRAWL SPACE
PIPE TUNNEL
PIPE TUNNEL
PIPE TUNNEL
COMPACT FILL
EXTERIOR
MECHANICAL
ENCLOSURE
CLASSROOM
50
DARK ROOM
59D
COMPUTER LAB
59
PHOTO STUDIO
51
VESTIBULE
59C
OFFICE
57
EQUIP / CHECK OUT
59A
STORAGE
59B
OFFICE
55
FILM
59E
ACOUSTICS STUDIO
52B
STORAGE
51A
CHANGING
51B
VESTIBULE
0-H
OPTICS LAB
52A
PHYSICS LAB
52
STORAGE
52C
B2 9' - 0"B2 9' - 0"
A1 9' - 0"A1 9' - 0"
A1 9' - 0"
A1 9' - 0"
B1 9' - 0"
A1 9' - 0"
A1 9' - 0"
A1 9' - 0"
A1 9' - 0"
A1 9' - 0"
A1 9' - 0"
A1 9' - 0"
A1 9' - 0"
A1 10' - 0"
B1 9' - 0"
A1 9' - 0"
E-1
A1 9' - 0"A1 9' - 0"A1 9' - 0"A1 9' - 0"
A1 9' - 0"
10.21
10.24
10.22
10.23
E-1
10.26
26.09
26.10
26.13
09.26
23.01
26.01 23.01
TYP
26.01
TYP
26.15
TYP
23.01TYP
23.01
26.01
26.06
TYP
TYP
23.01
26.01
26.01
TYP
23.02
23.01
26.01
23.01
TYP
TYP
TYP
23.0223.02
26.17
10.32
09.24
09.24
A514
C1
ACT-01:
2' x 2' LAY-IN ACOUSTICAL TILE & SUSPENSION SYSTEM, RE: FINISH SCHEDULE
CEILING LEGEND
TYPE A1
5/8" GYPSUM BOARD (PAINTED PNT-01 UNLESS NOTED ON PLAN) ON METAL STUD.
TYPE B1
5/8" GYPSUM BOARD (PAINTED PNT-01 UNLESS NOTED ON PLAN) ON METAL
SUSPENSION SYSTEM.
TYPE B2
EXPOSED STRUCTURE. PAINT PNT-02, RE: FINISH LEGEND
TYPE E-1
NOTE:
ALL DROPS NEED TO BE NON-COMBUSTIBLE METAL FRAMING OR LIGHT GAUGE METAL FRAMING AND
MEET L/360 STANDARD FOR ALLOWABLE DEFLECTION.
ACCOUSTIC FOAM ON 5/8" GYPSUM BOARD ON METAL SUSPENSION SYSTEM.
TYPE B3
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A130
LEVEL 00
RCP PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 00 REFLECTED CEILING PLAN
GENERAL NOTES - CEILING
1 VERIFY ALL MECHANICAL DUCT, GRILLE, DIFFUSER, AND VENT LOCATIONS WITH MECHANICAL DRAWINGS
2 CEILING GRID SHOWN IS ONLY A GRAPHIC REPRESENTATION OF CEILING. CEILING PATTERN IS TO BE CENTERED IN THE
ROOM, UNLESS NOTED OTHERWISE. CONTRACTOR SHALL VERIFY ACTUAL GRID LAYOUT/LOCATION
3 VERIFY AND COORDINATE ALL MECHANICAL DUCT, GRILL DIFFUSER & LOCATIONS, VENTS, AND QUANTITY WITH
MECHANICAL PLANS
4 VERIFY ALL LIGHTS, SMOKE DETECTORS, AND EXIT DEVICE LOCATIONS AND QUANTITIES WITH ELECTRICAL DRAWINGS.
SEE ARCHITECTURE FOR LIGHT LAYOUT LOCATION. LIGHT FIXTURES TO BE CENTERED AND SYMMETRICALLY LOCATED
IN UNITS AND SHARED SPACES UNLESS NOTED OTHERWISE
5 PROVIDE DEFLECTION TRACKS AT TOP OF ALL COLD FORMED METAL FRAMING; SEE SHEET SERIES AE500
6 MAKE FACTORY EDGE WHERE TILE IS CUT TYPICAL FOR ALL LAY-IN ACOUSTICAL TILE WITH REGULAR EDGE
7 SEE SHEET SERIES A600 FOR FINISH MATERIAL SPECIFICATIONS
8 VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES A400's. CONTRACTOR TO VERIFY AND MAXIMIZE CEILING HEIGHT
IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
KEYED NOTES
09.24 ADD ALTERNATE 4 - 4" PREMIUM ACCOUSTIC FOAM PANELS APPLIED TO WALLS AND CIELING OF THE ACCOUSTICS
LAB 52B4
09.26 1'-6" X 6'-0" ACOUSTIC PANEL. ARMSTRONG TECTUM DIRECT-ATTACHED TO BOTTOM OF FLOOR DECK AS BASIS OF
DESIGN. PAINT TO MATCH DECK PAINT.
10.21 WALL MOUNTED PROJECTOR SCREEN, OFOI
10.22 RE-USED EXISTING BLACKOUT CURTAIN AND CEILING TRACK, CFCI
10.23 BACKDROP CANVAS CURTAIN AND CEILING TRACK, CFCI. ENSURE THAT THEY ARE STRUCTURALLY AND
SEISMICALLY SUPPORTED.
10.24 CEILING MOUNTED PROJECTOR, OFCI
10.26 RE-INSTALL POWER PAPER ROLLER, RE: ELECTRICAL PLANS.
10.32 BID ALTERNATE 6 - LIGHT FIXTURE STRUCTURE AND RAIL WITH OUTLET AND SINGLE ACCORDIAN ARM IN PHOTO
STUDIO 51. OWNER TO PROVIDE LIGHT, RE: SPECIFICATIONS
23.01 MECHANICAL DUCT, RE: MECHANICAL
23.02 MECHANICAL EQUIPMENT, RE: MECHANICAL
26.01 LIGHT FIXTURE, RE: ELECT.
26.06 DUPLEX POWER RECEPTACLE, RE: ELECTRICAL
26.09 HAIR LIGHT, RE: ELECTRICAL
26.10 DARK ROOM LIGHT, OFOI
26.13 CABLE TRAY BELOW THE LAY-IN CEILING. MOUNT TO THE FLOOR DECK ABOVE AT 9'-0" AFF. DESIGN STRURCTURAL
LOAD FOR 5LBS PER SQUARE FOOT.
26.15 WALL MOUNTED CLOCK. RE: ELECTRICAL DRAWINGS
26.17 BID ALTERNATE 7 - ADDITIONAL HAIR LIGHT IN PHOTO STUDIO 51, RE: SPECIFICATION
F
F
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
PLANRTARIUM RM
107
LIGHT TRAP
I-Y
HAZ. STORAGE
167
HAZ. STORAGE
166
ROCK LABORATORY
164
MEN'S T.R.
162
WOMEN'S T.R.
160
PIPE CHASE
I-Q
HALLWAY
1-T
LAB PREP ROOM
161
ELEVATOR
1-M
CUST.
147
STAIRWELL
1-P
PHYSICAL GEOLOGY ROOM
158
PHYSICAL SCIENCE DISPLAY
ROOM
156
SEISMOGRAPH ROOM
154
RESOURCE ROOM
150A
AUTO TUTORIAL ROOM
171
STORAGE
171A
LABORATORY RM
179
OFFICE
175
OFFICE
176
OFFICE
180
OFFICE
182
OFFICE
184
STORAGE RM
133
LECTURE HALL
172
SHOP RM
133A
PHYSICS CLASSROOM
105
OFFICE
112
OFFICE
114
OFFICE
116
OFFICE
118
OFFICE
118A
ADVANCED LAB
126
LECTURE HALL
127
LAB STORAGE RM
126A
ADVANCED LAB
128
ADVANCED LAB RM
129
LABORATORY
141
OFFICE
150
OFFICE
148
OFFICE
146
OFFICE
144
WOMEN'S RM
132
MEN'S RM
134
PHYSICS LECTURE HALL
131
LECTURE HALL
145 PREP/STORAGE RM
143
OFFICE
110
OFFICE
186
MINEROLOGY LAB
149
HALLWAY
I-N
HALLWAY
I-L
HALLWAY
I-G
HALLWAY
I-K
HALLWAY
I-F
HALLWAY
I-W
HALLWAY
I-D
UNISEX RM
136
STORAGE
172A
STORAGE
131A
VESTIBULE
I-A
STAIRWELL
I-C
STAIRWELL
I-B
OFFICE
142
HALLWAY
1-U
STAIRWELL
1-V
BDF
138
STAIRWELL
1-S
STAIRWELL
1-H
STAIRWELL
1-E
ELEVATOR
1-J
09.27 09.27
ACT-01:
2' x 2' LAY-IN ACOUSTICAL TILE & SUSPENSION SYSTEM, RE: FINISH SCHEDULE
CEILING LEGEND
TYPE A1
5/8" GYPSUM BOARD (PAINTED PNT-01 UNLESS NOTED ON PLAN) ON METAL STUD.
TYPE B1
5/8" GYPSUM BOARD (PAINTED PNT-01 UNLESS NOTED ON PLAN) ON METAL
SUSPENSION SYSTEM.
TYPE B2
EXPOSED STRUCTURE. PAINT PNT-02, RE: FINISH LEGEND
TYPE E-1
NOTE:
ALL DROPS NEED TO BE NON-COMBUSTIBLE METAL FRAMING OR LIGHT GAUGE METAL FRAMING AND
MEET L/360 STANDARD FOR ALLOWABLE DEFLECTION.
ACCOUSTIC FOAM ON 5/8" GYPSUM BOARD ON METAL SUSPENSION SYSTEM.
TYPE B3
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A131
LEVEL 01
RCP PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 01 REFLECTED CEILING PLAN
GENERAL NOTES - CEILING
1 VERIFY ALL MECHANICAL DUCT, GRILLE, DIFFUSER, AND VENT LOCATIONS WITH MECHANICAL DRAWINGS
2 CEILING GRID SHOWN IS ONLY A GRAPHIC REPRESENTATION OF CEILING. CEILING PATTERN IS TO BE CENTERED IN THE
ROOM, UNLESS NOTED OTHERWISE. CONTRACTOR SHALL VERIFY ACTUAL GRID LAYOUT/LOCATION
3 VERIFY AND COORDINATE ALL MECHANICAL DUCT, GRILL DIFFUSER & LOCATIONS, VENTS, AND QUANTITY WITH
MECHANICAL PLANS
4 VERIFY ALL LIGHTS, SMOKE DETECTORS, AND EXIT DEVICE LOCATIONS AND QUANTITIES WITH ELECTRICAL DRAWINGS.
SEE ARCHITECTURE FOR LIGHT LAYOUT LOCATION. LIGHT FIXTURES TO BE CENTERED AND SYMMETRICALLY LOCATED
IN UNITS AND SHARED SPACES UNLESS NOTED OTHERWISE
5 PROVIDE DEFLECTION TRACKS AT TOP OF ALL COLD FORMED METAL FRAMING; SEE SHEET SERIES AE500
6 MAKE FACTORY EDGE WHERE TILE IS CUT TYPICAL FOR ALL LAY-IN ACOUSTICAL TILE WITH REGULAR EDGE
7 SEE SHEET SERIES A600 FOR FINISH MATERIAL SPECIFICATIONS
8 VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES A400's. CONTRACTOR TO VERIFY AND MAXIMIZE CEILING HEIGHT
IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
KEYED NOTES
09.27 REPLACE, PATCH AND REPAIR CEILING AS NEEDED. RE: FINISH SCHEDULE FOR PAINT.
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
INSTRUMENT RM
203A
CHEMISTRY STOCK RM
213
OFFICE
213A
CLASSROOM
270
CLASSROOM
268
MEN'S RM
266
WOMEN'S RM
264
OFFICE
252
OFFICE
253
OFFICE
250
OFFICE
248
OFFICE
246 OFFICE
244
OFFICE
242
OFFICE
240
OFFICE
238
WORK ROOM
243
OFFICE
236
OFFICE
234
OFFICE
239
OFFICE
237
OFFICE
235
OFFICE
233
OFFICE
232
CLASSROOM
255
CLASSROOM
277
OFFICE
259
OFFICE
261
OFFICE
263
OFFICE
265
MEN'S ROOM
226
WOMEN'S ROOM
220
GENERAL CHEM LAB
282
CHEM STOCK RM
282A
OFFICE
286
OFFICE
285
OFFICE
289 OFFICE
290
OFFICE
291
OFFICE
292
OFFICE
294
OFFICE
296
OFFICE
298
CHEMISTRY LAB
204
CHEMISTRY LAB
214
CHEMISTRY LAB
210
CHEMISTRY PREP RM
281
CLASSROOM
276
CUST RM
267
BDF RM
280
CUST RM
228
INSTRUMENT RM
203B
CLASSROOM
229
CLASSROOM
279
CLASSROOM
297 CLASSROOM
299
CHEMISTRY LAB
203
STORAGE
258
STORAGE RM
277A
WORK ROOM
287A
SEC/ RECEP RM
287
HALLWAY
2-U HALLWAY
2-D
HALLWAY
2-F
HALLWAY
2-S
LOUNGE
2-V
HALLWAY
2-J
HALLWAY
2-M
SECRETARY/RECEPTION RM
230
HALLWAY
2-K
CLASSROOM
260
CLASSROOM
262
HALLWAY
2-L
CUST STOR
216
STAIRWELL
2-HELEVATOR
2-G
STAIRWELL
2-T
HALLWAY
2-B
STAIRWELL
2-A
STAIRWELL
2-C
BIO-CHEMISTRY LAB
272
A1 9' - 0"
23.04
B3
A514
________________TYP
26.11
09.27
23.01
TYP
26.01
TYP
26.01
TYP
26.12
TYP
26.06TYP
TYP
23.04
26.15
23.01
A1
A514
________________
08.04
ACT-01:
2' x 2' LAY-IN ACOUSTICAL TILE & SUSPENSION SYSTEM, RE: FINISH SCHEDULE
CEILING LEGEND
TYPE A1
5/8" GYPSUM BOARD (PAINTED PNT-01 UNLESS NOTED ON PLAN) ON METAL STUD.
TYPE B1
5/8" GYPSUM BOARD (PAINTED PNT-01 UNLESS NOTED ON PLAN) ON METAL
SUSPENSION SYSTEM.
TYPE B2
EXPOSED STRUCTURE. PAINT PNT-02, RE: FINISH LEGEND
TYPE E-1
NOTE:
ALL DROPS NEED TO BE NON-COMBUSTIBLE METAL FRAMING OR LIGHT GAUGE METAL FRAMING AND
MEET L/360 STANDARD FOR ALLOWABLE DEFLECTION.
ACCOUSTIC FOAM ON 5/8" GYPSUM BOARD ON METAL SUSPENSION SYSTEM.
TYPE B3
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A132
LEVEL 02
RCP PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 02 REFLECTED CEILING PLAN
GENERAL NOTES - CEILING
1 VERIFY ALL MECHANICAL DUCT, GRILLE, DIFFUSER, AND VENT LOCATIONS WITH MECHANICAL DRAWINGS
2 CEILING GRID SHOWN IS ONLY A GRAPHIC REPRESENTATION OF CEILING. CEILING PATTERN IS TO BE CENTERED IN THE
ROOM, UNLESS NOTED OTHERWISE. CONTRACTOR SHALL VERIFY ACTUAL GRID LAYOUT/LOCATION
3 VERIFY AND COORDINATE ALL MECHANICAL DUCT, GRILL DIFFUSER & LOCATIONS, VENTS, AND QUANTITY WITH
MECHANICAL PLANS
4 VERIFY ALL LIGHTS, SMOKE DETECTORS, AND EXIT DEVICE LOCATIONS AND QUANTITIES WITH ELECTRICAL DRAWINGS.
SEE ARCHITECTURE FOR LIGHT LAYOUT LOCATION. LIGHT FIXTURES TO BE CENTERED AND SYMMETRICALLY LOCATED
IN UNITS AND SHARED SPACES UNLESS NOTED OTHERWISE
5 PROVIDE DEFLECTION TRACKS AT TOP OF ALL COLD FORMED METAL FRAMING; SEE SHEET SERIES AE500
6 MAKE FACTORY EDGE WHERE TILE IS CUT TYPICAL FOR ALL LAY-IN ACOUSTICAL TILE WITH REGULAR EDGE
7 SEE SHEET SERIES A600 FOR FINISH MATERIAL SPECIFICATIONS
8 VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES A400's. CONTRACTOR TO VERIFY AND MAXIMIZE CEILING HEIGHT
IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
KEYED NOTES
08.04 BID ALTERNATE 1 - ROLLER WINDOW SHADES IN THE BIO-CHEMISTRY LAB 272
09.27 REPLACE, PATCH AND REPAIR CEILING AS NEEDED. RE: FINISH SCHEDULE FOR PAINT.
23.01 MECHANICAL DUCT, RE: MECHANICAL
23.04 BID ALTERNATE 2 - SNORKEL IN BIO-CHEMISTRY LAB 272, INCLUDING DUCTS TO SNORKELS. USE LABS-USA FX2
EXHAUST SNORKEL CHEM MODEL AS BASIS OF DESIGN. LENGTH OF ARM, MOUNTING STYLE, AND HOOD TYPE TBD.
RE: MECHANICAL EXHAUST.
26.01 LIGHT FIXTURE, RE: ELECT.
26.06 DUPLEX POWER RECEPTACLE, RE: ELECTRICAL
26.11 ELECTRICAL POWER AND DATA CEILING PANEL, RE: ELECTRICAL
26.12 TELEVISION, OFOI. RE: RCP AND DETAIL
26.15 WALL MOUNTED CLOCK. RE: ELECTRICAL DRAWINGS
CASEWORK TAG101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
C
D
E
4 5 6
A411AE5
A411BB2 B1
A411B
E5
E1E4
E3
D1
E1
COMPUTER LAB
59
EQUIP / CHECK OUT
59A
PHOTO STUDIO
51
STORAGE
59B
OFFICE
57
OFFICE
55
DARK ROOM
59D
VESTIBULE
59C
FILM
59E
STORAGE
51A
E2
A411A
D3
A411B
D2
C1
D1D4
A411AD4
A411A D5
A411B
E3
A411B
C3
C4
A411BB4
CHANGING
51BB3
A411AC5A411AC5
MI
R
22.05
26.08
A411A D4
(OPP)
10.26
10.23
10.22
(ABOVE)
24
"
1'
-
2
"
48"
36"
24
"
24"
09.29
09.29
09.30
IN BACKGROUND 34"90"
4'
-
0
"
E1
A581
________________
59A.1 51.1
RE: FLOOR PLAN
BACKGROUND
34
"
11.14
33"30"30"30"30"30"30"FILLER
212212 212 212 212 212 212
59C
PL-01
PL-02
WB-02
34
"
FILLER 30"30"30"30"30"30"
26.15
212 212 212 212 212 212
06.03
PL-02
PL-01 WB-02
5'
-
0
"
IN BACKGROUND
CL EQEQ
11.04
59.1 59.2
10.25
4'
-
0
"
18"9"
CL
2' - 11 7/8"
5'
-
0
"
CL
59A.2
E1
A581
________________
4'
-
0
"
10.25
E1
A581
________________
18"9"
CL
EQ EQ
34
"
SS-01
D3
A581
________________
1. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK.
2. DO NOT SCALE DRAWINGS
3. RE: SHEET G011 FOR TYPICAL MOUNTAIN HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-
MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT.
4. UPPER, LOWER, AND TALL CABINETS NOT TO EXCEED 36" IN WIDTH, UNLESS NOTED OTHERWISE.
5. UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE CABINETS - TYP.
6. ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE MOUNTED HORIZONTALLY
7. PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8. PROVIDE ALUMINUM EDGE MOLDING @ ALL TILE TO H.M. DOOR TRANSITIONS
9. PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS. RE: FINISH SCHEDULE
10. PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS. RE: FINISH SCHEDULE
11. ALL EXPOSED STEEL COLUMNS TO BE PAINTED TO MATCH ADJACENT WALL
12. ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
13. COUNTERTOP EDGE PROFILES TO BE SQUARE EDGE. IF SHOWN IN ELEVATION, PROVIDE 4" BACKSPLASH
14. ALL WOOD GRAIN TO RUN VERTICALLY, UNLESS NOTED OTHERWISE
15. CALLED OUT RESTROOM ACCESSORIES TO BE INSTALLED AT EVERY STALL
16. ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
17. PROVIDE MILLWORK LOCKS WITH CAMPUS STANDARD LOCKS WHERE INDICATED WITH LOCK SYMBOL AT
MILLWORK ELEVATION
GENERAL NOTES
OPEN TO BEYOND
34
"
48"48"
250 250 PL-01
PL-02
WB-02
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A411A
ENLARGED
PLANS AND
INTERIOR
ELEVATIONS
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
KEYED NOTES
06.03 TECH STATION, OFOI
09.29 LEVEL 5 WALL FINISH. WALL TO RECEIVE PHOTO BACKDROP PAINT, RE: FINISH SCHEDULE
09.30 PAINT ELECTRICAL PANEL, PNT-01, RE: FINISH SCHEDULE
10.22 RE-USED EXISTING BLACKOUT CURTAIN AND CEILING TRACK, CFCI
10.23 BACKDROP CANVAS CURTAIN AND CEILING TRACK, CFCI. ENSURE THAT THEY ARE STRUCTURALLY AND SEISMICALLY
SUPPORTED.
10.25 MARKER BOARD, 4'X4', OFCI
10.26 RE-INSTALL POWER PAPER ROLLER, RE: ELECTRICAL PLANS.
11.04 FLAT PANEL TV, OFCI, 3/4" BLOCKING AT ALL LOCATIONS
11.14 LARGE ROUND WASTE BIN
22.05 FLOOR SINK, RE: PLUMBING
26.08 LIGHT INDICATOR, RE: ELECTRICAL
26.15 WALL MOUNTED CLOCK. RE: ELECTRICAL DRAWINGS
PL-01 PLASTIC LAMINATE, CABINETS, RE: FINISH SCHEDULE
PL-02 PLASTIC LAMINATE, COUNTERTOP, RE: FINISH SCHEDULE
SS-01 EPOXY RESIN COUNTERTOP, RE: FINISH SCHEDULE
WB-02 WALL BASE, RE: FINISH SCHEDULE
1/4" = 1'-0"A1 LEVEL 00 ENLARGED FLOOR PLAN- PHOTOGRAPHY LAB
1/4" = 1'-0"E1 COMPUTER LAB 59 - NORTH
1/4" = 1'-0"E3 COMPUTER LAB 59 - EAST
1/4" = 1'-0"E5 COMPUTER LAB 59 - SOUTH
1/4" = 1'-0"D1 COMPUTER LAB 59 - WEST
1/4" = 1'-0"D3 EQUIP / CHECK OUT 59A - EAST
1/4" = 1'-0"D4 OFFICE 55 - SOUTH
1/4" = 1'-0"D5 FILM 59E - NORTH
1/4" = 1'-0"C5 COMPUTER LAB 59 - ISLAND
CASEWORK TAG101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
26.15
34
"
OPEN TO BEYOND
FILLER 33"30"30"36"
END PANEL END PANEL
16"
212 212 212 152
10.06
SS-01
PL-01 WB-02
10.31 TYP (6)
WB-01WB-02
PNT-01
COLUMN 36"36"36"FILLER
250250212
36
"
SS-01
PL-01WB-02
10.31TYP (3)
FILLER 40"40"40"40"FILLER
31"31"31"31"A581
C1
C3
A581
________________
SS-01
PL-01
WB-02
250250
36
"
A2
A581
________________
61
"
101"
22.11
PL-01
CL
EQ EQ
5'
-
0
"
CL
CL
EQ EQ
CL
EQ EQ
11.04
11.0911.09
26.01
B1
A514
B2
A514
51.2 51B 51A
WB-03WB-01WB-01
09.29
PNT-04
06.03
51.1
WB-03 WB-01
09.29
PNT-04
59A.2
E1
A581
________________
48
"
7' - 6"7' - 2"
D2
A581
________________
20
"
16
"
16
"
16
"
247"
51A
FILLER 48"44"48"FILLER
402402402
PL-01
WB-02
OPEN TO
BEYOND
77"
D3
A581
________________
36"36"FILLER
30
"
24
"
30
"
302302
C-13
PL-02
PL-01
34
"
6"
FILLER 30"33"FILLER
212 152
10.06
10.01
PL-02
PL-01
WB-02
26.01
CLCL1' - 4"1' - 1"
10.03
4'
-
0
"
E1
A581
________________
1' - 2"1' - 6"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A411B
INTERIOR
ELEVATIONS
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
GENERAL NOTES - INTERIOR ELEVATIONS
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE DRAWINGS
3 RE: SHEET SERIES G000 FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED
ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
4 UPPER, LOWER, AND TALL MILLWORK CABINETS NOT TO EXCEED 36" IN WIDTH, UNLESS NOTED OTHERWISE
5 UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE CABINETS - TYPICAL
6 ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE HORIZONTALLY ALIGNED AND MOUNTED
HORIZONTALLY
7 PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8 PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS; SEE DETAILS AND FINISH SCHEDULE
9 PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS; SEE DETAILS AND FINISH SCHEDULE
10 ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
11 RE ACCESSORY SCHEDULE FOR WHO PROVIDES RESTROOM ACCESSORIES
12 RE: SHEET A700 SERIES FOR MATERIAL SPECIFICATIONS
13 RE: SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
14 RE: SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
15 RE: SHEET SERIES A500 FOR CASEWORK DETAILS
KEYED NOTES
06.03 TECH STATION, OFOI
09.29 LEVEL 5 WALL FINISH. WALL TO RECEIVE PHOTO BACKDROP PAINT, RE: FINISH SCHEDULE
10.01 MIRROR, RE: ACCESSORY SCHEDULE
10.03 SOAP DISPENSER, RE: ACCESSORY SCHEDULE
10.06 PAPER TOWEL DISPENSER, RE: ACCESSORY SCHEDULE
10.31 CABINET LOCK. RE: HARDWARE SCHEDULE
11.04 FLAT PANEL TV, OFCI, 3/4" BLOCKING AT ALL LOCATIONS
11.09 WHITE BOARD, OFOI, CONTRACTOR TO PROVIDE BLOCKING
22.11 PHOTO PROCESSING SINK, RE: PLUMBING
26.01 LIGHT FIXTURE, RE: ELECT.
26.15 WALL MOUNTED CLOCK. RE: ELECTRICAL DRAWINGS
PL-01 PLASTIC LAMINATE, CABINETS, RE: FINISH SCHEDULE
PL-02 PLASTIC LAMINATE, COUNTERTOP, RE: FINISH SCHEDULE
PNT-01 PAINTED GYP, RE: FINISH SCHEDULE
PNT-04 PAINTED GYP, RE: FINISH SCHEDULE
SS-01 EPOXY RESIN COUNTERTOP, RE: FINISH SCHEDULE
WB-01 WALL BASE, RE: FINISH SCHEDULE
WB-02 WALL BASE, RE: FINISH SCHEDULE
WB-03 WALL BASE, RE: FINISH SCHEDULE
1/4" = 1'-0"E1 DARK ROOM 59D - NORTH
1/4" = 1'-0"E2 DARK ROOM 59D - EAST ONE
1/4" = 1'-0"E3 DARK ROOM 59D - EAST TWO
1/4" = 1'-0"E4 DARK ROOM 59D - SOUTH
1/4" = 1'-0"E5 DARK ROOM 59D - WEST
1/4" = 1'-0"D1 PHOTO STUDIO 51 - NORTH
1/4" = 1'-0"D2 PHOTO STUDIO 51 - EAST
1/4" = 1'-0"D4 PHOTO STUDIO 51 - SOUTH
1/4" = 1'-0"C1 PHOTO STUDIO 51 - WEST
1/4" = 1'-0"C3 STORAGE 51A - EAST
1/4" = 1'-0"C4 STORAGE 51A - WEST
1/4" = 1'-0"B1 STORAGE 59B - NORTH
1/4" = 1'-0"B2 STORAGE 59B - SOUTH
1/4" = 1'-0"B4 CHANGING 51B - SOUTH
1/4" = 1'-0"B3 CHANGING 51B - EAST
B
6 7
A412
E2
E1
D1
E4
A412D4
D8
D3
PHYSICS LAB
52
ACOUSTICS STUDIO
52B
STORAGE
52C
OPTICS LAB
52A
A412
C3
C1
C2
2'
-
0
"
2'-0"
1'
-
8
"
22.18 22.18
22.17
14
"
1' - 2"
1'
-
2
"
1'
-
2
"
1'
-
2
"
1'
-
2
"
2'
-
0
"
3'
-
3
"
14"
09.24
CASEWORK TAG101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
52.2
22.17
05.15
26.13
52C 52.1
34
"
211
117"20"30"33"
212 152
RE: FLOOR PLAN
IN FOREGROUND
PL-01
SS-01
A2
A581
________________
PL-01
20
"
16
"
16
"
16
"
60
"
16
"
A2
A581
________________
PL-01
WB-02
52B
05.15
26.13
60
"
16
"
137 1/8"
A2
A581
________________
PL-01
PL-01
TYP
60
"
16
"
132 1/8"25 7/8"132 1/8"47 7/8"162"16 1/4"
A2
A581
________________
TYP
D2
A581
________________
72
"
16
"
72"
PL-01
10.25
CL
EQ EQ
4'
-
8
"
CL
72"
D2
A581
________________
54
"
16
"
54"
417
PL-01
D2
A581
________________
20
"
16
"
16
"
16
"
D2
A581
________________
20
"
16
"
16
"
16
"
52C
16"D2
A581
________________
20
"
16
"
16
"
16
"
1. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK.
2. DO NOT SCALE DRAWINGS
3. RE: SHEET G011 FOR TYPICAL MOUNTAIN HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-
MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT.
4. UPPER, LOWER, AND TALL CABINETS NOT TO EXCEED 36" IN WIDTH, UNLESS NOTED OTHERWISE.
5. UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE CABINETS - TYP.
6. ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE MOUNTED HORIZONTALLY
7. PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8. PROVIDE ALUMINUM EDGE MOLDING @ ALL TILE TO H.M. DOOR TRANSITIONS
9. PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS. RE: FINISH SCHEDULE
10. PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS. RE: FINISH SCHEDULE
11. ALL EXPOSED STEEL COLUMNS TO BE PAINTED TO MATCH ADJACENT WALL
12. ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
13. COUNTERTOP EDGE PROFILES TO BE SQUARE EDGE. IF SHOWN IN ELEVATION, PROVIDE 4" BACKSPLASH
14. ALL WOOD GRAIN TO RUN VERTICALLY, UNLESS NOTED OTHERWISE
15. CALLED OUT RESTROOM ACCESSORIES TO BE INSTALLED AT EVERY STALL
16. ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
17. PROVIDE MILLWORK LOCKS WITH CAMPUS STANDARD LOCKS WHERE INDICATED WITH LOCK SYMBOL AT
MILLWORK ELEVATION
GENERAL NOTES
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A412
ENLARGED
PLANS AND
INTERIOR
ELEVATIONS
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
KEYED NOTES
05.15 ANGLE IRON AIR TANK SUPPORT BY CFCI, BASIS OF DESIGN: GLOBAL INDUSTRIES WALL MOUNT 3 CYLINDER BRACKET
09.24 ADD ALTERNATE 4 - 4" PREMIUM ACCOUSTIC FOAM PANELS APPLIED TO WALLS AND CIELING OF THE ACCOUSTICS LAB
52B4
10.25 MARKER BOARD, 4'X4', OFCI
22.17 EMERGENCY SHOWER AND EYE WASH STATION, RE: PLUMBING
22.18 EXISTING FLOOR DRAIN, RE: PLUBMING
26.13 CABLE TRAY BELOW THE LAY-IN CEILING. MOUNT TO THE FLOOR DECK ABOVE AT 9'-0" AFF. DESIGN STRURCTURAL LOAD
FOR 5LBS PER SQUARE FOOT.
PL-01 PLASTIC LAMINATE, CABINETS, RE: FINISH SCHEDULE
SS-01 EPOXY RESIN COUNTERTOP, RE: FINISH SCHEDULE
WB-02 WALL BASE, RE: FINISH SCHEDULE
1/4" = 1'-0"1 LEVEL 00 ENLARGED FLOOR PLAN - PHYSICS
1/4" = 1'-0"E1 PHYSICS LAB 52 - NORTH
1/4" = 1'-0"E2 PHYSICS LAB 52 - EAST
1/4" = 1'-0"E4 PHYSICS LAB 52 - SOUTH
1/4" = 1'-0"D1 PHYSICS LAB 52 - WEST
1/4" = 1'-0"D3 OPTICS LAB 52A - NORTH
1/4" = 1'-0"D4 OPTICS LAB 52A - SOUTH
1/4" = 1'-0"D8 OPTICS LAB 52A - WEST
1/4" = 1'-0"C1 STORAGE 52C - EAST
1/4" = 1'-0"C2 STORAGE 52C - SOUTH
1/4" = 1'-0"C3 STORAGE 52C - WEST
1. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK.
2. DO NOT SCALE DRAWINGS
3. RE: SHEET G011 FOR TYPICAL MOUNTAIN HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-
MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT.
4. UPPER, LOWER, AND TALL CABINETS NOT TO EXCEED 36" IN WIDTH, UNLESS NOTED OTHERWISE.
5. UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE CABINETS - TYP.
6. ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE MOUNTED HORIZONTALLY
7. PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8. PROVIDE ALUMINUM EDGE MOLDING @ ALL TILE TO H.M. DOOR TRANSITIONS
9. PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS. RE: FINISH SCHEDULE
10. PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS. RE: FINISH SCHEDULE
11. ALL EXPOSED STEEL COLUMNS TO BE PAINTED TO MATCH ADJACENT WALL
12. ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
13. COUNTERTOP EDGE PROFILES TO BE SQUARE EDGE. IF SHOWN IN ELEVATION, PROVIDE 4" BACKSPLASH
14. ALL WOOD GRAIN TO RUN VERTICALLY, UNLESS NOTED OTHERWISE
15. CALLED OUT RESTROOM ACCESSORIES TO BE INSTALLED AT EVERY STALL
16. ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
17. PROVIDE MILLWORK LOCKS WITH CAMPUS STANDARD LOCKS WHERE INDICATED WITH LOCK SYMBOL AT
MILLWORK ELEVATION
GENERAL NOTES
CASEWORK TAG101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
1
C
D
E
2 3
A413D3
A413 E1A413D1
C4
E4
BIO-CHEMISTRY LAB
272
22.17
A413 E3 A413D4
36"36"
36"36"
31"
30"
26.16
26.16
A601
C1
A1
A601
A2
A601
A601
B2
A601
B3
33"33"
CASEWORK
MATCH EXISTING
100 100
26.1226.1226.12
02.42
10.06 10.06WV-01
SS-01
WB-02
10.30
26.0626.06 26.0602.41
02.41
02.40
33.03
6.05
21.02
26.15
42"
FILLER
33"33"33"33"
212 212 212 272
05.15
SS-01
PL-01 WB-02 10.31
TYP (6)
OPEN TO BEYOND
63"36"
34"
100 100
23.0523.0402.43
02.42 WV-01 SS-01WB-02
22.16 02.4102.40
30"
37"37"37"37"37"
100 100 100
26.1226.1226.12
09.28
WB-02
SS-01
SS-01
PL-01
OPEN KNEE
SPACE
OPEN KNEE
SPACE
10.30
A2
A601
B2
A601
B3
A601
A1
A514
________________
34"
18"63"18"
230230
SF1
3'-5 1/2"
3'-6 1/2"
4'-0"
10.06
36 3/4"23"
WB-02OPEN KNEE SPACE
PL-01
SS-01
A2
A581
________________PL-01
10.31
TYP (2)
A601
C6
33"33"33"33"
END PANEL FILLER
FOREGROUND
42"
OPEN TO
BEYOND
272 212 212 212
10.25
CLEQ EQ
SS-01
PL-01
OPEN TO BEYOND
WB-02
10.31
TYP (6)
C-13 C-13 272
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A413
ENLARGED
PLANS AND
INTERIOR
ELEVATIONS
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
KEYED NOTES
02.40 EXISTING AIR AND GAS LINES TO REMAIN.
02.41 EXISTING CUP SINK AND FAUCET TO REMAIN.
02.42 EXISTING COUNTERTOP AND UNDERCOUNTER CABINETS TO REMAIN.
02.43 EXISTING UPPER SHELVING TO REMAIN.
05.15 ANGLE IRON AIR TANK SUPPORT BY CFCI, BASIS OF DESIGN: GLOBAL INDUSTRIES WALL MOUNT 3 CYLINDER BRACKET
6.05 NEW COUNTERTOP AND BACKSPLASH
09.28 NEW SOLID SURFACE WINDOW SILL, RE: FINISH SCHEDULE
10.06 PAPER TOWEL DISPENSER, RE: ACCESSORY SCHEDULE
10.25 MARKER BOARD, 4'X4', OFCI
10.30 WALL MOUNTED FIRE EXTINGUISHER
10.31 CABINET LOCK. RE: HARDWARE SCHEDULE
21.02 FIRE BLANKET CABINET, RE: CODE REVIEW PLAN. VERIFY LOCATION WITH OWNER PRIOR TO PLACEMENT.
22.16 SINK, RE: PLUMBING
22.17 EMERGENCY SHOWER AND EYE WASH STATION, RE: PLUMBING
23.04 BID ALTERNATE 2 - SNORKEL IN BIO-CHEMISTRY LAB 272, INCLUDING DUCTS TO SNORKELS. USE LABS-USA FX2
EXHAUST SNORKEL CHEM MODEL AS BASIS OF DESIGN. LENGTH OF ARM, MOUNTING STYLE, AND HOOD TYPE TBD. RE:
MECHANICAL EXHAUST.
23.05 RELOCATED EXISTING FUME HOODS, RE: MECHANICAL
26.06 DUPLEX POWER RECEPTACLE, RE: ELECTRICAL
26.12 TELEVISION, OFOI. RE: RCP AND DETAIL
26.15 WALL MOUNTED CLOCK. RE: ELECTRICAL DRAWINGS
26.16 OUTLETS ON THE BACK OF CASEWORK. COORDINATE WITH ELECTRICAL.
33.03 NEW AIR AND GAS LINES AND NOZZLES
PL-01 PLASTIC LAMINATE, CABINETS, RE: FINISH SCHEDULE
SS-01 EPOXY RESIN COUNTERTOP, RE: FINISH SCHEDULE
WB-02 WALL BASE, RE: FINISH SCHEDULE
WV-01 WOOD VENEER, CABINETS, RE: FINISH SCHEDULE
1/4" = 1'-0"1 LEVEL 02 ENLARGED FLOOR PLAN - BIO-CHEMISTRY LAB
1/4" = 1'-0"E1 BIO-CHEMISTRY LAB 272 - NORTH ONE
1/4" = 1'-0"E3 BIO-CHEMISTRY LAB 272 - NORTH TWO
1/4" = 1'-0"E4 BIO-CHEMISTRY LAB 272 - EAST
1/4" = 1'-0"D1 BIO-CHEMISTRY LAB 272 - SOUTH ONE
1/4" = 1'-0"D3 BIO-CHEMISTRY LAB 272 - SOUTH TWO
1/4" = 1'-0"D4 BIO-CHEMISTRY LAB 272 - SOUTH THREE
1/4" = 1'-0"C4 BIO-CHEMISTRY LAB 272 - WEST
CASEWORK TAG101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
11.09 11.09
12' - 0"12' - 0"1' - 10 1/2"
4' - 8"
CL4' - 0"
10.24 26.01
EQEQ
4' - 0"
4' - 8"
CL11.09 11.09
26.01
4' - 0"
CL
EQ EQ
CL
EQ EQ
4' - 8"
CL
50
11.09 11.09
11.09 11.09
12' - 0"6' - 0"1' - 7 1/2"
4' - 0"
4' - 8"
CL
10.24
B3
A514
________________
26.01 300M
54"
54"
25"
PL-01
OPEN TO BEYOND
55 57 59.2 59.1 69
09.3021.01
44 1/2"
02.2710.06
34"
152
SS-01WV-01
40"36"24"24"24"24"24"24"24"FILLERFILLER24"24"24"24"24"24"24"
A1
A581
________________A1
A581
________________WB-0210.31
TYP (16)
A4
A581
________________
22.01
FRP-01
5' - 0"
3' - 0"
22.19
4' - 0"
CL
1' - 10"
10.33
5' - 0"
3' - 0"
22.01
FRP-01
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A414
INTERIOR
ELEVATIONS
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
GENERAL NOTES - INTERIOR ELEVATIONS
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE DRAWINGS
3 RE: SHEET SERIES G000 FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED
ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
4 UPPER, LOWER, AND TALL MILLWORK CABINETS NOT TO EXCEED 36" IN WIDTH, UNLESS NOTED OTHERWISE
5 UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE CABINETS - TYPICAL
6 ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE HORIZONTALLY ALIGNED AND MOUNTED
HORIZONTALLY
7 PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8 PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS; SEE DETAILS AND FINISH SCHEDULE
9 PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS; SEE DETAILS AND FINISH SCHEDULE
10 ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
11 RE ACCESSORY SCHEDULE FOR WHO PROVIDES RESTROOM ACCESSORIES
12 RE: SHEET A700 SERIES FOR MATERIAL SPECIFICATIONS
13 RE: SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
14 RE: SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
15 RE: SHEET SERIES A500 FOR CASEWORK DETAILS
KEYED NOTES
02.27 EXISTING UPPER CABINETS TO REMAIN AND TO BE PROTECTED DURING CONSTRUCTION.
09.30 PAINT ELECTRICAL PANEL, PNT-01, RE: FINISH SCHEDULE
10.06 PAPER TOWEL DISPENSER, RE: ACCESSORY SCHEDULE
10.24 CEILING MOUNTED PROJECTOR, OFCI
10.31 CABINET LOCK. RE: HARDWARE SCHEDULE
10.33 MOP/BROOM HOLDER, OFOI
11.09 WHITE BOARD, OFOI, CONTRACTOR TO PROVIDE BLOCKING
21.01 FIRE EXTINGUISHER CABINET, RE: CODE REVIEW PLAN. VERIFY LOCATION WITH OWNER PRIOR TO PLACEMENT.
22.01 MOP SINK, RE: PLUMBING
22.19 CHEMICAL STATION, RE: PLUMBING
26.01 LIGHT FIXTURE, RE: ELECT.
FRP-01 FIBER REINFORCED PANEL, RE: FINISH SCHEDULE
PL-01 PLASTIC LAMINATE, CABINETS, RE: FINISH SCHEDULE
SS-01 EPOXY RESIN COUNTERTOP, RE: FINISH SCHEDULE
WB-02 WALL BASE, RE: FINISH SCHEDULE
WV-01 WOOD VENEER, CABINETS, RE: FINISH SCHEDULE
1/4" = 1'-0"E1 CLASSROOM 50 - NORTH
1/4" = 1'-0"E2 CLASSROOM 50 - EAST
1/4" = 1'-0"E4 CLASSROOM 50 - SOUTH
1/4" = 1'-0"D1 CLASSROOM 50 - WEST
1/4" = 1'-0"D2 VESTIBULE 0-H - NORTH
1/4" = 1'-0"C1 HALLWAY 0-C - EAST
1/4" = 1'-0"D3 PHYSICAL GEOLOGY ROOM 158 - EAST
1/4" = 1'-0"B1 CUST RM 68 - SOUTH
1/4" = 1'-0"B2 CUST RM 68 - WEST
E
F
4 5
MEN'S RM
134
UNISEX RM
136
WOMEN'S RM
132
A415E3 E1
E4
E2
A415D4 E5
C1
D2
A415 D1
D3
D5
C2
A415 C4
C5
B2
B3
A415 C3B1
F
5
A415D4
SI
M
E5
SI
M
D2SIM
C1 SIM
A415
C2 SIM
D3SIM
D5
SI
M
D1
SI
M
A415B2
SI
M
B3 SIM
C4
SI
M
C5SIM
A415 C3
SI
M
B1
SI
M
1. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK.
2. DO NOT SCALE DRAWINGS
3. RE: SHEET G011 FOR TYPICAL MOUNTAIN HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-
MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT.
4. UPPER, LOWER, AND TALL CABINETS NOT TO EXCEED 36" IN WIDTH, UNLESS NOTED OTHERWISE.
5. UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE CABINETS - TYP.
6. ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE MOUNTED HORIZONTALLY
7. PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8. PROVIDE ALUMINUM EDGE MOLDING @ ALL TILE TO H.M. DOOR TRANSITIONS
9. PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS. RE: FINISH SCHEDULE
10. PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS. RE: FINISH SCHEDULE
11. ALL EXPOSED STEEL COLUMNS TO BE PAINTED TO MATCH ADJACENT WALL
12. ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
13. COUNTERTOP EDGE PROFILES TO BE SQUARE EDGE. IF SHOWN IN ELEVATION, PROVIDE 4" BACKSPLASH
14. ALL WOOD GRAIN TO RUN VERTICALLY, UNLESS NOTED OTHERWISE
15. CALLED OUT RESTROOM ACCESSORIES TO BE INSTALLED AT EVERY STALL
16. ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
17. PROVIDE MILLWORK LOCKS WITH CAMPUS STANDARD LOCKS WHERE INDICATED WITH LOCK SYMBOL AT
MILLWORK ELEVATION
GENERAL NOTES
CASEWORK TAG101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
5' - 4"
CLCL
2' - 9 1/2"0' - 9 1/2"
E6
A571
________________
E4
A571
________________TL-02
TL-03
PNT-01
10.10
10.16
10.05
10.29
5' - 4"
D138
E6
A571
________________
E4
A571
________________
TL-03
TL-02
PNT-01
5' - 4"
E6
A571
________________
E4
A571
________________
TL-03
TL-02
PNT-01
CL
4' - 6"
10.06
24"
6"
34"
1' - 6 1/2"
5' - 4"
CL
E6
A571
________________
E4
A571
________________TL-02
TL-03
PNT-01
10.27
10.02
22.03
22.16
10.28
CL
2' - 6"
10.03
5' - 4"
1' - 5 3/8"3' - 1"
CL CL
RE: FLOOR PLAN
IN FOREGROUND
22.03
10.27
TYP (2)
TYP (2)
TL-02
TL-03
E6
A571
________________
E5
A571
________________
E4
A571
________________
PNT-01
OPEN TO
BEYOND
5' - 4"
E5
A571
________________
E6
A571
________________
E4
A571
________________
TL-03
TL-02
PNT-01
CL
1' - 10 1/2"
10.06
RE: FLOOR PLAN
IN BACKGROUND
E4
A571
________________
E6
A571
________________
E5
A571
________________
TL-03
TL-02
PNT-01
10.05
5' - 4"
D304
E4
A571
________________
E6
A571
________________
TL-03
TL-02
PNT-01
OPEN TO
BEYOND
5' - 4"
E6
A571
________________
E5
A571
________________
E4
A571
________________
TL-03
TL-02
PNT-01
5' - 4"
34"
6"
24"
CLCL
1' - 2 15/16"2' - 8 1/4"
E4
A571
________________
E5
A571
________________
E6
A571
________________
TL-03
TL-02
PNT-01
10.28
22.16
TYP (2)
TYP (2)
CL2' - 7"
10.03
5' - 4"
E6
A571
________________
E5
A571
________________
E4
A571
________________
PNT-01
TL-03
TL-02
CL
1' - 0"
10.03
OPEN TO
BEYOND
5' - 4"
E6
A571
________________
E5
A571
________________
E4
A571
________________
PNT-01
TL-03
TL-02
5' - 4"
E4
A571
________________
E6
A571
________________
PNT-01
TL-03
TL-02
OPEN TO
BEYOND
34"
6"
24"
CLCL
2' - 0 1/4"1' - 11 1/4"
E4
A571
________________
E5
A571
________________E5
A571
________________
E6
A571
________________
PNT-01
TL-03
TL-02
10.28
22.16
TYP (2)
TYP (2)
CL0' - 8"
5' - 4"
2' - 6 1/4"
CL
D307
E4
A571
________________
E6
A571
________________
E5
A571
________________
PNT-01
TL-02
10.05
CL0' - 10"
10.03
OPEN TO
BEYOND
5' - 4"
E6
A571
________________
E4
A571
________________
E5
A571
________________E5
A571
________________
TL-03
TL-02
PNT-01
1' - 5 1/2"3' - 0"3' - 1"
CL CLCL
5' - 4"
E6
A571
________________
E4
A571
________________TL-02
TL-03
PNT-01
10.27
22.03
TYP (3)
TYP (3)
5' - 4"
2' - 7 1/8"
CL
E5
A571
________________
E4
A571
________________
E6
A571
________________
TL-03
TL-02
PNT-01
10.05
CL2' - 2"
10.06
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A415
RESTROOM
ENLARGED
PLANS AND
INTERIOR
ELEVATIONS
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set1/4" = 1'-0"A1 LEVEL 01 ENLARGED FLOOR PLAN - RESTROOMS
1/4" = 1'-0"A3 LEVEL 02 ENLARGED FLOOR PLAN - RESTROOMS
KEYED NOTES
10.02 36" GRAB BAR, RE: ACCESSORY SCHEDULE
10.03 SOAP DISPENSER, RE: ACCESSORY SCHEDULE
10.05 TOILET PAPER DISPENSER, RE: ACCESSORY SCHEDULE
10.06 PAPER TOWEL DISPENSER, RE: ACCESSORY SCHEDULE
10.10 42" GRAB BAR, RE: ACCESSORY SCHEDULE
10.16 18" VERTICAL GRAB BAR, RE: ACCESSORY SCHEDULE
10.27 WALL MOUNTED TOILET SEAT PROTECTOR, OFCI
10.28 18"X24" WALL MOUNTED FRAMELES MIRROR, RE: ACCESSORY SCHEDULE
10.29 SANITARY NAPKIN DISPOSAL, RE: ACCESSORY SCHEDULE
22.03 TOILET FIXTURE, RE: PLUMBING
22.16 SINK, RE: PLUMBING
PNT-01 PAINTED GYP, RE: FINISH SCHEDULE
TL-02 GENERAL WALL TILE
TL-03 ACCENT WALL TILE
1/4" = 1'-0"E1 UNISEX RM 136 - NORTH
1/4" = 1'-0"E2 UNISEX RM 136 - EAST
1/4" = 1'-0"E3 UNISEX RM 136 - SOUTH
1/4" = 1'-0"E4 UNISEX RM 136 - WEST
1/4" = 1'-0"E5 MEN'S RM 134 - NORTH ONE
1/4" = 1'-0"D1 MEN'S RM 134 - NORTH TWO
1/4" = 1'-0"D2 MEN'S RM 134 - EAST ONE
1/4" = 1'-0"D3 MEN'S RM 134 - EAST TWO
1/4" = 1'-0"D4 MEN'S RM 134 - SOUTH ONE
1/4" = 1'-0"D5 MEN'S RM 134 - SOUTH TWO
1/4" = 1'-0"C1 MEN'S RM 134 - WEST ONE
1/4" = 1'-0"C2 MEN'S RM 134 - WEST TWO
1/4" = 1'-0"C3 WOMEN'S RM 132 - NORTH ONE
1/4" = 1'-0"C4 WOMEN'S RM 132 - NORTH TWO
1/4" = 1'-0"C5 WOMEN'S RM 132 - EAST
1/4" = 1'-0"B1 WOMEN'S RM 132 - SOUTH ONE
1/4" = 1'-0"B2 WOMEN'S RM 132 - SOUTH TWO
1/4" = 1'-0"B3 WOMEN'S RM 132 - WEST
LAYERS LEGEND
SA = GYPSUM BOARD BOTH SIDE OF CORE
SB = GYPSUM BOARD ONE SIDE OF CORE
SF = GYPSUM BOARD, ONE LAYER CORE SIDE, ONE LAYER PLYWOOD SIDE
SH = GYPSUM BOARD, ONE LAYER HAT CHANNEL SIDE
SG = GYPSUM BOARD, ONE LAYER CORE SIDE, ONE LAYER HAT CHANNEL SIDE
NON-FIRE RATED WALL TAG (description)
SA6a
CORE MATERIAL (SEE LEGEND)
LAYERS (SEE LEGEND)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
FIRE RATED WALL TAG (description)
FIRE RATING
1 SA6 a
CORE MATERIAL (SEE LEGEND)
LAYERS (SEE LEGEND)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
CORE SIZE LEGEND
C = CONCRETE WALLS, MASONRY
S = STEEL STUDS
CORE MATERIAL LEGEND
WALL TYPE HEAD CONDITION LEGEND
IF NULL = TYPICAL PARTITION FLOOR TO FLOOR/CEILING/ROOF
a = PARTITION EXTEND FROM FLOOR TO 6" ABOVE CEILING (SEE E4/A501)
b = ACOUSTIC PARTITION (SEE E5/A501)
c = 1 - HR FIRE RATED PARTITION
d = 2 - HR FIRE RATED PARTITION
STEEL STUDS
1 =A7/8"
3 = 2 1/2"
4 = 3 5/8"
6 = 6"
8 = 8"
SUPERSCRIPT NOTES -
A - HAT CHANNEL FURRING IN LIEU OF METAL STUD
B - IF WALL IS STRUCTURAL, DO NOT TAG WALL OR INCLUDE IN WALL TYPES
GYP BOARD SCHEDULE
5/8" GYPSUM BOARD
5/8" TYPE X GYPSUM BOARD
5/8" MOISTURE RESISTANCE AND MOLD-
RESISTANT GYPSUM BOARD (TYPE X WHERE FIRE
RATED)
5/8" GLASS MAT MOISTURE AND MOLD-RESISTANT
GYPSUM TILE BACKER (TYPE X WHERE FIRE RATED)
5/8" CEMENT BOARD
ALL PARTITIONS UNLESS NOTED OTHERWISE BELOW
FIRE RATED PARTITIONS
WET OR HIGH HUMIDITY, HEAVY MOISTURE EXPOSURE AREAS SUCH AS
TOILET ROOMS, SHOWERS, LOCKER ROOMS, AND JANITOR CLOSETS,
EXCEPT WHERE WALL TILE OCCURS. USE AT KITCHEN WALLS FROM
FLOOR TO 12" ABOVE COUNTERTOP, EXCEPT WHERE TILE BACKSPLASH
OCCURS.
LIMITED WATER EXPOSURE AREAS WHERE WALL TILE OCCURS, BEHIND
FIBERGLASS SHOWER ENCLOSURES, AND KITCHEN WALLS FROM FLOOR
TO 12" ABOVE COUNTERTOP WHERE TILE BACKSPLASH OCCURS
WET OR HIGH HUMIDITY, HEAVY MOISTURE EXPOSURE AREAS
WHERE WALL TILE OCCURS, EXCEPT AT BACKSPLASHES
1. AT FIRE RATED PARTITIONS WHERE CEMENT BOARD IS REQUIRED, PROVIDE CEMENT BOARD ON TOP OF TYPE X GYPSUM
BOARD, OR PROVIDE A TESTED FIRE-RESISTANCE DESIGN THAT ALLOWS REPLACEMENT OF THE TYPE X GYPSUM BOARD
WITH CEMENT BOARD.
2. REFER TO THE ENVIRONMENTAL CLASSIFICATIONS IN THE CURRENT EDITION OF THE TILE COUNCIL OF NORTH AMERICA
HANDBOOK FOR CERAMIC, GLASS AND STONE TILE INSTALLATION.
GYP BOARD NOTES
STEEL FRAMING
(RE: CORE SIZE LEGEND)
STEEL FRAMING
(RE: CORE SIZE LEGEND)
SEALANT (BOTH SIDES)
RUNNER TRACK
INSULATION TYPE AS INDICATED
IN SCHEDULE
SILL
PLAN
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
INTERIOR PARTITION
SA_
5/8" GYP. BOARD, TYPE X,
BOTH SIDES
STEEL FRAMING
(RE: CORE SIZE LEGEND)
STEEL FRAMING
(RE: CORE SIZE LEGEND)
SEALANT
RUNNER TRACK
INSULATION TYPE AS INDICATED
IN SCHEDULE
SILL
PLAN
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
INTERIOR PARTITION
SB_
5/8" GYP. BOARD, TYPE X
1/2"
FOR SB2 WALL TYPE HOLD
FRAMING 1/2" OFF OF
EXISISTING WALL TO LEAVE A
MINIMUM OF 3" BETWEEN
EXISTING WALL FACE AND
INSIDE FACE OF STUDS.
3" MIN.
CONCRETE MASONRY UNITS WITH
REINFORCING PER STRUCTURAL
SOLID GROUTED MASONRY
SILL
PLAN
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
INTERIOR PARTITION
CD_
CEILING AS SCHEDULED, REFER
TO REFLECTED CEILING PLAN
CONTINUOUS DEFLECTION
TRACK AND INNER SLIP TRACK
SCHEDULED WALL
STUD BRACING TO
STRUCTURE/DECK (ABOVE) AT
6' O.C. (ALTERNATING)
WALL TYPE
VARIES PER
1
3/4 MIN
2 MAX
SOUND ATTENUATION BATT AS
APPLICABLE
0' - 6"
ACOUSTIC SEALANT (BOTH
SIDES) IF APPLICABLE
INNER SLIP TRACK
SCHEDULED WALL
CONTINUOUS DEFLECTION TRACK
SOUND ATTENUATION BATT
AS APPLICABLE
SCHEDULED
FLOOR/CEILING/ROOF
STEEL FRAMING
(RE: CORE SIZE LEGEND)
STEEL FRAMING
(RE: CORE SIZE LEGEND)
SEALANT (BOTH SIDES)
RUNNER TRACK
INSULATION TYPE AS INDICATED
IN SCHEDULE
SILL
PLAN
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
INTERIOR PARTITION
SF_
5/8" GYP. BOARD, TYPE X,
BOTH SIDES
3/4" FIRE TREATED SHEATHING
SILL
PLAN
INSULATION TYPES AS
INDICATED IN SCHEDULE
SEALANT
BOTTOM TRACK
5/8" GYP. BOARD, TYPE X,
BOTH SIDES
STEEL FRAMING
(RE: CORE SIZE LEGEND)
STEEL FRAMING
(RE: CORE SIZE LEGEND)
RESILIENT CHANNEL @ 16" O.C.,
U.N.O., (RE: LEGEND)
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
INTERIOR PARTITION
SH_
SILL
PLAN
INSULATION TYPE AS
INDICATED IN SCHEDULE
SEALANT (BOTH SIDES)
BOTTOM TRACK
5/8" GYP. BOARD, TYPE X
STEEL FRAMING
(RE: CORE SIZE LEGEND)
STEEL FRAMING
(RE: CORE SIZE LEGEND)
RESILIENT CHANNEL @ 16" O.C.,
U.N.O., (RE: LEGEND)
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
INTERIOR PARTITION
SG_
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A501
WALL
ASSEMBLIES
- INTERIOR
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
GENERAL NOTES - PARTITIONS
1. REFER TO DIMENSION PLANS FOR WALL TYPE LOCATIONS
2. REFER TO SCHEDULES & DETAILS FOR FINISHES. WALL TYPES REFER TO BASE WALL ONLY.
3. "LINE OF STRUCTURE" AS SHOWN AT THE HEAD CONDITIONS OF EACH WALL TYPE IS DIAGRAMMATIC ONLY AND DOES
NOT INDICATE THE EXACT CONSTRUCTION CONDITION. RATED WALLS ARE TO TERMINATE AT STRUCTURAL MEMBERS
WITH A FIRE RESISTANT RATING. WHERE REQ'D APPROPRIATE FRAMING AND GYP BOARD IS TO BE INSTALLED AND
OFFSET AROUND STRUCTURAL MEMBERS OR OTHER OBSTRUCTIONS SUCH AS PIPING OR DUCTWORK, TO MAINTAIN THE
FIRE RESISTANCE RATING. NON-RATED WALLS THAT CONTINUE TO STRUCTURE ARE TO TERMINATE AT PROPER
LOCATIONS TO MAINTAIN THE INTENT OF THE CONTINUOUS PLANE OF ONE LAYER OF GYP BOARD AS A NOISE, SMOKE OR
OTHER TYPE OF BARRIER.
4. SPACING OF THE METAL STUDS HAS NOT BEEN INDICATED ON THE WALL TYPES OR DETAILS. REFER TO STRUCTURAL
STUD DETAILS SHEET
5. ALL GYP BOARD SHALL BE 5/8", U.N.O.
6. REFER TO GYP BOARD SCHEDULE BELOW FOR GYP BOARD REQUIREMENTS PER LOCATION AND WALL TYPE
7. ALL WALL ASSEMBLIES TO BE FILLED W/ SOUND ATTENUATION BATTS, U.N.O.
8. VARYING INSULATION REQUIREMENTS HAVE NOT BEEN INDICATED ON THE WALL TYPES; FOR WALL TYPES WITH VARYING
INSULATION TYPES, REFERENCE INSULATION PLAN
9. VARYING LOAD BEARING REQUIREMENTS HAVE NOT BEEN INDICATED ON THE WALL TYPES; FOR WALL TYPES WITH
VARYING LOAD BEARING REQUIREMENTS, REFERENCE LOAD BEARING PLAN
10. SOUND ATTENUATION BLANKETS/BATTS SHALL EXTEND THE FULL HEIGHT OF THE WALLS, U.N.O.
11. THERMAL AND SOUND INSULATION AND COVERING WHICH ARE INSTALLED IN CONCEALED AND EXPOSED SPACES AND AS
COVERING OVER PIPE AND TUBING SHALL BE TESTED IN ACCORDANCE WITH AMERICAN SOCIETY OF TESTING MATERIALS
(ASTM) E 84 AND HAVE A FLAME SPREAD OF 0-25 AND A SMOKE INDEX OF 0-450.
12. SUPPORT INSULATION WITH CHICKEN WIRE IN PARTITIONS WITHOUT GYP BOARD ON BOTH SIDES TO STRUCTURE.
13. ALL RATED WALLS SHALL BE CONSTRUCTED FIRST. SECONDARY WALLS TO ABUT, BUT NOT PENETRATE RATED WALLS.
14. FIRESTOPPING TO BE PROVIDED AT PENETRATIONS THROUGH RATED WALLS AS SPECIFIED.
15. UL DESIGN NUMBERS REFER TO FIRE RESISTANCE IN MOST CURRENT EDITION OF THE UL DIRECTORY.
16. PROVIDE ALL COMPONENTS REQUIRED PER THE INDICATED DESIGN NUMBER OR TEST REFERENCE LISTING NUMBER,
INCLUDING BUT NOT LIMITED TO FASTENER SIZE AND SPACING.
17. APPROPRIATE SUBMITTAL INFORMATION MUST BE PROVIDED TO SUBSTANTIATE THAT THE MATERIALS AND ASSEMBLY
USED BY THE CONTRACTOR HAVE BEEN TESTED BY A RECOGNIZED TESTING AGENCY TO MEET THE FIRE RESISTANCE
RATING SCHEDULED ON THESE WALL TYPES.
18. MAINTAIN 1/2" SPACE BETWEEN FLOOR SLAB AND BOTTOM OF GYP BOARD ON ALL WALLS.
19. STOP STUD 1" BELOW METAL RUNNER (TOP TRACK) TO ALLOW FOR VERTICAL EXPANSION DO NOT ATTACH STUDS OR
GYP BOARD TO TOP TRACK.
20. U.N.O. ALL WALLS TO BE LEVEL 4 FINISH
21. REFER TO INTERIOR DETAILS FOR ADDITIONAL INFORMATION.
PARTITION
TAG
INSULATION
TYPE
FIRE
RATING
HEAD
DETAIL
STUD
DEPTH
CORE SIZE
(NOM.)
TOTAL
THICKNESS FIRE TEST
STC
RATING
0|SA4|a NR E5/A501 3 5/8" 4 0' - 4 7/8" 0 NA
0|SA4|b GL. FIBER NR E6/A501 3 5/8" 4 0' - 4 7/8" 0 <varies>
0|SA4|a NA NR E5/A501 3 5/8" 4 0' - 4 7/8" 0 NA
0|SA4|b NA NR E6/A501 3 5/8" 4 0' - 4 7/8" 0 NA
0|SA6|<varies>GL. FIBER NR E6/A501 6" 6 0' - 7 1/4" NA NA
0|SA6|a NA NR E5/A501 6" 6 0' - 7 1/4" NA NA
0|SA6|b NA NR E6/A501 6" 6 0' - 7 1/4" NA NA
NOTE: IF FIRE RATING IS BLANK, WALL IS NOT RATED.
NOTE: IF FIRE RATING IS BLANK, WALL IS NOT RATED.
PARTITION
TAG
INSULATION
TYPE
FIRE
RATING
HEAD
DETAIL
STUD
DEPTH
CORE SIZE
(NOM.)
TOTAL
THICKNESS FIRE TEST
STC
RATING
0|SB1|a NA NR E5/A501 1 5/8" 1.5 0' - 2 1/4" 0 NA
0|SB3|b GL. FIBER NR E6/A501 2 1/2" 2.5 0' - 3 1/8" 0 NA
0|SB3|a NA NR E5/A501 2 1/2" 2.5 0' - 3 1/8" 0 NA
0|SB3|b NA NR E6/A501 2 1/2" 2.5 0' - 3 1/8" 0 NA
0|SB4|b GL. FIBER NR E6/A501 3 5/8" 4 0' - 4 1/4" 0 NA
0|SB4|a NA NR E5/A501 3 5/8" 4 0' - 4 1/4" 0 NA
0|SB6|a NA NR E5/A501 6" 6 0' - 6 5/8" 0 NA
PARTITION
TAG
INSULATION
TYPE
FIRE
RATING
HEAD
DETAIL
CORE SIZE
(NOM.)TOTAL THICKNESS LOAD
BEARING
FIRE
TEST
STC
RATING
CD6 0' - 5 5/8"
3" = 1'-0"E4 STEEL STUD PARTITION HEAD 6" ABOVE CEILING
3" = 1'-0"E5 TYPICAL STEEL STUD PARTITION HEAD
PARTITION
TAG
INSULATION
TYPE
FIRE
RATING
HEAD
DETAIL
STUD
DEPTH
CORE SIZE
(NOM.)
TOTAL
THICKNESS FIRE TEST
STC
RATING
0|SF6|b GL. FIBER NR E6/A501 6" 6 0' - 8" NA 45
NOTE: IF FIRE RATING IS BLANK, WALL IS NOT RATED.
MATCH ADJACENT
PARTITION
TAG
INSULATION
TYPE
FIRE
RATING
HEAD
DETAIL
STUD
DEPTH
CORE SIZE
(NOM.)
TOTAL
THICKNESS FIRE TEST
STC
RATING
0|SH2|b GL. FIBER NR E6/A501 3 5/8" 4 0' - 4" NA NA
PARTITION
TAG
INSULATION
TYPE
FIRE
RATING
HEAD
DETAIL
STUD
DEPTH
CORE SIZE
(NOM.)
TOTAL
THICKNESS FIRE TEST
STC
RATING
0|SG4|b GL. FIBER NR E6/A501 3 5/8" 4 0' - 5 3/4" NA 60
NOTE: IF FIRE RATING IS BLANK, WALL IS NOT RATED.NOTE: IF FIRE RATING IS BLANK, WALL IS NOT RATED.
EXISTING STRUCTURE
UNISTRUT ATTACHED TO
EXISTING STRUCTURE ABOVE
12"
PROJECTOR / TV MOUNT BY OWNER
SCHEDULED CEILING RE: CEILING PLAN
APROXIMATLEY 1 1/2" X 1 1/2" ANGLE
IRON ATTACHED TO UNISTRUT
1 1/2" PIPE, THREADED ON THE END
TO RECIEVE OWNER PROVIDED
PROJECTOR / TV MOUNT
1 1/2" FITTING WELDED TO ANGLE IRON TO
RECIEVE PIPE, PAINTED FINISH; PNT-0190°FIRST LINE OF BRACING 6'-0" OR LESS
FROM WALL BOUNDARY
CEILING SUSPENSION
SYSTEM
WALL
SPLAY WIRE
COMPRESSION POST
1 2 '-0 " (M A X .)
NOTE:
AREAS SMALLER THAN 144 SQ. FT. AND WITH WALLS ON FOUR
SIDES EXTENDING TO THE STRUCTURE NEED NOT BE BRACED.
BOUNDARY WALLS MUST BE BRACED TOP AND BOTTOM
INDEPENDENT OF CEILING TO QUALIFY.
1
2
'
-
0
"
(
M
A
X
.
)
6 '-0 " M A X .
TYP.
D1
A514
METAL FURRING
CHANNEL @ 16" O.C.
(TYP)
FIRST LINE OF BRACING
4'-0" OR LESS FROM
WALL BOUNDARY
RUNNER CHANNEL
@ 4'-0" O.C. (TYP)
4'-0" TYP.
12'-0" TYP.
NOTE:
AREAS SMALLER THAN 144 SQ. FT. AND WITH
WALLS ON FOUR SIDES, EXTENDING TO THE
STRUCTURE, DO NOT NEED TO BE BRACED.
BOUNDARY WALLS MUST BE BRACED TOP
AND BOTTOM INDEPENDENT OF CEILING.
12'-0" TYP.
TYP.
D1
A514
NOTE 1- ALL SPLAY WIRES TO BE IN LINE WITH ATTACHED
COMPONENT
NOTE 2- ALL SPLAY WIRES TO BE TAUT AND TIED BOTH ENDS WITH MINIMUM OF THREE TURNS IN 1" OF RUN.
NOTE 3- COMPLY WITH IBC 2015, ASTM C635, ASTM C636 AND CISCA
STANDARDS
NOTE 4- SPLAY WIRES SHALL ATTACH TO STRUCTURAL GIRDER OR JOIST ONLY, DO NOT ATTACH TO ROOF DECK.
NOTE 5- METAL COMPRESSION POST (STRUT) FASTENED TO THE MAIN RUNNER SHALL BE EXTENDED TO AND FASTENED
TO THE STRUCTURAL MEMBERS SUPPORTING THE ROOF OR FLOOR ABOVE. COMPRESSION POSTS & SPLAY WIRES TO BE
INSTALLED EVERY 12' O.C. BOTH DIRECTIONS STARTING 6' FROM WALL. SEE COMPRESSION POST ALLOWABLE LENGTHS
TABLE FOR SIZES. SEE DETAILS 3 & 4 FOR TYPICAL BRACING.
NOTE 6- ALL LIGHT FIXTURES SHALL BE POSITIVELY ATTACHED TO THE SUSPENDED CEILING SYSTEM. WHEN
INTERMEDIATE SYSTEMS ARE USED, ATTACH NO. 12 GAGE HANGERS TO THE GRID MEMBERS WITHIN 3" OF EACH CORNER
OF EACH FIXTURE. LIGHT FIXTURES WEIGHING LESS THAN 56 LBS. SHALL HAVE TWO NO. 12 GAGE HANGERS CONNECTED
FROM THE FIXTURE HOUSING TO THE STRUCTURE ABOVE. COMPLY WITH IBC 2015
NOTE 7- ALL LIGHT FIXTURES SHALL BE POSITIVELY ATTACHED 20 LBS. SHALL BE POSITIVELY ATTACHED TO THE CEILING
SUSPENSION MAIN RUNNERS. TERMINALS OR SERVICES WEIGHING 20 LBS., BUT NOT MORE THAT 56 LBS., SHALL IN
ADDITION HAVE TWO NO. 12 GAGE HANGERS CONNECTED TO THE CEILING SYSTEM HANGERS OR TO THE STRUCTURE
ABOVE. TERMINALS OR SERVICES WEIGHING MORE THAN 56 LBS. SHALL BE SUPPORTED DIRECTLY FROM THE STRUCTURE
ABOVE BY APPROVED HANGERS. COMPLY WITH IBC 2015
NOTE 8- ALL GRID SYSTEM IN SEISMIC ZONE D OR GREATER ARE REQUIRED TO BE HEAVY DUTY. REFER REQUIREMENTS
TO ASCE 7 REQUIREMENTS.
NOTE 9- CEILINGS WITHOUT RIGID BRACING MUST HAVE 2" OVERSIZED TRIM RINGS FOR SPRINKLERS AND OTHER
PENETRATIONS, COORDINATE W/ SPECIFICATIONS.
NOTE 10 - SUSPENDED ACOUSTIC CEILINGS INSTALLED IN SEISMIC DESIGN CATEGORY D SHALL BE INSTALLED
ACCORDING TO IBC 808.1.1.1, IBC 1613.1, ASTM C 635, ASTCM C 636, AND ASCE 7-10.
NOTE 11 - ACOUSTICAL PANEL CEILINGS REQUIRES SEISMIC DESIGN TO BE COMPLETED BY A LICENSE ENGINEER AND
SUBMITTED FOR REVIEW AND APPROVAL. RE: SPECIFICATIONS.
STRUCTURE
SPLAY WIRE - SECURE
TO STRUCTURE
MAIN TEE
CROSS TEE
VERTICAL HANGER
WIRE ADJACENT
TO POST
SPRING CLIP INSERTS
IN HOLE IN POST
STRUT ASSEMBLY TOP CLIP
MECHANICALLY FASTENED TO
DECK PER MANUFACTURERS
RECOMMENDATIONS
BULB CLIP ATTACHING
COMPRESSION POST AND
MAIN RUNNER MECHANICALLY
FASTENED PER
MANUFACTURERS
RECOMMENDATIONS
A FASTENER OR SPLAY
WIRES MAYBE INSERTED
INTO THE TAB OF THE POST
AND THROUGH A
CONVENIENCE HOLE IN THE
MAIN TEE BULB
COMPRESSION POST -
INSTALL WITHIN 2" OF
CROSS TEE INTERSECTION
45° OR LESS
45° OR
LESS 45° OR
LESS
45° OR LESS
COMPRESSION POST ALLOWABLE LENGTHS TABLE
13/16" x 13/32" STRUT 19 GA
MATERIAL TYP. ALLOWABLE LENGTH
24"
1 5/8" x 13/16" STRUT 12 GA 48"
13/16" x 13/16" STRUT 19 GA 54"
1 5/8" x 1" STRUT 12 GA 60"
3 5/8" x 1 1/4" STRUT 16 GA 82"
1 1/4" x 1 1/4" STRUT 14 GA 84"
1 5/8" x 1 3/8" STRUT 12 GA 96"
1 5/8" x 1 5/8" STRUT 12 GA 108"
1 5/8" x 2 7/16" STRUT 12 GA 120"
NOTES
1. THE INFORMATION PROVIDED IS FOR QUICK REFERENCE
ONLY. OTHER RESTRICTIONS AND EXEMPTIONS MAY APPLY.
2. WALL MOLDING SHOULD NOT BE USED AS STRUTS.
3. A STRUCTURAL ENGINEER SHOULD BE CONSULTED FOR LENGTHS
GREATER THAT 14'.
C R O S S T E E
HEAVY DUTY MAIN RUNNER
12 GA. METAL
HANGER WIRES
HEAVY DUTY MAIN RUNNER
4'-0" TYPICAL
3" MAX., TYP.
SLACK
WIRES #12 WIRE HANGER AT EACH
CORNER OF FIXTURE (TYP.)
INDEPENDENT OF CEILING
SUPPORT SYSTEM
12 GA. HANGER SEE
SPECIFICATION
1 1/2" C.R. CHANNEL @
48" O.C.
5/8" TYPE 'X' GYP BD
3/4" FURRING CHANNELS @
24" O.C.
8" MAX8" MAX
FASTENER ON ALL
MEMBERS @ TWO
ADJACENT WALLS ONLY
PER MFG REQ.
7/8" SEISMIC CLIP BY
MANUFACTURER
SCHED. CEILING TILE
CEILING GRID MAIN RUNNER
OR CROSS TEE
GRID PERPENDICULAR TO
CEILING NOT ATTACHED TO
CLOSURE ANGLE (TWO
ADJACENT WALLS)
HANGER 12 GA. @ 4'-0" O.C.
MAX.
NOTE 1 - ALL HANGER WIRES TO BE IN LINE WITH ATTACHED
COMPONENT OR SHALL BE COUNTERSLOPED NOT GREATER THAN
1/6
NOTE 2 - ALL HANGER WIRES TO BE TAUT AND TIED BOTH ENDS W/
MIN. OF 4 TURNS IN 1" OF RUN.
0' - 8" MAX0' - 8" MAX
SCREW INTO MOLDING
AT PERIMETER
ANGLE MOLDING BY
MANUFACTURER
SCHED. GYPSUM PANEL
DRYWALL MAIN
RUNNER OR
CROSS TEE
HANGER 12 GA. @ 4'-0"
O.C. MAX.
1. ALL HANGER WIRES TO BE IN LINE WITH ATTACHED COMPONENT OR SHALL
BE COUNTERSLOPED NOT GREATER THAN 1/6
2. ALL HANGER WIRES TO BE TAUT AND TIED BOTH ENDS W/ MIN. OF 4 TURNS
IN 1" OF RUN.
NOTE:
SCHEDULED WALL -
SEE FLOOR PLAN
CEILING AS SCHEDULED
BID ALTERNATE 1 - MANUAL ROLLER
SHADE SYSTEM,(RS-01) RE: FINISH
SCHEDULE. BREAK AT VERT. WINDOW
MULLION. FASTEN PER MANUF. SPEC'S
SNAPLOC FRONT FASCIA COVER:
ARCH. TO SELECT FINISH COLOR
FROM MANUF. STANDARD COLORS.
EXISTING EXTERIOR
STOREFRONT SYSTEM &
GLAZING
SA6 b
3"
DRAPERY TRACK, ALUMINUM
STRAIGHT TRACK, CEILING
MOUNT, FINISH:
MANUAL RIPPLEFOLD DRAPERY
3/4" PLYWOOD BACKER
6" FRAMED HEADER
SCHEDULED WALL
SEE PLAN
C
6
B1
A514
B2
A514
SB
4
a
SB
4
a
SA
6
b
3"
DRAPERY TRACK, ALUMINUM
STRAIGHT TRACK, CEILING
MOUNT, FINISH:
MANUAL RIPPLEFOLD DRAPERY
3/4" PLYWOOD BACKER
6" FRAMED HEADER
SA6 b
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A514
CEILING
DETAILS
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1 1/2" = 1'-0"B3 PROJECTER / TV POLE MOUNT
12" = 1'-0"A4 CEILING SEISMIC BRACING AT LAY-IN
12" = 1'-0"A6 CEILING SEISMIC BRACING GYP.
1 1/2" = 1'-0"C3 CEILING SEISMIC BRACING
1/64" = 1'-0"A2 TYP. CEILING FIXTURE SUPPORT
1 1/2" = 1'-0"A3 SUSPENDED CEILING CHANNEL DETAIL
1 1/2" = 1'-0"B5 LAY-IN CEILING DETAIL - CLIP ANGLE
1 1/2" = 1'-0"B6 TYP SUSP. GYP. BD. CLG. - CLIP ANGLE
3" = 1'-0"A1 MANUAL ROLLER SHADE DETAIL-SURFACE MOUNTED
3" = 1'-0"B1 BULK HEAD SECTION DETAIL 1
1 1/2" = 1'-0"C1 BULK HEAD CEILING DETAIL
3" = 1'-0"B2 BULK HEAD SECTION DETAIL 2
EXISTING CONCRETE
FLOOR OVER DECK
SCHEDULED
FLOORING
TS-04 TRANSITION
RE: TRANSITION STRIP
SCHEDULE
CONCRETE FLOOR AS
SCHEDULED
SCHEDULED DOOR,
AS OCCURS.
EXISTING CONCRETE
FLOOR OVER DECK
FLOORING AS
SCHEDULED
TS-03 TRANSITION, RE:
TRANSITION STRIP
SCHEDULE
SCHEDULED DOOR, AS
OCCURS.
MORTAR BED
OVER CRACK
ISOLATION
SINGLE
COMPONENT
GROUT
SCHEDULED FLOOR TILE
EXISTING CONCRETE
FLOOR OVER DECK
METAL COVE TS-01 RE:
TRANSITION STRIP SCHEDULE
MORTAR BED
OVER CRACK ISOLATION
SINGLE COMPONENT
GROUT
PORCELAIN FLOOR TILE
SCHEDULED WALL FINISH
SCHEDULED. WALL TILE,
RE: FINISH PLAN
THINSET LATEX-PORTLAND
CEMENT MORTAR BOND COAT
WALL AS SCHED. SEE FLOOR
PLAN FOR TYPE
TYPE 7 TRANSITION RE:
TRANSITION STRIP SCHEDULE
SCHEDULED. WALL TILE,
RE: FINISH PLAN
SINGLE COMPONENT GROUT
1 7/8"
BACKER BOARD
TRANSITION STRIP,TS-03 ; RE:
TRANSITION SCHEDULE
SCHEDULED WALL
TL-02; RE: FINISH SCHEDULE
PAINTED GYP. SEE ELEVATION FOR
FINISH
EXISTING CONCRETE
FLOOR OVER DECK
FLOORING AS
SCHEDULED
TS-05 TRANSITION
RE: TRANSITION STRIP
SCHEDULE
FLOORING AS
SCHEDULED
SCHEDULED DOOR,
AS OCCURS.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A571
INTERIOR
DETAILS
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
3" = 1'-0"E1 CARPET TO CONCRETE TRANSITION
3" = 1'-0"E2 TILE TO CARPET
3" = 1'-0"E4 METAL COVE BASE - TITLE TO TILE
3" = 1'-0"E5 TILE TO TILE TO OUTSIDE CORNER
3" = 1'-0"E6 TILE EDGE DETAIL
3" = 1'-0"D1 CARPET TO SHEET VINYL TRANSITION
0' - 3"
0' - 4"
RE
:
E
L
E
V
A
T
I
O
N
S
0' - 4"
24"
RE
:
E
L
E
V
A
T
I
O
N
S
RE
:
E
L
E
V
A
T
I
O
N
S
12"
SCHEDULED FINISH FLOOR; RE:
FINISH FLOOR PLANS
LOWER CABINET; RE: ELEVATION FOR
CABINET TYPE
WALL AS SCHEDULED; RE:
PLAN FOR TYPE
UPPER CABINET, RE: ELEVATION FOR
CABINET TYPE
BACKSPLASH WHERE
OCCURS, RE: ELEVATION,
SAME MATERIAL AS
COUNTERTOP, CALKING AT
JOINTS TO MATCH
COUNTERTOP MATERIAL
BASE TO MATCH MILLWORK MATERIAL
UNLESS NOTED IN ELEVATIONS
RE: PLAN VIEW
VARIES
SHELF: 3/4" PLYWOOD WITH WHITE MELAMINE FINISH,
UNO. RE: INTERIOR ELEVATIONS.
ALL EDGES TO HAVE MATCHING PVC EDGEBANDING
KV 185 WHITE (WH) DOUBLE BRACKETS, COORDINATING
BRACKET PER SHELF DEPTH, RE: PLAN VIEW FOR SHELF
DEPTH
PROVIDE 3/4" PLYWOOD SHEATHING FOR
BACKING/BLOCKING
WALL BASE AS SCHEDULED, RE: FINISH PLAN
FINISHED FLOOR
RE: ELEVATION
WALL AS SCHEDULED, RE: PLAN VIEW
KV 85 WHITE (WH) SERIES STANDARDS, COORDINATING
STANDARD PER OVERALL SHELVING HEIGHT, RE: ELEVATION
FOR SHELVING HEIGHTS
WALL AS SCHEDULED; SEE FLOOR PLAN FOR
WALL TYPES
FINISHED FLOOR
COUNTERTOP: 3/4" PLYWOOD SUBSTRATE,
RE: ELEVATION FOR FINISH TYPE
BASE AS SPECIFIED. SEE ELEVATION
FULL CONCEALED STEEL SUPPORT BRACKET.
FINISH TO MATCH ADJACENT WALL COLOR/FINISH
(WHERE EXPOSED). FINISH ALSO TO MATCH
ADJACENT WALL COLOR/FINISHED FOR EXPOSED
BRACKET ON EXISTING WALLS.
1' - 10"0' - 2"
4" BACKSPLASH WHERE OCCURS, RE: ELEVATION, MATERIAL
TO MATCH COUNTERTOP MATERIAL, ADHERED TO WALL WITH
CALKING AT WALL JOINT
2' - 0"
CALKING AT JOINT TO MATCH WALL FINISH
WALL AS SCHEDULED,
RE: PLAN VIEW
1/2" THICK, MDF, EASED
EDGES, PAINTED PNT-01;
RE: FINISH SCHEDULE
COAT HOOK, RE: ACCESSORY
SCHEDULERE: ELEVATIONS
0' - 4 1/2"
48"
36"
2
8
3
/
4
"
0' - 9 11/16"
0 ' - 9 3 /3 2 "
12"
15 3/4"
DIVIDER: 3/4" PLYWOOD SUBSTRATE.
FACED WITH PLASTIC LAMINATE
(PL-01)
WALL AS SCHEDULED; SEE FLOOR PLAN FOR
WALL TYPES
CALKING AT JOINT TO MATCH WALL FINISH
COUNTERTOP RE: INTERIOR ELEVATIONS FOR
FINISH.
COUNTERTOP SUPPORT BRACKET
1"
48"
ELEVATION SECTION
WALL AS SCHEDULED, RE: PLAN VIEW
COUNTERTOP: 3/4" PLYWOOD SUBSTRATE WITH PENOLIC
RESIN FINISH, SQUARE, EASED EDGE - SCRIBE TIGHTLY TO
WALL, MATCHING 4" BACKSPLASH WHERE OCCURS. RE:
ELEVATIONS FOR FINISH TYPE.
REMOVABLE DRYING SHELF: WIRE MESH ATTACHED TO 3/4"
PLYWOOD.
REMOVABLE DRYING SHELF: 3/4" PLYWOOD PLASTIC
LAMINATE WRAPPED. RE: ELEVATIONS FOR FINISH TYPE.
RUBBER BASE, WB-02. RE: FINISH SCHEDULE
SIDE PANEL, BLACK MELAMINE FINISH
CABINET 3/4" PLYWOOD W/ PLASTIC LAMINATE,
RE: ELEVATIONS FOR FINISH TYPE.
3/4" RAIL FOR DRYING SHELVES TO REST ON. WHITE
MELAMINE FINISH
3"
4"
36"
EQ
1 1/2"
EQ
TYP
3/4"
EQ
EQ
EQ
EQ
36"
1/2" FIXED PLYWOOD SHELF
1/2" PLYWOOD DRAWER GLIDES
*REFER TO EXISTING CASEWORK FOR DIMENSIONS. IF THERE ARE ANY
DISCREPENCIES IN CONSTRUCTION, MATCH THE EXISTING CABINETS.
1/4"
CARPET INSET,
EM-01, RE: FINISH
SCHEDULE
RUBBER BASE, WB-02, RE: FINISH
SCHEDULE
FINISHED FLOOR, RE: FLOOR PLAN
CABINET HARDWARE TO MATCH
EXISTING HARDWARE
LOCK, OLYMPUS LOCKS
PER CAMPUS STANDARD
44 1/2"
EXISTING WALL
TEFLON MATERIAL, MAKE
FLUSH WITH CARPET SQUARE
COUNTERSUNK SCREW
1"
3/4" MDF WITH BULL NOSE
EDGES. WOOD VENEER
FINISH, WV-01, RE:FINISH
SCHEDULE
3/4" SOLID WOOD OAK DRAWERS. SCREWED
TOGETHER.
TYP
3 1/2"
TYP
4 1/8"
BACKSPLASH. SS-01
0' - 4"
0' - 0 3/4"
RE: PLAN VIEW
VARIES
SHELF: 3/4" PLYWOOD WITH, WITH A 3/4" LIP. PL-01
FINISH, UNO. RE: INTERIOR ELEVATIONS.
ALL EDGES TO HAVE MATCHING PVC EDGEBANDING
KV 185 WHITE (WH) DOUBLE BRACKETS, COORDINATING
BRACKET PER SHELF DEPTH, RE: PLAN VIEW FOR SHELF
DEPTH
PROVIDE 3/4" PLYWOOD SHEATHING FOR
BACKING/BLOCKING
WALL BASE AS SCHEDULED, RE: FINISH PLAN
FINISHED FLOOR
RE: ELEVATION
WALL AS SCHEDULED, RE: PLAN VIEW
KV 85 WHITE (WH) SERIES STANDARDS, COORDINATING
STANDARD PER OVERALL SHELVING HEIGHT, RE: ELEVATION
FOR SHELVING HEIGHTS
1"
1/2" FIXED PLYWOOD
SHELF
RUBBER BASE, WB-02, RE: FINISH
SCHEDULE
FINISHED FLOOR, RE: FLOOR PLAN
EXISTING WALL
CABINET: WOOD VENEER FINISH,
WV-01, RE:FINISH SCHEDULE
CABINET HARDWARE TO MATCH
EXISTING HARDWARE
LOCK, OLYMPUS LOCKS
PER CAMPUS STANDARD
26 1/4"
34"
EXISTING COLUMN BEYOND
OPEN CAVITY
COUNTERTOP: 3/4" PLYWOOD SUBSTRATE WITH
PHENOLIC RESIN FINISH, SQUARE, EASED EDGE -
SCRIBE TIGHTLY TO WALL, MATCHING 4"
BACKSPLASH WHERE OCCURS. RE: ELEVATIONS
FOR FINISH TYPE.
APRON FRONT
4"
23 3/4"
4 1/2"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A581
CASEWORK
DETAILS
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1 1/2" = 1'-0"C5 TYPICAL CASEWORK DETAIL
1 1/2" = 1'-0"D2 TYPICAL ADJUSTABLE SHELVING DETAIL
1 1/2" = 1'-0"D3 COUNTERTOP WITH SUPPORT BRACKET
3" = 1'-0"E1 MOUNTED COAT HOOK SECTION
1 1/2" = 1'-0"C1 PHOTO DIVIDER DETAIL
1 1/2" = 1'-0"C3 DRYING RACK CABINET
1 1/2" = 1'-0"A1 GEOLOGY ROCK STORAGE
1 1/2" = 1'-0"A2 TYPICAL CHEMICAL SHELVING DETAIL 1 1/2" = 1'-0"A4 GEOLOGY CABINET
PAINTED HOLLOW METAL
FRAME.
DOOR
SEALANT,
EACH SIDE
TYPES
RE: WALL
PAINTED HOLLOW
METAL FRAME.
DOOR
SEALANT,
EACH SIDE
TYPES
RE: WALL
HEADER, RE:
STRUCTURAL
SCHEDULED WALL
F1
2"SEE SCHED.2"
SEE DOOR SCHEDULE
2"
HOLLOW METAL
F2
HOLLOW METAL
2"SEE SCHED.
2"
2' - 0"2"
SEE DOOR SCHEDULE
2"
G1
FROSTED FILM ON THE
INSIDE OF THE GLASS
2"1'-10"
4'-0"
1"1"
F3
ALUM STOREFRONT
2"
SEE DOOR SCHEDULE
2"
G1
2'-0"
7'-2"
SEE SCHED.2"2"
B5
A601
________________
A4
A601
________________
A5
A601
________________
WOOD FLUSH
D2
SEE SCHED.
SEE SCHED.
C.L. OF HARDWARE
3' - 4"
WOOD FLUSH
D3
SEE SCHED.
SEE SCHED.
C.L. OF HARDWARE
3' - 4"
6"6"
2'-4"
6"
G1
G1
4'-0"
2'-0"
1"1"
FROSTED FILM ON THE
INSIDE OF THE GLASS
AT OFFICES ONLY
HOLLOW METAL DOUBLE DOOR
D5
VERIFY W/ EXISTING
VERIFY W/ EXIST VERIFY W/ EXIST
VERIFY W/ EXIST
3' - 4"
WOOD FLUSH DOUBLE DOOR
D6
VERIFY W/ EXISTING
VERIFY W/ EXIST VERIFY W/ EXIST
VERIFY W/ EXIST
3' - 4"
ALUMINUM
D1
SEE SCHED.
SEE SCHED.
6"
5"
2' - 3"
10"
C.L. OF HARDWARE
3' - 4"
6"
G1
6"
WOOD FLUSH
D4
SEE SCHED.
SEE SCHED.
C.L. OF HARDWARE
3' - 4"
6"
5'-6"
6"
G1
HOLLOW METAL
D7
SEE SCHED.
SEE SCHED.
C.L. OF HARDWARE
3' - 4"
6"
SCHEDULED WALL,
SEE WALL TYPES
INSULATION TO EXTEND TO
DECK
STOREFRONT SYSTEM,
RE: SPECIFICATIONS
SEALANT BOTH
SIDES TYP.
SHIM
BOX HEADER
GYP BOARD "J"
BEAD (BOTH SIDES)
SCHEDULED WALL
GLAZING, SEE WINDOW TYPES
& GLAZING SCHEDULE
SEALANT BOTH SIDES TYP.
STOREFRONT SYSTEM
SHIM
GYP BOARD
BACKER ROD & SEALANT
BOTH SIDES TYPICAL
SHIM SPACE
FINISHED FLOOR
WINDOW / STOREFRONT
SYSTEM, SPECIFICATIONS
PROVIDE MATCHING ALUMINUM 'L'
STRIP TO STOREFRONT, TO
COVER EXISTING TRAVERTINE
WHERE OCCURS
GENERAL NOTES -STOREFRONT
A. WINDOW TYPES KEY:
SF# (STORE FRONT SYSTEM) :
2" X 4 1/2" (B.O.D. = KAWNEER TRIFAB VERSAGLAZE 451T)
B. UNLESS OTHERWISE SPECIFIED, MAX GLASS PANEL WIDTH SIZE SHALL NOT BE GREATER THAN
5'-0", ALL GLASS PANEL WIDTHS SHALL BE EQUAL.
C. OVERALL DIMENSIONS ARE FROM OUTSIDE FACE OF MULLION; INTERIOR/FIELD DIMENSIONS
ARE TO CENTERLINE OF MULLION
D. PROVIDE TEMPERED GLASS AT ALL CODE REQUIRED LOCATIONS
E. CONTRACTOR SHALL BE THE RESPONSIBLE PARTY FOR THE ENERGY PERFORMANCE RATINGS
OF THE FENESTRATION SYSTEM IN ACCORDANCE WITH THE NATIONAL FENESTRATION RATING
COUNCIL REQUIREMENTS. CONTRACTOR SHALL ACQUIRE LABEL CERTIFICATES FOR SITE-BUIT
GLAZING SYSTEMS AS REQUIRED BY THE CODE OFFICAL. CONTRACTOR SHALL HAVE THE
OPTION OF SELECTING EITHER THE "CERTIFIED PRODUCT" OR "CERTIFIED PROJECT PATH" PER
NFRC 100
G1 1/4" CLEAR GLAZING -TEMPERED
GLAZING SCHEDULE
METAL WALL FRAMING STUD @
16" O.C., ATTACH TO DECK
STORE FRONT RIBBON ASSEMBLY
SYSTEM, STANDARD ALUMINUM
FINISH, RE: SPECIFICATIONS
SEALANT BOTH SIDES TYP.SHIM
5/8" GYP BOARD, TYP
METAL CORNER, EACH SIDE
SB3 b SB4 b
2 1/2" METAL FRAMING STUD @
16" O.C., ATTACH TO DECK
STORE FRONT RIBBON ASSEMBLY
SYSTEM, STANDARD ALUMINUM
FINISH, RE: SPECIFICATIONS
SEALANT BOTH SIDES TYP.
SHIM
5/8" GYP BOARD, TYP
METAL CORNER, EACH SIDE
STORE FRONT RIBBON
ASSEMBLY SYSTEM, STANDARD
ALUMINUM FINISH, RE:
SPECIFICATIONS
SEALANT BOTH SIDES TYP.
SHIM
5/8" GYP BOARD, TYP
SB3 b
EXISTING MASONRY WALL TO
REMAINBACKSPLASH, RE: FINISH
SCHED.
EPOXY RESIN SILL TO
MATCH NEW COUNTERTOP
FINISH. INSTALL ON BOTH
SIDES OF STOREFRONT.
RE: FINISH SCHED SS-01
1
EXISTING WALL AND FINISH TO REAMAIN
COVER CUT OPENING WITH
WITH NEW SILL, RE: FINISH
SCHED SS-01
EXISTING GLAZING TO REMAIN
CONTINUOUS SEALANTAT THE
PERIMETER OF THE NEW SILL
1
C
EXISTING WALL AND FINISH TO
REMAIN
NEW INFILL FRAMING AND GYP
BOARD TO COVER CUT OPENING
EXISTING GLAZING TO REMAIN 1
FRAME OVER (LEFT OR RIGHT)
TO THE NEAREST MULLION.
COVER ALL NEW FRAMING WITH
5/8" GYPSUM BOARD AND FINISH
EXISTING WALL AND FINISH TO
REAMAIN
EXISTING GLAZING TO REMAIN
NEW WALL AS
SCHEDULED, RE:
DIMENSION PLANS
B1
A601
C1
A601
A1
A601
3'-5 1/2"
3'-6 1/2"
4'-0"
SF1
ALUM STOREFRONT
G1
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A601
DOOR &
WINDOW
TYPES AND
SCHEDULE
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
GENERAL NOTES - DOORS
1 ALL HOLLOW METAL FRAMES AND DOORS ARE TO BE PAINTED TO MATCH ADJACENT WALL FINISH, UNLESS NOTED
OTHERWISE
2 ALL INTERIOR HOLLOW METAL FRAME WIDTHS ARE TO MATCH WALL WIDTHS; COORDINATE WITH VERTICAL ASSEMBLY
TYPES
3 WOOD GRAIN DIRECTION TO BE VERTICAL, UNLESS NOTED OTHERWISE
4 FINISH OF METAL FRAMES ADJACENT TO METAL PANEL TO MATCH METAL PANEL COLOR, UNLESS NOTED OTHERWISE
5 COLOR TRANSITIONS TO OCCUR AT INSIDE OF FRAME STOP
6 DOORS SERVING SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE SHALL NOT BE PROVIDED WITH A LATCH OR LOCK
OTHER THAN PANIC HARDWARE. SEE DOOR HARDWARE SPECIFICATIONS
7 PROVIDE TEMPERED GLASS AT ALL CODE REQUIRED LOCATIONS
8 REFER TO SPECIFICATIONS FOR ALL HARDWARE SETS
ALL DOOR HANDLES & HARDWARE USED ON THE PROJECT MUST NOT REQUIRE PINCHING, TIGHT GRASPING, OR TWISTING OF THE WRIST IN ORDER TO OPERATE, IN ACCORDANCE WITH 2018 IBC 1010.1.9.1
DOOR SCHEDULE - ALL
wt
ROOMS DOOR DIMENSIONS DOOR FRAME FIRE
RATING
MS_Card
Access HwSet#
DOOR
NUMBER COMMENTSTO RM # WIDTH HEIGHT THK TYPE MATERIAL FINISH TYPE MATERIAL FINISH
LEVEL 00
0-H VESTIBULE 0-H 3' - 0" 6' - 10" 1 3/4" D1 ALUMINUM DARK BRONZE F3 ALUMINUM DARK BRONZE No AL01 0-H
50 CLASSROOM 50 3' - 0" 7' - 0" 1 3/4" D2 WOOD-SOLID CORE STAINED F1 HM PAINTED; PNT-03 No 05 50
51.1 PHOTO STUDIO 51 3' - 0" 7' - 0" 1 3/4" D3 WOOD-SOLID CORE STAINED F1 HM PAINTED; PNT-03 No 06 51.1
51.2 PHOTO STUDIO 51 3' - 0" 7' - 0" 1 3/4" D4 WOOD-SOLID CORE STAINED F1 HM PAINTED; PNT-03 No 11 51.2
51A STORAGE 51A 3' - 0" 7' - 0" 1 3/4" D4 WOOD-SOLID CORE STAINED F1 HM PAINTED; PNT-03 No 03 51A
51B CHANGING 51B 3' - 0" 7' - 0" 1 3/4" D4 WOOD-SOLID CORE STAINED F1 HM PAINTED; PNT-03 No 10 51B
52.1 HALLWAY O-C 5' - 0" 7' - 0" 1 3/4" D6 WOOD-SOLID CORE STAINED F1 HM PAINTED; PNT-03 Yes 17 52.1
52.2 PHYSICS LAB 52 3' - 0" 7' - 0" 1 3/4" D7 HM DOOR PAINTED; PNT-03 F1 HM PAINTED; PNT-03 No 12 52.2
52A OPTICS LAB 52A 3' - 0" 7' - 0" 1 3/4" D4 WOOD-SOLID CORE STAINED F1 HM PAINTED; PNT-03 No 08 52A
52B ACOUSTICS STUDIO 52B 3' - 0" 7' - 0" 1 3/4" D3 WOOD-SOLID CORE STAINED F1 HM PAINTED; PNT-03 No 02 52B
52C STORAGE 52C 3' - 0" 7' - 0" 1 3/4" D2 WOOD-SOLID CORE STAINED F1 HM PAINTED; PNT-03 No 03 52C
55 OFFICE 55 3' - 0" 7' - 0" 1 3/4" D2 WOOD-SOLID CORE STAINED F2 HM PAINTED; PNT-03 No 08 55
57 OFFICE 57 3' - 0" 7' - 0" 1 3/4" D2 WOOD-SOLID CORE STAINED F2 HM PAINTED; PNT-03 No 08 57
59.1 COMPUTER LAB 59 3' - 0" 7' - 0" 1 3/4" D3 WOOD-SOLID CORE STAINED F1 HM PAINTED; PNT-03 No 04 59.1
59.2 COMPUTER LAB 59 3' - 0" 7' - 0" 1 3/4" D3 WOOD-SOLID CORE STAINED F1 HM PAINTED; PNT-03 Yes 07 59.2
59A.1 EQUIP / CHECK OUT 59A 3' - 0" 7' - 0" 1 3/4" D3 WOOD-SOLID CORE STAINED F1 HM PAINTED; PNT-03 No 08 59A.1
59A.2 EQUIP / CHECK OUT 59A 3' - 0" 7' - 0" 1 3/4" D3 WOOD-SOLID CORE STAINED F1 HM PAINTED; PNT-03 No 08 59A.2
59C VESTIBULE 59C 3' - 0" 7' - 0" 1 3/4" D3 WOOD-SOLID CORE STAINED EXIST EXISTING HM PAINTED; PNT-03 No 13 59C
59D DARK ROOM 59D 3' - 0" 7' - 0" 1 3/4" D4 WOOD-SOLID CORE STAINED F1 HM PAINTED; PNT-03 No 01 59D
59E FILM 59E 3' - 0" 7' - 0" 1 3/4" D4 WOOD-SOLID CORE STAINED F1 HM PAINTED; PNT-03 No 01 59E
68 CUST RM 68 3' - 0" 7' - 0" 1 3/4" D7 HM DOOR PAINTED; PNT-03 F1 HM PAINTED; PNT-03 No 15 68
69 MECHANICAL ROOM 69 5' - 0" 7' - 0" 1 3/4" D5 HM DOOR PAINTED; PNT-03 F1 HM PAINTED; PNT-03 90 MIN No 16 69
LEVEL 02
272 BIO-CHEMISTRY LAB 272 3' - 0" 7' - 0" 1 3/4" D2 WOOD-SOLID CORE STAINED F3 HM PAINTED; PNT-03 No 09 272
276 CLASSROOM 276 3' - 0" 7' - 0" 1 3/4" D2 WOOD-SOLID CORE STAINED F2 HM PAINTED; PNT-03 No 14 276
3" = 1'-0"E2 HM JAMB STUD DETAIL
3" = 1'-0"E1 HM HEAD STUD DETAIL
1/4" = 1'-0"D4 FRAME TYPES
1/4" = 1'-0"C2 DOOR TYPES
3" = 1'-0"B5 INTERIOR STOREFRONT HEAD TYP
3" = 1'-0"A4 INTERIOR STOREFRONT JAMB
3" = 1'-0"A5 INTERIOR STOREFRON @ FLOOR TYP
GLAZING GENERAL NOTES
1 CONTRACTOR TO CONFIRM AND VERIFY QUANTITIES OF ALL GLAZING TYPES
2 ALL GLAZING DIMENSIONS TO BE FIELD VERIFIED PRIOR TO BIDDING, ORDERING, AND INSTALLING
3 ROUGH OPENING REQUIREMENTS SHALL BE COORDINATED WITH WINDOW MANUFACTURER, TYP
4 ALL CURTAINWALL SYSTEMS REQUIRE DELEGATED DESIGN SUBMITTAL
5 SEE DOOR SCHEDULE FOR SCHEDULED GLAZING WITHIN DOORS
6 SEE FLOOR PLAN AND ELEVATIONS FOR WALL TYPE AND MATERIAL CONDITION IN REFERING TO WINDOW AND
STOREFRONT DETAILS
7 SAFETY GLAZING SHALL BE INSTALLED IN HAZARDOUS LOCATIONS WITH IBC 2406.4, THIS INCLUDES GLAZING IN WINDOW,
STOREFRONT, AND DOOR TYPES.
*Refer to hardware specifications for doors with electrical hardware.
3" = 1'-0"B1 BIO-CHEM. LAB WINDOW HEAD DETAIL - INT.
3" = 1'-0"C1 BIO-CHEM. LAB WINDOW JAMB DETAIL - INT.
3" = 1'-0"A1 BIO-CHEM. LAB WINDOW SILL DETAIL - INT.
1 1/2" = 1'-0"A2 BIO- CHEMISTRY LAB SILL DETAIL - EXTERIOR
1 1/2" = 1'-0"B2 BIO-CHEM. LAB JAMB DETAIL - EXTERIOR 1
1 1/2" = 1'-0"B3 BIO-CHEM. LAB JAMB DETAIL - EXTERIOR 2
1/4" = 1'-0"C6 WINDOW TYPES
FLOOR FINISH LEGEND
CARPET TILE
Room name
101
F
B
W WALL FINISH
BASE FINISH
FLOOR FINISH
ROOM NUMBER
FINISH KEY
FINISH CODE; REFER TO
ELEVATIONS FOR ENTIRE
SCOPE.
REFER TO FINISH SCHEDULE
FOR BASIS OF DESIGN.
CPT-02
CPT-01
SHEET GOOD FLOORING
EPOXY FLOORING
RF-01
SF-01
SEALED CONCRETECNC-01
NOTE: INDICATES MAIN FIELD FINISH; ASSUME THIS
FINISH IN ENTIRE AREA UNLESS AN ACCENT IS CALLED
OUT IN PLANS OR ELEVATION
CARPET TILE
*MULTIPLE FINISHES;
SEE ELEVATION
TYP. ROOM FINISH TAG ACCENT TAG
XX
-
X
X
EX
T
E
N
T
O
F
F
I
N
I
S
H
SC
O
P
E
ENTRY MAT TILEEM-01
TL-01 PORCELAIN TILE
RF-02 LUXURY VINYL PLANK
* SEE ENLARGED FINISH PLANS + INTERIOR ELEVATIONS+ FINISH SCHEDULE SHEET FOR
MORE INFORMATION *
ARROWS REPRESENT
EXTENT OF SCOPE
EXISTINGEXISTCPT-03 CARPET TILE
PHYSICS LAB
52
SF-01
WB-01
PNT-01
CLASSROOM
50
CPT-01
WB-01
PNT-01
PHOTO STUDIO
51
RF-01
RB-01
PNT-01
COMPUTER LAB
59
CPT-01
WB-01
PNT-01
DARK ROOM
59D
RF-01
WB-01
PNT-01
EQUIP / CHECK OUT
59A
CPT-02
WB-01
PNT-01
HALLWAY
O-C
CPT-01
WB-01
PNT-01
MEN'S RM
66
EXIST
EXIST
EXIST
WOMEN'S RM
64
EXIST
EXIST
EXIST
STORAGE
51A
RF-01
WB-01
PT-01
VESTIBULE
59C
RF-01
WB-01
PNT-01
FILM
59E
RF-01
WB-01
PNT-01
VESTIBULE
0-H
EM-01
WB-01
PT-01
CHANGING
51B
RF-01
WB-01
PT-01
STORAGE
52C
SF-01
WB-01
PNT-01
OPTICS LAB
52A
CPT-01
WB-01
PNT-01
ACOUSTICS STUDIO
52B
CPT-01
WB-01
WC-01
CUST RM
68
EXIST
WB-01
PNT-01
VESTIBULE
O-A
EM-01
WB-01
PNT-01
OFFICE
55
CPT-02
WB-01
PNT-01
OFFICE
57
CPT-02
WB-01
PNT-01
STORAGE
59B
CPT-02
WB-01
PNT-01
RF-02
19'-10"
WB-02
WB-02
WB-02
WB
-
0
2
WB
-
0
2
WB-02
WB-02
WB
-
0
2
WB-02
WB
-
0
2
PNT-04
WB-03
LEVEL 5 FINISH
DIRECTION OF FLOORING
TS-02
TS-04
TS-05
TS-05
TS-05TS-05
TS-04
TS-04
EXIST
SF-01
09.30
09.30
DIRECTION OF FLOORING
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A700
LEVEL 00
FINISH
PLANS
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
GENERAL NOTES - FINISH
1 RE: FLOOR PLANS FOR INTERIOR ELEVATIONS
2 ALL MATERIALS TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
3 FLOORING MATERIAL TRANSITIONS TO OCCUR AT CENTERLINE OF DOOR THRESHOLDS, UNLESS NOTED OTHERWISE
4 PREPARE FLOORS/WALLS TO RECEIVE FINISH MATERIAL. REFER TO MANUFACTURER'S RECOMMENDATIONS FOR
SURFACE PREPARATION. NOTIFY ARCHITECT IF CONDITIONS ARE INADEQUATE FOR REQUIRED INSTALLATION
5 RE: ROOM FINISH LEGEND ON SHEET SERIES A700 FOR MORE INFORMATION
6 RE: DIMENSION PLAN SHEET SERIES A120 FOR WALL TYPE LOCATIONS; RE: SHEET SERIES A500 FOR WALL TYPE AND
ASSEMBLY DESCRIPTIONS
7 CONTRACTOR TO PROVIDE SOLID BLOCKING AT ALL CASEWORK, FIXED FURNISHINGS, AND EQUIPMENT. COORDINATE
WITH ELEVATIONS, SECTIONS, FURNITURE, FIXTURE SHEETS, AND SPECIFICATIONS
8 RE: SHEET SERIES A500 FOR TYPICAL DETAILS
9 TILE INSTALLER TO FOLLOW TCNA & ANSI GUIDELINES
10 ALL FLOORING MATERIALS ARE TO RUN WALL TO WALL AND BENEATH CASEWORK
11 VERIFY LOCATION OF POINT OR ORIGIN OF TILE AND CONTROL JOINTS ON SHOP DRAWINGS AND WITH ARCHITECT
ON-SITE PRIOR TO INSTALLATION
12 ALL GROUT TO BE SEALED
13 GENERAL CONTRACTOR TO COORDINATE POWER/DATA PLACEMENT WITH FURNITURE PROVIDER
14 LEVEL 5 FINISH REQUIRED FOR ALL WALL GRAPHIC AND WALLCOVERING LOCATIONS. SEE FINISH PLANS AND ELEVATIONS
FOR LOCATIONS
15 ALL METAL STUD WALLS TO DECK ABOVE, UNLESS NOTED OTHERWISE; SEE SHEET SERIES A500 FOR WALL TYPES
16 PROVIDE DEFLECTION TRACKS AT ALL STUD WALLS RE: DETAILS ON SHEET SERIES A500
17 ALL EXPOSED METAL TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
3/16" = 1'-0"A1 LEVEL 00 FINISH PLAN
WOMEN'S RM
132
TL-01
TS-01
*
MEN'S RM
134
TL-01
TS-01
*
UNISEX RM
136
TL-01
TS-01
*
PHYSICAL GEOLOGY ROOM
158
EXIST
WB-01
PNT-01
TS-02 TS-02 TS-02
FLOOR FINISH LEGEND
CARPET TILE
Room name
101
F
B
W WALL FINISH
BASE FINISH
FLOOR FINISH
ROOM NUMBER
FINISH KEY
FINISH CODE; REFER TO
ELEVATIONS FOR ENTIRE
SCOPE.
REFER TO FINISH SCHEDULE
FOR BASIS OF DESIGN.
CPT-02
CPT-01
SHEET GOOD FLOORING
EPOXY FLOORING
RF-01
SF-01
SEALED CONCRETECNC-01
NOTE: INDICATES MAIN FIELD FINISH; ASSUME THIS
FINISH IN ENTIRE AREA UNLESS AN ACCENT IS CALLED
OUT IN PLANS OR ELEVATION
CARPET TILE
*MULTIPLE FINISHES;
SEE ELEVATION
TYP. ROOM FINISH TAG ACCENT TAG
XX
-
X
X
EX
T
E
N
T
O
F
F
I
N
I
S
H
SC
O
P
E
ENTRY MAT TILEEM-01
TL-01 PORCELAIN TILE
RF-02 LUXURY VINYL PLANK
* SEE ENLARGED FINISH PLANS + INTERIOR ELEVATIONS+ FINISH SCHEDULE SHEET FOR
MORE INFORMATION *
ARROWS REPRESENT
EXTENT OF SCOPE
EXISTINGEXISTCPT-03 CARPET TILE
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A701
LEVEL 01
FINISH
PLANS
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
3/16" = 1'-0"A1 LEVEL 01 FINISH PLAN
GENERAL NOTES - FINISH
1 RE: FLOOR PLANS FOR INTERIOR ELEVATIONS
2 ALL MATERIALS TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
3 FLOORING MATERIAL TRANSITIONS TO OCCUR AT CENTERLINE OF DOOR THRESHOLDS, UNLESS NOTED OTHERWISE
4 PREPARE FLOORS/WALLS TO RECEIVE FINISH MATERIAL. REFER TO MANUFACTURER'S RECOMMENDATIONS FOR
SURFACE PREPARATION. NOTIFY ARCHITECT IF CONDITIONS ARE INADEQUATE FOR REQUIRED INSTALLATION
5 RE: ROOM FINISH LEGEND ON SHEET SERIES A700 FOR MORE INFORMATION
6 RE: DIMENSION PLAN SHEET SERIES A120 FOR WALL TYPE LOCATIONS; RE: SHEET SERIES A500 FOR WALL TYPE AND
ASSEMBLY DESCRIPTIONS
7 CONTRACTOR TO PROVIDE SOLID BLOCKING AT ALL CASEWORK, FIXED FURNISHINGS, AND EQUIPMENT. COORDINATE
WITH ELEVATIONS, SECTIONS, FURNITURE, FIXTURE SHEETS, AND SPECIFICATIONS
8 RE: SHEET SERIES A500 FOR TYPICAL DETAILS
9 TILE INSTALLER TO FOLLOW TCNA & ANSI GUIDELINES
10 ALL FLOORING MATERIALS ARE TO RUN WALL TO WALL AND BENEATH CASEWORK
11 VERIFY LOCATION OF POINT OR ORIGIN OF TILE AND CONTROL JOINTS ON SHOP DRAWINGS AND WITH ARCHITECT
ON-SITE PRIOR TO INSTALLATION
12 ALL GROUT TO BE SEALED
13 GENERAL CONTRACTOR TO COORDINATE POWER/DATA PLACEMENT WITH FURNITURE PROVIDER
14 LEVEL 5 FINISH REQUIRED FOR ALL WALL GRAPHIC AND WALLCOVERING LOCATIONS. SEE FINISH PLANS AND ELEVATIONS
FOR LOCATIONS
15 ALL METAL STUD WALLS TO DECK ABOVE, UNLESS NOTED OTHERWISE; SEE SHEET SERIES A500 FOR WALL TYPES
16 PROVIDE DEFLECTION TRACKS AT ALL STUD WALLS RE: DETAILS ON SHEET SERIES A500
17 ALL EXPOSED METAL TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
MEN'S ROOM
226
TL-01
TS-01
*
WOMEN'S ROOM
220
TL-01
TS-01
*
BIO-CHEMISTRY LAB
272
SF-01
RB-01
PNT-01
TS-04
TS-02 TS-02
CPT-03
09.30
FLOOR FINISH LEGEND
CARPET TILE
Room name
101
F
B
W WALL FINISH
BASE FINISH
FLOOR FINISH
ROOM NUMBER
FINISH KEY
FINISH CODE; REFER TO
ELEVATIONS FOR ENTIRE
SCOPE.
REFER TO FINISH SCHEDULE
FOR BASIS OF DESIGN.
CPT-02
CPT-01
SHEET GOOD FLOORING
EPOXY FLOORING
RF-01
SF-01
SEALED CONCRETECNC-01
NOTE: INDICATES MAIN FIELD FINISH; ASSUME THIS
FINISH IN ENTIRE AREA UNLESS AN ACCENT IS CALLED
OUT IN PLANS OR ELEVATION
CARPET TILE
*MULTIPLE FINISHES;
SEE ELEVATION
TYP. ROOM FINISH TAG ACCENT TAG
XX
-
X
X
EX
T
E
N
T
O
F
F
I
N
I
S
H
SC
O
P
E
ENTRY MAT TILEEM-01
TL-01 PORCELAIN TILE
RF-02 LUXURY VINYL PLANK
* SEE ENLARGED FINISH PLANS + INTERIOR ELEVATIONS+ FINISH SCHEDULE SHEET FOR
MORE INFORMATION *
ARROWS REPRESENT
EXTENT OF SCOPE
EXISTINGEXISTCPT-03 CARPET TILE
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A702
LEVEL 02
FINISH
PLANS
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
3/16" = 1'-0"A1 LEVEL 02 FINISH PLAN
GENERAL NOTES - FINISH
1 RE: FLOOR PLANS FOR INTERIOR ELEVATIONS
2 ALL MATERIALS TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
3 FLOORING MATERIAL TRANSITIONS TO OCCUR AT CENTERLINE OF DOOR THRESHOLDS, UNLESS NOTED OTHERWISE
4 PREPARE FLOORS/WALLS TO RECEIVE FINISH MATERIAL. REFER TO MANUFACTURER'S RECOMMENDATIONS FOR
SURFACE PREPARATION. NOTIFY ARCHITECT IF CONDITIONS ARE INADEQUATE FOR REQUIRED INSTALLATION
5 RE: ROOM FINISH LEGEND ON SHEET SERIES A700 FOR MORE INFORMATION
6 RE: DIMENSION PLAN SHEET SERIES A120 FOR WALL TYPE LOCATIONS; RE: SHEET SERIES A500 FOR WALL TYPE AND
ASSEMBLY DESCRIPTIONS
7 CONTRACTOR TO PROVIDE SOLID BLOCKING AT ALL CASEWORK, FIXED FURNISHINGS, AND EQUIPMENT. COORDINATE
WITH ELEVATIONS, SECTIONS, FURNITURE, FIXTURE SHEETS, AND SPECIFICATIONS
8 RE: SHEET SERIES A500 FOR TYPICAL DETAILS
9 TILE INSTALLER TO FOLLOW TCNA & ANSI GUIDELINES
10 ALL FLOORING MATERIALS ARE TO RUN WALL TO WALL AND BENEATH CASEWORK
11 VERIFY LOCATION OF POINT OR ORIGIN OF TILE AND CONTROL JOINTS ON SHOP DRAWINGS AND WITH ARCHITECT
ON-SITE PRIOR TO INSTALLATION
12 ALL GROUT TO BE SEALED
13 GENERAL CONTRACTOR TO COORDINATE POWER/DATA PLACEMENT WITH FURNITURE PROVIDER
14 LEVEL 5 FINISH REQUIRED FOR ALL WALL GRAPHIC AND WALLCOVERING LOCATIONS. SEE FINISH PLANS AND ELEVATIONS
FOR LOCATIONS
15 ALL METAL STUD WALLS TO DECK ABOVE, UNLESS NOTED OTHERWISE; SEE SHEET SERIES A500 FOR WALL TYPES
16 PROVIDE DEFLECTION TRACKS AT ALL STUD WALLS RE: DETAILS ON SHEET SERIES A500
17 ALL EXPOSED METAL TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A710
FINISH
SCHEDULES,
ACCESSORY
SCHEDULES
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
SCEDULED MATERIALS AND FINISHES SHALL BE USED FOR BASIS OF DESIGN U.N.O.
FINISH SCHEDULE
CODE PRODUCT TYPE MANUFACTERER STYLE COLOR DIVISION FINISH NOTES/ REMARKS SPECIFICATION
DIVISION 06 - WOODS, PLASTICS & COMPOSITES
FRP-01 FIBER-GLASS REINFORCED PANEL MARLITE SMOOTH WHITE S100G DIVISION 06 - WOODS, PLASTICS & COMPOSITES AT ALL JANITOR SINKS, COORDINATING FACTORY TRIM PROVIDED AT ALL OUTSIDE EDGES, INSTALLATION PER
MANUFACTURERS INSTRUCTIONS
PL-01 PLASTIC LAMINATE WILSONART GRAPHITE 10657 DIVISION 06 - WOODS, PLASTICS & COMPOSITES BASE CABINETS MATTE FINISH 60
PL-02 PLASTIC LAMINATE WILSONART STANDARD LAMINATE CRISP LINEN 4942 DIVISION 06 - WOODS, PLASTICS & COMPOSITES COUNTERTOPS FINE VELVET FINISH 38
WV-01 WOOD VENEER RED OAK CHERRY MOHOGANY DIVISION 06 - WOODS, PLASTICS & COMPOSITES FINISH TO MATCH EXISTING CABINETS. CONTRACTOR TO FIELD
VERIFY WITH OWNER
GRAIN TO RUN VERTICAL, ALKYD WIPING STAIN
DIVISION 07 - THERMAL & MOISTURE PROTECTION
SAT-01 SPRAY-ON THERMAL & ACOUSTICAL INSULATION INTERNATIONAL CELLULOSE CORPORATION K13 DIVISION 07 - THERMAL & MOISTURE PROTECTION
DIVISION 09 - BASE & TRANSITIONS
TS-01 METAL COVE BASE SCHLUTER DILEX-AHK SATIN ANNODIZED ALUMINUM DIVISION 09 - BASE & TRANSITIONS HEIGHT TO MATCH MATERIAL THICKNESS. INTSTALL PER MANUFACTURERS INSTRUCTIONS.
TS-02 METAL FLOOR TRANSITION STRIP SCHLUTER SCHIENE SATIN ANNODIZED ALUMINUM DIVISION 09 - BASE & TRANSITIONS HEIGHT TO MATCH MATERIAL THICKNESS. INTSTALL PER MANUFACTURERS INSTRUCTIONS.
TS-03 METAL EDGE TRIM SCHLUTER JOLLY SATIN ANNODIZED ALUMINUM DIVISION 09 - BASE & TRANSITIONS HEIGHT TO MATCH MATERIAL THICKNESS. INTSTALL PER MANUFACTURERS INSTRUCTIONS.
TS-04 RUBBER FLOOR TRANSITION TARKETT EG-XX-H TO BE SELECTED FROM MANUFACTURERS FULL LINE OF COLORS DIVISION 09 - BASE & TRANSITIONS 1/4" MATERIAL TO FLOOR 100% VULCANIZED RUBBER TRANSITION STRIP
TS-05 RUBBER FLOOR TRANSITION TARKETT SLT-XX-A TO BE SELECTED FROM MANUFACTURERS FULL LINE OF COLORS DIVISION 09 - BASE & TRANSITIONS 1/4" MATERIAL TO 1/8" MATERIAL 100% VULCANIZED RUBBER TRANSITION STRIP
WB-01 RUBBER WALL BASE TARKETT 4" TRADITIONAL WALL BASE, WITH TOE 01 SNOW WHITE DIVISION 09 - BASE & TRANSITIONS INSTALLATION PER MANUFACTURERS INSTURCTIONS, RE: FINISH PLANS AND ELEVATIONS FOR LOCATIONS
WB-02 RUBBER WALL BASE TARKETT 4" TRADITIONAL WALL BASE, TOELESS COOL METAL VL4 DIVISION 09 - BASE & TRANSITIONS BASE AT CASEWORK INSTALLATION PER MANUFACTURERS INSTRUCTIONS, RE: FINISH PLANS AND ELEVATIONS FOR LOCATIONS.
WB-03 RUBBER WALL BASE TARKETT 4" TRADITIONAL WALL BASE, WITH TOE 29 MOON ROCK DIVISION 09 - BASE & TRANSITIONS INSTALLATION PER MANUFACTURERS INSTRUCTIONS, RE: FINISH PLANS AND ELEVATIONS FOR LOCATIONS.
DIVISION 09 - CEILINGS
ACP-01 ACOUSTICAL CEILING PANEL USG 2110 RADAR WHITE DIVISION 09 - CEILINGS 24" X 24" USG 15/16" DOWN SUSPENSION SYSTEM
SC-01 SPECIALTY CEILING SOUNDASSURED ACOUSTIC FOAM PANELS CHARCOAL DIVISION 09 - CEILINGS 12"x12"x4" PANEL. ATTACHED TO GYP CEILING. RE: MANUFACTURER'S RECOMMENDATIONS
DIVISION 09 - FLOORS
CPT-01 CARPET TILE INTERFACE SOURCE MATERIAL - STREAMING GRAPHITE 106308 DIVISION 09 - FLOORS 2. GENERAL CAPRET FLOORING 25CM x 1M, ASHLAR INSTALLATION, DIRECT GLUE, INSTALATION PER MANUFACTURERS INSTALLATION
INSTRUCTIONS, RE: FINISH PLANS FOR LOCATIONS AND INSTALLATION DIRECTION.
CPT-02 CARPET TILE INTERFACE OPEN AIR 404 NICKEL 106750 DIVISION 09 - FLOORS 2. GENERAL CAPRET FLOORING 50CM x 50CM, MONOLITHIC, DIRECT GLUE, INSTALLATION PER MANUFACTURERS INSTALLATION INSTRUCTIONS, RE:
FINISH PLANS FOR LOCATIONS AND INSTALLATION DIRECTION
CPT-03 CARPET TILE INTERFACE ENTROPY PRALINE 9606 DIVISION 09 - FLOORS 2. GENERAL CAPRET FLOORING 50CM x 50CM, NON DIRECTIONAL, DIRECT GLUE, INTALLATION PER MANUFACTURERS INSTALLATION
INSTRUCTIONSM RE: FINISH PLANS FOR LOCATIONS AND INSTALLATION DIRECTION
EM-01 CARPET TILE - ENTRY MAT INTERFACE STEP REPEAT IRON 104940 DIVISION 09 - FLOORS 2. GENERAL CAPRET FLOORING -
RF-01 SHEET VINYL PATCRAFT MEANING SHEET 1584V EXPERIENCE 00590 DIVISION 09 - FLOORS 79"x65' SHEET SIZE, INSTALLATION PER MANUFACTURERS INSTRUCTIONS
RF-02 LUXURY VINYL TILE INTERFACE #A004 LEVEL SET TEXTURED WOODGRAINS A00417 SILVER DUNE DIVISION 09 - FLOORS 25CMx1M, 22MIL, ASHLAR INSTALLATION, RE: FINISH PLANS FOR LOCATIONS AND FLOORING DIRECTIONS. DIRECT
GLUE, INSTALLATION PER MANUFACTURERS INSTRUCTIONS
SF-01 EPOXY FLOORING RUST-OLEUM 9100 SERIES EPOXY SILVER GRAY DIVISION 09 - FLOORS TWO COATS MINIMUM
DIVISION 09 - PAINT & WALLCOVERING
PNT-01 FIELD WALL PAINT SHERWIN WILLIAMS CASHMERE SHELL WHITE BYUI CUSTOM MATCH DIVISION 09 - PAINT & WALLCOVERING MEDIUM LUSTER
PNT-02a FIELD CEILIING PAINT SHERWIN WILLIAMS BYUI STANDARD FOR CEILING PAINT SHELL WHITE SW8917 DIVISION 09 - PAINT & WALLCOVERING FLAT FINISH
PNT-02b EXPOSED DECK PAINT SHERWIN WILLIAMS BYUI STANDARD FOR CEILING PAINT IRON ORE SW7069 DIVISION 09 - PAINT & WALLCOVERING FLAT FINISH
PNT-03a TRIM PAINT (HOLLOW METAL FRAMES)PITTSBURG PAINTS BYUI STANDARD FOR DOOR + DOOR FRAME PAINT BLACK 164 MIXED WITH WHITE 36 DIVISION 09 - PAINT & WALLCOVERING CONFIRM COLOR MATCHES EXISTING BASEMENT FRAMES ACRYLIC, DTM, MEDIUM LUSTRE
PNT-03b TRIM PAINT (HOLLOW METAL FRAMES)BENJAMIN MOORE C235-4B BYUI STANDARD FOR DOOR + DOOR FRAME PAINT RX 4x 29.2500, BB 7x 1.2500, WH 0x 1.5000 DIVISION 09 - PAINT & WALLCOVERING CONFIRM COLOR MATCHES EXISTING LEVEL 2 FRAMES ACRYLIC, DTM, MEDIUM LUSTRE
PNT-04 ACCENT PAINT SHERWIN WILLIAMS GAUNTLET GRAY SW7019 DIVISION 09 - PAINT & WALLCOVERING FLAT FINISH. DRY WALL TO BE PREPARED TO LEVEL 5 FINISH
BEFORE PAINTING
WC-01 WALL COVERING SOUNDASSURED ACOUSTIC FOAM PANELS CHARCOAL DIVISION 09 - PAINT & WALLCOVERING 12"x12"x4" PANEL
DIVISION 09 - TILE
TL-01 FLOOR TILE DALTILE SOCIETY PARK LANE GRAY SO47 DIVISION 09 - TILE POLISHED, 12"x24", THICKNESS: 3/8", INSTALL: ONE THIRD OFFSET, GROUT: TBD, RE: FINISH PLANS FOR LOCATIONS
TL-02 WALL TILE DALTILE COLOR WHEEL - LINEAR MATTE ARCTIC WHITE 0790 DIVISION 09 - TILE 4"x12", HORIZONTAL, STACKED BOND INSTALLATION, THICKNESS 3/8", GROUT: TBD, RE: ELEVATIONS + FINISH PLANS
FOR LOCATIONS. FULL TILE TOP ROW
TL-03 WALL TILE DALTILE COLOR WHEEL - LINEAR NAVY K189 DIVISION 09 - TILE 4"x12", HORIZONTAL, STACKED BOND INSTALLATION, THICKNESS 3/8", GROUT: TBD, RE: ELEVATIONS + FINISH PLANS
FOR LOCATIONS. FULL TILE TOP ROW
DIVISION 12 - FURNISHINGS
RS-01 ROLLER SHADES DRAPER SINGLE SHADE 1% OPENESS, MANUAL SCREEN FABRIC: MERMET E SCREEN, PEARL GRAY DIVISION 12 - FURNISHINGS 1% OPEN -
SS-01 EPOXY RESIN COUNTERTOP AMERICAN EPOXY SCIENTIFIC BLACK DIVISION 12 - FURNISHINGS PRODUCT TO MATCH EXISTING COUNTERTOP 1" THICK, 3/16" RADIUS, 96" LENGTH
HARDWARE SCHEDULE
PRODUCT TYPE MODEL FINISH SPECIFICATIONS
CABINET PULL - BASEMENT LEVEL AMEROCK EDGE PULL SATIN NICKEL 3.75"
WALL HOOKS RICHELIEU DOUBLE ROBE HOOK, NH1253021195 BRUSHED NICKEL RE: ELEVATIONS FOR QTY.
CABINET LOCKS OLYMPUS LOCKER PER CAMPUS STANDARD
CABINET PULL - LEVEL 1 AND 2 MATCH EXISTING HARDWARE
SCHEDULED MATERIALS AND FINISHES SHALL BE USED FOR BASIS OF DESIGN U.N.O.
ACCESSORY SCHEDULE
CODE PRODUCT TYPE MANUFACTURER MAKE/MODEL FINISH COMMENTS
10.01 FRAMELESS MIRROR N/A 24" W x 42" H PENCIL EDGE GRIND ADHERED DIRECTLY TO FINISH WALL
10.02 36" GRAB BAR BOB B-2111 SATIN FINISH; STAINLESS STEEL CONTRACTOR PROVIDED / CONTRACTOR INSTALLED, INSTALL PER MANUFACTURER'S RECOMMENDATIONS. SEE G011 FOR MOUNTING HEIGHTS.
10.03 WALL MOUNTED SOAP DISPENSER OWNER PROVIDED/ OWNER INSTALLED INSTALL PER MANUFACTURER'S RECOMMENDATIONS. SEE G01 1 FOR MOUNTING HEIGHTS
10.05 TOILET PAPER HOLDER OWNER PROVIDED/ OWNER INSTALLED INSTALL PER MANUFACTURER'S RECOMMENDATIONS. SEE G01 1 FOR MOUNTING HEIGHTS
10.06 PAPER TOWEL DISPENSER OWNER PROVIDED/ OWNER INSTALLED INSTALL PER MANUFACTURER'S RECOMMENDATIONS. SEE G01 1 FOR MOUNTING HEIGHTS
10.10 42" GRAB BAR BOB B-2111 SATIN FINISH; STAINLESS STEEL CONTRACTOR PROVIDED / CONTRACTOR INSTALLED, INSTALL PER MANUFACTURER'S RECOMMENDATIONS. SEE G011 FOR MOUNTING HEIGHTS.
10.16 18" GRAB BAR BOB B-2111 SATIN FINISH; STAINLESS STEEL CONTRACTOR PROVIDED / CONTRACTOR INSTALLED, INSTALL PER MANUFACTURER'S RECOMMENDATIONS. SEE G011 FOR MOUNTING HEIGHTS.
10.20 SANITARY NAPKIN DISPOSAL OWNER PROVIDED/ OWNER INSTALLED INSTALL PER MANUFACTURER'S RECOMMENDATIONS. SEE G01 1 FOR MOUNTING HEIGHTS
10.27 TOILET SEAT COVER DISPENSER BOBRICK B-4221 SATIN FINISH; STAINLESS STEEL INSTALL PER MANUFACTURER'S RECOMMENDATIONS. SEE G011 FOR MOUNTING HEIGHTS
10.28 FRAMELESS MIRROR N/A 18" W x24" H PENCIL EDGE GRIND ADHERED DIRECTLY TO FINISH WALL
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
STORAGE
18
CUST OFFICE
16
CUSTODIAL LAUNDRY RM
14
MEN'S RM
66
WOMEN'S RM
64
MECHANICAL ROOM
69
MECHANICAL RM
10
VESTIBULE
O-A
MECH RM
12
HALLWAY
O-C
STORAGE
63
STAIRWELL
O-B
PIPE CHASE
O-Q
ELEVATOR
O-D
MECH RM
67
CUST RM
68
STAIRWELL
0-F
STORAGE
20 ELEVATOR
0-K
ELEC VAULT
80
HALLWAY
0-N
COMPACT FILL
COMPACT FILL
COMPACT FILL
CRAWL SPACE
PIPE TUNNEL
PIPE TUNNEL
PI
P
E
T
U
N
N
E
L
CRAWL SPACE
PIPE TUNNEL
PIPE TUNNEL
PIPE TUNNEL
COMPACT FILL
EXTERIOR
MECHANICAL
ENCLOSURE
CLASSROOM
50
DARK ROOM
59D
COMPUTER LAB
59
PHOTO STUDIO
51
VESTIBULE
59C
OFFICE
57
EQUIP / CHECK OUT
59A
STORAGE
59B OFFICE
55
FILM
59E
ACOUSTICS STUDIO
52B
STORAGE
51A
CHANGING
51B
VESTIBULE
0-H
OPTICS LAB
52A
PHYSICS LAB
52
STORAGE
52C
(PHOTO EQUIPMENT) (PHOTO EQUIPMENT)
POSITRON LAB HIGH ALTITUDE RESEARCH TEAM
VACUUM AND THIN FILMS LAB
needs straps
A910
A1
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A900
LEVEL 00
FURNITURE
PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 00 FURNITURE PLAN
NOTE:
FURNITURE IS OWNER FURNISHED AND
OWNER INSTALLED, UNLESS NOTED
OTHERWISE. THE FOLLOWING LAYOUT
IS TO HELP COORDINATE
INFRASTURCTURE AND SUPPORT FOR
THE FURNITURE. UPDATES WILL BE
PROVIDED BY BYUI AT A LATER DATE.
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
PLANRTARIUM RM
107
LIGHT TRAP
I-Y
HAZ. STORAGE
167
HAZ. STORAGE
166
ROCK LABORATORY
164 MEN'S T.R.
162
WOMEN'S T.R.
160
PIPE CHASE
I-Q
HALLWAY
1-T
LAB PREP ROOM
161
ELEVATOR
1-M
CUST.
147
STAIRWELL
1-P PHYSICAL GEOLOGY ROOM
158
PHYSICAL SCIENCE DISPLAY
ROOM
156
SEISMOGRAPH ROOM
154
RESOURCE ROOM
150A
AUTO TUTORIAL ROOM
171
STORAGE
171A
LABORATORY RM
179
OFFICE
175
OFFICE
176
OFFICE
180
OFFICE
182
OFFICE
184
STORAGE RM
133
LECTURE HALL
172
SHOP RM
133A
PHYSICS CLASSROOM
105
OFFICE
112
OFFICE
114
OFFICE
116
OFFICE
118
OFFICE
118A
ADVANCED LAB
126
LECTURE HALL
127
LAB STORAGE RM
126A
ADVANCED LAB
128
ADVANCED LAB RM
129
LABORATORY
141
OFFICE
150
OFFICE
148
OFFICE
146
OFFICE
144
WOMEN'S RM
132
MEN'S RM
134
PHYSICS LECTURE HALL
131
LECTURE HALL
145 PREP/STORAGE RM
143
OFFICE
110
OFFICE
186
MINEROLOGY LAB
149
HALLWAY
I-N
HALLWAY
I-L
HALLWAY
I-G
HALLWAY
I-K
HALLWAY
I-F
HALLWAY
I-W
HALLWAY
I-D
UNISEX RM
136
STORAGE
172A
STORAGE
131A
VESTIBULE
I-A
STAIRWELL
I-C
STAIRWELL
I-B
OFFICE
142
HALLWAY
1-U
STAIRWELL
1-V
BDF
138
STAIRWELL
1-S
STAIRWELL
1-H
STAIRWELL
1-E
ELEVATOR
1-J
A911
A1
30"
30"
35 1/2"
23'-5 1/2"
66"
20'-5 1/8"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A901
LEVEL 01
FURNITURE
PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 01 FURNITURE PLAN
NOTE:
FURNITURE IS OWNER FURNISHED AND
OWNER INSTALLED, UNLESS NOTED
OTHERWISE. THE FOLLOWING LAYOUT
IS TO HELP COORDINATE
INFRASTURCTURE AND SUPPORT FOR
THE FURNITURE. UPDATES WILL BE
PROVIDED BY BYUI AT A LATER DATE.
A A
1
1
B B
C C
D D
E E
F F
G G
H H
J J
K K
L L
M M
N N
P P
2
2
3
3
4
4
5
5
6
6
7
7
8
8
INSTRUMENT RM
203A
CHEMISTRY STOCK RM
213
OFFICE
213A
CLASSROOM
270
CLASSROOM
268
MEN'S RM
266
WOMEN'S RM
264
OFFICE
252
OFFICE
253
OFFICE
250
OFFICE
248
OFFICE
246 OFFICE
244
OFFICE
242
OFFICE
240
OFFICE
238
WORK ROOM
243
OFFICE
236
OFFICE
234
OFFICE
239
OFFICE
237
OFFICE
235
OFFICE
233
OFFICE
232
CLASSROOM
255
CLASSROOM
277
OFFICE
259
OFFICE
261
OFFICE
263
OFFICE
265
MEN'S ROOM
226
WOMEN'S ROOM
220
GENERAL CHEM LAB
282
CHEM STOCK RM
282A
OFFICE
286
OFFICE
285
OFFICE
289 OFFICE
290
OFFICE
291
OFFICE
292
OFFICE
294
OFFICE
296
OFFICE
298
CHEMISTRY LAB
204
CHEMISTRY LAB
214
CHEMISTRY LAB
210
CHEMISTRY PREP RM
281
CLASSROOM
276
CUST RM
267
BDF RM
280
CUST RM
228
INSTRUMENT RM
203B
CLASSROOM
229
CLASSROOM
279
CLASSROOM
297 CLASSROOM
299
CHEMISTRY LAB
203
STORAGE
258
STORAGE RM
277A
WORK ROOM
287A
SEC/ RECEP RM
287
HALLWAY
2-U HALLWAY
2-D
HALLWAY
2-F
HALLWAY
2-S
LOUNGE
2-V
HALLWAY
2-J
HALLWAY
2-M
SECRETARY/RECEPTION RM
230
HALLWAY
2-K
CLASSROOM
260
CLASSROOM
262
HALLWAY
2-L
CUST STOR
216
STAIRWELL
2-HELEVATOR
2-G
STAIRWELL
2-T
HALLWAY
2-B
STAIRWELL
2-A
STAIRWELL
2-C
BIO-CHEMISTRY LAB
272
ALL NEW STALLS, FIXTURES AND PLUMBING TO BE REPLACED TO
MATCH EXISTING LAYOUT. NEW TILE WALLS, TILE TBD
BA
C
K
S
I
D
E
BA
C
K
S
I
D
E
FR
O
N
T
S
I
D
E
FR
O
N
T
S
I
D
E
CURRENTLY DI WANTER HERE
A911
A4
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A902
LEVEL 02
FURNITURE
PLAN
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/8" = 1'-0"A1 LEVEL 02 FURNITURE PLAN
NOTE:
FURNITURE IS OWNER FURNISHED AND
OWNER INSTALLED, UNLESS NOTED
OTHERWISE. THE FOLLOWING LAYOUT
IS TO HELP COORDINATE
INFRASTURCTURE AND SUPPORT FOR
THE FURNITURE. UPDATES WILL BE
PROVIDED BY BYUI AT A LATER DATE.
PHOTO STUDIO
51
DARK ROOM
59D
COMPUTER LAB
59
EQUIP / CHECK OUT
59A
STORAGE
59B
STORAGE
51A
CHANGING
51B
VESTIBULE
0-H
CLASSROOM
50
STORAGE
52C
PHYSICS LAB
52
ACOUSTICS STUDIO
52B
OPTICS LAB
52A
OFFICE
57
OFFICE
55
C-16 P-21 P-21
C-16 C-16 C-16 C-16 C-16
P-18
P-14
P-20
VESTIBULE
O-A
HALLWAY
O-C
FILM
59E
VESTIBULE
59C
G-6
G-6 TYP
G-1 TYP
G-4
P-1
TYP
P-2
TYP
G-4
P-9
P-12 P-12
P-11
C-13
G-10G-10G-10
G-10
G-10
G-10
G-2
G-12
G-11
TYP
TYP
TYP
TYP
G-1
G-4 P-1
P-19
P-19
P-19
G-2
TYP
G-8
TYP TYP
P-6
P-6
P-6
P-7
P-7
G-8 G-8P-3
P-4 P-4
G-4
G-9G-9
G-8
G-5
G-5
G-5 P-8
G-5
G-5
G-5
G-5
P-16
C-17
P-15
P-15
P-17
P-10
4' - 6"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A910
EQUIPMENT
& FURNITURE
PLANS &
SCHEDULE
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
1/4" = 1'-0"A1 LEVEL 00 ENLARGED EQUIPMENT & FURNITURE PLAN
FURNITURE SCHEDULE - LEVEL 0
Room # Room Name
Type
Mark Asset Name Count Existing New CFCI OFCI OFOI Special Requirements
50 CLASSROOM G-11 20 ● ●
50 CLASSROOM G-12 Classroom Chair 40 ● ●
51 PHOTO STUDIO G-6 Classroom Chair 24 ● ●
51 PHOTO STUDIO P-9 Mobile Computer Cart 1 ● ●
52 PHYSICS LAB C-16 Table 2'-6" x 6'-0" 6 ● ●
52 PHYSICS LAB C-17 Table 2'-6" x 4'-0" 1 ● ●
52 PHYSICS LAB G-6 Classroom Chair 12 ●
52 PHYSICS LAB P-18 Table 2'-6" x 4'-0" 1 ● ●
52 PHYSICS LAB P-19 Dividing Wall w/ White Boards 3
52 PHYSICS LAB P-21 Table 3'-6" x 8'-0" 2 ● ●
52A OPTICS LAB G-1 Task Chair 1 ● ●
52A OPTICS LAB G-8 Task Chair 1 ● ●
52A OPTICS LAB P-1 Table 2'-0" x 6'-0" 1 ●●
52A OPTICS LAB P-14 Table 2'-6" x 5'-0" 1 ●●
55 OFFICE G-8 Task Chair 1 ● ●
55 OFFICE G-9 Office Chair 2 ●
55 OFFICE P-12 Work Station w/ Computer 1 ● ●
57 OFFICE G-8 Task Chair 1 ● ●
57 OFFICE G-9 Office Chair 2 ●
57 OFFICE P-12 Work Station w/ Computer 1 ● ●
59 COMPUTER LAB G-1 Task Chair 18 ● ●
59 COMPUTER LAB P-1 Table 2'-0" x 6'-0" 9 ● ●
59 COMPUTER LAB P-2 Table 2'-0" x 3'-0" 3 ● ●
59A EQUIP / CHECK OUT G-8 Task Chair 1 ● ●
59A EQUIP / CHECK OUT P-10 Large Format Printer 1 ●
59A EQUIP / CHECK OUT P-11 Work Station w/ Computer 1 ●
272 BIO-CHEMISTRY LAB C-16 Table 2'-6" x 6'-0" 1 ●●
272 BIO-CHEMISTRY LAB C-17 Table 2'-6" x 4'-0" 24 ● ●
272 BIO-CHEMISTRY LAB G-1 Task Chair 4 ● ●
O-C HALLWAY G-10 Bench 6 ● ● FABRIC: DESIGNTEX, STYLE: TILT 3001-801, COLOR: SLATE
EQUIPMENT SCHEDULE - LEVEL 0
Room # Room Name
Type
Mark Asset Name Count Existing New CFCI OFCI OFOI Special Requirements
51 PHOTO STUDIO G-4 Computer 1 ●●
51 PHOTO STUDIO G-5 Waste Bin 2 ●●
52 PHYSICS LAB G-2 Tank 15 ●●
52 PHYSICS LAB G-5 Waste Bin 2 ●●
52 PHYSICS LAB P-15 Vacuum Fusion Pump 2 ●●
52 PHYSICS LAB P-16 Aneealing Oven 1 ●●
52 PHYSICS LAB P-17 Geranium Lithium Detector 1 ●●
52 PHYSICS LAB P-20 NitrogenTank 1 ●●
52A OPTICS LAB G-4 Computer 1 ●●
59 COMPUTER LAB G-4 Computer 18 ●●
59 COMPUTER LAB G-5 Waste Bin 1 ●●
59 COMPUTER LAB P-3 Photo Printer 10 ●●
59 COMPUTER LAB P-4 Dry Mount Press 2 ●●
59 COMPUTER LAB P-5 Flatbed Scanner 8 ●●
59A EQUIP / CHECK OUT G-4 Computer 1 ●●
59B STORAGE C-13 Refrigerator 1 ●●
59D DARK ROOM G-5 Waste Bin 1 ●●
59D DARK ROOM P-6 Photo Enlarger 3 ●●
59D DARK ROOM P-7 UV Equipment 2 ●●
59D DARK ROOM P-8 NitrogenTank 1 ●●
NOTE:
FURNITURE IS OWNER FURNISHED AND
OWNER INSTALLED, UNLESS NOTED
OTHERWISE. THE FOLLOWING LAYOUT
IS TO HELP COORDINATE
INFRASTURCTURE AND SUPPORT FOR
THE FURNITURE. UPDATES WILL BE
PROVIDED BY BYUI AT A LATER DATE.
C-9
C-10 C-12
C-11
C-14 C-15
C-17 C-17C-17
C-17 C-17 C-17
C-17
C-17
C-17
C-17
C-17
C-17
C-17
C-17C-17
C-17C-17
C-17C-17C-17C-17
C-17 C-17 C-17
C-19
C-20 C-21
C-22
C-22
C-23
C-24
C-25
C-26
C-27 C-28 C-29
C-30
C-31
C-33
C-32
C-18 C-18 C-18
C-18C-18
C-18
C-18 C-18 C-18
C-18
C-8
G-5
G-5C-4
G-4
G-4
G-3
C-3
G-2
G-2
G-2
C-5
C-6
G-4
C-7
G-2
G-2
G-2
G-1
G-1
G-1
G-1
C-1
C-2
C-16
C-13 C-13
G-5
TYP
4' - 0"
TYP
2' - 6"
BIO-CHEMISTRY LAB
272
A601
C1
A601
B2
A601
B3
G-7
G-6
PHYSICAL GEOLOGY ROOM
158
TYP
TYP
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 002294
4/28/2023
A911
EQUIPMENT
& FURNITURE
PLANS &
SCHEDULES
22.0540
04/28/2023
281 S Center St, Rexburg, ID 83440
Romney 2023
Remodel
Bid Set
FURNITURE SCHEDULE - LEVEL 2
Room # Room Name
Type
Mark Asset Name Count Existing New CFCI OFCI OFOI Special Requirements
272 BIO-CHEMISTRY LAB C-16 Table 2'-6" x 6'-0" 1 ●●
272 BIO-CHEMISTRY LAB C-17 Table 2'-6" x 4'-0" 24 ● ●
272 BIO-CHEMISTRY LAB G-1 Task Chair 4 ● ●
EQUIPMENT SCHEDULE - LEVEL 2
Room # Room Name
Type
Mark Asset Name Count Existing New CFCI OFCI OFOI Special Requirements
272 BIO-CHEMISTRY LAB C-1 Balance 1 ●●
272 BIO-CHEMISTRY LAB C-2 PH Meter 1 ●●
272 BIO-CHEMISTRY LAB C-3 Chromatograph Mass Spec 1 ●●
272 BIO-CHEMISTRY LAB C-4 Portable Chromatograph Mass Spec 1 ●●
272 BIO-CHEMISTRY LAB C-5 RO System 1 ●●
272 BIO-CHEMISTRY LAB C-6 Visible Spectrophotometer 1 ●●
272 BIO-CHEMISTRY LAB C-7 Chromatograph 1 ●●
272 BIO-CHEMISTRY LAB C-8 Floor Shaker 1 ●●
272 BIO-CHEMISTRY LAB C-9 FPLC 1 ●●
272 BIO-CHEMISTRY LAB C-10 Fraction Collector 1 ●●
272 BIO-CHEMISTRY LAB C-11 Sonicator Power Supply 1 ●●
272 BIO-CHEMISTRY LAB C-12 Sonicator 1 ●● Compressed air quick connect , see mechanical drawings
272 BIO-CHEMISTRY LAB C-13 Refrigerator 2 ●●
272 BIO-CHEMISTRY LAB C-14 Freezer - Negative 80 1 ●●
272 BIO-CHEMISTRY LAB C-15 Freezer - Negative 20 1 ●●
272 BIO-CHEMISTRY LAB C-18 Microcentrifuge 10 ●●
272 BIO-CHEMISTRY LAB C-19 Autoclave 1 ●● 240V, see electrical
272 BIO-CHEMISTRY LAB C-20 Tube Furnace 1 ●● 208V, see electrical
272 BIO-CHEMISTRY LAB C-21 Gas Mixing Manifold 1 ●●
272 BIO-CHEMISTRY LAB C-22 Nano Drop 2 ●●
272 BIO-CHEMISTRY LAB C-23 Thermocycler 1 ●●
272 BIO-CHEMISTRY LAB C-24 Micro Centrifuge 1 ●●
272 BIO-CHEMISTRY LAB C-25 Hot Block 1 ●●
272 BIO-CHEMISTRY LAB C-26 Hot Block 1 ●●
272 BIO-CHEMISTRY LAB C-27 Eisa Plate Reader 1 ●●
272 BIO-CHEMISTRY LAB C-28 Spectrophotomer 1 ●●
272 BIO-CHEMISTRY LAB C-29 Gel Imaging 1 ●●
272 BIO-CHEMISTRY LAB C-30 White Light Gel Imaging 1 ●●
272 BIO-CHEMISTRY LAB C-31 Rocking Platform 1 ●●
272 BIO-CHEMISTRY LAB C-32 Centrifuge 1 ●●
272 BIO-CHEMISTRY LAB C-33 Incubator 1 ●●
272 BIO-CHEMISTRY LAB G-2 Tank 6 ●●
272 BIO-CHEMISTRY LAB G-3 CPU 1 ●●
272 BIO-CHEMISTRY LAB G-5 Waste Bin 3 ●●
1/4" = 1'-0"A4 LEVEL 02 ENLARGED EQUIPMENT & FURNITURE PLAN
1/4" = 1'-0"A1 LEVEL 01 ENLARGED EQUIPMENT & FURNITURE PLAN
FURNITURE SCHEDULE - LEVEL 1
Room # Room Name
Type
Mark Asset Name Count Existing New CFCI OFCI OFOI Special Requirements
158 PHYSICAL GEOLOGY
ROOM
G-6 Classroom Chair 36 ●●
158 PHYSICAL GEOLOGY
ROOM
G-7 Geology Table 18 ● ●
NOTE:
FURNITURE IS OWNER FURNISHED AND
OWNER INSTALLED, UNLESS NOTED
OTHERWISE. THE FOLLOWING LAYOUT
IS TO HELP COORDINATE
INFRASTURCTURE AND SUPPORT FOR
THE FURNITURE. UPDATES WILL BE
PROVIDED BY BYUI AT A LATER DATE.
STRUCTURAL GENERAL NOTES
BASIS OF DESIGN
1.GOVERNING BUILDING CODE...............................................2018 IBC
2.OCCUPANCY CATEGORY.......................................................III
3.LOAD COMBINATIONS:
ASD -GRAVITY AND LATERAL.......................................1605.3.1
4.GRAVITY DESIGN:
DEAD LOAD
ROOF................................................................................NA
FLOOR..............................................................................60 PSF
PARTITIONS.....................................................................20 PSF
LIVE LOAD (UNIFORMLY DISTRIBUTED LOADS)
ROOMS..............................................................................80 PSF
FIRST FLOOR CORRIDORS.............................................100 PSF
CORRIDORS ABOVE FIRST FLOOR................................80 PSF
LIVE LOAD (CONCENTRATED LOADS)
ALL AREAS.........................................................................2000 LBS
ROOF LIVE LOAD
(NOT CONCURRENT WITH ROOF SNOW LOAD)............20 PSF
ROOF SNOW LOAD
GROUND SNOW LOAD...................................................NA
5.LATERAL DESIGN:
WIND DESIGN PER ASCE 7-16
ULTIMATE DESIGN WIND SPEED..................................NA
SEISMIC DESIGN
SEISMIC DESIGN PROCEDURE.....................................NA
GENERAL
1.THE GENERAL CONTRACTOR SHALL:
A.BECOME FAMILIAR WITH ALL PORTIONS OF THE CONTRACT DOCUMENTS AND INSURE THAT ALL
SUBCONTRACTORS ARE FAMILIAR WITH THOSE PORTIONS PERTAINING TO THEIR AREA OF
WORK. NO DEVIATIONS WILL BE ALLOWED UNLESS AGREED UPON BY ALL PARTIES IN
WRITING PRIOR TO CONSTRUCTION FABRICATION.
B.VERIFY ALL DIMENSIONS AND ELEVATIONS. COORDINATE ALL DOORS, WINDOWS, NON-
BEARING INTERIOR AND EXTERIOR WALLS, ELEVATIONS, SLOPES, STAIRS, CURBS, DRAINS,
RECESSES, DEPRESSIONS, RAILINGS, WATERPROOFING, FINISHES, CHAMFERS, KERFS, ETC.
C.FIELD VERIFY ALL SITE CONDITIONS AND IMMEDIATELY NOTIFY THE ARCHITECT AND
STRUCTURAL ENGINEER REGARDING ACTUAL CONDITIONS AT THE SITE WHICH ARE NOT PER
THE DRAWINGS.
D.COORDINATE ALL WORK BETWEEN THE VARIOUS TRADES AND SUBCONTRACTORS. REPORT
ANY MODIFICATIONS TO THE STRUCTURAL PORTION OF THE BUILDING BY OTHER TRADES TO
THE ARCHITECT AND STRUCTURAL ENGINEER.
E.BE RESPONSIBLE FOR SAFETY AND PROTECTION IN AND AROUND THE JOB SITE AND/OR
ADJACENT PROPERTIES.
F.REPORT PROGRESS OF WORK TO ARCHITECT AND STRUCTURAL ENGINEER.
G.COORDINATE AND VERIFY ROOF, FLOOR, AND WALL OPENINGS REQUIRED WITH
ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND/OR OTHER DRAWINGS PRIOR TO
CONSTRUCTION. REPORT OPENINGS REQUIRED WHICH ARE NOT SPECIFICALLY SHOWN ON
THE STRUCTURAL DRAWINGS TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR REVIEW.
h.COORDINATE ANY CONSTRUCTION SITUATION NOT COVERED BY THESE PLANS, GENERAL
NOTES, OR SPECIFICATIONS WITH THE ARCHITECT AND STRUCTURAL ENGINEER.
2.CONTRACT DOCUMENTS:
A.REFER TO THE SPECIFICATIONS FOR INFORMATION NOT COVERED BY THESE GENERAL NOTES
OR THE DRAWINGS.
B.DETAILS, SECTIONS AND NOTES SHOWN ON THE STRUCTURAL DRAWINGS ARE INTENDED TO
BE TYPICAL AND SHALL APPLY TO ALL SIMILAR SITUATIONS ELSEWHERE, UNLESS NOTED OR
SHOWN OTHERWISE.
C.THE CONTRACT DOCUMENTS SHALL TAKE PRECEDENCE OVER SHOP DRAWINGS UNLESS
SPECIFICALLY NOTED OTHERWISE.
D.INFORMATION ON DRAWINGS INDICATING EXISTING CONDITIONS IS BASED ON BEST PRESENT
KNOWLEDGE, BUT MAY NOT BE ENTIRELY ACCURATE AND MUST BE FIELD VERIFIED.
3.BUILDING CODE COMPLIANCE:
A.INSPECTION, TESTING, CONSTRUCTION, WORKMANSHIP AND MATERIALS SHALL CONFORM TO
THE REQUIREMENTS OF THE GOVERNING BUILDING CODE AND STANDARDS. ASTM, IBC, AND
OTHER DESIGNATIONS SHALL BE AS AMENDED TO LATEST DATE UNLESS NOTED OTHERWISE.
4.CONSTRUCTION SEQUENCE, SHORING, AND BRACING REQUIREMENTS:
A.THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE METHOD, MEANS, AND SEQUENCE OF
ALL STRUCTURAL ERECTION EXCEPT WHEN SPECIFICALLY NOTED OTHERWISE ON THE
DRAWINGS. THE CONTRACTOR SHALL PROVIDE TEMPORARY SHORING AND BRACING TO
PROVIDE ADEQUATE VERTICAL AND LATERAL SUPPORT DURING ERECTION. THIS SHORING AND
BRACING SHALL REMAIN IN PLACE UNTIL ALL PERMANENT MEMBERS ARE PLACED AND ALL
FINAL CONNECTIONS ARE COMPLETED, INCLUDING ALL ROOF AND FLOOR ATTACHMENTS.
B.SHORING AND SUPPORTING FORM WORK FOR SUSPENDED CONCRETE OR MASONRY
MATERIAL SHALL REMAIN IN PLACE AND SHALL NOT BE REMOVED UNTIL THE STRUCTURAL
MEMBERS HAVE ACQUIRED SUFFICIENT STRENGTH TO SAFELY SUPPORT THEIR OWN WEIGHT
AND ANY ADDITIONAL CONSTRUCTION, STORAGE, AND/OR OTHER LOADS TO WHICH THE MAY
BE SUBJECTED.
5.OMISSIONS AND/OR CONFLICTS:
A.OMISSIONS IN AND/OR CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE CONTRACT
DOCUMENTS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT AND
STRUCTURAL ENGINEER AND SHALL BE RESOLVED BEFORE PROCEEDING WITH ANY WORK
INVOLVED.
B.IN CASE OF CONFLICTS IN THE STRUCTURAL WORK, THE MOST STRINGENT REQUIREMENTS, AS
DIRECTED BY THE ARCHITECT AND STRUCTURAL ENGINEER, SHALL BE IMPLEMENTED AT NO
ADDITIONAL COST TO THE OWNER.
6.MISCELLANEOUS:
A.DURING AND AFTER CONSTRUCTION, THE CONTRACTOR AND/OR OWNER SHALL KEEP THE
LOADS ON THE STRUCTURE WITHIN THE LIMITS OF THE DESIGN.
B.OBSERVATION VISITS TO THE SITE BY REPRESENTATIVES OF THE ARCHITECT AND/OR
STRUCTURAL ENGINEER SHALL NOT BE CONSTRUED AS INSPECTION NOR APPROVAL OF
CONSTRUCTION.
C.ALL WORK SHALL BE DONE IN ACCORDANCE WITH OSHA REQUIREMENTS. ANY CONFLICTS
BETWEEN THESE DOCUMENTS AND OSHA REQUIREMENTS SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT AND STRUCTURAL ENGINEER BEFORE PROCEEDING WITH
WORK.
STRUCTURAL STEEL
1.CODES AND STANDARDS:
A.STRUCTURAL STEEL DESIGN, FABRICATION, AND ERECTION SHALL COMPLY WITH:
I.THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) "SPECIFICATION FOR
STRUCTURAL STEEL BUILDINGS (AISC 360-16)", WITH "COMMENTARY".
II.AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES (AISC 303-10)"
EXCLUDING SECTIONS 1.5.1,4.4,7.5.4, AND 7.13.3.
III.AMERICAN WELDING SOCIETY (AWS-D1.1) "STRUCTURAL WELDING CODE -STEEL",
EXCLUDING ITEMS CONFLICTING WITH AISC REQUIREMENTS.
2.MATERIALS:
A.STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992. OTHER
STRUCTURAL STEEL SHAPES, PLATES, ANGLES, ETC. SHALL CONFORM TO ASTM A36.
RUSSIAN STEEL IS NOT PERMITTED.
B.HOLLOW STRUCTURAL SECTIONS SHALL CONFORM TO ASTM A500, GRADE C, WITH A MINIMUM
YIELD STRENGTH Fy = 50 KSI.
C.HIGH STRENGTH BOLTS SHALL CONFORM TO ASTM A325. ANCHOR RODS SHALL HAVE
HEADED STUDS AND SHALL CONFORM TO ASTM F1554. ALL OTHER BOLTS SHALL CONFORM TO
ASTM A307 OR BETTER.
3.CONSTRUCTION:
A.FABRICATION SHALL BE DONE IN AN APPROVED FABRICATOR'S SHOP.
B.CAMBER IN BEAMS SHALL BE AS INDICATED ON PLANS.
C.PROVIDE A SHOP COAT OF PAINT ON ALL STEEL ITEMS, EXCEPT AT AREAS OF WELDING
AND/OR BOLTING.
D.USE HIGH STRENGTH (8000 PSI MINIMUM AT 28 DAY), NON-SHRINK, LIQUID EPOXY GROUT
BENEATH ALL STEEL BASE PLATES AND BEARING PLATES. MIX GROUT WITH SAND OR PEA
GRAVEL AS RECOMMENDED BY THE MANUFACTURER. PLACE GROUT AS SOON AS STEEL
MEMBER HAS BEEN PROPERLY POSITIONED AND ALIGNED.
4.BOLTED CONNECTIONS:
A.STEEL TO STEEL BOLTED CONNECTIONS SHALL BE MADE WITH ASTM A325 HIGH
STRENGTH BOLTS AND NUTS, UNLESS NOTED OTHERWISE. BOLTS SHALL CARRY THE
IDENTIFYING MARK OF THREE (3) RADIAL LINES.
B.ALL OTHER BOLTED CONNECTIONS SHALL BE MADE WITH BOLTS AND NUTS CONFORMING TO
ASTM A307 UNLESS NOTED OTHERWISE.
C.BOLTS SHALL BE 3/4" DIAMETER, TYPICAL, UNLESS NOTED OTHERWISE. STANDARD
SPACING SHALL BE 3" O.C. AND STANDARD EDGE DISTANCE SHALL BE 1.1/2", TYPICAL, UNLESS
NOTED OTHERWISE.
D.BOLT SHALL BE BEARING TYPE CONNECTIONS WITH THREADS EXCLUDED UNLESS NOTED
OTHERWISE.
E.BOLTED CONNECTIONS SHALL BE TIGHTENED SNUG TIGHT AND SHALL
HAVE WASHERS AS REQUIRED BY AISC UNLESS NOTED OTHERWISE.
F.ENLARGING OF HOLES SHALL BE ACCOMPLISHED BY MEANS OF REAMING. DO NOT USE A
TORCH ON ANY BOLT HOLES.
5.WELDED CONNECTIONS:
A.WELDING AND GAS CUTTING SHALL BE DONE PER AWS.
B.WELDERS SHALL BE CURRENTLY CERTIFIED ACCORDING TO AWS. ALL WELDING PROCEDURES
SHALL BE PRE-QUALIFIED. WELDERS SHALL FOLLOW WELDING PROCEDURES.
C.WELDED CONNECTIONS SHALL BE MADE USING LOW HYDROGEN MATCHING FILLER MATERIAL
ELECTRODES, UNLESS NOTED OTHERWISE.
D.WELDS SHALL HAVE THE SLAG REMOVED.
E.FULL PENETRATION WELDS, SHOP OR FIELD, SHALL HAVE BACKER BARS REMOVED, BE BACK
GOUGED, AND REWELDED PER AWS TO HAVE FULL PENETRATION WELD.
7.SUBMITTALS:
A.THE FOLLOWING ITEMS SHALL BE SUBMITTED TO THE ARCHITECT AND STRUCTURAL ENGINEER
FOR REVIEW PRIOR TO FABRICATION, ERECTION, INSTALLATION, OR OTHERWISE BEING
INCORPORATED INTO THE WORK.
STRUCTURAL STEEL SHOP DRAWINGS.
WELDING PROCEDURES AND CERTIFICATIONS.
B.A MINIMUM OF TWO WEEKS SHALL BE ALLOWED FOR THE REVIEW OF ALL SUBMITTALS BY THE
ARCHITECT AND STRUCTURAL ENGINEER.
C.REQUESTS FOR SUBSTITUTIONS SHALL BE SUBMITTED TO THE ARCHITECT AND STRUCTURAL
ENGINEER IN WRITING. REASON(S) FOR THE REQUEST AND COST DIFFERENTIALS SHALL BE
INCLUDED IN THE REQUESTS. SUBSTITUTIONS ARE NOT ALLOWED UNLESS APPROVED IN
WRITING BY THE ARCHITECT AND STRUCTURAL ENGINEER.
8.DEFERRED SUBMITTALS:
A.THE FOLLOWING ITEMS REQUIRING DEFERRED SUBMITTALS ARE LISTED BELOW. THESE ITEMS
SHALL BE DESIGNED AND FABRICATED BY THE MANUFACTURER ACCORDING TO THE
SPECIFICATIONS GIVEN IN THE CONTRACT DOCUMENTS.
NO DEFERRED SUBMITTALS
SOILS
1.SOILS REPORT BY: NA
2.SOILS REPORT NUMBER AND DATE:NA
3.SOIL BEARING PRESSURE:NA
QUALITY ASSURANCE PLAN FOR STRUCTURE
1.INSPECTION:
A.THE OWNER SHALL PROVIDE SPECIAL INSPECTION BY QUALIFIED INSPECTORS FOR THE
FOLLOWING TYPES OF CONSTRUCTION IN ACCORDANCE WITH IBC, SECTION 1704 AND 1707, THE
SPECIFICATIONS, AND THE ATTACHED TABLES INCLUDED IN THESE GENERAL NOTES.
BOLTING: ALL HIGH STRENGTH BOLTS AND BOLTS EMBEDDED IN CONCRETE AND/OR
EPOXY. SEE ATTACHED TABLE LABELED REQUIRED VERIFICATION AND INSPECTION OF
CONCRETE/STEEL CONSTRUCTION.
WELDING: ALL SHOP AND FIELD WELDS. INSPECTOR SHALL BE AWS-QC1 CERTIFIED. SEE
ATTACHED TABLE LABELED REQUIRED VERIFICATION AND INSPECTION OF STEEL
CONSTRUCTION.
2.TESTING:
A.THE OWNER SHALL PROVIDE TESTING BY QUALIFIED TESTING AGENCIES FOR THE FOLLOWING
TYPES OF CONSTRUCTION IN ACCORDANCE WITH IBC, SECTION 1708 AND THE SPECIFICATIONS.
BOLTING: PROPER INSTALLATION AND CORRECT TORQUE AND/OR TENSION.
WELDING:TYPE, SIZE, LENGTH, AND QUALITY OF ALL SHOP AND FIELD WELDS BY
APPROVED METHODS. ULTRASONICALLY TEST ALL COMPLETE PENETRATION WELDS.
3.STRUCTURAL OBSERVATIONS:
A.THE STRUCTURAL ENGINEER SHALL BE NOTIFIED TO PERFORM STRUCTURAL OBSERVATIONS
AT SIGNIFICANT STAGES OF CONSTRUCTION.:
B.THE STRUCTURAL ENGINEER SHALL PROVIDE A COPY OF THE OBSERVATION REPORT TO THE
ARCHITECT FOR FURTHER DISTRIBUTION.
4.THE CONTRACTOR SHALL:
A.SUBMIT A STATEMENT OF RESPONSIBILITY TO THE OWNER AND BUILDING OFFICIAL PRIOR TO
COMMENCING WORK ON STRUCTURE THAT INCLUDES AWARENESS OF THE QUALITY
ASSURANCE PLAN REQUIREMENTS, ACKNOWLEDGMENT THAT CONTROL WILL BE EXERCISED
TO OBTAIN CONFORMANCE TO CONSTRUCTION DOCUMENTS, PROCEDURES FOR EXERCISING
CONTROL, METHOD AND FREQUENCY OF REPORTING, AND IDENTIFICATION AND
QUALIFICATIONS OF PERSONNEL IN CHARGE OF CONTROL.
B.CORRECT ALL WORK FOUND TO BE DEFICIENT AT NO ADDITIONAL COST TO THE OWNER.
C.COORDINATE ALL THE REQUIRED INSPECTIONS, TESTING, AND/OR STRUCTURAL
OBSERVATIONS OF THE QUALITY ASSURANCE PLAN. DO NOT PROCEED WITH SUBSEQUENT
WORK UNTIL THE REQUIRED INSPECTIONS, TESTING, AND STRUCTURAL OBSERVATIONS HAVE
BEEN PROVIDED. NOTIFY THE ARCHITECT AND STRUCTURAL ENGINEER AT LEAST 48 HOURS
PRIOR TO ANY REQUIRED OBSERVATIONS.
D.PROVIDE COPIES OF THE DAILY INSPECTION REPORTS AND ALL TESTING RESULTS TO THE
ARCHITECT, STRUCTURAL ENGINEER, OWNER, AND BUILDING OFFICIAL.
POST-INSTALLED ANCHORS
1.EPOXY ANCHORS:
A.THE FOLLOWING EPOXY ADHESIVES SYSTEMS SHALL BE ALLOWED:
FOR CONCRETE:
SIMPSON SET-XP
HILTI HIT-RE 500-V3
HILTI HIT-RE 100
FOR SOLID GROUTED MASONRY:
SIMPSON SET
HILTI HIT HY 200
FOR UNGROUTED MASONRY:
SIMPSON ET
HILTI HY 270
B.ANCHOR RODS SHALL BE ASTM A-307, THREADED AND GALVANIZED, AND THE DIAMETER AS
INDICATED ON PLAN.
C.SCREEN TUBES SHALL BE USED AT UNGROUTED MASONRY UNITS.
D.ALL ANCHORS SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. AS A MINIMUM BOLT
HOLES SHALL BE WIRE BRUSHED AND CLEANED WITH COMPRESSED AIR.
E.INSTALLATION OF ADHESIVE ANCHORS THAT ARE TO BE UNDER SUSTAINED TENSION LOADING IN
HORIZONTAL TO VERTICALLY OVERHEAD ORIENTATION SHALL BE DONE BY A CERTIFIED ADHESIVE
ANCHOR INSTALLER (AAI) AS CERTIFIED THROUGH ACI AND IN ACCORDANCE WITH ACI 318-2014
(Section 17.8.2.2). PROOF OF CURENT CERTIFICATION SHALL BE SUBMITTED TO THE ENGINEER FOR
APPROVAL PRIOR TO COMMENCEMENT OF INSTALLATION.
F.PER ACI 318-2014 (Section 17.1.2) ADHESIVE ANCHORS SHALL BE INSTALLLED IN CONCRETE HAVING A
MINIMUM AGE OF 21 DAYS AT TIME OF ANCHOR INSTALLATION. FOR INSTALLATIONS SOONER THAN 21
DAYS CONSULT ADHESIVE MANUFACTURER.
G.IF TEMPERATURE OF BASE MATERIAL AT TIME OF ADHESIVE INSTALLATION IS AT 45 DEGREES
(FAHRENHEIT) OR LESS, AN “ACRYLIC” (COLD WEATHER) ADHESIVE IS REQUIRED –ie DEWALT AC200+,
HILTI HY200, SIMPSON AT-XP.
2.MECHANICAL ANCHORS
A.THE FOLLOWING MECHANICAL ANCHORS SHALL BE ALLOWED:
SIMPSON TITEN HD
HILTI KWIK HUS-EZ
B.ALL ANCHORS SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. AS A MINIMUM BOLT
HOLES SHALL BE WIRE BRUSHED AND CLEANED WITH COMPRESSED AIR.
3.SUBSTITUTES: CONTRACTOR SHALL SUBMIT A WRITTEN REQUEST FOR APPROVAL TO THE
ARCHITECT AND STRUCTURAL ENGINEER.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
SE-001
GENERAL
NOTES
BE23002
04/08/2023
Enter address here
ROMNEY
2023
REMODEL
Project Status
04/28/2023
A
1
B
C
D
E
F
GH
J
K
L
MN
P
2 3 4 5 6 7 8
L6X6X5/16 L6X6X5/16 L6X6X5/16 L6X6X5/16
L6X6X3/8HSS6X4X1/4A1
SE-501
A1
SE-501
A2
SE-501
A2
SE-501
L6X6X5/16
L6X6X5/16
A2
SE-501
A3
SE-501
A4
SE-501
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
SE-101
LEVEL 1
FRAMING
PLAN
BE23002
04/08/2023
Enter address here
ROMNEY
2023
REMODEL
Project Status
1/8" = 1'-0"SE-101
A1 Level 1
04/28/2023
A
1
B
C
D
E
F
GH
J
K
L
MN
P
2 3 4 5 6 7 8
PROVIDE L6X6X3/16 LINTEL FOR HOOD PENETRATIONS. BEAR 6" ON MASONRY EACH SIDE.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
SE-102
ROOF
FRAMING
PLAN
BE23002
04/08/2023
Enter address here
ROMNEY
2023
REMODEL
Project Status
1/8" = 1'-0"SE-102
A1 ROOF
04/28/2023
EXISTING WALL -EXTERIOR SIDE
AREA TO BE REMOVED
TITEN TURBO, TYPICAL COMPRESSION
FLANGE BRACING.
WINDOW FRAME ANGLE SEE PLAN.
MITER AT CORNERS AND WELD
TOGETHER.
TITEN TURBO ON BOTH LEGS OF
"COLUMN" ANGLES, SEE DETAILS A2-
A4.
0'
-
1
1
/
2
"
0' - 1 1/2"
0' - 4"
NEW OPENING
0'
-
1
1
/
2
"
0' - 2" END 0' - 8" TYP.¼"ØX1¾" TITEN TURBOB1
SE-501
ANGLE, SEE PLAN FOR SIZE, USE ON ALL 3
SIDES OF DOOR. 1/4"Ø TITEN TURBO MASONRY
SCREWS AT 8"O.C. EMBED 1.25". BOTH FACES
FOR VERTICAL MEMBERS
ELEVATION
B1
SE-501
MITER AT CORNERS AND BUTT WELD.
ANGLE, SEE PLAN FOR SIZE, USE ON ALL
3 SIDES OF DOOR. 1/4"Ø TITEN TURBO
MASONRY SCREWS AT 8"O.C. EMBED
1.25". BOTH FACES FOR VERTICAL
MEMBERS
ELEVATION
B1
SE-501
L8X4X1/2 BY 7.5" WITH (2)
5/8"ØX5.5" HILTI KWIK-EZ BOLTS
SPACED 5"O.C.
MITER AT CORNERS AND BUTT WELD.
ANGLE, SEE PLAN FOR SIZE, USE ON ALL
3 SIDES OF DOOR. 1/4"Ø TITEN TURBO
MASONRY SCREWS AT 8"O.C. EMBED
1.25". BOTH FACES FOR VERTICAL
MEMBERS
ELEVATION
B1
SE-501
1/4
EXISTING MASONRY. SHORE AS
REQUIRED.
MITER AT CORNERS AND BUTT WELD.
COLUMN, SEE PLAN WITH 1/2"X4.5"X7"
BASE PLATE WITH (2) 3/4" TITEN HD
BOLTS. SHIM AS REQUIRED TO LEVEL.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
SE-501
DETAILS
BE23002
04/08/2023
Enter address here
ROMNEY
2023
REMODEL
Project Status
1" = 1'-0"SE-501
B1
3/4" = 1'-0"SE-501
A1
3/4" = 1'-0"SE-501
A2
3/4" = 1'-0"SE-501
A3
3/4" = 1'-0"SE-501
A4
04/28/2023
GRILLE AND DIFFUSER SCHEDULE
SYMBOL DESCRIPTION MANUFACTURER MODEL REMARKS
S-1 CEILING DIFFUSER - LAY-IN KRUEGER 1400 -
S-2 CEILING DIFFUSER - SURFACE KRUEGER SH -
R-1 CEILING RETURN - LAY-IN KRUEGER 6490 -
R-2 CEILING RETURN - SURFACE KRUEGER 6490 -
E-1 SURFACE MOUNT CEILING EXHAUST KRUEGER EGC5 -
E-2 LAY-IN CEILING EXHAUST KRUEGER EGC5 -
SEE SPECIFICATION SECTION 23
VARIABLE VOLUME AIR BOXES WITH REHEAT (VAVR) SELECTION CHART
SYSTEM AIR PRESSURE COIL
SYMBOL TITUS CFM TITUS OPERATING DROP W/ 1 ROW DIMENSION REMARKS
SIZE RANGE MODEL STATIC IN. W.C. COIL IN. W.C. INCH.
VAVR_ 6 0-349 DESV 0.75 0.30 12"x8"
VAVR_ 8 350-599 DESV 0.75 0.30 12"x10"
VAVR_ 9 600-749 DESV 0.75 0.30 14"x12"-1/2"
VAVR_ 10 750-999 DESV 0.75 0.30 14"x12"-1/2"
VAVR_ 12 1000-1349 DESV 0.75 0.30 16"x15"
VAVR_ 14 1350-1899 DESV 0.75 0.30 20"x17"-1/2"
VAVR_ 16 1900-2399 DESV 0.75 0.30 24"x18"
VAVR_ 24x16 2400-4800 DESV 0.75 0.30 38"x18"
CABINET HEATER
SYMBOL
NOMINAL AIR
FLOW CFM
TYPE
HEATING COILS
TRANE MODEL REMARKS# OF
ROWS
BTUH
ENT. WTR
TEMP F°
LVG. WTR
TEMP F°
ENT. AIR
TEMP F°
LVG. AIR
TEMP F°
GPM
MAX
PRESS
DROP
FT.
VOLTS HERTZ PHASE
CH-1 470 CEILING RESSED 4
50,000 180 160 30 100 5.2 3.7 115 60 1 CW00458 1, 2
CH-2 470 CEILING RESSED 4
50,000 180 160 30 100 5.2 3.7 115 60 1 CW00458 1, 2
CH-3 470 CEILING RESSED 4
50,000 180 160 30 100 5.2
3.7 115 60 1 CW00458 1, 2
1. PROVIDE W/ FACTORY DISCONNECT
2. 35% PROPYLENE GLYCOL
SEE SPECIFICATION 23
VARIABLE VOLUME WITH REHEAT (VAVR)
BALANCE MINIMUM MAX.HEATING COIL 30% PROPYLENE GLYCOL MIN.
SYMBOL AIRFLOW AIRFLOW AIRFLOW HTG. CAPACITY
GPM
EWT MIN MAX. PRESSURE TITUS INLET REMARKS
CLG. CFM CFM HTG. CFM BTU/HR DEG F. ROWS DROP, FT. W.C. SIZE SIZE IN.
VAVR-0-C 1800 320 765 27,571 1.9 180 2 0.6 14 14
VAVR-50 1370 320 320 10,166 0.7 180 1 0.0 14 14
VAVR-51 1300 235 235 4,468 0.5 180 1 0.1 12 12
VAVR-52 1170 235 300 10,833 0.8 180 1 0.3 12 12
VAVR-52A 565 105 150 5,433 0.5 180 1 0.3 8 8
VAVR-55 130 60 100 1,831 0.5 180 1 0.3 6 6
VAVR-57 130 60 100 1,831 0.5 180 1 0.3 6 6
VAVR-59 2295 420 420 7,782 0.5 180 1 0.1 16 16
VAVR-59A 740 135 135 2,511 0.5 180 1 0.1 9 9
VAVR-59D 430 105 105 1,965 0.5 180 1 0.3 8 8
VAVR-64 950 165 680 24,461 1.7 180 2 0.6 10 10
ROOM SERVICE REQUIREMENTS
ROOM MAX REQUIRED SUPPLY AIR GENERAL ROOM EXHAUST AIR FUME HOOD EXHAUST SNORKEL EXHAUST AIR CABINET EXHAUST MISC.
ROOM ROOM NAME SQUARE RETURN COOLING ROOM AIR VALVE MAX. DESIGN MIN. DESIGN HEATING MAX. PRESS. TITUS VAV BOX SIZE PHOENIX VALVE HEATING COIL AIR VALVE MAX. MIN. MAX. PRESS. PHOENIX AIR VALVE MAX. MIN. MAX. PRESS. PHOENIX SNORKEL AIR VALVE MAX. MIN. MAX. PRESS. PHOENIX QTY. TOTAL EXHAUST ROOM RECYCLE REMARKS
NO.FOOTAGE AIR CFM CFM OFFSET SYMBOL ('S)CFM CFM CFM DROP (IN.)COLD HOT BOX SIZE COIL SIZE BTU/HR GPM SYMBOL ('S)CFM CFM DROP VALVE SIZE SYMBOL ('S)CFM CFM DROP VALVE SIZE SIZE SYMBOL ('S)CFM CFM DROP VALVE SIZE CFM PRESSURE AIR
282 GENERAL CHEM. LAB 1777 0 2600 290 (E)-MAV-282B 2215 835 1350 0.75 - - 2x12 42"x16" 61,134 6.1 EXV-282A 930 0 0.75 12 (E)-EXV-282B 785 325 0.75 10 - - - - - - 1 10 - NEG. NO
(E)-MAV-282B 2215 835 1350 0.75 2x12 42"x16" 61,134 6.1 (E)-EXV-282B 785 325 0.75 10
EXV-282D 0.75
EXV-282E 0.75 8
(E)-EXV-282B 785 325 0.75 10 FOR RE-BALANCE ONLY
(E)-EXV-282B 785 325 0.75 10
(E)-EXV-282B 785 325 0.75 10
(E)-EXV-282B 785 325 0.75 10
RM. TOTAL 4430 1670 2700 4710 1950 10
272 BIO-CHEMISTRY 1752 0 1650 300 MAV-272 1665 360 900 0.75 - -2x10 45,954 4.6 EXV-272 1290 0 0.75 12 (E)-EXV-272A 785 325 0.75 10 - - - - - - 1 10 NEG. NO
(E)-EXV-272B 785 325 0.75 10 USE THIS SCHEUDLE FOR
FOR BASE BID ONLY
RM. TOTAL 1665 360 900 1570 650 10
272 BIO-CHEMISTRY 1752 0 1650 300 MAV-272 1665 680 900 0.75 - -2x10 45,954 4.6 EXV-272 1290 320 0.75 12 (E)-EXV-272A 785 325 0.75 10 6" DIA. EXV-272A 160 0 - - 1 10 NEG. NO USE THIS SCHEDULE FOR
(E)-EXV-272B 785 325 0.75 10 6" DIA. EXV-272B 160 BASE BID WITH
ADD ALTERNATE #2
RM. TOTAL 1665 680 900 1570 650 320 10
PROVIDE THE SINGLE PHOENIX VALVES WITH SQUARE FLANGED OUTLETS AND UNFLANGED INLETS.
COILS BASED ON 190 DEG. ENTERING WATER TEMPERATURE WITH 40% GLYCOL. AND 55 DEG. ENTERING AIR TEMPERATURE.
INLINE EXHAUST FAN
SYMBOL
MAXIMUM AIRFLOW
CFM
TOTAL STATIC
PRESSURE IN. W.C.BHP (W)FAN RPM
ELECTRICAL
DRIVE TYPE COOK MODEL
MAX WEIGHT
(LBS)
MAXIMUM SOUND LEVELS dB (OCTAVE BAND)
REMARKS
VOLTS PHASE HERTZ MOTOR HP 1 2 3 4 5 6 7 8 LWA dBA
IEF-1 500 0.8 127 1765 115 1 60 1/3 DIRECT GNVF-700 40 67 68 67 62 58 55 52 49 65 53 1, 2, 3
NOTES:
1. WITH LOW LEAKAGE DAMPER, RUSKIN CD-50 OR BETTER, MAX LEAKAGE 3 CFM/FT2 AT 1" W.C. WIRE DAMPER TO OPEN WHEN FAN RUNS.
2. WITH EC MOTOR
SYMBOL LEGEND
CIRCUIT BALANCE VALVES
(E)
CHWS
CHWR
HWR
HWS
FSRD
FD
D
T
S
S.F.D.
A.D.
H.D.
RISE
24"x12"
24"x18"
SEE SPECIFICATION SECTION 230523
16 - 25
10 - 15
6 - 9
1.5 - 2.5
3 - 5
1.5 - 2.5
GPM
RANGE
.5 - 1.4
26 - 45
CONNECTION
5
5
5
5
5
5
5
5
PRESSURE
DROP
AVERAGE
IN FT
1/2ASO50L
AS100
AS150
AS125
AS200
ASO75L
ASO5OH
ASO75H
1
1-1/4
1-1/2
2
3/4
3/4
1/2
FLOWSET
SIZE SIZE (IN)
-
-
-
-
-
-
-
REMARKS
-
HOT WATER SUPPLY
COLD WATER
CHILLED WATER RETURN
CHILLED WATER SUPPLY
HOT WATER RETURN
SOIL OR WASTE
DOMESTIC HOT WATER
EXISTING
DOMESTIC HOT WATER RECIRCULATING
VENT
CONCENTRIC REDUCER
THERMOMETER
GAUGE WITH GAUGE COCK
GAUGE COCK
ECCENTRIC REDUCER
THERMOMETER OR GAUGE WELL
SAFETY OR RELIEF VALVE
SOLENOID VALVE
GLOBE VALVE
PIPE GUIDE
PIPE ANCHOR
BLIND FLANGE
PRESSURE/TEMPERATURE TEST PLUG (PETE'S PLUG)
FLOW CONTROLLER OR BALANCE VALVE
FLOOR DRAIN, FLOOR SINK OR ROOF DRAIN
PRESSURE REDUCING VALVE - (PRV)
STEAM TRAP
DIRT LEG
DRAIN
STRAINER
CHECK VALVE
BUTTERFLY VALVE
PLUG VALVE
CAP
EXHAUST GRILLE
OPPOSED BLADE DAMPER
PARALLEL BLADE DAMPER
BRANCH DUCT TAKE-OFF
SPIN-IN FITTING
THERMOSTAT
TEMPERATURE SENSOR
DROP IN PIPE
VALVE IN RISE
BALL VALVE
GATE VALVE
2 WAY CONTROL VALVE
3 WAY CONTROL VALVE
CONTROL VALVE (PLAN VIEW)
RISE IN PIPE
UNION
NEW CONNECTION
FLAT OVAL (CROSS SECTION)
ROUND DUCT (CROSS SECTION)
SUPPLY DUCT (CROSS SECTION)
HAND DAMPER
SUPPLY AIR DIRECTION
TURNING VANES IN DUCT
ACCESS DOOR FOR FIRE DAMPER
ACCOUSTICAL LINING IN DUCT
DROP OR RISE IN SUPPLY DUCT
SUPPLY DIFFUSER
COMBINATION SMOKE/FIRE DAMPER
RISE OR DROP IN ROUND OVAL DUCT
INSIDE CLEAR DIMENSION IN INCHES
DUCT SIZE, INSIDE CLEAR DIMENSION IN INCHES
RETURN AIR OR EXHAUST DUCT (CROSS SECTION)
RETURN AIR OR EXHAUST DIRECTION
RETURN AIR GRILLE
DUCT RISE
DESCRIPTIONSYMBOL
SEE SPECIFICATION SECTION 233616
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
M-001
Mechanical
Schedules
and Symbol
Legend
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DM
(E)10"Ø
(E)10"Ø
(E)16"x12"(E)14"x10"
(E)8"Ø
(E)8"Ø
(E)12"Ø
(E)14"Ø
(E)24"Ø
(E
)
2
1
"
Ø
(E)10"Ø
(E)14"Ø
(E)8"Ø
(E)16"x12"
(E
)
1
9
"
Ø
(E)19"Ø
(E)10"Ø
(E)12"x12"
(E)10"Ø
(E
)
1
2
"
Ø
(E
)
1
2
"
x
1
2
"
(E)10"Ø
(E)19"Ø
(E)10"Ø
(E)10"Ø
(E)12"Ø
(E)12"Ø
(E)16"x12"
(E)16"x12"
(E)14"x14"
(E)12"Ø
(E)20"x10"
(E)8"x6"
(E)14"x14"
(E)20"x10"
(E)12"x12"
(E)8"x10"
(E)12"x12"
(E)14"x12"
(E)16"x12"
(E)14"Ø(E)16"x12"
(E)20"x10"(E)14"x12"
(E)10"x6"
(E)30"x30"
(E) EXHAUST RISER
(E)10"x12"
(E)8"Ø(E)8"Ø(E)8"Ø(E)8"Ø(E)8"Ø(E)8"Ø
(E)8"x6"(E)8"x6"(E)8"x6"(E)8"x6"(E)8"x6"
(E)8"Ø
(E)8"Ø(E)8"Ø
(E)8"x6"
(E)8"x6"(E)8"Ø
(E)12"Ø
(E)8"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"x12"
(E)10"Ø
(E)10"Ø
(E)8"Ø
(E)20"x10"
(E)10"Ø
(E)10"Ø
(E) EXHAUST RISER
(E)10"x6"
(E)10"x10"(E)10"x6"
(E)14"x10" (E)14"x8"
(E)8"x4" (E)8"x4"
(E) CABINET HEATER
(E) CABINET HEATER
T
T T
T
T
T
T
T
T
T
T
T
T
T
T
T
AAAA
1111
BBBB
CCCC
DDDD
EEEE
FFFF
GGGG
HHHH
JJJJ
KKKK
LLLL
MMMM
NNNN
PPPP
2222 3333 4444 5555 6666 7777 8888
1111
22223333
4444
5555
6666
6666 5555
6666
5555
5555
5555
5555 5555 5555
5555
5555
5555
5555
5555
1111
1111
1111
1111
1111
1111
1111
1111
1111
1111
2222
3333
333333333333
3333
3333 3333
33333333
3333
3333
3333
3333
3333
3333
3333
3333
3333
3333
3333 3333
2222
3333 3333
33333333
3333 3333
2222
3333
3333
2222
3333
3333 3333 3333
3333
3333
33333333333333333333
2222
22222222
3333
3333
3333
7777
88888888
dbkbo^i=klqbp
A.A.A.A.FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING
REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR
PATCHWORK. PATCHWORK. PATCHWORK. PATCHWORK.
INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK
INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL
OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES,
HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS
NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF
THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING
UNITS. UNITS. UNITS. UNITS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
EXISTING PIPING INSULATION MAY CONTAIN EXISTING PIPING INSULATION MAY CONTAIN EXISTING PIPING INSULATION MAY CONTAIN EXISTING PIPING INSULATION MAY CONTAIN
ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE
REMOVAL AND HANDLING OF ANY SUSPECT REMOVAL AND HANDLING OF ANY SUSPECT REMOVAL AND HANDLING OF ANY SUSPECT REMOVAL AND HANDLING OF ANY SUSPECT
MATERIALS. IF DURING THE COARSE OF THE MATERIALS. IF DURING THE COARSE OF THE MATERIALS. IF DURING THE COARSE OF THE MATERIALS. IF DURING THE COARSE OF THE
WORK ANY SUSPECT MATERIALS ARE WORK ANY SUSPECT MATERIALS ARE WORK ANY SUSPECT MATERIALS ARE WORK ANY SUSPECT MATERIALS ARE
ENCOUNTERED BY THE CONTRACTOR, THE ENCOUNTERED BY THE CONTRACTOR, THE ENCOUNTERED BY THE CONTRACTOR, THE ENCOUNTERED BY THE CONTRACTOR, THE
CONTRACTOR IS TO IMMEDIATELY STOP WORK IN CONTRACTOR IS TO IMMEDIATELY STOP WORK IN CONTRACTOR IS TO IMMEDIATELY STOP WORK IN CONTRACTOR IS TO IMMEDIATELY STOP WORK IN
THE AREA AND NOTIFY THE OWNER.THE AREA AND NOTIFY THE OWNER.THE AREA AND NOTIFY THE OWNER.THE AREA AND NOTIFY THE OWNER.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
M.M.M.M.
N.N.N.N.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
MD100
Level 00
Mechanical
Demolition
Plan
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DRAWING NOTES
NOTE
# DESCRIPTION
1111 REMOVE EXISTING VAV BOX AND BRANCHREMOVE EXISTING VAV BOX AND BRANCHREMOVE EXISTING VAV BOX AND BRANCHREMOVE EXISTING VAV BOX AND BRANCH
DUCTWORK COMPLETE.DUCTWORK COMPLETE.DUCTWORK COMPLETE.DUCTWORK COMPLETE.
2222 REMOVE EXISTING EXHAUST DUCTWORK ASREMOVE EXISTING EXHAUST DUCTWORK ASREMOVE EXISTING EXHAUST DUCTWORK ASREMOVE EXISTING EXHAUST DUCTWORK AS
SHOWN.SHOWN.SHOWN.SHOWN.
3333 REMOVE EXISTING GRILLES AND DIFFUSERS ASREMOVE EXISTING GRILLES AND DIFFUSERS ASREMOVE EXISTING GRILLES AND DIFFUSERS ASREMOVE EXISTING GRILLES AND DIFFUSERS AS
SHOWN.SHOWN.SHOWN.SHOWN.
4444 REMOVE SECTION OF EXISTING MAIN DUCTWORKREMOVE SECTION OF EXISTING MAIN DUCTWORKREMOVE SECTION OF EXISTING MAIN DUCTWORKREMOVE SECTION OF EXISTING MAIN DUCTWORK
AS SHOWN.AS SHOWN.AS SHOWN.AS SHOWN.
5555 REMOVE EXISTING TEMPERATURE SENSORREMOVE EXISTING TEMPERATURE SENSORREMOVE EXISTING TEMPERATURE SENSORREMOVE EXISTING TEMPERATURE SENSOR
COMPLETE.COMPLETE.COMPLETE.COMPLETE.
6666 REMOVE EXISTING CABINET HEATERS COMPLETE.REMOVE EXISTING CABINET HEATERS COMPLETE.REMOVE EXISTING CABINET HEATERS COMPLETE.REMOVE EXISTING CABINET HEATERS COMPLETE.
7777 REMOVE EXISTING DUCT THROUGH WALL ANDREMOVE EXISTING DUCT THROUGH WALL ANDREMOVE EXISTING DUCT THROUGH WALL ANDREMOVE EXISTING DUCT THROUGH WALL AND
ABANDON. WALL OPENING SHALL BE INSULATEDABANDON. WALL OPENING SHALL BE INSULATEDABANDON. WALL OPENING SHALL BE INSULATEDABANDON. WALL OPENING SHALL BE INSULATED
AND SEALED.AND SEALED.AND SEALED.AND SEALED.
8888 EXISTING CABINET HEATERS TO REMAIN.EXISTING CABINET HEATERS TO REMAIN.EXISTING CABINET HEATERS TO REMAIN.EXISTING CABINET HEATERS TO REMAIN.
SCALE:SCALE:SCALE:SCALE:MD100MD100MD100MD100 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
LEVEL 00 MECHANICAL DEMOLITION PLAN1111
0000555510101010 10101010 20202020
S SS S
T
T
S
S
S
S S
S S S S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S S S S
S
S
S
S
S
S S
S
S S
S
S
S
S
S
S
S
(E
)
1
6
"
X
1
0
"
(E
)
1
4
"
X
1
0
"
(E)10"Ø
(E)10"Ø
(E)16"x14"
(E)12"Ø
(E)14"Ø
(E)12"Ø
(E)12"Ø
(E
)
1
8
"
x
1
4
"
(E)14"Ø
(E)8"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)14"x14"
(E)10"x12"
(E)10"x4"
(E
)
2
2
"
x
2
2
"
(E)10"x8"
(E)10"x10"
(E
)
3
3
"
Ø
(E)33"Ø
(E
)
3
2
"
Ø
(E
)
1
2
"
Ø
(E
)
1
2
"
Ø
(E)18"x14"
(E)14"Ø (E)14"Ø
(E
)
1
2
"
x
1
2
"
(E)14"x10"
(E)27"Ø (E)24"Ø (E)21"Ø (E)20"Ø
(E)18"Ø (E)16"Ø
(E)18"Ø(E)15"Ø(E)14"Ø
(E)12"x10"
(E)10"x12"
(E
)
1
2
"
Ø
(E
)
1
2
"
Ø
(E
)
1
2
"
Ø
(E
)
1
8
"
x
1
4
"
(E
)
1
8
"
x
1
4
"
(E)14"x12"(E)12"x12"
(E)F.D
(E)60"x24" RA
(E)F.D
(E)F.D
(E)12"Ø
(E)12"Ø
(E)12"Ø
(E)10"Ø (E)10"Ø
(E)10"Ø (E)10"Ø (E)10"Ø (E)10"Ø
(E)10"Ø (E)10"Ø
(E)10"x8"
(E)10"x12"
(E)12"Ø (E)12"Ø (E)12"Ø (E)12"Ø
(E)12"Ø
(E)10"Ø (E)10"Ø
(E)10"Ø (E)10"Ø
(E)10"Ø (E)10"Ø
(E)10"Ø (E)10"Ø
(E
)
1
6
"
X
1
0
"
(E
)
1
6
"
X
1
0
"
(E
)
1
8
"
x
1
4
"
(E
)
1
8
"
x
1
4
"
(E)12"Ø
(E)10"Ø (E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)12"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)14"x12"
(E)14"x12"
(E)10"Ø
(E)10"Ø (E)10"Ø (E)10"Ø (E)10"Ø
(E)10"Ø
(E
)
2
8
"
x
1
6
"
F
.
O
.
C
O
L
D
(E)18"x14" F.O. HOT
(E)16"∅ COLD
(E
)
1
6
"
x
1
0
"
E
X
H
.
(E)14"x8" EXH.
(E)16"x5"
(E)16"x18"
EXH. UP
(E)ALARM
(E)T.I.
(E)10"x10"+1"AL
(E)26"x14" EXH.
(E
)
2
6
"
x
1
6
"
E
X
H
.
(E)18"x18"
(E)38"x22" F.O. COLD(E)20"x16"(E)16"∅ COLD
(E
)
8
"
∅
(E)26"x14" EXH.
(E)10"x12"+1"AL
(E
)
1
0
"
∅
(E)10"x10"
+1"AL
(E
)
6
"
∅
(E
)
8
"
∅
(E)22"x14"+1"AL
(E)16"x10"
(E)18"x12"
(E)26"x14" EXH.
10"x8"
(E)18"x14"+1"AL
(E
)
1
2
"
∅
(E)14"x10"+1"AL(E)16"x12"+1"AL
(E)16"x12"+1"AL (E)14"x10"+1"AL
(E
)
2
6
"
x
1
4
"
E
X
H
.
(E)8"x10"+1"AL(E)10"x12"+1"AL
(E)20"x12"
(E
)
1
2
"
∅
(E)12"x12"
+1"AL (E)8"x8"+1"AL
(E)10"x8"+1"AL
(E
)
1
0
"
∅
(E)12"x8"
(E
)
1
0
"
x
8
"
(E)8"x8"+1"AL
(E
)
8
"
∅
(E
)
1
0
"
x
6
"
(E)14"x10"
(E)22"x14" F.O. COLD
(E)18"x14"
(E)18"x14" F.O. HOT
(E)30"∅ COLD
(E
)
3
8
"
x
1
6
"
F
.
O
.
C
O
L
D
(E)38"x16" F.O. COLD
(E)22"x14"+1"AL
(E)30"x16"+1"AL
(E)22"∅ HOT
(E
)
4
0
"
x
1
8
"
E
X
H
.
(E
)
3
0
"
x
1
6
"
(E)30"x16"+1"AL
(E)36"x12"
(E)36"x12"
(E)30"x16"+1"AL
22
"
x
1
6
"
(E)22"x16" F.O. HOT
(E)14"x10"
+1"AL
(E)18"x14" F.O.
(E
)
8
"
∅
(E
)
8
"
∅
(E)16"x14"
(E)14"x12" F.O.
(E
)
1
4
"
∅
(E
)
6
"
∅
(E)30"x16"+1"AL
(E)30"x16"+1"AL
(E
)
2
6
"
x
1
6
"
F
.
O
.
C
O
L
D
(E)36"x18" F.O COLD
(E)10"x8"
(E
)
6
"
∅
(E)22"x14" F.O.HOT
HRRHRS
HWR
HWS
(E)28"∅
COLD
HRS
HWS
HRR
HWR
HRRHRS
HWS
HWR
HR
R
HW
R
HR
S
HW
S
HW
R
HW
S
HR
R
HR
S
(E)3/4"(E)2"
(E)24"x14"
COLD
HR
R
HR
S
HW
R
HW
S
(E)1-1/4"
(E)10"x8"
+1"AL
(E)8"x8"
+1"AL
(E
)
8
"
∅
(E)3"
(E)24"∅
(E
)
1
2
"
∅
(E)10"x10"+1"AL
(E)8"x8"
+1"AL
(E)8"x8"
+1"AL
(E)10"x8"
+1"AL
(E
)
8
"
∅
(E
)
8
"
∅
(E
)
6
"
∅
(E
)
1
2
"
∅
(E)20"x10"
(E)26"x12"
(E)26"x12"
(E)26"x12"
(E)26"x14"
(E)42"x12"
(E)26"x12"
(E)20"∅
(E)10"Ø
(E)12"Ø (E)12"Ø (E)12"Ø
(E)12"Ø (E)12"Ø
(E)12"Ø
(E)12"Ø
(E)12"Ø
(E)12"Ø
(E)12"Ø
(E)12"Ø
(E)12"Ø
(E)12"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø (E)8"Ø (E)8"Ø (E)8"Ø (E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø (E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø (E)8"Ø
(E)8"Ø (E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø (E)8"Ø
(E)8"Ø(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø (E)8"Ø
(E)8"Ø(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)8"Ø
(E)6"Ø
(E)6"Ø
(E)6"Ø
(E)6"Ø (E)6"Ø (E)6"Ø
(E
)
8
"
∅
(E)6"Ø
(E)6"Ø
(E)6"Ø
(E)6"Ø
(E)6"Ø
(E)8"Ø
(E
)
8
"
∅
(E)8"Ø
(E)6"Ø
(E)12"Ø
(E)8"Ø
(E)8"Ø
(E)14"Ø
(E)6"Ø(E)6"Ø
(E
)
8
"
∅
(E)1-1/4"
(E)1-1/4"
(E)12"Ø
(E)12"Ø
(E)1-1/2"
(E)8"x8"
+1"AL
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø (E)10"Ø (E)10"Ø (E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"Ø
(E)10"x10"
+1"AL
(E)10"x10"
+1"AL
(E)10"x10"
+1"AL
(E)10"x10"
+1"AL
(E)12"x12"
+1"AL
(E)14"Ø
(E)10"Ø
(E)14"Ø
(E)14"Ø
(E)16"∅ COLD
(E)8"Ø
(E)1-1/4"
(E)1-1/4"
(E)10"Ø
(E)8"x8"
+1"AL
(E)2"
(E)3"
(E)1-1/2"
(E)12"Ø (E)12"Ø
(E)12"Ø
(E)12"Ø(E)12"Ø
(E)12"Ø
(E)12"Ø
(E)12"Ø
(E)12"Ø (E)12"Ø
(E)12"Ø(E)12"Ø
(E)8"Ø
(E)6"Ø
(E)10"x10"
+1"AL
(E)12"Ø
(E)3/4"
(E)3/4"
(E)2"
(E)2"
(E)3"
(E)10"Ø (E)8"x10"+1"AL
(E)28"∅
COLD
(E)3"
(E)12"Ø
(E)12"Ø
(E)3/4"
(E)4"
(E)16"x10"
(E)10"x12"+1"AL
(E)14"Ø HOT
(E)10"Ø
(E)1"
(E)1"
(E)12"Ø
(E)1-1/4"
(E)1-1/2"
(E)14"Ø
(E)3/4"
AAAA
1111
BBBB
CCCC
DDDD
EEEE
FFFF
GGGG
HHHH
JJJJ
KKKK
LLLL
MMMM
NNNN
PPPP
2222 3333 4444 5555 6666 7777 8888
1111
2222
2222
1111
1111
1111
1111
1111 1111
1111
1111
1111
1111
1111
3333
4444
4444
dbkbo^i=klqbp
A.A.A.A. FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING
REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR
PATCHWORK. PATCHWORK. PATCHWORK. PATCHWORK.
INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK
INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL
OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES,
HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS
NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF
THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING
UNITS. UNITS. UNITS. UNITS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
EXISTING PIPING INSULATION MAY CONTAIN EXISTING PIPING INSULATION MAY CONTAIN EXISTING PIPING INSULATION MAY CONTAIN EXISTING PIPING INSULATION MAY CONTAIN
ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE
REMOVAL AND HANDLING OF ANY SUSPECT REMOVAL AND HANDLING OF ANY SUSPECT REMOVAL AND HANDLING OF ANY SUSPECT REMOVAL AND HANDLING OF ANY SUSPECT
MATERIALS. IF DURING THE COARSE OF THE MATERIALS. IF DURING THE COARSE OF THE MATERIALS. IF DURING THE COARSE OF THE MATERIALS. IF DURING THE COARSE OF THE
WORK ANY SUSPECT MATERIALS ARE WORK ANY SUSPECT MATERIALS ARE WORK ANY SUSPECT MATERIALS ARE WORK ANY SUSPECT MATERIALS ARE
ENCOUNTERED BY THE CONTRACTOR, THE ENCOUNTERED BY THE CONTRACTOR, THE ENCOUNTERED BY THE CONTRACTOR, THE ENCOUNTERED BY THE CONTRACTOR, THE
CONTRACTOR IS TO IMMEDIATELY STOP WORK IN CONTRACTOR IS TO IMMEDIATELY STOP WORK IN CONTRACTOR IS TO IMMEDIATELY STOP WORK IN CONTRACTOR IS TO IMMEDIATELY STOP WORK IN
THE AREA AND NOTIFY THE OWNER.THE AREA AND NOTIFY THE OWNER.THE AREA AND NOTIFY THE OWNER.THE AREA AND NOTIFY THE OWNER.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
M.M.M.M.
N.N.N.N.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
MD102
Level 02
Mechanical
Demolition
Plan
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DRAWING NOTES
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 REMOVE DIFFUSERS AND GRILLES WITH BRANCHREMOVE DIFFUSERS AND GRILLES WITH BRANCHREMOVE DIFFUSERS AND GRILLES WITH BRANCHREMOVE DIFFUSERS AND GRILLES WITH BRANCH
DUCTWORK.DUCTWORK.DUCTWORK.DUCTWORK.
2222 REMOVE EXISTING VAVR BOX W/ CONTROLSREMOVE EXISTING VAVR BOX W/ CONTROLSREMOVE EXISTING VAVR BOX W/ CONTROLSREMOVE EXISTING VAVR BOX W/ CONTROLS
COMPLETE.COMPLETE.COMPLETE.COMPLETE.
3333 REMOVE EXISTING TEMPERATURE SENSORREMOVE EXISTING TEMPERATURE SENSORREMOVE EXISTING TEMPERATURE SENSORREMOVE EXISTING TEMPERATURE SENSOR
COMPLETE.COMPLETE.COMPLETE.COMPLETE.
4444 REFERENCE PLUMBING DRAWINGS FOR WORK INREFERENCE PLUMBING DRAWINGS FOR WORK INREFERENCE PLUMBING DRAWINGS FOR WORK INREFERENCE PLUMBING DRAWINGS FOR WORK IN
THIS AREA.THIS AREA.THIS AREA.THIS AREA.
SCALE:SCALE:SCALE:SCALE:MD102MD102MD102MD102 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
LEVEL 02 MECHANICAL DEMOLITION PLAN1111
CAP
CAP
(E) 3" HWR
(E) 3" HWS
(E) 1-1/2"
HWR/S
(E)2" HWR/S
(E) 3/4" HWS(E) 3/4" HWS
(E) 3/4" HWR/S
(E) CABINET HEATER
(E) CABINET HEATER (E) 1-1/2" HWR/S (E) 1-1/4" HWR/S
(E) 1-1/4" HWR/S
(E) 3/4" HWR/S
(E) 3" HWR/S (E) CABINET HEATER
(E) 3/4"
HWR/S
(E) 1"
HWR/S
dbkbo^i=klqbp
A.A.A.A. FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING
REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR
PATCHWORK. PATCHWORK. PATCHWORK. PATCHWORK.
INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK
INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL
OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES,
HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS
NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF
THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING
UNITS. UNITS. UNITS. UNITS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
EXISTING PIPING INSULATION MAY CONTAIN EXISTING PIPING INSULATION MAY CONTAIN EXISTING PIPING INSULATION MAY CONTAIN EXISTING PIPING INSULATION MAY CONTAIN
ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE
REMOVAL AND HANDLING OF ANY SUSPECT REMOVAL AND HANDLING OF ANY SUSPECT REMOVAL AND HANDLING OF ANY SUSPECT REMOVAL AND HANDLING OF ANY SUSPECT
MATERIALS. IF DURING THE COARSE OF THE MATERIALS. IF DURING THE COARSE OF THE MATERIALS. IF DURING THE COARSE OF THE MATERIALS. IF DURING THE COARSE OF THE
WORK ANY SUSPECT MATERIALS ARE WORK ANY SUSPECT MATERIALS ARE WORK ANY SUSPECT MATERIALS ARE WORK ANY SUSPECT MATERIALS ARE
ENCOUNTERED BY THE CONTRACTOR, THE ENCOUNTERED BY THE CONTRACTOR, THE ENCOUNTERED BY THE CONTRACTOR, THE ENCOUNTERED BY THE CONTRACTOR, THE
CONTRACTOR IS TO IMMEDIATELY STOP WORK IN CONTRACTOR IS TO IMMEDIATELY STOP WORK IN CONTRACTOR IS TO IMMEDIATELY STOP WORK IN CONTRACTOR IS TO IMMEDIATELY STOP WORK IN
THE AREA AND NOTIFY THE OWNER.THE AREA AND NOTIFY THE OWNER.THE AREA AND NOTIFY THE OWNER.THE AREA AND NOTIFY THE OWNER.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
M.M.M.M.
N.N.N.N.
AAAA
1111
BBBB
CCCC
DDDD
EEEE
FFFF
GGGG
HHHH
JJJJ
KKKK
LLLL
MMMM
NNNN
PPPP
2222 3333 4444 5555 6666 7777 8888
1111
2222
3333
4444
5555
2222
3333
3333
3333 3333
1111
1111
1111 1111
3333
3333
3333
3333
3333
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
MD200
Level 00
Mechanical
Piping
Demolition
Plan
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DRAWING NOTES
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 SHUTOFF HEATING WATER SYSTEM, DRAIN ANDSHUTOFF HEATING WATER SYSTEM, DRAIN ANDSHUTOFF HEATING WATER SYSTEM, DRAIN ANDSHUTOFF HEATING WATER SYSTEM, DRAIN AND
SAVE GLYCOL FOR REUSE. REMOVE A SECTIONSAVE GLYCOL FOR REUSE. REMOVE A SECTIONSAVE GLYCOL FOR REUSE. REMOVE A SECTIONSAVE GLYCOL FOR REUSE. REMOVE A SECTION
OF HWS AND HWR PIPING INCLUDING ISOLATIONOF HWS AND HWR PIPING INCLUDING ISOLATIONOF HWS AND HWR PIPING INCLUDING ISOLATIONOF HWS AND HWR PIPING INCLUDING ISOLATION
VALVES, BALANCE VALVE STRAINER, CONTROLVALVES, BALANCE VALVE STRAINER, CONTROLVALVES, BALANCE VALVE STRAINER, CONTROLVALVES, BALANCE VALVE STRAINER, CONTROL
VALVE, ETC. SERVING VAV FAN POWERED BOXVALVE, ETC. SERVING VAV FAN POWERED BOXVALVE, ETC. SERVING VAV FAN POWERED BOXVALVE, ETC. SERVING VAV FAN POWERED BOX
OR REHEAT BOX. CAP AT MAIN UNLESS PIPING ISOR REHEAT BOX. CAP AT MAIN UNLESS PIPING ISOR REHEAT BOX. CAP AT MAIN UNLESS PIPING ISOR REHEAT BOX. CAP AT MAIN UNLESS PIPING IS
GOING TO BE RECONNECTED TO A NEW VAVGOING TO BE RECONNECTED TO A NEW VAVGOING TO BE RECONNECTED TO A NEW VAVGOING TO BE RECONNECTED TO A NEW VAV
REHEAT BOX. SEE REMODEL PLAN.REHEAT BOX. SEE REMODEL PLAN.REHEAT BOX. SEE REMODEL PLAN.REHEAT BOX. SEE REMODEL PLAN.
2222 WITH SYSTEM DRAINED AND ISOLATED, REMOVEWITH SYSTEM DRAINED AND ISOLATED, REMOVEWITH SYSTEM DRAINED AND ISOLATED, REMOVEWITH SYSTEM DRAINED AND ISOLATED, REMOVE
THE EXISTING PNEUMATICCONTROL VALVE.THE EXISTING PNEUMATICCONTROL VALVE.THE EXISTING PNEUMATICCONTROL VALVE.THE EXISTING PNEUMATICCONTROL VALVE.
3333 REMOVE EXISTING FAN POWERED VAV BOX. SEEREMOVE EXISTING FAN POWERED VAV BOX. SEEREMOVE EXISTING FAN POWERED VAV BOX. SEEREMOVE EXISTING FAN POWERED VAV BOX. SEE
DRAWING MD100.DRAWING MD100.DRAWING MD100.DRAWING MD100.
4444 REMOVE EXISTING VAV REHEAT BOX.REMOVE EXISTING VAV REHEAT BOX.REMOVE EXISTING VAV REHEAT BOX.REMOVE EXISTING VAV REHEAT BOX.
5555 SHUTOFF HEATING WATER SYSTEM, DRAIN ANDSHUTOFF HEATING WATER SYSTEM, DRAIN ANDSHUTOFF HEATING WATER SYSTEM, DRAIN ANDSHUTOFF HEATING WATER SYSTEM, DRAIN AND
SAVE GLYCOL FOR REUSE. REMOVE THE EXISTINGSAVE GLYCOL FOR REUSE. REMOVE THE EXISTINGSAVE GLYCOL FOR REUSE. REMOVE THE EXISTINGSAVE GLYCOL FOR REUSE. REMOVE THE EXISTING
1" AND 2" ISOLATION VALVES. REPLACE WITH1" AND 2" ISOLATION VALVES. REPLACE WITH1" AND 2" ISOLATION VALVES. REPLACE WITH1" AND 2" ISOLATION VALVES. REPLACE WITH
NEW BALL VALVES.NEW BALL VALVES.NEW BALL VALVES.NEW BALL VALVES.
SCALE:SCALE:SCALE:SCALE:MD200MD200MD200MD200 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
LEVEL 00 MECHANICAL PIPING DEMOLITION PLAN1111
CAP
HRR
HRS
HWRHWS
HRS
HWS
HRR
HWR
HRR
HRS
HWS HWR
HR
R
HW
R
HR
S
HW
S
HW
R
HW
S
HR
R
HR
S
(E)3/4"(E)2"
HR
R
HR
S
HW
R
HW
S
(E)1-1/4"
(E)3"
(E)1-1/4"
(E)1-1/4"
(E)1-1/2"
(E)1-1/4"
(E)1-1/4"
(E)2"
(E)3"
(E)1-1/2"
(E)3/4"
(E)3/4"
(E)2"
(E)2"
(E)3"
(E)3"
(E)3/4"
(E)4"
(E)1"
(E)1"
(E)1-1/4"
(E)1-1/2"
(E)3/4"
(E) 1-1/4" HWR/S
(E) 3/4" HWR/S
(E) 2" HWR/S(E) 1-1/4"
HWR/S
(E) 1" HWR/S
(E) 3/4"
HWR/S
(E) 3/4" HWR/S
(E) 2-1/2" HWR/S
(E) 3/4"
HWR/S
(E) 3/4" HWR/S
(E) 3/4" HWR/S
(E) 2" HWR/S (E) 2" HWR/S
(E) 2" HWR/S
(E) 1-1/2" HWR/S (E) 1-1/2"
HWR/S
(E) 1-1/4"
HWR/S
(E) 1-1/4"
HWR/S
(E) 1-1/4"
HWR/S
(E) 1-1/4"
HWR/S
(E) 1" HWR/S (E) 3/4"
HWR/S
(E) 3/4" HWR/S (E) 3/4" HWR/S
(E) 3/4" HWR/S
(E) 3/4" HWR/S (E) 3/4" HWR/S
(E) 3/4" HWR/S
(E) 3/4" HWR/S
(E) 3/4" HWR/S
(E) VAVR-271
(E) VAVR-272
(E) VAVR-268
(E) VAVR-270 (E) VAVR-262 (E) VAVR-260
(E) VAVR-255B (E) VAVR-239
(E) VAVR-238
(E) VAVR-234
(E) VAVR-230
(E) VAVR-243
(E) VAVR-252
(E) VAVR-276
(E) VAVR-255A
(E) 1-1/2"
HWR/S
dbkbo^i=klqbp
A.A.A.A. FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING
REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR
PATCHWORK. PATCHWORK. PATCHWORK. PATCHWORK.
INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK
INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL
OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES,
HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS
NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF
THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING
UNITS. UNITS. UNITS. UNITS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
EXISTING PIPING INSULATION MAY CONTAIN EXISTING PIPING INSULATION MAY CONTAIN EXISTING PIPING INSULATION MAY CONTAIN EXISTING PIPING INSULATION MAY CONTAIN
ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE ASBESTOS. THE OWNER IS RESPONSIBLE FOR THE
REMOVAL AND HANDLING OF ANY SUSPECT REMOVAL AND HANDLING OF ANY SUSPECT REMOVAL AND HANDLING OF ANY SUSPECT REMOVAL AND HANDLING OF ANY SUSPECT
MATERIALS. IF DURING THE COARSE OF THE MATERIALS. IF DURING THE COARSE OF THE MATERIALS. IF DURING THE COARSE OF THE MATERIALS. IF DURING THE COARSE OF THE
WORK ANY SUSPECT MATERIALS ARE WORK ANY SUSPECT MATERIALS ARE WORK ANY SUSPECT MATERIALS ARE WORK ANY SUSPECT MATERIALS ARE
ENCOUNTERED BY THE CONTRACTOR, THE ENCOUNTERED BY THE CONTRACTOR, THE ENCOUNTERED BY THE CONTRACTOR, THE ENCOUNTERED BY THE CONTRACTOR, THE
CONTRACTOR IS TO IMMEDIATELY STOP WORK IN CONTRACTOR IS TO IMMEDIATELY STOP WORK IN CONTRACTOR IS TO IMMEDIATELY STOP WORK IN CONTRACTOR IS TO IMMEDIATELY STOP WORK IN
THE AREA AND NOTIFY THE OWNER.THE AREA AND NOTIFY THE OWNER.THE AREA AND NOTIFY THE OWNER.THE AREA AND NOTIFY THE OWNER.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
M.M.M.M.
N.N.N.N.
AAAA
1111
BBBB
CCCC
DDDD
EEEE
FFFF
GGGG
HHHH
JJJJ
KKKK
LLLL
MMMM
NNNN
PPPP
2222 3333 4444 5555 6666 7777 8888
1111
2222
2222
1111
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
MD202
Level 02
Mechanical
Piping
Demolition
Plan
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DRAWING NOTES
0000555510101010 10101010 20202020
NOTE
#DESCRIPTION
1111 SHUTOFF HEATING WATER SYSTEM, DRAIN ANDSHUTOFF HEATING WATER SYSTEM, DRAIN ANDSHUTOFF HEATING WATER SYSTEM, DRAIN ANDSHUTOFF HEATING WATER SYSTEM, DRAIN AND
SAVE GLYCOL FOR REUSE. REMOVE A SECTIONSAVE GLYCOL FOR REUSE. REMOVE A SECTIONSAVE GLYCOL FOR REUSE. REMOVE A SECTIONSAVE GLYCOL FOR REUSE. REMOVE A SECTION
OF HWS AND HWR PIPING INCLUDING ISOLATIONOF HWS AND HWR PIPING INCLUDING ISOLATIONOF HWS AND HWR PIPING INCLUDING ISOLATIONOF HWS AND HWR PIPING INCLUDING ISOLATION
VALVES, BALANCE VALVE STRAINER, CONTROLVALVES, BALANCE VALVE STRAINER, CONTROLVALVES, BALANCE VALVE STRAINER, CONTROLVALVES, BALANCE VALVE STRAINER, CONTROL
VALVE, ETC. SERVING VAV FAN POWERED BOXVALVE, ETC. SERVING VAV FAN POWERED BOXVALVE, ETC. SERVING VAV FAN POWERED BOXVALVE, ETC. SERVING VAV FAN POWERED BOX
OR REHEAT BOX. CAP AT MAIN UNLESS PIPING ISOR REHEAT BOX. CAP AT MAIN UNLESS PIPING ISOR REHEAT BOX. CAP AT MAIN UNLESS PIPING ISOR REHEAT BOX. CAP AT MAIN UNLESS PIPING IS
GOING TO BE RECONNECTED TO A NEW VAVGOING TO BE RECONNECTED TO A NEW VAVGOING TO BE RECONNECTED TO A NEW VAVGOING TO BE RECONNECTED TO A NEW VAV
REHEAT BOX. SEE REMODEL PLAN.REHEAT BOX. SEE REMODEL PLAN.REHEAT BOX. SEE REMODEL PLAN.REHEAT BOX. SEE REMODEL PLAN.
2222 REMOVE EXISTING VAV REHEAT BOX.REMOVE EXISTING VAV REHEAT BOX.REMOVE EXISTING VAV REHEAT BOX.REMOVE EXISTING VAV REHEAT BOX.
SCALE:SCALE:SCALE:SCALE:MD202MD202MD202MD202 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
LEVEL 02 MECHANICAL PIPING DEMOLITION PLAN1111
AAAA
1111
BBBB
CCCC
DDDD
EEEE
FFFF
GGGG
HHHH
JJJJ
KKKK
LLLL
MMMM
NNNN
PPPP
2222 3333 4444 5555 6666 7777 8888
66
MEN'S RM
64
WOMEN'S RM
O-C
HALLWAY
O-A
VESTIBULE
69
MECHANICAL ROOM
68
CUST RM
59
COMPUTER LAB
59D
DARK ROOM
59E
FILM
59C
VESTIBULE
51
PHOTO STUDIO
59A
EQUIP / CHECK OUT
59B
STORAGE
57
OFFICE
55
OFFICE
50
CLASSROOM
0-H
VESTIBULE
51B
CHANGING
52C
STORAGE
52
PHYSICS LAB
52B
ACOUSTICS STUDIO
52A
OPTICS LAB
67
O-D
ELEVATOR
18
STORAGE
16
CUST OFFICE
14
CUSTODIAL LAUNDRY RM
12
MECH RM
0-K
ELEVATOR
10
MECHANICAL RM
O-B
STAIRWELL
63
STORAGE
1111
2222
3333
5555
6666
7777
8888
9999
10101010
11111111
12121212
13131313
14141414
36"x24"F.O.36"x24"F.O.36"x24"F.O.36"x24"F.O.
16161616
22"Ø22"Ø22"Ø22"Ø
22
"
Ø
22
"
Ø
22
"
Ø
22
"
Ø
8"x8" EXH.8"x8" EXH.8"x8" EXH.8"x8" EXH.
4444 4444
4444
4444
4444
4444
2222 2222
3333
CHCHCHCH
1111
CHCHCHCH
2222
CHCHCHCH
2222
2222
2222
12121212 12121212 12121212
12121212121212121212121212121212
5555
2222 2222
13131313
13131313
13131313
13131313
13131313
14141414
14141414
14141414
14141414
14141414
14141414
14141414
5555 5555
9999
8888
8888
3333
3333
3333
3333
33333333
3333 3333
6666
6666
6666
1111
7777
7777
7777
7777
8888
8"Ø8"Ø8"Ø8"Ø
59D59D59D59D
VAVRVAVRVAVRVAVR10
"
x
1
0
"
+
1
"
A
L
10
"
x
1
0
"
+
1
"
A
L
10
"
x
1
0
"
+
1
"
A
L
10
"
x
1
0
"
+
1
"
A
L
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
14"Ø14"Ø14"Ø14"Ø
51515151
VAVRVAVRVAVRVAVR
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
14
"
x
1
4
"
+
1
"
A
L
14
"
x
1
4
"
+
1
"
A
L
14
"
x
1
4
"
+
1
"
A
L
14
"
x
1
4
"
+
1
"
A
L
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø 8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
6"Ø6"Ø6"Ø6"Ø
5555
14"Ø14"Ø14"Ø14"Ø
59595959
VAVRVAVRVAVRVAVR
18
"
x
1
4
"
+
1
"
A
L
18
"
x
1
4
"
+
1
"
A
L
18
"
x
1
4
"
+
1
"
A
L
18
"
x
1
4
"
+
1
"
A
L
10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
16"Ø16"Ø16"Ø16"Ø
0000----CCCC
VAVRVAVRVAVRVAVR
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL
H.D.H.D.H.D.H.D.
12"Ø, TYP.12"Ø, TYP.12"Ø, TYP.12"Ø, TYP.6"Ø6"Ø6"Ø6"Ø
55555555
VAVRVAVRVAVRVAVR
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
6"Ø6"Ø6"Ø6"Ø
57575757
VAVRVAVRVAVRVAVR
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
H.D.H.D.H.D.H.D.
14"Ø14"Ø14"Ø14"Ø
50505050
VAVRVAVRVAVRVAVR
16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
6"Ø6"Ø6"Ø6"Ø
10"Ø10"Ø10"Ø10"Ø
52A52A52A52A
VAVRVAVRVAVRVAVR
10"x12"+1"AL10"x12"+1"AL10"x12"+1"AL10"x12"+1"AL
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
12"Ø12"Ø12"Ø12"Ø
12"Ø12"Ø12"Ø12"Ø
52525252
VAVRVAVRVAVRVAVR
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
14
"
x
1
2
"
+
1
"
A
L
14
"
x
1
2
"
+
1
"
A
L
14
"
x
1
2
"
+
1
"
A
L
14
"
x
1
2
"
+
1
"
A
L
12"Ø12"Ø12"Ø12"Ø
64646464
VAVRVAVRVAVRVAVR
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
H.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"Ø
15151515
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
10
"
x
1
0
"
+
1
"
A
L
10
"
x
1
0
"
+
1
"
A
L
10
"
x
1
0
"
+
1
"
A
L
10
"
x
1
0
"
+
1
"
A
L
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø8"
Ø
8"
Ø
8"
Ø
8"
Ø
8"Ø8"Ø8"Ø8"Ø
10
"
Ø
10
"
Ø
10
"
Ø
10
"
Ø
59A59A59A59A
VAVRVAVRVAVRVAVR
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø18181818
19191919
17171717
17171717
17171717
17171717 17171717
17171717
17171717
17171717
17171717
1717171717171717
1717171717171717
17171717
17171717
17171717
20202020
20202020
17171717
17171717
4444
25252525
17171717
1717171721212121
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
22222222
23232323
12"x8" EXH.12"x8" EXH.12"x8" EXH.12"x8" EXH.
1111
IEFIEFIEFIEF
LVTPLVTPLVTPLVTP
18181818
18181818
6"x6"6"x6"6"x6"6"x6"
24242424
4444
4444
4444
2222
2222
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
MH100
Level 00
Mechanical
Remodel Plan
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DRAWING NOTES
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MH100MH100MH100MH100 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
LEVEL 00 MECHANICAL REMODEL PLAN1111
NOTE
#
DIFFUSER
CALLOUT DESCRIPTION
1111 S-1S-1S-1S-1 215 CFM, 8"Ø NK S.A. DIFFUSER215 CFM, 8"Ø NK S.A. DIFFUSER215 CFM, 8"Ø NK S.A. DIFFUSER215 CFM, 8"Ø NK S.A. DIFFUSER
2222 R-1R-1R-1R-1 22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
3333 S-1S-1S-1S-1 255 CFM, 10"Ø NK S.A. DIFFUSER255 CFM, 10"Ø NK S.A. DIFFUSER255 CFM, 10"Ø NK S.A. DIFFUSER255 CFM, 10"Ø NK S.A. DIFFUSER
4444 R-1R-1R-1R-1 22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
5555 S-1S-1S-1S-1 50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER
6666 S-2S-2S-2S-2 225 CFM, 10"Ø NK S.A. DIFFUSER225 CFM, 10"Ø NK S.A. DIFFUSER225 CFM, 10"Ø NK S.A. DIFFUSER225 CFM, 10"Ø NK S.A. DIFFUSER
7777 S-1S-1S-1S-1 360 CFM, 12"Ø NK S.A. DIFFUSER360 CFM, 12"Ø NK S.A. DIFFUSER360 CFM, 12"Ø NK S.A. DIFFUSER360 CFM, 12"Ø NK S.A. DIFFUSER
8888 S-1S-1S-1S-1 185 CFM, 8"Ø NK S.A. DIFFUSER185 CFM, 8"Ø NK S.A. DIFFUSER185 CFM, 8"Ø NK S.A. DIFFUSER185 CFM, 8"Ø NK S.A. DIFFUSER
9999 S-1S-1S-1S-1 130 CFM, 8"Ø NK S.A. DIFFUSER130 CFM, 8"Ø NK S.A. DIFFUSER130 CFM, 8"Ø NK S.A. DIFFUSER130 CFM, 8"Ø NK S.A. DIFFUSER
10101010 S-2S-2S-2S-2 230 CFM, 10"Ø NK S.A. DIFFUSER230 CFM, 10"Ø NK S.A. DIFFUSER230 CFM, 10"Ø NK S.A. DIFFUSER230 CFM, 10"Ø NK S.A. DIFFUSER
11111111 S-1S-1S-1S-1 335 CFM, 12"Ø NK S.A. DIFFUSER335 CFM, 12"Ø NK S.A. DIFFUSER335 CFM, 12"Ø NK S.A. DIFFUSER335 CFM, 12"Ø NK S.A. DIFFUSER
12121212 S-1S-1S-1S-1 140 CFM, 8"Ø NK S.A. DIFFUSER140 CFM, 8"Ø NK S.A. DIFFUSER140 CFM, 8"Ø NK S.A. DIFFUSER140 CFM, 8"Ø NK S.A. DIFFUSER
13131313 S-1S-1S-1S-1 220 CFM, 10"Ø NK S.A. DIFFUSER220 CFM, 10"Ø NK S.A. DIFFUSER220 CFM, 10"Ø NK S.A. DIFFUSER220 CFM, 10"Ø NK S.A. DIFFUSER
14141414 S-1S-1S-1S-1 150 CFM, 8"Ø NK S.A. DIFFUSER150 CFM, 8"Ø NK S.A. DIFFUSER150 CFM, 8"Ø NK S.A. DIFFUSER150 CFM, 8"Ø NK S.A. DIFFUSER
15151515 E-1E-1E-1E-1 100 CFM, 8"x8" NK EXHAUST AIR100 CFM, 8"x8" NK EXHAUST AIR100 CFM, 8"x8" NK EXHAUST AIR100 CFM, 8"x8" NK EXHAUST AIR
GRILLEGRILLEGRILLEGRILLE
16161616 CONNECT NEW 36"x24" F.O. DUCT TOCONNECT NEW 36"x24" F.O. DUCT TOCONNECT NEW 36"x24" F.O. DUCT TOCONNECT NEW 36"x24" F.O. DUCT TO
EXISTING AIR PLENUM. INSTALL DUCTEXISTING AIR PLENUM. INSTALL DUCTEXISTING AIR PLENUM. INSTALL DUCTEXISTING AIR PLENUM. INSTALL DUCT
SO THAT THE DUCT OPENING DOESSO THAT THE DUCT OPENING DOESSO THAT THE DUCT OPENING DOESSO THAT THE DUCT OPENING DOES
NOT INTERFER WITH EXISTING FIRENOT INTERFER WITH EXISTING FIRENOT INTERFER WITH EXISTING FIRENOT INTERFER WITH EXISTING FIRE
SPRINKLER RISER.SPRINKLER RISER.SPRINKLER RISER.SPRINKLER RISER.
17171717 14"x12"+1"AL TRANSFER AIR OPENING14"x12"+1"AL TRANSFER AIR OPENING14"x12"+1"AL TRANSFER AIR OPENING14"x12"+1"AL TRANSFER AIR OPENING
IN WALL ABOVE CEILING W/ SOUNDIN WALL ABOVE CEILING W/ SOUNDIN WALL ABOVE CEILING W/ SOUNDIN WALL ABOVE CEILING W/ SOUND
BOOT.BOOT.BOOT.BOOT.
18181818 R.A. OPENING IN WALL ABOVE CEILINGR.A. OPENING IN WALL ABOVE CEILINGR.A. OPENING IN WALL ABOVE CEILINGR.A. OPENING IN WALL ABOVE CEILING
AS LARGE AS POSSIBLE.AS LARGE AS POSSIBLE.AS LARGE AS POSSIBLE.AS LARGE AS POSSIBLE.
19191919 EXISTING 40"x20" R.A. OPENING INEXISTING 40"x20" R.A. OPENING INEXISTING 40"x20" R.A. OPENING INEXISTING 40"x20" R.A. OPENING IN
WALL ABOVE CEILING.WALL ABOVE CEILING.WALL ABOVE CEILING.WALL ABOVE CEILING.
20202020 E-1E-1E-1E-1 275 CFM, 10"x10" NK EXHAUST AIR275 CFM, 10"x10" NK EXHAUST AIR275 CFM, 10"x10" NK EXHAUST AIR275 CFM, 10"x10" NK EXHAUST AIR
GRILLE. CONNECT TO EXISTINGGRILLE. CONNECT TO EXISTINGGRILLE. CONNECT TO EXISTINGGRILLE. CONNECT TO EXISTING
DUCTWORK.DUCTWORK.DUCTWORK.DUCTWORK.
21212121 E-1E-1E-1E-1 75 CFM, 6"x6" NK EXHAUST AIR GRILLE75 CFM, 6"x6" NK EXHAUST AIR GRILLE75 CFM, 6"x6" NK EXHAUST AIR GRILLE75 CFM, 6"x6" NK EXHAUST AIR GRILLE
22222222 E-1E-1E-1E-1 400 CFM 12"x12" NK EXHAUST AIR400 CFM 12"x12" NK EXHAUST AIR400 CFM 12"x12" NK EXHAUST AIR400 CFM 12"x12" NK EXHAUST AIR
GRILLE.GRILLE.GRILLE.GRILLE.
23232323 TRANSITION 12"x8" EXHAUST DUCT ANDTRANSITION 12"x8" EXHAUST DUCT ANDTRANSITION 12"x8" EXHAUST DUCT ANDTRANSITION 12"x8" EXHAUST DUCT AND
CONNECT TO EXISTING 14"x12" DUCTCONNECT TO EXISTING 14"x12" DUCTCONNECT TO EXISTING 14"x12" DUCTCONNECT TO EXISTING 14"x12" DUCT
PENETRATING THROUGH EXTERIORPENETRATING THROUGH EXTERIORPENETRATING THROUGH EXTERIORPENETRATING THROUGH EXTERIOR
WALL.WALL.WALL.WALL.
24242424 38"x28" OPENING WITH FIRE/SMOKE38"x28" OPENING WITH FIRE/SMOKE38"x28" OPENING WITH FIRE/SMOKE38"x28" OPENING WITH FIRE/SMOKE
DAMPER. TRANSITION AND CONNECTDAMPER. TRANSITION AND CONNECTDAMPER. TRANSITION AND CONNECTDAMPER. TRANSITION AND CONNECT
DAMPER TO SUPPLY AIR DUCT.DAMPER TO SUPPLY AIR DUCT.DAMPER TO SUPPLY AIR DUCT.DAMPER TO SUPPLY AIR DUCT.
FIRE/SMOKE DAMPER TO BE A FRONTFIRE/SMOKE DAMPER TO BE A FRONTFIRE/SMOKE DAMPER TO BE A FRONTFIRE/SMOKE DAMPER TO BE A FRONT
ACCESS TYPE DAMPER TO MOUNTACCESS TYPE DAMPER TO MOUNTACCESS TYPE DAMPER TO MOUNTACCESS TYPE DAMPER TO MOUNT
FLUSH TO THE PLENUM SIDE OF THEFLUSH TO THE PLENUM SIDE OF THEFLUSH TO THE PLENUM SIDE OF THEFLUSH TO THE PLENUM SIDE OF THE
WALL.WALL.WALL.WALL.
25252525 30"x24" R.A. OPENING IN WALL ABOVE30"x24" R.A. OPENING IN WALL ABOVE30"x24" R.A. OPENING IN WALL ABOVE30"x24" R.A. OPENING IN WALL ABOVE
CEILING WITH FIRE/SMOKE DAMPER.CEILING WITH FIRE/SMOKE DAMPER.CEILING WITH FIRE/SMOKE DAMPER.CEILING WITH FIRE/SMOKE DAMPER.
AAAA
1111
BBBB
CCCC
DDDD
EEEE
FFFF
GGGG
HHHH
JJJJ
KKKK
LLLL
MMMM
NNNN
PPPP
2222 3333 4444 5555 6666 7777 8888
270
CLASSROOM
268
CLASSROOM
266
MEN'S RM
264
WOMEN'S RM
262
CLASSROOM
260
CLASSROOM
2-M
HALLWAY
267
CUST RM
265
OFFICE
263
OFFICE
261
OFFICE
259
OFFICE
276
CLASSROOM
272
BIO-CHEMISTRY LAB
2-S
HALLWAY
277A
STORAGE RM
277
CLASSROOM 255
CLASSROOM
2-V
LOUNGE
258
STORAGE
253
OFFICE
252
OFFICE
250
OFFICE
248
OFFICE
246
OFFICE
244
OFFICE
230
SECRETARY/RECEPTION RM
243
WORK ROOM
2-L
HALLWAY
242
OFFICE
240
OFFICE
238
OFFICE
239
OFFICE
237
OFFICE
235
OFFICE
233
OFFICE
236
OFFICE
234
OFFICE
232
OFFICE
2-K
HALLWAY
2-J
HALLWAY
2-D
HALLWAY
214
CHEMISTRY LAB
213
CHEMISTRY STOCK RM
2-H
STAIRWELL 216
CUST STOR
2-G
ELEVATOR
220
WOMEN'S ROOM
226
MEN'S ROOM
228
CUST RM280
BDF RM
2-T
STAIRWELL
279
CLASSROOM
229
CLASSROOM
203A
INSTRUMENT RM
213A
OFFICE
203
CHEMISTRY LAB
210
CHEMISTRY LAB
299
CLASSROOM
297
CLASSROOM
281
CHEMISTRY PREP RM
203B
INSTRUMENT RM
2-B
HALLWAY
2-C
STAIRWELL
2-A
STAIRWELL
204
CHEMISTRY LAB
298
OFFICE
296
OFFICE
294
OFFICE
292
OFFICE
291
OFFICE
290
OFFICE
289
OFFICE
287
SEC/ RECEP RM
286
OFFICE
285
OFFICE
282A
CHEM STOCK RM
287A
WORK ROOM
2-U
HALLWAY
282
GENERAL CHEM LAB
2-F
HALLWAY
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø1111
2222
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
18
"
x
1
4
"
+
1
"
A
L
18
"
x
1
4
"
+
1
"
A
L
18
"
x
1
4
"
+
1
"
A
L
18
"
x
1
4
"
+
1
"
A
L
1111
1111
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.1111
8"Ø8"Ø8"Ø8"Ø H.D.H.D.H.D.H.D.
1111 1111
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
1111
1111
1111
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
14
"
Ø
14
"
Ø
14
"
Ø
14
"
Ø
12"Ø12"Ø12"Ø12"Ø
12
"
Ø
12
"
Ø
12
"
Ø
12
"
Ø
10
"
Ø
E
X
H
.
10
"
Ø
E
X
H
.
10
"
Ø
E
X
H
.
10
"
Ø
E
X
H
.
272272272272
MAVMAVMAVMAV
272272272272
EXVEXVEXVEXV
3333
2222
4444
2"
Ø
2"
Ø
2"
Ø
2"
Ø
18
"
x
1
6
"
F
.
O
.
18
"
x
1
6
"
F
.
O
.
18
"
x
1
6
"
F
.
O
.
18
"
x
1
6
"
F
.
O
.
272A272A272A272A
EXVEXVEXVEXV
8"Ø8"Ø8"Ø8"Ø
272B272B272B272B
EXVEXVEXVEXV
8"Ø8"Ø8"Ø8"Ø
5555
5555
7777
16"Ø16"Ø16"Ø16"Ø
14"x14"14"x14"14"x14"14"x14"
6666
6666
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
MH102
Level 02
Mechanical
Remodel Plan
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DRAWING NOTES
0000555510101010 10101010 20202020
NOTE
#
DIFFUSER
CALLOUT DESCRIPTION
1111 S-1S-1S-1S-1 185 CFM, 8"Ø NK S.A. DIFFUSER185 CFM, 8"Ø NK S.A. DIFFUSER185 CFM, 8"Ø NK S.A. DIFFUSER185 CFM, 8"Ø NK S.A. DIFFUSER
2222 DROP 12"Ø EXHAUST DUCT DOWN TODROP 12"Ø EXHAUST DUCT DOWN TODROP 12"Ø EXHAUST DUCT DOWN TODROP 12"Ø EXHAUST DUCT DOWN TO
CHEMICAL FUME HOOD AND CONNECT.CHEMICAL FUME HOOD AND CONNECT.CHEMICAL FUME HOOD AND CONNECT.CHEMICAL FUME HOOD AND CONNECT.
TRANSITION AS REQUIRED.TRANSITION AS REQUIRED.TRANSITION AS REQUIRED.TRANSITION AS REQUIRED.
3333 E-2E-2E-2E-2 1290 CFM, 16"Ø NK EXHAUST AIR1290 CFM, 16"Ø NK EXHAUST AIR1290 CFM, 16"Ø NK EXHAUST AIR1290 CFM, 16"Ø NK EXHAUST AIR
GRILLEGRILLEGRILLEGRILLE
4444 2"Ø UNDERHOOD FLAMMABLE CABINET2"Ø UNDERHOOD FLAMMABLE CABINET2"Ø UNDERHOOD FLAMMABLE CABINET2"Ø UNDERHOOD FLAMMABLE CABINET
EXHAUST. SEE DETAIL 2/MH502.EXHAUST. SEE DETAIL 2/MH502.EXHAUST. SEE DETAIL 2/MH502.EXHAUST. SEE DETAIL 2/MH502.
5555 REFERENCE PLUMBING DRAWINGS FORREFERENCE PLUMBING DRAWINGS FORREFERENCE PLUMBING DRAWINGS FORREFERENCE PLUMBING DRAWINGS FOR
WORK IN THIS AREA.WORK IN THIS AREA.WORK IN THIS AREA.WORK IN THIS AREA.
6666 EXV-272A AND EXV-272B AND THIEREXV-272A AND EXV-272B AND THIEREXV-272A AND EXV-272B AND THIEREXV-272A AND EXV-272B AND THIER
ASSOCIATED DUCTWORK ANDASSOCIATED DUCTWORK ANDASSOCIATED DUCTWORK ANDASSOCIATED DUCTWORK AND
CONTROLS ARE PART OF ADD.CONTROLS ARE PART OF ADD.CONTROLS ARE PART OF ADD.CONTROLS ARE PART OF ADD.
ALTERNATE #2.ALTERNATE #2.ALTERNATE #2.ALTERNATE #2.
7777 THE AIR VALVES IN THIS ROOM (282)THE AIR VALVES IN THIS ROOM (282)THE AIR VALVES IN THIS ROOM (282)THE AIR VALVES IN THIS ROOM (282)
TO BE REBALANCED TO ACCOMMODATETO BE REBALANCED TO ACCOMMODATETO BE REBALANCED TO ACCOMMODATETO BE REBALANCED TO ACCOMMODATE
THE REMOVAL OF 2 FUME HOODS.THE REMOVAL OF 2 FUME HOODS.THE REMOVAL OF 2 FUME HOODS.THE REMOVAL OF 2 FUME HOODS.
REFERENCE EQUIPMENT SCHEDULES.REFERENCE EQUIPMENT SCHEDULES.REFERENCE EQUIPMENT SCHEDULES.REFERENCE EQUIPMENT SCHEDULES.
SCALE:SCALE:SCALE:SCALE:MH102MH102MH102MH102 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
LEVEL 02 MECHANICAL REMODEL PLAN1111
SINGLE VANE SCHEDULE
ONE SIDE
SQUARE ELBOW
NOTES:
RADIUS ELBOW
BOTH SIDES
45 DEG. ELBOW
45 DEG. TURNING VANE DETAIL
30 DEG. MAX.
1/2 W
INSIDE SQUARE, OUTSIDE RADIUS
ALL DUCTS (SUPPLY, RETURN
AND EXHAUST) TO HAVE TURNING
ELBOWS NOT ALLOWED.
2.
VANES IN SQUARE ELBOW.
1.
W
15 DEG. MAX.
TURNING
VANES
SINGLE
BLADE
SINGLE BLADE
SMALL
LARGE
2"
R
(51mm)
4-1/2"
(114mm)
1-1/2"
SP
(38mm)
3-1/4"
(83mm)
24
GA
(0.70mm)
22
(0.85mm)
22.5
(TYP.)
TURNING VANES,
SEE DETAIL AND
SCHEDULE BELOW
CL
45° LATERAL TEE
CONICAL 90° TEE
Y-BRANCH 90°
BRANCH TAKE-OFF
DIMENSIONS
FABRICATED ELBOW
D
R
ADD ONE PIECE FOR
EACH ADDITIONAL 18°
R = 1.5D
D = DUCT SIZE
0-35° ---- 2 PIECE
72-90° ----5 PIECE
36-71° ----3 PIECE
L
D
MITERED 90° ELBOW
REDUCER
OFFSET
1A MAX.
2"
1-1/4"
A
2A
TURNING
VANES
A
1-1/4"
D
45°
D = DUCT SIZE
DIMENSIONS
L = D/2+1"
D
2"
DUCT SIDE. PROVIDE 1" TRAILING
TO START AND STOP PARALLEL WITH
ANGLE OF DIRECTION CHANGE. VANES
EXHAUST) TO HAVE TURNING VANES
ALL DUCTS (SUPPLY, RETURN AND
WITH SQUARE TYPE ELBOWS AT ANY
EDGE.
NOTE:
kl=mlm=ofsbqp=^iiltba
HANGER STRAPS
`lkpqor`qflk=pq^ka^oap
ar`q=mbo=pj^`k^=es^`=ar`q
e^kdbo=pfwbp=clo=olrka
SELF TAPPING HEX HEAD SHEET
METAL SCREWS. STRAPS TO BE
TIGHT AGAINST DUCT
1"
kl=mlm=ofsbqp=^iiltba
TO BE TIGHT AGAINST DUCT.
HEAD SHEET METAL SCREWS. STRAPS
SELF TAPPING CADMIUM PLATED HEX
HANGER STRAPS e^kdbo=pfwbp=clo=ob`q^kdri^o
ar`q=mbo=pj^`k^=es^`=ar`q
`lkpqor`qflk=pq^ka^oap
ANGLE IRON
ROUND/OVAL DUCT
ANGLE IRON
HANGER STRAPS
e^kdbo=pfwbp=clo=olrka=L=ls^i
ar`q=mbo=pj^`k^=es^`=ar`q
`lkpqor`qflk=pq^ka^oap
ENDS OF LINER SHALL BE
COATED WITH ADHESIVE.
METAL DUCT
GALVANIZED SHEET
ALL ENDS OF LINER TO BE
BUTTED FIRMLY TOGETHER.
1 2 " C .C . MA X .
SIZED PER DRAWING
FROM EDGE OF LINER
NOT MORE THAN 2"
(T Y P .)
2 "
DUCT LINER
ADHESIVE
ADHERED TO
DUCT W/100%
DUCT LINER.
LINER TO BE
TOP AND BOTTOM SECTION
OF LINER SHALL OVERLAP
THE SIDES
FOR SIZING
ROUND DUCT, SEE PLANS
MADE DUCT. MAX. LENGTH 6'-0".
FASTEN WITH MASTIC AND BINDING
HIGH PRESSURE RATED FACTORY
SUPPLY AIR DIFFUSER, SEE
PLANS FOR SIZING
CEILING
STRAP. SEE DETAIL THIS SHEET
BINDING STRAP
ROUND SHEET METAL DUCT
6" MAX. LENGTH
FACTORY MADE DUCT
5/8" SCREW TIGHTENING BINDING
STRAP OR NYLON CINCHE BAND.
2"
NOTE:
FOR INSULATED DUCT, PROVIDE ONE
ADDITIONAL BAND AROUND THE
INSULATION.
RETURN AIR GRILLE
22 GA. SHEET
METAL SKIN
GRILLE
LENGTH
ACOUSTICAL
(1 2 " MI N .)
W
1" INTERIOR
LINING, 1# PCF
DENSITY
1/2 W (MI N . 8 "+A L )
1/2 W
1" WIDE HANGING
STRAP
SHEET METAL
SCREW, TYPICAL
W
TURN HANGER UNDER
2" AND FASTEN WITH
SHEET METAL SCREW
SHEET METAL DUCT
DUCT SECTION
LOCKING QUADRANT
STRAP 1/2" ROD
45° DUCT CONNECTION
BLADE WITH V-GROOVE
BLADE SECTION
1/2" ROD
BRANCH DUCT OR RUNOUT
TO DIFFUSER, SEE PLANS
FOR SIZING
RECTANGULAR DUCT, SEE
PLANS FOR SIZING
LOCKING QUADRANT
(ONE PER BLADE)
STRAP, RIVET TO BLADE
(TACK WELD ROD
SECURELY TO BLADE)
22 GA. BLADE 1/2"
SPRING LOADED END
TACK WELD OR RIVET
TO BLADE (BLADE MUST
CLEAR LINER OR DUCT
APPROX. 1/4" ON ALL SIDES)
BLADE MULTIPLES
DUCT DEPTH
UP TO 12" - 1 BLADE
UP TO 20" - 2 BLADES
UP TO 30 " - 3 BLADES
NOTES:
EQUAL CROSS SECTION AREA
AREA OF AxC SHALL BE EQUAL
MINIMUM AREA OF AxB SHALL
TO 1.5 x AREA OF AxB.
OF BRANCH DUCT.
C
HAND DAMPER WITH
LOCKING QUADRANT
A
PLANS FOR SIZING
RECTANGULAR DUCT, SEE
ROUND DUCT RUNOUT
TO DIFFUSER, SEE
PLANS FOR SIZING
B
45°
2.
1.
VERIFY REQUIRED SLEEVE
LENGTH PRIOR TO ORDERING
PROVIDE ACCESS DOOR TO FIRE
DAMPER LINKAGE AND SMOKE
DAMPER ACTUATOR LARGE ENOUGH
TO SERVICE AND RESET DAMPER.
12"x12" MINIMUM.
RETURN OR SUPPLY
AIR DUCT, SEE PLANS
FOR SIZES
DAMPER ACTUATOR
MINIMUM AND MAXIMUM CLEARANCE
AS REQUIRED BY MANUFACTURER
FIREWALL
SLIP CONNECTION (TYP.)
RETURN OR SUPPLY
AIR DUCT
FIRE/SMOKE DAMPER. LOCATE
IN WALL AS REQUIRED BY
MANUFACTURER
SLEEVE GAUGE AS REQUIRED BY
MANUFACTURER
16 GA. MIN. OR AS REQUIRED BY
MANUFACTURER ALL AROUND
DUCT-SEE PLANS FOR SIZE,
LOCATION AND CONTINUATION
NUMBER
HINGES
16 X 16
24 X 24
12 X 12
6 X 6
MAXIMUM
DIMENSION
GAUGE
BACK
24 2622
3 2 22 26
HANDLES
2
2
1
1
NUMBER
OF OF
26
26
26
26
DOOR
22
22
26
24
FRAME
BUTT HINGE
1"x1" (.025x.025)
LOCATION
ACCESS DOOR. SEE
PLANS FOR SIZE AND
SASH LOCK
GASKET
DUCT EXTERIOR
DENSITY FIBERGLASS
DUCT LINER 1" (.025) THICK
ONE AND ONE HALF POUND
NOTE:
IN ADDITION TO THOSE DOORS SHOWN
DOORS SHOWN IN THE DRAWINGS, THE
SHEET METAL CONTRACTOR SHALL
INSTALL AN ACCESS DOOR AT EACH
FIRE AND FIRE/ SMOKE DAMPER.
bnrfmjbkq=q^d
s^isb=q^d
THE OWNER
THE PLANS DIRECTED BY
LETTERING
BLACK FACED PLASTIC
INDICATE NORMALY OPEN OR NORMALLY
INDICATE SHUT-OFF, BALANCING, DRAIN ETC.
INDICATE CHILLED WATER,
HOT WATER, GAS ETC.
ANCHOR SECURELY
TO EQUIPMENT
LAMINATE WITH ENGRAVED
INDICATE EXHAUST FAN,
PUMP, ETC. INDICATE
EQUIPMENT MARK AS SHOWN
3/16" MINIMUM LETTER HEIGHT
FROM MANUFACTURER RECOMMENDATIONS
SAME AS MOTOR NAMEPLATE
INDICATE - STATIC PRESSURE, FOOT OF
HEAD ETC. AND RPM IF APPLICABLE
LUB. FREQUENCY:
MOTOR RPM/HP:
AREA SERVED:
LUBRICANT:
AT:
REFER TO PLANS
.
RPM
ATTACH AROUND VALVE HANDLE WITH CHAIN
INDICATE TONS, GPM, CFM ETC.
WITH STANDARD LETTERING
INDICATE GATE, BALL,
0.051" THICK BRASS TAG
SIZE:TYPE:
ITEM NAME/#:
CAPACITY:
CONTENTS:
FUNCTION:
POSITION:
CLOSED OR AS MARKED.
INDICATE VALVE SIZE
3"
M
I
N
I
M
U
M
6" MINIMUM
1-
1
/
2
"
M
I
N
.
3"
NOTE:
FROM MANUFACTURER RECOMMENDATIONS
1/8" MINIMUM LETTER HEIGHT
NOTE:CHECK VALVE ETC.
AS REQUIRED TO SIZE INDICATED
TRANSITION FROM DISCHARGE END
SEE PLANS FOR SIZING
BRANCH DUCT TO DIFFUSERS,
ON PLANS.
VAV BOX, SEE PLANS FOR
SIZING AND LOCATION.
BELL TYPE FITTING
VAV BOX AS REQUIRED
TRANSITION TO INLET OF
ALTERNATE TAKE-OFF TYPE
MAIN SUPPLY DUCT
STRAIGHT DUCTWORK, PROVIDE MINIMUM
LENGTH OF 18" OR 1.5 TIMES INLET
DUCT DIAMETER, WHICH EVER IS GREATER.
CONTROLS ENCLOSURE,
VERIFY WHICH SIDE OF
BOX WITH DRAWINGS
NO LINE OF SIGHT THROUGH
CONSTRUCTED SO THERE IS
SOUND BOOT TO BE
THE SOUND BOOT.
NOTE:
W W
+
2"W
L
WALL
W
W
W+2"
LINE OF SIGHT
1" INTERIOR ACOUSTICAL
LINING, 1 lb. DENSITY
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
MH501
Mechanical
Details
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
RECTANGULAR DUCT FITTINGS DETAIL1111
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
MEDIUM VELOCITY DUCT FITTINGS DETAIL2222
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
ROUND DUCT HANGER DETAIL3333
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
DUCT STRAP HANGER DETAIL4444
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
OVAL DUCT HANGER DETAIL5555
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
DUCT LINER DETAIL6666
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
DUCT TO DIFFUSER CONNECTION DETAIL7777
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
FACTORY MADE DUCT DETAIL8888
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
SOUND TRAP DETAIL9999
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
BRANCH DUCT AND DAMPER DETAIL10101010
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
DUCT CONNECTION DETAIL11111111
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
FIRE / SMOKE DAMPER DETAIL12121212
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
LOW PRESSURE DUCT ACCESS DOOR DETAIL13131313
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
IDENTIFICATION TAG DETAIL14141414
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
VAV BOX DETAIL15151515
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
TRANSFER/RETURN AIR SOUND BOOT DETAIL16161616
MAIN SUPPLY DUCT
FOR SIZING AND LOCATION
PHOENIX VALVE, SEE PLANS
REHEAT COIL WHERE
BOX AS REQUIRED
INDICATED
INLET OF VAV
TRANSITION TO
ACCESS DOOR,
12"x12" MINIMUM
DRAWBAND
DRAWBAND
SEE PLANS FOR
DUCT SIZE
AS REQUIRED TO SIZE INDICATED
TRANSITION FROM DISCHARGE END
ON PLANS.
5' MIN.
3' MIN.
DIFFUSERS, SEE
BRANCH DUCT TO
PLANS FOR SIZING.
DUCT SIZE.
WALL
TRANSITION FROM FUME
HOOD RECTANGULAR OUTLET
TO ROUND EXHAUST DUCT,
SEE PLANS FOR EXHAUST
FLAMMABLE STORAGE
CABINET
UNION, TYPICAL
2"
VALVE
CHEMICAL FUME
HOOD
EXHAUST DUCT
FLOOR
UNISTRUT SUPPORT
SYSTEM
2" TYPE L COPPER
PIPE
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
MH502
Mechanical
Details
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH502MH502MH502MH502
PHOENIX VALVE WITH REHEAT COIL DETAIL1111
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH502MH502MH502MH502
CHEMICAL FUME HOOD CONNECTION DETAIL2222
(E) 3" HWR
(E) 3" HWS
HWR/S
(E) 1-1/2"(E) 3/4"
HWR/S
(E)2" HWR/S
(E) 1"
HWR/S
(E) 1-1/2" HWR/S
(E) 3" HWR/S
(E) 1-1/4"
HWR/S
(E) 1-1/4"
HWR/S
dbkbo^i=klqbp
A.A.A.A.ALL HWS/R BRANCH LINES SERVING VAVR BOXES ALL HWS/R BRANCH LINES SERVING VAVR BOXES ALL HWS/R BRANCH LINES SERVING VAVR BOXES ALL HWS/R BRANCH LINES SERVING VAVR BOXES
SHALL BE 3/4" UNLESS OTHERWISE NOTED.SHALL BE 3/4" UNLESS OTHERWISE NOTED.SHALL BE 3/4" UNLESS OTHERWISE NOTED.SHALL BE 3/4" UNLESS OTHERWISE NOTED.
AAAA
1111
BBBB
CCCC
DDDD
EEEE
FFFF
GGGG
HHHH
JJJJ
KKKK
LLLL
MMMM
NNNN
PPPP
2222 3333 4444 5555 6666 7777 8888
66
MEN'S RM
64
WOMEN'S RM
O-C
HALLWAY
O-A
VESTIBULE
69
MECHANICAL ROOM
68
CUST RM
59
COMPUTER LAB
59D
DARK ROOM
59E
FILM
59C
VESTIBULE
51
PHOTO STUDIO
59A
EQUIP / CHECK OUT
59B
STORAGE
57
OFFICE
55
OFFICE
50
CLASSROOM
0-H
VESTIBULE51B
CHANGING
52C
STORAGE
52
PHYSICS LAB
52B
ACOUSTICS STUDIO
52A
OPTICS LAB
67
MECH RM
O-D
ELEVATOR
18
STORAGE
16
CUST OFFICE
14
CUSTODIAL LAUNDRY RM
12
MECH RM
0-K
ELEVATOR
10
MECHANICAL RM
O-B
STAIRWELL
63
STORAGE
64646464
VAVRVAVRVAVRVAVR
0000----CCCC
VAVRVAVRVAVRVAVR
59A59A59A59A
VAVRVAVRVAVRVAVR
57575757
VAVRVAVRVAVRVAVR
55555555
VAVRVAVRVAVRVAVR
1111
CHCHCHCH
2222
CHCHCHCH
52A52A52A52A
VAVRVAVRVAVRVAVR 52525252
VAVRVAVRVAVRVAVR
50505050
VAVRVAVRVAVRVAVR
3333
CHCHCHCH
51515151
VAVRVAVRVAVRVAVR
59D59D59D59D
VAVRVAVRVAVRVAVR
59595959
VAVRVAVRVAVRVAVR
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
1111----1/4" HWS/R1/4" HWS/R1/4" HWS/R1/4" HWS/R
1111----1/4" HWS/R1/4" HWS/R1/4" HWS/R1/4" HWS/R
1111
2222
3333
4444
1111
S
S
S
S
S
S
S
S
S S
S
S
S
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
MP200
Level 00
Mechanical
Piping
Remodel Plan
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DRAWING NOTES
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MP200MP200MP200MP200 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
LEVEL 00 MECHANICAL PIPING REMODEL PLAN1111
NOTE
# DESCRIPTION
1111 CONNECT NEW HWS/R PIPING TO EXISTING PIPING.CONNECT NEW HWS/R PIPING TO EXISTING PIPING.CONNECT NEW HWS/R PIPING TO EXISTING PIPING.CONNECT NEW HWS/R PIPING TO EXISTING PIPING.
REDUCE FROM EXISTING PIPE SIZE AS REQUIRED.REDUCE FROM EXISTING PIPE SIZE AS REQUIRED.REDUCE FROM EXISTING PIPE SIZE AS REQUIRED.REDUCE FROM EXISTING PIPE SIZE AS REQUIRED.
2222 REPLACE EXISTING CONTROL VALVE WITH NEWREPLACE EXISTING CONTROL VALVE WITH NEWREPLACE EXISTING CONTROL VALVE WITH NEWREPLACE EXISTING CONTROL VALVE WITH NEW
AND RECONNECT EXISTING HWS/R TO EXISTINGAND RECONNECT EXISTING HWS/R TO EXISTINGAND RECONNECT EXISTING HWS/R TO EXISTINGAND RECONNECT EXISTING HWS/R TO EXISTING
CABINET HEATER. PLACE CABINET HEATER IN FULLCABINET HEATER. PLACE CABINET HEATER IN FULLCABINET HEATER. PLACE CABINET HEATER IN FULLCABINET HEATER. PLACE CABINET HEATER IN FULL
OPERATION.OPERATION.OPERATION.OPERATION.
3333 INSTALL NEW BALL VALVES IN EXISTING 2" HWS/RINSTALL NEW BALL VALVES IN EXISTING 2" HWS/RINSTALL NEW BALL VALVES IN EXISTING 2" HWS/RINSTALL NEW BALL VALVES IN EXISTING 2" HWS/R
LINES.LINES.LINES.LINES.
4444 INSTALL NEW BALL VALVES IN EXISTING 1" HWS/RINSTALL NEW BALL VALVES IN EXISTING 1" HWS/RINSTALL NEW BALL VALVES IN EXISTING 1" HWS/RINSTALL NEW BALL VALVES IN EXISTING 1" HWS/R
LINES.LINES.LINES.LINES.
AAAA
1111
BBBB
CCCC
DDDD
EEEE
FFFF
GGGG
HHHH
JJJJ
KKKK
LLLL
MMMM
NNNN
PPPP
2222 3333 4444 5555 6666 7777 8888
270
CLASSROOM
268
CLASSROOM
266
MEN'S RM
264
WOMEN'S RM
262
CLASSROOM
260
CLASSROOM
2-M
HALLWAY
267
CUST RM
265
OFFICE 263
OFFICE
261
OFFICE
259
OFFICE
276
CLASSROOM
272
BIO-CHEMISTRY LAB
2-S
HALLWAY
277A
STORAGE RM
277
CLASSROOM 255
CLASSROOM
2-V
LOUNGE
258
STORAGE
253
OFFICE
252
OFFICE
250
OFFICE
248
OFFICE
246
OFFICE
244
OFFICE
230
SECRETARY/RECEPTION RM
243
WORK ROOM
2-L
HALLWAY
242
OFFICE
240
OFFICE
238
OFFICE
239
OFFICE
237
OFFICE
235
OFFICE
233
OFFICE
236
OFFICE
234
OFFICE
232
OFFICE
2-K
HALLWAY
2-J
HALLWAY
2-D
HALLWAY
214
CHEMISTRY LAB
213
CHEMISTRY STOCK RM
2-H
STAIRWELL 216
CUST STOR
2-G
ELEVATOR
220
WOMEN'S ROOM
226
MEN'S ROOM
228
CUST RM280
BDF RM
2-T
STAIRWELL
279
CLASSROOM
229
CLASSROOM
203A
INSTRUMENT RM
213A
OFFICE
203
CHEMISTRY LAB
210
CHEMISTRY LAB
299
CLASSROOM
297
CLASSROOM
281
CHEMISTRY PREP RM
203B
INSTRUMENT RM
2-B
HALLWAY
2-C
STAIRWELL
2-A
STAIRWELL
204
CHEMISTRY LAB
298
OFFICE
296
OFFICE
294
OFFICE
292
OFFICE
291
OFFICE
290
OFFICE
289
OFFICE
287
SEC/ RECEP RM
286
OFFICE
285
OFFICE
282A
CHEM STOCK RM
287A
WORK ROOM
2-U
HALLWAY
282
GENERAL CHEM LAB
2-F
HALLWAY
272272272272
MAVMAVMAVMAV
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
MP202
Level 02
Mechanical
Piping
Remodel Plan
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DRAWING NOTES
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
SCALE:SCALE:SCALE:SCALE:MP202MP202MP202MP202 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
LEVEL 02 MECHANICAL PIPING REMODEL PLAN1111
WALL, CEILING
STRUCTURAL
OF THE DIMENSION TABULATED FOR THE LARGER PIPE, PLUS ONE-HALF OF THE
DIMENSION TABULATED FOR THE SMALLER PIPE, TO DETERMINE THE MINIMUM
NOTES:
OR OTHER
MEMBER
3 1/2"
4 1/2"
DIMENSION
MINIMUM CENTERLINE SPACING
5 1/2"
6 1/2"
2"-2 1/2"
6"
8"
3"-3 1/2"
5"
4"
PIPE SIZE
1"-1 1/4"-1 1/2"
1/2"-3/4"
NOMINAL
8}"
9"
10"
8"
7 1/2"
16"
14"
13"
12"
11"
DIMENSION
5"
7"
6"
A
DIMENSION
6"
8"
10"
B
INSULATED PIPE
A B C C
5"
8"
7 1/2"
6"
5"
11"
9"
7"
6"
DIMENSION
4"
C D
3"
4"
OR OTHER
MEMBER
STRUCTURAL
WALL, CEILING
BARE PIPE
E D
1. DIM "C": WHERE PIPES OF DIFFERENT SIZE ARE RUN PARALLEL, USE ONE-HALF
CENTER LINE SPACING BETWEEN ADJACENT RUNS.
2. TABLE APPLIES ONLY TO PIPING RUNS WHICH ARE NOT DIMENSIONED ON THE
PIPING PLANS.
~~
~
SPLIT RING
ROD SIZE
HANGERS SIZES AND SPACING ARE FOR SINGLE PIPES. HANGER ROD LOADING
FOR TRAPEZE HANGERS SHALL NOT EXCEED THE TOTAL LOADING INDICATED.
IF SMALLER ROD SIZE IS USED, DECREASE MAXIMUN SPACING SO THAT TOTAL
LOADING IS NOT EXCEEDED. SUPPORT FROM STRUCTURE PANEL POINTS.
UP TO 2000 LBS. USE
1" AND SMALLER
MAX. SPACING
NOTE:
5" - 8"
2-1/2" - 4"
1-1/4" - 2"
PIPE SIZE
12
16
8
10
TRAPEZE HANGER
PIPE LOAD
2.5/20
50/800
20/240
6/60
WEIGHT/FT. TOTAL
P-1001.
DOUBLE NUT HANGER
"UNISTRUT" 1-5/8"
UP TO 700 LBS. USE
P-1000, FOR LOADING
CHANNEL-FOR LOADING
ROD. TYPICAL
3/8"
5/8"
7/8"
3/8"
CALSIUM SILICATE THERMAL
INSULATION INSERT 360 DEG.
COVERAGE/ENCASEMENT WITH
GALVANIZED PROTECTION
SHIELD, 360 DEG. COVERAGE/
ENCASEMENT
PIPE INSULATION
CLEVIS HANGER
CI
N
C
H
A
N
C
H
O
R
S
THRU-BOLT
CINCH ANCHORS
ANGLE
ADJUSTABLE
PIPE STAND
ROD
STEEL PLATE
BLOCK WALL
WELDED STEEL
WALL BRACKET
U-BOLT
STEEL STRAP
TURNBUCKLE
EYE BOLTS
OR BEAM/TRUSS
U-BOLTS
WALL BRACKET
STEEL OFFSET
EYE BOLT
PIPE CLAMP
TURNBUCKLE
ROD
CONNECTION
INSERTS
CLAMPS
I-BEAM
ANGLE
OR BEAM/TRUSS
CONNECTION
ROD
U-BOLTS
INSERTS
NOTE:
WHERE PIPES ARE INSULATED, THE INSULATION
IS TO PASS THROUGH THE CLAMP WITH EITHER
CALCIUM SILICATE BLOCKERS OR INSULATION
SHIELDS AS REQUIRED.
FIVE PIPE DIAMETERS MINIMUM
FIVE PIPE DIAMETERS MINIMUM
FLOW VENTURI OR
BALANCING DEVICE
VALVE OR OTHER FITTING
DIRECTION OF FLOW
DIRECTION
OF FLOW
FITTING
VALVE OR OTHER
TWO PIPE DIAMETERS MINIMUM
FS
REDUCER (TYPICAL)
UNION (TYPICAL)
MAIN OR BRANCH LINE
BALL VALVE
AIR CHNAMER
1-1/4" x 12" LONG
HIGH POINT
3/8"
WALLS, USE ASG ACOUSTICAL SEALANT.
FOR PENETRATIONS THROUGH SOUND
NOTE:
STANDARD WEIGHT STEEL PIPE
SLEEVE OF SIZE TO PASS PIPE
FINISHED ESCUTCHEON PLATE
FLUSH AGAINST WALL AND OF
SIZE TO COMPLETELY COVER
OPENING
FINISHED WALL SURFACE
PIPING EXPOSED TO VIEWCONCEALED PIPING
TERMINATE SLEEVE FLUSH WITH
FINISHED WALL SURFACES
SEAL OR CAULK SLEEVES THRU
FIRE WALLS IN A SMOKE TIGHT
MANNER
PIPE AND INSULATION TO BE
CENTERED IN SLEEVE-DO NOT
SUPPORT PIPE FROM SLEEVE
INTERIOR WALLS
HWR
MANUAL AIR VENT
HWS
SHUT-OFF BALL VALVE (TYP.)
AIR
FLOW
PROVIDE 1/2" BALL
VALVE FOR EACH
VENT HEADER
COPPER TEE W/
THREADED INSERT
& P/T PLUG.
1/2" BALL VALVE
W/ HOSE END & CAP
2-WAY MODULATING CONTROL
VALVE W/ UNION ENDS
COPPER
PIPE
COPPER
PIPE
NOTES:
1. INSTALL VALVES AS CLOSE TO COIL AS POSSIBLE.
MIN. 5 PIPE DIAMETERS
REDUCER
W/ MEMORY STOP & INDICATOR,
P AT RATED FLOW
VENTURI FOR 20" TO 50" W.G.
WILL NOT BE ACCEPTED). SELECT
(REFRIGERATION FLARE CONNS.
VENTURI W/ SCHRADER VALVES
FLOWSET ACCUSETTER VALVE
THREADED TO
SWEAT CONN.
SWEAT CONN.
THREADED TO
& P/T PLUG.
THREADED INSERT
COPPER TEE W/
2. VALVE SHALL BE INSTALLED WITHIN 2'-0" OF VALVE .B A
B
A
VALVE W/ UNION ENDS
MIN. 5 PIPE DIAMETERS
3-WAY MODULATING CONTROL
A
SHUT-OFF BALL VALVE (TYP.)
VALVES (REFRIGERATION FLARE
BALANCING VALVE W/ SCHRADER
W/ MEMORY STOP & INDICATOR,
CIRCUIT BALANCE VALVE
CONNS. WILL NOT BE ACCEPTED).
W/ HOSE END & CAP
2. VALVES & SHALL BE INSTALLED WITHIN 2'-0" OF VALVE
1. INSTALL VALVES AS CLOSE TO COIL AS POSSIBLE.
THREADED TO SWEAT
NOTES:
CB
CONNECTION
FLOW
AIR
C
1/2" BALL VALVE
THREADED INSERT
& P/T PLUG.
BALL VALVE W/
MEMORY STOP &
COPPER TEE W/
INDICATOR
B
VENT HEADER
MANUAL AIR VENT
VALVE FOR EACH
PROVIDE 1/2" BALL
INSERT AND P/T PLUG
COPPER TEE WITH THREADED
THREADED TO SWEAT
CONNECTION
N.O.
N.
C
.
C
NOTES:
HWS
REDUCER
HWR
A
1.
2.
VALVE PORTING IS DIAGRAMTIC. FIELD VERIFY ACTUAL PORTING OF TO BE
INSTALLED VALVE(S) PRIOR TO INSTALLATION INSURING PROPER FLOW
PATTERN.
TYPICAL FOR VAVR HW COILS WHERE INDICATED ON DRAWINGS.
ANCHOR INTO WALL (3/8" DIA. x3")
UNISTRUT PIPE CLAMP
PIPE INSULATION
UNISTRUT CHANNEL
WALL
HIGH DENSITY CALCIUM SILICATE
INSULATION INSERT 360 DEG.
COVERAGE / ENCASEMENT
GALVANIZED PROTECTION
SHIELD. 360 DEG.
COVERAGE/ENCASEMENT
16 GAGE MINIMUM (TYP.)
CONCRETE SLAB
CHANNEL GALVANIZED
1-5/8" x 1-5/8" UNISTRUT
UNISTRUT PIPE CLAMP
BOLTS, 3" LONG.
2-3/8" DIA. EXPANSION
3/8" x 4" x 8" PLATE WITH
3" x 3" x 3/16" ANGLE
1/4
ADJUSTMENT OF TENSION
DOUBLE NUT TO ALLOW
PIPING
1/4
PIPING
HIGH DENSITY CALSIUM SILICATE
INSULATION INSERT, 360 DEG.
COVERAGE/ENCASEMENT (TYPICAL).
GALVANIZED PROTECTION SHIELD
360 DEG. COVERAGE/ENCASEMENT
(TYPICAL)
GALVANIZED
(GALVANIZED)
GALVANIZED
GALVANIZED
EXTERIOR PIPE
INSULATION WITH
EMBOSED ALUMINUM
JACKET
EQUIPMENT
SIDE
SYSTEM
SIDE
REDUCER, TYPICAL
BOTH SIDES
CIRCUIT BALANCE
VALVE
METER CONNECTION
POINTS
UNION
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
MP501
Mechanical
Piping Details
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
PIPE CLEARANCE DATA DETAIL1111
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
PIPE HANGER DETAIL2222
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
TYPICAL PIPE SUPPORTS DETAIL3333
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
BALANCE / FLOW DEVICE INSTALLATION DETAIL4444
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
MANUAL AIR VENT DETAIL5555
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
PIPE PENETRATION DETAIL6666
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
2-WAY VAV HEATING COIL PIPING DETAIL7777
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
3-WAY VAV HEATING COIL PIPING DETAIL8888
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
WALL MOUNT PIPE SUPPORT DETAIL9999
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
EXTERIOR PIPE SUPPORT DETAIL10101010
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
CIRCUIT BALANCING VALVE DETAIL11111111
qebojlpq^qf`=jfufkd=s^isbp
_^`hcilt=mobsbkqbo=p`ebarib
t^qbo=e^jjbo=^oobpqbo=p`ebarib
WHA
4.
5.
6.
3.
2.
1.
G
VTR
CO
WCO
RD
FCO
FS
FD
NIC
CWV
(E)
DI
CA
mirj_fkd=^__obsf^qflkp
mirj_fkd=cfuqrob=p`ebarib mirj_fkd=pvj_li=ibdbka
dbkbo^i=mirj_fkd=klqbp
DIRECT WASTE
DESCRIPTION
WALL CLEAN OUT
SOIL / WASTE
CLEAN OUT
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DESCRIPTION
VENT THROUGH ROOFVTR
DHW
SYMBOL
DCW
CO
SYMBOL
WCO
V
W
VENT
DW
FLOOR DRAIN - 6" SQUARE STAINLESS STEEL STRAINERFD-1
DESCRIPTIONSYMBOL
P-1A
2"
HOTCOLD
1"
WASTE
3"
2"
VENT
2"
WATER CLOSET - WALL MOUNTED - ADA COMPLIANT
3/4"3" 2"
2"
TRAP
INT
INTURINAL - WALL MOUNTED - STANDARDP-2A
P-1B 3" 2"
WATER CLOSET - WALL MOUNTED STANDARD
INT
3/4"3" 2"INTURINAL - WALL MOUNTED - ADA COMPLIANTP-2B
REMARKS
HOSE BIBB - COLD, WITH VACUUM BREAKER
HOSE BIBB - HOT, WITH VACUUM BREAKER
FLOOR CLEAN OUT, NICKEL BRONZE SCORIATED TOP
WALL CLEAN OUT, STAINLESS STEEL ROUND COVERWCO
FCO
HB-2
HB-1
LAVATORY - WALL MOUNT - ADA COMPLIANTP-3 1/2"1/2"1-1/2" 2"1-1/2"
1"
3/4"
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3/4"
-
-
-
-
-
-
-
-
-
-
-
-
-
FIXTURE COUNTFC#
HAND SINK - COUNTER MOUNTEDP-4A 1/2" 1/2"2"1-1/2"1-1/2" -
LAB SINK - COUNTER MOUNTEDP-4B 1/2" 1/2"2"1-1/2"1-1/2" -
FLOOR DRAIN, FLOOR SINK OR ROOF DRAIN
GAS (NATURAL GAS)
DOMESTIC HOT WATER
SEWER OR WASTE
VENT THROUGH ROOF
VENT
COLD WATER
THERMOMETER
PRESSURE REDUCING VALVE - (PRV)
SAFETY OR RELIEF VALVE
FLOOR CLEAN OUT
WALL CLEAN OUT
CLEAN OUT
GAS SHUT OFF VALVE (GAS COCK)
DROP IN PIPE
RISE IN PIPE
VALVE IN RISE
GAS TYPE WATER HAMMER ARRESTOR
CAP
BALL VALVE
SYMBOL
UNION
DESCRIPTION
ALL PLUMBING SHALL BE DONE IN ACCORDANCE WITH THE LATEST ADOPTED EDITION OF
VALVE WITH HAND WHEEL. VALVE SHALL BE BALL TYPE, QUARTER TURN AS APPROVED
ALL WALL-HUNG PLUMBING FIXTURES SHALL BE SECURELY ATTACHED TO AND SUPPORTED
THE CONTRACTOR SHALL VERIFY ALL PLUMBING FIXTURES, EQUIPMENT REQUIREMENTS AND
LOCATIONS, AND ALL RELATED UTILITIES WITH THE MECHANICAL AND ARCHITECTURAL
PLANS AND SPECIFICATIONS AND SHALL PROVIDE ALL SERVICES AS REQUIRED.
BY FLOOR-MOUNTED CARRIERS OF ALL-METAL CONSTRUCTION. FIXTURE HANGERS OR ARMS
SHALL BE SUPPORTED FREE OF THE FINISHED WALL. HANGERS SHALL BE BY WADE,
EACH INDIVIDUAL FIXTURE SUPPLY SHALL BE PROVIDED WITH A CHROME-PLATED STOP
BY ENGINEER. STOPS SHALL BE ON BOTH HOT AND COLD WATER LINES.
FIXTURES AND ACCESSORIES SHALL BE AS SPECIFIED. EACH ITEM SHALL BE COMPLETE
WITH CHROME-PLATED BRASS TRIM. SEE PLUMBING FIXTURE SCHEDULE.
CAULK WITH SILICONE COMPOUND AROUND ALL FIXTURES AT INTERFACE WITH WALLS
THE IDAHO PLUMBING CODE AND/OR LOCAL ORDINANCES.
SMITH, JOSAM, OR ZURN.
AND/OR FLOOR.
NEW CONNECTION SYMBOL
NOT IN CONTRACT
COMBINATION WASTE VENT
EXISTING
MANUFACTURER/MODEL #
WHA-A
WHA-B
WHA-C
PPP SC-500
PPP SC-750
PPP SC-1000
MARK
PER PDI STANDARD PDI-WH 201
PER PDI STANDARD PDI-WH 201
PER PDI STANDARD PDI-WH 2011-11
12-32
33-60
1/2"
3/4"
1"
FIXTURE UNITS INLET SIZE
REMARKS
SEE SPECIFICATION 224200
SERVICE SINK - FLOOR MOUNTEDP-5 3/4"3"3/4"-2"3"
SERVICE SINK 1/2"
SERIVCE SIZE
LF009S
NUMBER
'WATT'S' MANUFACTURERSYMBOL
BFP-1
QTY.
2
SEE SPECIFICATION 230523
TEPID
-
-
-
-
-
-
-
-
-
-
-
-
-
DEIONIZED WATER SPOUTP-6 -3"-ADD. ALTERNATE #52"3"-
EMERGENCY SHOWER / EYEWASH STATIONP-7 -3"--2"3"1-1/4"
DI
1/2"
DIFFERENTIAL
PRESSURE
ALLOWABLE
MANUFACTURER
AND MODEL NO.SYMBOL LOCATION
FLOW
GPM
RATE REMARKS
OUTLET
WATER
TEMP. °F
SIZE
OUTLETINLET
SIZE
MV-1 WATTS LFUSG-B-M2 UNDER LAVATORY 2 5 105 1/2"1/2" ADJUSTABLE / ASSE 1070
MV-2 GUARDIAN G3800LF EMERGENCY SHOWER / EYE WASH 20 5 75 1"1" ADJUSTABLE / ANSI Z358.1
PSI
DARK ROOM SINKP-4C 1/2" 1/2"2"1-1/2"1-1/2" -
LAB SINK - COUNTER MOUNTEDP-4D 1/2" 1/2"2"1-1/2"1-1/2" -
-
-
DEIONIZED WATER (ADD. ALTERNATE #5)
COMPRESSED AIR
GAS
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
AIR
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
GAS TURRETP-8 -3"--2"3"-
COMPRESSED AIR TURRETP-9 -3"--2"3"-
1/2"
-
-
1/2"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
P-001
Plumbing
Schedules
and Symbol
Legend
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
(E)1/2"
(E)3/4"
(E)WH
(E)3/4"
(E
)
L
A
(E)1-1/2"
A
LA
LA
LA
WH
(E)3/4"
LA
(E)1-1/2"
LA
(E)3/4"(E)2-1/2"
LA
(E)1/2"
(E)1-1/2"
LA
(E)1-1/4"
(E)3/4"
(E)2"
(E)3/4"
(E)2-1/2"
(E)1"
(E)3/4"
(E)WH
(E)ICWIHW
(E) 1-1/4"
(E)2" GAS
(E)FD
(E)3"(E)1-1/2"
(E)2"
(E)2" WASTE FROM
ABOVE. DROP BELOW
SLAB.
FROM ABOVE
(E) 4" RD LEADER
(E)6" RD
(E)8" RD LEADER
DROPS BELOW
FLOOR SLAB
(E)8"
RD
(E)8"
(E
)
R
D
FROM ABOVE
(E) 4" RD LEADER
(E)5"
(E)4" RD LEADER
FROM ABOVE
UP TO EXISTING
PLANTER DRAIN
(E)2"
PLANTER DRAIN
UP TO EXISTING
CO
(E) DUCTWORK
(SEE MECHANICAL DWGS)
(E) 1-1/4" IHW
LA
(E)1/2"
(E)1/2"
(E)1/2"
(E) 1" IHW
(E)IHW
LA(E)ICW
(E) 1" IHW
(E)RD LEADER
FROM ABOVE
DC
W
DH
W
DH
W
R
(E) 1" IHW
(E) 3/4"
(E) 3/4"
(E) 3/4" IHWR
(E
)
R
D
(E)4"
(E)RD
(E)4" FROM
ABOVE
(E)1/2"
(E) 3/4"
IHWRIHWR
(E) 3/4" IHWR
(E)%%208"
(E)3/4"
(E)3/4"(E)1/2"
IH
W
R
IH
W
(E
)
I
C
W
(E)4"
(E)RD LEADER
FROM ABOVE
(E)1/2"(E)3/4"
DCWDCW
TO (E)URINALS
ABOVE
TO (E)LAV'S.
ABOVE
(E)1/2" DCW RISER
TO (E)DRINKING
FOUNTAINS ABOVE
(E)2"
DC
W
DC
W
(E)1/2"
ICW
DCW
DC
W
(E)3/4"
(E)3/4"
DC
W
(E)3/4"
(E)3/4"
(E)3/4"
(E
)
I
C
W
IC
W
(E)3/4"
(E)1/2"
(E)1/2"
DC
W
(E)1-1/2"
(E)3/4"
(E)1/2"
(E)3/4"
(E) 3/4"
(E)1-1/2"
(E)1-1/4"
(E) 3/4"
(E) 3/4"
(E)3/4"
AAAA
1111
BBBB
CCCC
DDDD
EEEE
FFFF
GGGG
HHHH
JJJJ
KKKK
LLLL
MMMM
NNNN
PPPP
2222
3333 4444 5555 6666 7777
8888
PD401PD401PD401PD401
1111
1111
1111
1111
1111
1111
1111
1111
1111
1111
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
PD100
Level 00
Plumbing
Demolition
Plan
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DRAWING NOTES
NOTE
# DESCRIPTION
1111 NO PLUMBING WORK IN THIS AREA. ALL FIXTURESNO PLUMBING WORK IN THIS AREA. ALL FIXTURESNO PLUMBING WORK IN THIS AREA. ALL FIXTURESNO PLUMBING WORK IN THIS AREA. ALL FIXTURES
AND ASSOCIATED PIPING TO REMAIN. PROTECTAND ASSOCIATED PIPING TO REMAIN. PROTECTAND ASSOCIATED PIPING TO REMAIN. PROTECTAND ASSOCIATED PIPING TO REMAIN. PROTECT
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
SCALE:SCALE:SCALE:SCALE:PD100PD100PD100PD100 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
LEVEL 00 PLUMBING DEMOLITION PLAN1111
0000555510101010 10101010 20202020
LEADER DN.
(E)4" RD
AW
(E)RO
(E)LG
LG
LG
LA
LA
LG
RO (E)RO
LG
RO
(E)LA RO
LA
RO
LA
LG
LA
LG
(E)4"
AW
A
W
(E)CO
(E)3"
(E)4"
(E)2"
AW
CO
AW
(E)3"VTR
(E)4"
(E)4"
AW AW
(E)6"
(E)4"
AW
(E)AW
(E)3"
CO
(E)3"
AW
(E)2"
(E)3"
(E)3" VENT UP
(E)3" VTR
(E)3" AW FROM
ABOVE
(E)6" WASTE DOWN
(E)1-1/2" VENT UP
(E) 1" IHW
AW
(E
)
G
LG
AW
(E)CO (E)3"
(E)CO
(E)2"
(E
)
A
W
(E)3"
(E)3"
(E)3"
(E)CO
(E)3"
(E)3"
LG
(E) 2"
(E) 2" LG
RO
(E) 4"
WASTE
(E) 4" ACID WASTE
FROM ABOVE
(E) 3/4" LG
(E) 1"ICW
(E) 1"
(E)1-1/4" LG
LA
(E) 1"IHW
LG
LG
(E) 1" G
G
(E) 1-1/4" IHW
(E) 1" ICW
(E) 3/4" LG
AW
(E)1/2"
(E) 1" IHW
(E) 3/4" LA
LA
(E) 1" ICW (E)3" AW
DOWN
FROM
ABOVE
RO
(E)FD
3"
(E) 3"
VENT UP
(E)4" RD
LEADER
(E)2" VENT UP
(E) 11/2" VENT UP
(E) 4" RD
DROP
(E)4" RD
LEADER
(E)4" RD LEADER
FROM ABOVE
(E) 4" W
(E) 4" W
FROM ABOVE
(E)1-1/2" VENT
FROM BELOW
LA
IH
W
IC
W
IH
W
R
LG
IHWR
ICW IHW
IH
W
IC
W
LA
LG
LG
IH
W
LA
IC
W
IH
W
R
(E)AW DN TO BELOW
MECHANICAL RM SLAB
(E
)
R
O
RO
(E)RO
RO
(E)1" LG
1"
(E)3/4" LA
(E)1-1/2" ICW
(E)3/4" IHWR
(E)1-1/4" IHW
IHWR IHW
ICW
LG
(E)3/4"
(E)1"
LA
(E)3" VENT UP
LG
(E) 1" IHW
(E)3"
(E) 3"
VENT RISER
(E)1-1/4"
(E) 1-1/4" LG
LG
(E)3/4"
(E) 1-1/4" ICW
(E) 3/4" LA
(E) 3/4" LG
RO
(E)1/2"
(E) 3/4" IHWR
1"
(E) 1-1/4" IHW
(E) 1-1/4" IHW
LG
LA
RO
(E)3"
(E)1/2" UP TO
(E) DRINKING FOUNTAIN
(E)2" SANITARY
WASTE DOWN
FROM ABOVE
(E)DRINKING
FOUNTAIN
(E)1-1/2" DOWN
(E) 2" SANITARY
WASTE DOWN.
(E)4" RD LEADER
FROM ABOVE
(E)3" AW
FROM ABOVE
TO BELOW
(E)DRINKING
FOUNTAIN
(E) 3/4" DCW
(E) 3/4" DCW
IH
W
DCW
DC
W
DCW
DC
W
DC
W
(E)3/4" DCW
(E) 3/4" DCW
DCW
(E) 3/4"
DCW DOWN
(E)3" WASTE
FROM ABOVE(E)1/2"
(E)1/2"
(E)1/2"
(E)1/2"(E)1/2"
(E)1/2"
(E)1/2"
(E)1/2"
(E)3/4"
(E)3/4"
(E)1/2"
(E)1/2"
(E)1/2"
(E)1/2"
(E)1/2"
(E)1-1/4"
(E)1-1/4"
(E)1-1/4"
(E)3/4"
(E)3/4"
LA
LG
LG
(E)3/4"
(E)3/4"
(E)3/4"
(E)3/4"
(E)3"
(E)3/4"
(E)1-1/4" LG
(E)3/4"(E)1-1/2"
(E) 3"
VENT UP
(E)3/4"
(E)1/2"
(E)3/4"
LG
LA
(E)1"
(E)1/2"
(E)1/2"
(E)1/2"(E)1/2"
(E)1/2"
(E)3/4"(E)1"
(E)3/4"
(E)1"
(E)1-1/4"(E)1"(E)1/2"(E)1/2"
(E)1/2"
(E)1/2"
(E)1/2"
(E)1"
(E) 2"
VENT UP
(E)1/2"
(E)1/2"
(E)CO
(E)1/2"(E)1"
(E)1/2"
(E)3/4"
(E)1"
(E)1-1/4"
(E)3/4"
(E)3/4"
(E)1/2"
(E)1/2"
(E)1"
(E)1/2"
(E)1/2"
(E)3/4"(E)1/2"
(E)1/2"
(E)1/2"(E)3/4"
(E)1/2"
(E)1/2"
(E)1"(E)1/2"
(E)3/4"
(E)1/2"
(E)3/4"
(E)3/4"
(E)1/2"
(E)1-1/4"
(E) 1"
(E)3/4"(E)1-1/4"
(E)1/2"
(E)1/2"
(E)1/2"
(E)1/2"
(E)3/4"
(E)1-1/4"
(E)1/2"
(E) 1"(E)3/4"
(E)2"
AAAA
1111
BBBB
CCCC
DDDD
EEEE
FFFF
GGGG
HHHH
JJJJ
KKKK
LLLL
MMMM
NNNN
PPPP
2222
3333 4444 5555 6666 7777
8888
PD402PD402PD402PD402
1111
1111
2222
1111
1111 1111 1111
1111
1111
1111
1111
1111 1111
1111
11111111
1111
1111
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
PD101
Level 01
Plumbing
Demolition
Plan
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DRAWING NOTES
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 NO PLUMBING WORK IN THIS AREA. ALL FIXTURESNO PLUMBING WORK IN THIS AREA. ALL FIXTURESNO PLUMBING WORK IN THIS AREA. ALL FIXTURESNO PLUMBING WORK IN THIS AREA. ALL FIXTURES
AND ASSOCIATED PIPING TO REMAIN. PROTECTAND ASSOCIATED PIPING TO REMAIN. PROTECTAND ASSOCIATED PIPING TO REMAIN. PROTECTAND ASSOCIATED PIPING TO REMAIN. PROTECT
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
2222 REMOVE EXISTING SINK. PROTECT ASSOCIATEDREMOVE EXISTING SINK. PROTECT ASSOCIATEDREMOVE EXISTING SINK. PROTECT ASSOCIATEDREMOVE EXISTING SINK. PROTECT ASSOCIATED
WATER, WASTE AND VENT PIPING PREPARATORYWATER, WASTE AND VENT PIPING PREPARATORYWATER, WASTE AND VENT PIPING PREPARATORYWATER, WASTE AND VENT PIPING PREPARATORY
FOR NEW SINK CONNECTION IN SAME LOCATION.FOR NEW SINK CONNECTION IN SAME LOCATION.FOR NEW SINK CONNECTION IN SAME LOCATION.FOR NEW SINK CONNECTION IN SAME LOCATION.
SEE REMODEL PLAN PL101.SEE REMODEL PLAN PL101.SEE REMODEL PLAN PL101.SEE REMODEL PLAN PL101.
SCALE:SCALE:SCALE:SCALE:PD101PD101PD101PD101 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
LEVEL 01 PLUMBING DEMOLITION PLAN1111
K-6716BANNO NC_SINKSCAST IRO N
AW
ICW, LG
ICW, IHW, LG, DCW
(E)3"VTR
ICW, LG
(E)3"VTR
ICW, LG ICW, LG
ICW, LG
W
V
ICW, IHW
IHW, ICW
(E)CO(E)3"
AW
RO, ICW, IHW
AW
(E)3"
LG
AW
IHW, ICW
(E)3"VTR
ICW, IHW
(E)3"
LG
(E)3"VTR
(E)3"VTR
ICW, IHW, LG, DCW
3"
(E)3"VTR
IHW
ICW
RO
ICW, IHW, LG, DCW
DCW, ICW, IHW, LG, RO
DCW, ICW, IHW, LG
LG, ICW LG, ICW
V
W
LG, ICW LG, ICW
(E)3" WASTE
DOWN, (E)3" VTR
(E)CO
(E)3"VTR
(E)3"VTR
(E)3"
LG
AW
(E)CO
(E)FD (E)FD
LG
(E)3"VTR
(E)1-1/2" VENT
(E)3"VTR
(E)1-1/2" VENT
(E)4"VTR
(E)FD
(E)2" VENT
(E)3" SOIL DOWN
3/4" STEAM
1/2" COND.
(E)3"VTR
(E)1-1/2" VENT
(E)3"VTR
ICW, IHW, LG, DCW
(E) 4" WASTE
(E)3"VTR
(E) 3"
DOWN
WCO
ICW, IHW, LG, RO
V
W
V
W
WCO
WCO
ICW
DCW, ICW, IHW, LG, RO
ICW, LG
(E) 3" W
W
V
W
V
WCO
ICW
LG
ICW
LG
LG
ICW
W
V
WASTE
DOWN
LG
WCO
(E) 4"
2"
2"3"
ICW, LG
3"
ICW, LG
W
V
3"
V
W
ICW, LG, LA
(E)3"VTR
2"
WCO
ICW, IHW, LG, RO, DCW
3"
3"
V
W
(E)3"VTR
3"VTR
3"
V W
WCO
(E)3"VTR
WV V
(E)3"VTR
W
(E)3"VTR
(E)3" WASTE
DOWN
(E) 3" V
(E)3"VTR
V
W
(E)3"VTR
(E) 3"
2" VENT
FROM BELOW
(E)3"VTR
(E) 4" RD
LEADER
FROM
ABOVE
(E) 4" RD
LEADER DOWN
4"
R
D
(E)3"VTR
(E)4" RD
LEADER
(E)4" RD
LEADER DN.
(E)3" VTR
(E)3" VTR
(E)2" DN
(E)3"VTR
(E)3"
(E)3"VTR(E)3"VTR
(E)4" RD LEADER
FROM ABOVE
(E)4" RD LEADER
DOWN
(E)2" AV UP
(E)3"AW DOWN
(E)3"VTR
ICW
IHW
LGLG
IHW
ICW
LG
ICW
IHW
IHW
ICW
RO
(E) 4" RD
LEADER
FROM
ABOVE
IC
W
LG LG
IC
W
LG
IC
W
IC
W
IH
W
RO
RO
IC
W
IH
W
(E) 4" RD
LEADER
FROM
ABOVE
(E)3"
LA
2" VENT
FROM BELOW
3" VENT
FROM BELOW
(E) 3" VENT
FROM BELOW
3"
2"
2"
2"
2"
3"
3"
3"
3"
2"
2"
2"
2"
(E)3" AW
DOWN
ICW, LG
LA
(E)DRINKING
FOUNTAIN
(E)1/2" DCW
(E)RO
DCW
DCW DCW
DCW
DCW
(E)4" RD
(E)3"VTR
2" VENT
FROM BELOW
2"
(E)3"VTR
FS
(E)3" WASTE
DOWN
AAAA
1111
BBBB
CCCC
DDDD
EEEE
FFFF
GGGG
HHHH
JJJJ
KKKK
LLLL
MMMM
NNNN
PPPP
2222
3333 4444 5555 6666 7777
8888
PD402PD402PD402PD402
2222
PD402PD402PD402PD402
3333
1111 1111 1111
1111
1111
1111
111111111111
1111
1111
1111
1111
1111
1111
1111
1111
1111
2222 2222
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
PD102
Level 02
Plumbing
Demolition
Plan
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DRAWING NOTES
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 NO PLUMBING WORK IN THIS AREA. ALL FIXTURESNO PLUMBING WORK IN THIS AREA. ALL FIXTURESNO PLUMBING WORK IN THIS AREA. ALL FIXTURESNO PLUMBING WORK IN THIS AREA. ALL FIXTURES
AND ASSOCIATED PIPING TO REMAIN. PROTECTAND ASSOCIATED PIPING TO REMAIN. PROTECTAND ASSOCIATED PIPING TO REMAIN. PROTECTAND ASSOCIATED PIPING TO REMAIN. PROTECT
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
2222 FUME HOOD TO BE RELOCATED. SEEFUME HOOD TO BE RELOCATED. SEEFUME HOOD TO BE RELOCATED. SEEFUME HOOD TO BE RELOCATED. SEE
MECHANICAL PLANS. DISCONNECT AND CAPMECHANICAL PLANS. DISCONNECT AND CAPMECHANICAL PLANS. DISCONNECT AND CAPMECHANICAL PLANS. DISCONNECT AND CAP
ASSOCIATED WATER AND NATURAL GAS PIPING INASSOCIATED WATER AND NATURAL GAS PIPING INASSOCIATED WATER AND NATURAL GAS PIPING INASSOCIATED WATER AND NATURAL GAS PIPING IN
CEILING SPACE PREPARATORY FOR NEWCEILING SPACE PREPARATORY FOR NEWCEILING SPACE PREPARATORY FOR NEWCEILING SPACE PREPARATORY FOR NEW
CONNECTION. SEE REMODEL PLAN PL102. FIELDCONNECTION. SEE REMODEL PLAN PL102. FIELDCONNECTION. SEE REMODEL PLAN PL102. FIELDCONNECTION. SEE REMODEL PLAN PL102. FIELD
VERIFY EXACT LOCATION.VERIFY EXACT LOCATION.VERIFY EXACT LOCATION.VERIFY EXACT LOCATION.
SCALE:SCALE:SCALE:SCALE:PD102PD102PD102PD102 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
LEVEL 02 PLUMBING DEMOLITION PLAN1111
G
G
G
G G G
G
G
G
DW
(E)FD (E)FD
(E)FD
(E)FD
(E)FD
(E)FD
(E)FD(E)FD
(E)FS
(E)FS
(E) 6"
(E) 2"
(E) 2"
(E) 2"
(E) 2"
(E) 2"
(E
)
W
C
O
(E) 2"
(E) 2"
(E) 2"
(E) 8" RD
(E) 4" RD
(E) 4" RD
(E) 6"
(E) WCO
(E) 6"
(E) SUMP
PUMP
(E)FD
(E) 2"
(E) 2"
(E) 6"
(E) 6"
(E) WCO
(E) 2"
(E) 2"
(E) 2"
(E) 2"
(E) 2"
(E) 2"
(E) 4"
(E) 4"
(E) 4"
(E) 8" RD
(E) 1/2"
(E) 4" VENT UP
(E) 2"
(E) 2" VENT UP
(E) 2"
(E) 1/2"
(E) 1-1/2"
(E) 1"
(E) 1-1/4"(E) 1-1/4"
(E) 1-1/2"
(E) 1-1/2"
(E) 1/2"
(E) 1-1/4"(E) 1-1/4"(E) 1/2"
(E) 1"
(E) 1/2"(E) 1/2"(E) 1/2"
(E) 1/2"
(E) 2" VENT UP
(E) 3/4"
(E) 1-1/2"
(E) 3"
(E) 3/4"
(E) 3/4"
(E) 3/4"
(E) 1/2"
(E) 3/4"
(E) 3/4"
(E) 3"
(E) 1-1/4"
(E) 3/4"
(E) 1-1/2"
(E) 1-1/2"
(E) 3/4"
(E) 3/4"(E) 3/4"(E) 3/4"
(E) 3/4"
(E) 3/4" GAS
FROM ABOVE
(E) 1-1/4"
(E) 3"
(E) 1/2"
(E) 3/4"
(E) 2" VENT UP
(E) 2" VENT UP
(E)WH
(E) 3/4"
(E)WH
(E) 2"
(E) 2"
(E) 2"(E) 2"
(E) 2"
(E) 2-1/2"
VENT UP
(E) 2"
(E)WH
(E) 3/4"
A
A
A A A
A
A
A
AAAA
BBBB
CCCC
DDDD
3333 4444 5555 6666 7777
1111
2222
3333
4444
5555
6666
7777
8888
9999
10101010
11111111
12121212
1111
1111 1111
11111111
1111
2222
2222
2222
2222
3333
11111111
11111111
11111111
11111111
11111111
11111111
11111111
11111111
1111111111111111
11111111
10101010 10101010 10101010 10101010 10101010
10101010
10101010
10101010
9999 99999999
9999
9999
9999
9999
9999
9999
9999
3333
3333
3333
5555
5555
5555
5555 5555 5555 5555 5555 5555
5555
5555
5555
5555
5555 5555
5555
5555
5555
5555
5555
5555
5555
5555
5555 5555
5555
6666
6666
6666
6666
12121212
CAPCAPCAPCAP CAPCAPCAPCAP
CAPCAPCAPCAP
CAPCAPCAPCAP
CAPCAPCAPCAP
CAPCAPCAPCAP
CAPCAPCAPCAP CAPCAPCAPCAP
9999
CAPCAPCAPCAP CAPCAPCAPCAP CAPCAPCAPCAP CAPCAPCAPCAP
CAPCAPCAPCAPCAPCAPCAPCAP
CAPCAPCAPCAP CAPCAPCAPCAP
CAPCAPCAPCAP
CAPCAPCAPCAP
5555
CAPCAPCAPCAP
CAPCAPCAPCAP
CAPCAPCAPCAP
CAPCAPCAPCAP
CAPCAPCAPCAP
CAPCAPCAPCAP
CAPCAPCAPCAP
3333
9999
9999 9999 9999
9999
9999
9999
9999
9999
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
PD401
Enlarged
Level 00
Plumbing
Demolition
Plan
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
SCALE:SCALE:SCALE:SCALE:PD401PD401PD401PD401 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ENLARGED LEVEL 00 PLUMBING DEMOLITION PLAN1111
00002.52.52.52.55555 5555 10101010
DRAWING NOTES
NOTE
# DESCRIPTION
1111 EXISTING WATER CLOSET AND/OR URINAL TOEXISTING WATER CLOSET AND/OR URINAL TOEXISTING WATER CLOSET AND/OR URINAL TOEXISTING WATER CLOSET AND/OR URINAL TO
REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.
2222 EXISTING LAVATORY AND ASSOCIATED PIPING TOEXISTING LAVATORY AND ASSOCIATED PIPING TOEXISTING LAVATORY AND ASSOCIATED PIPING TOEXISTING LAVATORY AND ASSOCIATED PIPING TO
REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.
3333 EXISTING FLOOR DRAIN AND/OR FLOOR SINK TOEXISTING FLOOR DRAIN AND/OR FLOOR SINK TOEXISTING FLOOR DRAIN AND/OR FLOOR SINK TOEXISTING FLOOR DRAIN AND/OR FLOOR SINK TO
REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.
4444 REMOVE EXISTING SERVICE SINK ANDREMOVE EXISTING SERVICE SINK ANDREMOVE EXISTING SERVICE SINK ANDREMOVE EXISTING SERVICE SINK AND
ASSOCIATED WATER PIPING BACK TO MAIN ANDASSOCIATED WATER PIPING BACK TO MAIN ANDASSOCIATED WATER PIPING BACK TO MAIN ANDASSOCIATED WATER PIPING BACK TO MAIN AND
CAP. REMOVE VENT PIPING BACK TO MAIN ANDCAP. REMOVE VENT PIPING BACK TO MAIN ANDCAP. REMOVE VENT PIPING BACK TO MAIN ANDCAP. REMOVE VENT PIPING BACK TO MAIN AND
CAP. CAP AND ABANDON WASTE PIPING BELOWCAP. CAP AND ABANDON WASTE PIPING BELOWCAP. CAP AND ABANDON WASTE PIPING BELOWCAP. CAP AND ABANDON WASTE PIPING BELOW
FLOOR.FLOOR.FLOOR.FLOOR.
5555 REMOVE EXISTING SINK AND ASSOCIATED WATERREMOVE EXISTING SINK AND ASSOCIATED WATERREMOVE EXISTING SINK AND ASSOCIATED WATERREMOVE EXISTING SINK AND ASSOCIATED WATER
PIPING BACK TO MAIN AND CAP. REMOVE VENTPIPING BACK TO MAIN AND CAP. REMOVE VENTPIPING BACK TO MAIN AND CAP. REMOVE VENTPIPING BACK TO MAIN AND CAP. REMOVE VENT
PIPING BACK TO MAIN AND CAP. CAP ANDPIPING BACK TO MAIN AND CAP. CAP ANDPIPING BACK TO MAIN AND CAP. CAP ANDPIPING BACK TO MAIN AND CAP. CAP AND
ABANDON WASTE PIPING BELOW FLOOR.ABANDON WASTE PIPING BELOW FLOOR.ABANDON WASTE PIPING BELOW FLOOR.ABANDON WASTE PIPING BELOW FLOOR.
6666 REMOVE EXISTING FLOOR DRAIN. CAP ANDREMOVE EXISTING FLOOR DRAIN. CAP ANDREMOVE EXISTING FLOOR DRAIN. CAP ANDREMOVE EXISTING FLOOR DRAIN. CAP AND
ABANDON ASSOCIATED WASTE AND VENT PIPINGABANDON ASSOCIATED WASTE AND VENT PIPINGABANDON ASSOCIATED WASTE AND VENT PIPINGABANDON ASSOCIATED WASTE AND VENT PIPING
BELOW FLOOR.BELOW FLOOR.BELOW FLOOR.BELOW FLOOR.
NOTE
# DESCRIPTION
7777 REMOVE EXISTING SERVICE SINK AND CAPREMOVE EXISTING SERVICE SINK AND CAPREMOVE EXISTING SERVICE SINK AND CAPREMOVE EXISTING SERVICE SINK AND CAP
ASSOCIATED WATER PIPING PREPARATORY FORASSOCIATED WATER PIPING PREPARATORY FORASSOCIATED WATER PIPING PREPARATORY FORASSOCIATED WATER PIPING PREPARATORY FOR
NEW CONNECTION. CAP VENT PIPINGNEW CONNECTION. CAP VENT PIPINGNEW CONNECTION. CAP VENT PIPINGNEW CONNECTION. CAP VENT PIPING
PREPARATORY FOR NEW CONNECTION. REMOVEPREPARATORY FOR NEW CONNECTION. REMOVEPREPARATORY FOR NEW CONNECTION. REMOVEPREPARATORY FOR NEW CONNECTION. REMOVE
WASTE PIPING AS SHOWN HATCHED.WASTE PIPING AS SHOWN HATCHED.WASTE PIPING AS SHOWN HATCHED.WASTE PIPING AS SHOWN HATCHED.
8888 EXISTING SUMP PUMP TO REMAIN. PROTECTEXISTING SUMP PUMP TO REMAIN. PROTECTEXISTING SUMP PUMP TO REMAIN. PROTECTEXISTING SUMP PUMP TO REMAIN. PROTECT
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
9999 REMOVE EXISTING PIPING WHERE SHOWNREMOVE EXISTING PIPING WHERE SHOWNREMOVE EXISTING PIPING WHERE SHOWNREMOVE EXISTING PIPING WHERE SHOWN
HATCHED.HATCHED.HATCHED.HATCHED.
10101010 PROTECT EXISTING GAS AND/OR AIR PIPINGPROTECT EXISTING GAS AND/OR AIR PIPINGPROTECT EXISTING GAS AND/OR AIR PIPINGPROTECT EXISTING GAS AND/OR AIR PIPING
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
11111111 PROTECT EXISTING ROOF DRAIN PIPING DURINGPROTECT EXISTING ROOF DRAIN PIPING DURINGPROTECT EXISTING ROOF DRAIN PIPING DURINGPROTECT EXISTING ROOF DRAIN PIPING DURING
CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.
12121212 REMOVE EXISTING VENT THROUGH ROOF. PATCHREMOVE EXISTING VENT THROUGH ROOF. PATCHREMOVE EXISTING VENT THROUGH ROOF. PATCHREMOVE EXISTING VENT THROUGH ROOF. PATCH
AND SEAL ROOF COMPLETE.AND SEAL ROOF COMPLETE.AND SEAL ROOF COMPLETE.AND SEAL ROOF COMPLETE.
(E)4"
(E)FD
(E)3"
(E) 2"
VENT UP
(E)CO
LEADER DN.
(E)4" RD
(E)FD(E)FD
K-6716BANNO NC_SINKSCAST IRO N
(E)3" WASTE
DOWN, (E)3" VTR
(E)FD (E)FD
(E)1-1/2" VENT
(E)3"VTR
(E)1-1/2" VENT
(E)4"VTR
(E)FD
(E)2" VENT
(E)1-1/2" VENT
(E)3"VTR(E)4" RD
LEADER DN.
(E)3" VTR
(E)2" VENT
FROM BELOW
(E)2"
EEEE
FFFF
4444 5555
11112222
3333
6666
7777
8888
8888
8888
8888
2222
2222
2222
2222
6666
6666 6666
3333
1111
1111 1111
1111
1111
3333
6666
1111
1111
1111
EEEE
FFFF
4444 5555
1111
2222
3333
4444
5555
6666
7777
5555
2222
1111
1111
1111
3333 3333
1111 1111
1111
1111 2222
2222
5555 5555
5555
6666
6666
6666
10101010
(E) SERVICE SINK
1111
CCCC
DDDD
EEEE
2222 3333
9999
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
PD402
Enlarged
Plumbing
Demolition
Plans
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
00002.52.52.52.55555 5555 10101010
DRAWING NOTES
SCALE:SCALE:SCALE:SCALE:PD402PD402PD402PD402 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ENLARGED LEVEL 01 PLUMBING DEMOLITION PLAN1111
NOTE
# DESCRIPTION
1111 REMOVE EXISTING WATER CLOSET AND/ORREMOVE EXISTING WATER CLOSET AND/ORREMOVE EXISTING WATER CLOSET AND/ORREMOVE EXISTING WATER CLOSET AND/OR
URINAL. REMOVE ASSOCIATED WATER, WASTEURINAL. REMOVE ASSOCIATED WATER, WASTEURINAL. REMOVE ASSOCIATED WATER, WASTEURINAL. REMOVE ASSOCIATED WATER, WASTE
AND VENT PIPING IN CHASE SPACE PREPARATORYAND VENT PIPING IN CHASE SPACE PREPARATORYAND VENT PIPING IN CHASE SPACE PREPARATORYAND VENT PIPING IN CHASE SPACE PREPARATORY
FOR NEW. SEE REMODEL PLAN PL403.FOR NEW. SEE REMODEL PLAN PL403.FOR NEW. SEE REMODEL PLAN PL403.FOR NEW. SEE REMODEL PLAN PL403.
2222 REMOVE EXISTING LAVATORY AND ASSOCIATEDREMOVE EXISTING LAVATORY AND ASSOCIATEDREMOVE EXISTING LAVATORY AND ASSOCIATEDREMOVE EXISTING LAVATORY AND ASSOCIATED
WATER, WASTE AND VENT PIPING IN WALLWATER, WASTE AND VENT PIPING IN WALLWATER, WASTE AND VENT PIPING IN WALLWATER, WASTE AND VENT PIPING IN WALL
PREPARATORY FOR NEW. SEE REMODEL PLANPREPARATORY FOR NEW. SEE REMODEL PLANPREPARATORY FOR NEW. SEE REMODEL PLANPREPARATORY FOR NEW. SEE REMODEL PLAN
PL403.PL403.PL403.PL403.
3333 EXISTING FLOOR DRAIN TO REMAIN. PROTECTEXISTING FLOOR DRAIN TO REMAIN. PROTECTEXISTING FLOOR DRAIN TO REMAIN. PROTECTEXISTING FLOOR DRAIN TO REMAIN. PROTECT
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
4444 EXISTING SERVICE SINK TO REMAIN. PROTECTEXISTING SERVICE SINK TO REMAIN. PROTECTEXISTING SERVICE SINK TO REMAIN. PROTECTEXISTING SERVICE SINK TO REMAIN. PROTECT
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
5555 PROTECT EXISTING VENT THROUGH ROOFPROTECT EXISTING VENT THROUGH ROOFPROTECT EXISTING VENT THROUGH ROOFPROTECT EXISTING VENT THROUGH ROOF
PREPARATORY FOR NEW CONNECTION. SEEPREPARATORY FOR NEW CONNECTION. SEEPREPARATORY FOR NEW CONNECTION. SEEPREPARATORY FOR NEW CONNECTION. SEE
REMODEL PLAN PL403.REMODEL PLAN PL403.REMODEL PLAN PL403.REMODEL PLAN PL403.
6666 PROTECT EXISTING VENT RISE DURINGPROTECT EXISTING VENT RISE DURINGPROTECT EXISTING VENT RISE DURINGPROTECT EXISTING VENT RISE DURING
CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.
7777 PROTECT EXISTING 4" RD LEADER DROP DURINGPROTECT EXISTING 4" RD LEADER DROP DURINGPROTECT EXISTING 4" RD LEADER DROP DURINGPROTECT EXISTING 4" RD LEADER DROP DURING
CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.
8888 PROTECT EXISTING WASTE PIPING BELOW FLOOR.PROTECT EXISTING WASTE PIPING BELOW FLOOR.PROTECT EXISTING WASTE PIPING BELOW FLOOR.PROTECT EXISTING WASTE PIPING BELOW FLOOR.
9999 REMOVE EXISTING LAB SINK AND ASSOCIATEDREMOVE EXISTING LAB SINK AND ASSOCIATEDREMOVE EXISTING LAB SINK AND ASSOCIATEDREMOVE EXISTING LAB SINK AND ASSOCIATED
WATER, WASTE AND VENT PIPING. REMOVE TOWATER, WASTE AND VENT PIPING. REMOVE TOWATER, WASTE AND VENT PIPING. REMOVE TOWATER, WASTE AND VENT PIPING. REMOVE TO
CEILING SPACE AND BELOW FLOOR PREPARATORYCEILING SPACE AND BELOW FLOOR PREPARATORYCEILING SPACE AND BELOW FLOOR PREPARATORYCEILING SPACE AND BELOW FLOOR PREPARATORY
FOR NEW CONNECTION. SEE REMODEL PLANFOR NEW CONNECTION. SEE REMODEL PLANFOR NEW CONNECTION. SEE REMODEL PLANFOR NEW CONNECTION. SEE REMODEL PLAN
PL404.PL404.PL404.PL404.
10101010 REMOVE AND PROTECT EXISTING REDUCEDREMOVE AND PROTECT EXISTING REDUCEDREMOVE AND PROTECT EXISTING REDUCEDREMOVE AND PROTECT EXISTING REDUCED
PRESSURE PRINCIPLE BACK FLOW PREVENTER ANDPRESSURE PRINCIPLE BACK FLOW PREVENTER ANDPRESSURE PRINCIPLE BACK FLOW PREVENTER ANDPRESSURE PRINCIPLE BACK FLOW PREVENTER AND
ASSOCIATED PRV, VALVING, PIPING ANDASSOCIATED PRV, VALVING, PIPING ANDASSOCIATED PRV, VALVING, PIPING ANDASSOCIATED PRV, VALVING, PIPING AND
CHEMICAL SOAP DISPENSER FOR REINSTALLATIONCHEMICAL SOAP DISPENSER FOR REINSTALLATIONCHEMICAL SOAP DISPENSER FOR REINSTALLATIONCHEMICAL SOAP DISPENSER FOR REINSTALLATION
IN NEW LOCATION. SEE REMODEL PLAN.IN NEW LOCATION. SEE REMODEL PLAN.IN NEW LOCATION. SEE REMODEL PLAN.IN NEW LOCATION. SEE REMODEL PLAN.
SCALE:SCALE:SCALE:SCALE:PD402PD402PD402PD402 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ENLARGED LEVEL 02 PLUMBING DEMOLITION PLAN2222
00002.52.52.52.55555 5555 10101010
SCALE:SCALE:SCALE:SCALE:PD402PD402PD402PD402 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ENLARGED LEVEL 02 PLUMBING DEMOLITION PLAN3333
00002.52.52.52.55555 5555 10101010
AAAA
1111
BBBB
CCCC
DDDD
EEEE
FFFF
GGGG
HHHH
JJJJ
KKKK
LLLL
MMMM
NNNN
PPPP
2222
3333 4444 5555 6666 7777
8888
66
MEN'S RM
64
WOMEN'S RM
O-C
HALLWAY
O-A
VESTIBULE
69
MECHANICAL ROOM
68
CUST RM
59
COMPUTER LAB
59D
DARK ROOM
59E
FILM
59C
VESTIBULE
51
PHOTO STUDIO
59A
EQUIP / CHECK OUT
59B
STORAGE
57
OFFICE
55
OFFICE
50
CLASSROOM
0-H
VESTIBULE
51B
CHANGING
52C
STORAGE
52
PHYSICS LAB
52B
ACOUSTICS STUDIO
52A
OPTICS LAB
67
MECH RM
O-D
ELEVATOR
18
STORAGE
16
CUST OFFICE
14
CUSTODIAL LAUNDRY RM
12
MECH RM
0-K
ELEVATOR
10
MECHANICAL RM
O-B
STAIRWELL
63
STORAGE
PL401PL401PL401PL401
1111
PL402PL402PL402PL402
1111
1111 1111
1111
1111
1111
1111
1111
1111
1111
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
PL100
Level 00
Plumbing
Remodel Plan
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DRAWING NOTES
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:PL100PL100PL100PL100 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
LEVEL 00 PLUMBING REMODEL PLAN1111
NOTE
# DESCRIPTION
1111 NO PLUMBNIG WORK IN THIS AREA. PROTECTNO PLUMBNIG WORK IN THIS AREA. PROTECTNO PLUMBNIG WORK IN THIS AREA. PROTECTNO PLUMBNIG WORK IN THIS AREA. PROTECT
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
AAAA
1111
BBBB
CCCC
DDDD
EEEE
FFFF
GGGG
HHHH
JJJJ
KKKK
LLLL
MMMM
NNNN
PPPP
2222
3333 4444 5555 6666 7777
8888
136
UNISEX RM
134
MEN'S RM
132
WOMEN'S RM
1-J
ELEVATOR
138
BDF1-V
STAIRWELL
1-U
HALLWAY
149
MINEROLOGY LAB
145
LECTURE HALL
143
PREP/STORAGE RM
141
LABORATORY
144
OFFICE
142
OFFICE
146
OFFICE
148
OFFICE
150
OFFICE
150A
RESOURCE ROOM154
SEISMOGRAPH ROOM
156
PHYSICAL SCIENCE DISPLAY ROOM158
PHYSICAL GEOLOGY ROOM
1-P
STAIRWELL
160
WOMEN'S T.R.
162
MEN'S T.R.
164
ROCK LABORATORY
167
HAZ. STORAGE
166
HAZ. STORAGE
I-N
HALLWAY
1-T
HALLWAY
1-S
STAIRWELL
171
AUTO TUTORIAL ROOM
171A
STORAGE
175
OFFICE
176
OFFICE
179
LABORATORY RM
172
LECTURE HALL
133A
SHOP RM172A
STORAGE
133
STORAGE RM
131
PHYSICS LECTURE HALL
129
ADVANCED LAB RM
I-F
HALLWAY
128
ADVANCED LAB
126A
LAB STORAGE RM
126
ADVANCED LAB
127
LECTURE HALL
107
PLANRTARIUM RM
105
PHYSICS CLASSROOM
1-H
STAIRWELL
I-G
HALLWAY
I-L
HALLWAY
I-D
HALLWAY
180
OFFICE
182
OFFICE
184
OFFICE
186
OFFICE
I-B
STAIRWELL
I-C
STAIRWELL
110
OFFICE
112
OFFICE
114
OFFICE
116
OFFICE
118
OFFICE
118A
OFFICE
PL403PL403PL403PL403
1111
PL403PL403PL403PL403
2222
1111 PPPP----4D4D4D4D
2222
1111 1111
1111
1111
1111
1111
1111
1111
1111
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
PL101
Level 01
Plumbing
Remodel Plan
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DRAWING NOTES
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 NO PLUMBNIG WORK IN THIS AREA. PROTECTNO PLUMBNIG WORK IN THIS AREA. PROTECTNO PLUMBNIG WORK IN THIS AREA. PROTECTNO PLUMBNIG WORK IN THIS AREA. PROTECT
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
2222 CONNECT NEW LAB SINK (P-4D) TO EXISTINGCONNECT NEW LAB SINK (P-4D) TO EXISTINGCONNECT NEW LAB SINK (P-4D) TO EXISTINGCONNECT NEW LAB SINK (P-4D) TO EXISTING
WATER, WASTE AND VENT PIPING.WATER, WASTE AND VENT PIPING.WATER, WASTE AND VENT PIPING.WATER, WASTE AND VENT PIPING.
SCALE:SCALE:SCALE:SCALE:PL101PL101PL101PL101 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
LEVEL 01 PLUMBING REMODEL PLAN1111
K-6716BANNO NC_SINKSCAST IRO N
AW
ICW, LG
ICW, IHW, LG, DCW
(E)3"VTR
ICW, LG
(E)3"VTR
ICW, LG ICW, LG
ICW, LG
W
V
ICW, IHW
IHW, ICW
(E)CO(E)3"
AW
RO, ICW, IHW
AW
(E)3"
LG
AW
IHW, ICW
(E)3"VTR
ICW, IHW
(E)3"
LG
(E)3"VTR
(E)3"VTR
ICW, IHW, LG, DCW
3"
(E)3"VTR
IHW
ICW
RO
ICW, IHW, LG, DCW
DCW, ICW, IHW, LG, RO
DCW, ICW, IHW, LG
LG, ICW LG, ICW
V
W
LG, ICW LG, ICW
(E)3" WASTE
DOWN, (E)3" VTR
(E)CO
(E)3"VTR
(E)3"VTR
(E)3"
LG
AW
(E)CO
(E)FD (E)FD
LG
(E)3"VTR
(E)1-1/2" VENT
(E)3"VTR
(E)1-1/2" VENT
(E)4"VTR
(E)FD
(E)2" VENT
(E)3" SOIL DOWN
3/4" STEAM
1/2" COND.
(E)3"VTR
(E)1-1/2" VENT
(E)3"VTR
ICW, IHW, LG, DCW
(E) 4" WASTE
(E)3"VTR
(E) 3"
DOWN
WCO
ICW, IHW, LG, RO
V
W
V
W
WCO
WCO
ICW
DCW, ICW, IHW, LG, RO
ICW, LG
(E) 3" W
W
V
W
V
WCO
ICW
LG
ICW
LG
LG
ICW
W
V
WASTE
DOWN
LG
WCO
(E) 4"
2"
2"3"
ICW, LG
3"
ICW, LG
W
V
3"
V
W
ICW, LG, LA
(E)3"VTR
2"
WCO
ICW, IHW, LG, RO, DCW
3"
3"
V
W
(E)3"VTR
3"VTR
3"
V W
WCO
(E)3"VTR
WV V
(E)3"VTR
W
(E)3"VTR
(E)3" WASTE
DOWN
(E) 3" V
(E)3"VTR
V
W
(E)3"VTR
(E) 3"
2" VENT
FROM BELOW
(E)3"VTR
(E) 4" RD
LEADER
FROM
ABOVE
(E) 4" RD
LEADER DOWN
4"
R
D
(E)3"VTR
(E)4" RD
LEADER
(E)4" RD
LEADER DN.
(E)3" VTR
(E)3" VTR
(E)2" DN
(E)3"VTR
(E)3"
(E)3"VTR(E)3"VTR
(E)4" RD LEADER
FROM ABOVE
(E)4" RD LEADER
DOWN
(E)2" AV UP
(E)3"AW DOWN
(E)3"VTR
ICW
IHW
LGLG
IHW
ICW
LG
ICW
IHW
IHW
ICW
RO
(E) 4" RD
LEADER
FROM
ABOVE
IC
W
LG LG
IC
W
LG
IC
W
IC
W
IH
W
RO
RO
IC
W
IH
W
(E) 4" RD
LEADER
FROM
ABOVE
(E)3"
LA
2" VENT
FROM BELOW
3" VENT
FROM BELOW
(E) 3" VENT
FROM BELOW
3"
2"
2"
2"
2"
3"
3"
3"
3"
2"
2"
2"
2"
(E)3" AW
DOWN
ICW, LG
LA
(E)DRINKING
FOUNTAIN
(E)1/2" DCW
(E)RO
DCW
DCW DCW
DCW
DCW
(E)4" RD
(E)3"VTR
2" VENT
FROM BELOW
2"
(E)3"VTR
FS
(E)3" WASTE
DOWN
AAAA
1111
BBBB
CCCC
DDDD
EEEE
FFFF
GGGG
HHHH
JJJJ
KKKK
LLLL
MMMM
NNNN
PPPP
2222
3333 4444 5555 6666 7777
8888
270
CLASSROOM
268
CLASSROOM
266
MEN'S RM
264
WOMEN'S RM
262
CLASSROOM
260
CLASSROOM
2-M
HALLWAY
267
CUST RM
265
OFFICE
263
OFFICE
261
OFFICE
259
OFFICE
276
CLASSROOM
272
BIO-CHEMISTRY LAB
2-S
HALLWAY
277A
STORAGE RM
277
CLASSROOM
255
CLASSROOM
2-V
LOUNGE
258
STORAGE
253
OFFICE
252
OFFICE
250
OFFICE
248
OFFICE
246
OFFICE
244
OFFICE
230
SECRETARY/RECEPTION RM
243
WORK ROOM
2-L
HALLWAY
242
OFFICE
240
OFFICE
238
OFFICE
239
OFFICE
237
OFFICE
235
OFFICE
233
OFFICE
236
OFFICE
234
OFFICE
232
OFFICE
2-K
HALLWAY
2-J
HALLWAY
2-D
HALLWAY
214
CHEMISTRY LAB
213
CHEMISTRY STOCK RM
2-H
STAIRWELL 216
CUST STOR
2-G
ELEVATOR
220
WOMEN'S ROOM
226
MEN'S ROOM
228
CUST RM
280
BDF RM
2-T
STAIRWELL
279
CLASSROOM
229
CLASSROOM
203A
INSTRUMENT RM
213A
OFFICE
203
CHEMISTRY LAB 210
CHEMISTRY LAB
299
CLASSROOM
297
CLASSROOM
281
CHEMISTRY PREP RM
203B
INSTRUMENT RM
2-B
HALLWAY
2-C
STAIRWELL
2-A
STAIRWELL
204
CHEMISTRY LAB
298
OFFICE
296
OFFICE
294
OFFICE
292
OFFICE
291
OFFICE
290
OFFICE
289
OFFICE
287
SEC/ RECEP RM
286
OFFICE
285
OFFICE
282A
CHEM STOCK RM287A
WORK ROOM
2-U
HALLWAY
282
GENERAL CHEM LAB
2-F
HALLWAY
PL403PL403PL403PL403
3333
PL403PL403PL403PL403
4444
PL404PL404PL404PL404
1111
PL404PL404PL404PL404
2222
1111 1111
1111
1111
1111
11111111
1111
1111
1111
1111
1111
1111
2222 2222
3333
2"2"2"2"
4444
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
PL102
Level 02
Plumbing
Remodel Plan
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DRAWING NOTES
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 NO PLUMBNIG WORK IN THIS AREA. PROTECTNO PLUMBNIG WORK IN THIS AREA. PROTECTNO PLUMBNIG WORK IN THIS AREA. PROTECTNO PLUMBNIG WORK IN THIS AREA. PROTECT
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
2222 CONNECT NEW 2" WASTE TO EXISTING 3" WASTECONNECT NEW 2" WASTE TO EXISTING 3" WASTECONNECT NEW 2" WASTE TO EXISTING 3" WASTECONNECT NEW 2" WASTE TO EXISTING 3" WASTE
AT APPROXIMATELY THIS LOCATION. FIELD VERIFYAT APPROXIMATELY THIS LOCATION. FIELD VERIFYAT APPROXIMATELY THIS LOCATION. FIELD VERIFYAT APPROXIMATELY THIS LOCATION. FIELD VERIFY
EXISTING SIZE AND LOCATION.EXISTING SIZE AND LOCATION.EXISTING SIZE AND LOCATION.EXISTING SIZE AND LOCATION.
3333 CONNECT NEW 2" VENT TO EXISTING 2" VENT ATCONNECT NEW 2" VENT TO EXISTING 2" VENT ATCONNECT NEW 2" VENT TO EXISTING 2" VENT ATCONNECT NEW 2" VENT TO EXISTING 2" VENT AT
APPROXIMATELY THIS LOCATION. FIELD VERIFYAPPROXIMATELY THIS LOCATION. FIELD VERIFYAPPROXIMATELY THIS LOCATION. FIELD VERIFYAPPROXIMATELY THIS LOCATION. FIELD VERIFY
EXISTING SIZE AND LOCATION.EXISTING SIZE AND LOCATION.EXISTING SIZE AND LOCATION.EXISTING SIZE AND LOCATION.
4444 CONNECT NEW 1/2" NATURAL GAS AND 1/2"CONNECT NEW 1/2" NATURAL GAS AND 1/2"CONNECT NEW 1/2" NATURAL GAS AND 1/2"CONNECT NEW 1/2" NATURAL GAS AND 1/2"
DOMESTIC COLD WATER TO EXISTING NATURALDOMESTIC COLD WATER TO EXISTING NATURALDOMESTIC COLD WATER TO EXISTING NATURALDOMESTIC COLD WATER TO EXISTING NATURAL
GAS AND DOMESTIC COLD WATER PIPING INGAS AND DOMESTIC COLD WATER PIPING INGAS AND DOMESTIC COLD WATER PIPING INGAS AND DOMESTIC COLD WATER PIPING IN
CEILING SPACE AT APPROXIMATELY THISCEILING SPACE AT APPROXIMATELY THISCEILING SPACE AT APPROXIMATELY THISCEILING SPACE AT APPROXIMATELY THIS
LOCATION. FIELD VERIFY EXISTING SIZE ANDLOCATION. FIELD VERIFY EXISTING SIZE ANDLOCATION. FIELD VERIFY EXISTING SIZE ANDLOCATION. FIELD VERIFY EXISTING SIZE AND
LOCATION.LOCATION.LOCATION.LOCATION.
SCALE:SCALE:SCALE:SCALE:PL102PL102PL102PL102 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
LEVEL 02 PLUMBING REMODEL PLAN1111
(E)FD(E)FD
(E)FS
(E)FS
(E) 6"
(E) 2"
(E) 2"
(E) 2"
(E) 2"
(E) 2"
(E
)
W
C
O
(E) 2"
(E) 2"
(E) 2"
(E) 8" RD
(E) 4" RD
(E) 4" RD
(E) 6"
(E) WCO
(E) 6"
(E) SUMP
PUMP
(E)FD
(E) 2"
(E) 2"
(E) 6"
(E) 6"
(E) 2"
(E) 2"
(E) 2"(E) 2"
(E) 2"
(E) 4"
(E) 4"
(E) 4"
(E) 8" RD
(E) 4" VENT UP
(E) 2"
(E) 2" VENT UP
(E) 2"
(E) 2" VENT UP
(E) 2-1/2"
VENT UP
(E) 2"
(E)FD
K-4330KING STO NC_TO ILETSVITREO US CHINA
K-4330KING STO NC_TO ILETSVITREO US CHINA
K-4330KING STO NC_TO ILETSVITREO US CHINA
K-4330KING STO NC_TO ILETSVITREO US CHINA
K-4989-TFRESHM
A
N
C
_
U
R
I
N
A
L
S
V
I
T
R
E
O
U
S
C
H
I
N
A
K-4989-TFRESHM
A
N
C
_
U
R
I
N
A
L
S
V
I
T
R
E
O
U
S
C
H
I
N
A
K-4330KING STO NC_TO ILETSVITREO US CHINA
K-2196-8PENNING
T
O
N
L
A
V
A
T
O
R
Y
V
I
T
R
E
O
U
S
C
H
I
N
A
K-2196-8PENNING
T
O
N
L
A
V
A
T
O
R
Y
V
I
T
R
E
O
U
S
C
H
I
N
A
K-2196-8PENNING
T
O
N
L
A
V
A
T
O
R
Y
V
I
T
R
E
O
U
S
C
H
I
N
A
K-2196-8PENNING
T
O
N
L
A
V
A
T
O
R
Y
V
I
T
R
E
O
U
S
C
H
I
N
A
K-2196-8PENNING
T
O
N
L
A
V
A
T
O
R
Y
V
I
T
R
E
O
U
S
C
H
I
N
A
AAAA
BBBB
CCCC
DDDD
EEEE
3333 4444 5555 6666 7777
68
CUST RM
67
MECH RM
O-D
ELEVATOR
69
MECHANICAL ROOM
59
COMPUTER LAB
59D
DARK ROOM
59C
VESTIBULE
59E
FILM
51A
STORAGE
51B
CHANGING
0-H
VESTIBULE
51
PHOTO STUDIO
59A
EQUIP / CHECK OUT
59B
STORAGE
57
OFFICE
55
OFFICE
50
CLASSROOM
52C
STORAGE
52
PHYSICS LAB
52B
ACOUSTICS STUDIO
52A
OPTICS LAB
O-C
HALLWAY
O-A
VESTIBULE
64
WOMEN'S RM
66
MEN'S RM
63
STORAGE
O-B
STAIRWELL
1111
2222
3333
5555
6666
7777
8888
9999
4444
3333
1111
1111
1111
1111
1111
1111
2222
2222
2222
2222
6666
3333
3333
3333 PPPP----4B4B4B4B
PPPP----4A4A4A4A
PPPP----4D4D4D4D
6666
6666
6666
6666
6666
6666
6666
6666
6666
6666 6666
6666 6666
6666 6666
6666
6666
6666
66666666
6666
6666
6666
6666
7777
7777
7777
7777
7777
7777
2"2"2"2"
3"3"3"3"6666
9999
2"2"2"2"
2"2"2"2"
2"2"2"2"
9999
8888
2"2"2"2"
2"2"2"2"
9999
8888
3333
PPPP----7777
6666
2"2"2"2"WCOWCOWCOWCOPPPP----4C4C4C4C
FDFDFDFD----1111
FDFDFDFD----1111
2"2"2"2"
2"2"2"2"
PPPP----5555
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
PL401
Enlarged
Level 00
Plumbing
Remodel Plan
- Waste &
Vent
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
00002.52.52.52.55555 5555 10101010
DRAWING NOTES
SCALE:SCALE:SCALE:SCALE:PL401PL401PL401PL401 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ENLARGED LEVEL 00 PLUMBING REMODEL PLAN -WASTE & VENT1111
NOTE
# DESCRIPTION
1111 EXISTING WATER CLOSET AND/OR URINAL TOEXISTING WATER CLOSET AND/OR URINAL TOEXISTING WATER CLOSET AND/OR URINAL TOEXISTING WATER CLOSET AND/OR URINAL TO
REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.
2222 EXISTING LAVATORY TO REMAIN. PROTECTEXISTING LAVATORY TO REMAIN. PROTECTEXISTING LAVATORY TO REMAIN. PROTECTEXISTING LAVATORY TO REMAIN. PROTECT
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
3333 EXISTING FLOOR DRAIN AND/OR FLOOR SINK TOEXISTING FLOOR DRAIN AND/OR FLOOR SINK TOEXISTING FLOOR DRAIN AND/OR FLOOR SINK TOEXISTING FLOOR DRAIN AND/OR FLOOR SINK TO
REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.
4444 CONNECT NEW 3" WASTE TO EXISTING WASTE ATCONNECT NEW 3" WASTE TO EXISTING WASTE ATCONNECT NEW 3" WASTE TO EXISTING WASTE ATCONNECT NEW 3" WASTE TO EXISTING WASTE AT
APPROXIMATELY THIS LOCATION. FIELD VERIFYAPPROXIMATELY THIS LOCATION. FIELD VERIFYAPPROXIMATELY THIS LOCATION. FIELD VERIFYAPPROXIMATELY THIS LOCATION. FIELD VERIFY
EXACT LOCATION.EXACT LOCATION.EXACT LOCATION.EXACT LOCATION.
5555 EXISTING SUMP PUMP TO REMAIN. PROTECTEXISTING SUMP PUMP TO REMAIN. PROTECTEXISTING SUMP PUMP TO REMAIN. PROTECTEXISTING SUMP PUMP TO REMAIN. PROTECT
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
6666 CAP AND ABANDON EXISTING WASTE BELOWCAP AND ABANDON EXISTING WASTE BELOWCAP AND ABANDON EXISTING WASTE BELOWCAP AND ABANDON EXISTING WASTE BELOW
FLOOR.FLOOR.FLOOR.FLOOR.
NOTE
# DESCRIPTION
7777 CAP AND ABANDON EXISTING VENT PIPING INCAP AND ABANDON EXISTING VENT PIPING INCAP AND ABANDON EXISTING VENT PIPING INCAP AND ABANDON EXISTING VENT PIPING IN
CEILING SPACE.CEILING SPACE.CEILING SPACE.CEILING SPACE.
8888 CONNECT NEW 2" WASTE TO EXISTING WASTE ATCONNECT NEW 2" WASTE TO EXISTING WASTE ATCONNECT NEW 2" WASTE TO EXISTING WASTE ATCONNECT NEW 2" WASTE TO EXISTING WASTE AT
APPROXIMATELY THIS LOCATION. FIELD VERIFYAPPROXIMATELY THIS LOCATION. FIELD VERIFYAPPROXIMATELY THIS LOCATION. FIELD VERIFYAPPROXIMATELY THIS LOCATION. FIELD VERIFY
EXACT LOCATION.EXACT LOCATION.EXACT LOCATION.EXACT LOCATION.
9999 CONNECT NEW 2" VENT TO EXISTING VENT PIPINGCONNECT NEW 2" VENT TO EXISTING VENT PIPINGCONNECT NEW 2" VENT TO EXISTING VENT PIPINGCONNECT NEW 2" VENT TO EXISTING VENT PIPING
AT APPROXIMATELY THIS LOCATION. FIELD VERIFYAT APPROXIMATELY THIS LOCATION. FIELD VERIFYAT APPROXIMATELY THIS LOCATION. FIELD VERIFYAT APPROXIMATELY THIS LOCATION. FIELD VERIFY
EXACT LOCATION.EXACT LOCATION.EXACT LOCATION.EXACT LOCATION.
G
G
G
G G G
G
G
G
DW
(E) 1/2"
(E) 1-1/2"
(E) 1"
(E) 1-1/2"
(E) 1-1/2"
(E) 1-1/4"
(E) 3/4"
(E) 1-1/2"
(E) 3"
(E) 3/4"
(E) 3/4"
(E) 3/4"
(E) 3/4"
(E) 3"
(E) 1-1/4"
(E) 3/4"
(E) 1-1/2"
(E) 1-1/2"
(E) 3/4"(E) 3/4"(E) 3/4"
(E) 3/4"
(E) 3/4" GAS
FROM ABOVE
(E) 1-1/4"
(E) 3"
(E)WH
(E) 3/4"
(E)WH
(E)WH
(E) 3/4"
(E) 3/4"
K-4330KING STO NC_TO ILETSVITREO US CHINA
K-4330KING STO NC_TO ILETSVITREO US CHINA
K-4330KING STO NC_TO ILETSVITREO US CHINA
K-4330KING STO NC_TO ILETSVITREO US CHINA
K-4989-TFRESHM
A
N
C
_
U
R
I
N
A
L
S
V
I
T
R
E
O
U
S
C
H
I
N
A
K-4989-TFRESHM
A
N
C
_
U
R
I
N
A
L
S
V
I
T
R
E
O
U
S
C
H
I
N
A
K-4330KING STO NC_TO ILETSVITREO US CHINA
K-2196-8PENNING
T
O
N
L
A
V
A
T
O
R
Y
V
I
T
R
E
O
U
S
C
H
I
N
A
K-2196-8PENNING
T
O
N
L
A
V
A
T
O
R
Y
V
I
T
R
E
O
U
S
C
H
I
N
A
K-2196-8PENNING
T
O
N
L
A
V
A
T
O
R
Y
V
I
T
R
E
O
U
S
C
H
I
N
A
K-2196-8PENNING
T
O
N
L
A
V
A
T
O
R
Y
V
I
T
R
E
O
U
S
C
H
I
N
A
K-2196-8PENNING
T
O
N
L
A
V
A
T
O
R
Y
V
I
T
R
E
O
U
S
C
H
I
N
A
A
A
A A A
A
A
A
AAAA
BBBB
CCCC
DDDD
EEEE
3333 4444 5555 6666 7777
68
CUST RM
67
MECH RM
O-D
ELEVATOR
69
MECHANICAL ROOM
59
COMPUTER LAB
59D
DARK ROOM
59C
VESTIBULE
59E
FILM
51A
STORAGE
51B
CHANGING 0-H
VESTIBULE
51
PHOTO STUDIO
59A
EQUIP / CHECK OUT
59B
STORAGE
57
OFFICE
55
OFFICE
50
CLASSROOM
52C
STORAGE
52
PHYSICS LAB
52B
ACOUSTICS STUDIO
52A
OPTICS LAB
O-C
HALLWAY
O-A
VESTIBULE
64
WOMEN'S RM
66
MEN'S RM
63
STORAGE
O-B
STAIRWELL
1111
2222
3333
4444
5555
1111
1111 1111
1111
1111
1111
2222
2222
2222
2222
CAPCAPCAPCAP CAPCAPCAPCAP
CAPCAPCAPCAP
CAPCAPCAPCAP
CAPCAPCAPCAP CAPCAPCAPCAP
CAPCAPCAPCAPCAPCAPCAPCAP
CAPCAPCAPCAP
CAPCAPCAPCAP
CAPCAPCAPCAP
CAPCAPCAPCAP
PPPP----4B4B4B4B
PPPP----4A4A4A4A
PPPP----4D4D4D4D
1/2"1/2"1/2"1/2"
3333
1"1"1"1"
6666
1/2"1/2"1/2"1/2"
3333
CAPCAPCAPCAP
PPPP----7777
PPPP----6666
MVMVMVMV
2222
1"1"1"1"
PPPP----6666
HBHBHBHB----1111
HBHBHBHB----2222
1/2" DI1/2" DI1/2" DI1/2" DI
DI
DIDIDI
DI
DIDIDI
1/2"1/2"1/2"1/2"
DIDIDIDIDIDIDIDIDIDIDIDIDIDIDIDI
1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"
1/2" DI1/2" DI1/2" DI1/2" DI
7777
8888
PPPP----4C4C4C4C
DI
DIDIDI
1/2"1/2"1/2"1/2"
3333
8888
9999
9999 9999
9999
9999
9999
9999
9999
9999
PPPP----5555
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
PL402
Enlarged
Level 00
Plumbing
Remodel Plan
- Water & Gas
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
00002.52.52.52.55555 5555 10101010
DRAWING NOTES
SCALE:SCALE:SCALE:SCALE:PL402PL402PL402PL402 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ENLARGED LEVEL 00 PLUMBING REMODEL PLAN -WATER & GAS1111
NOTE
# DESCRIPTION
1111 EXISTING WATER CLOSET AND/OR URINAL TOEXISTING WATER CLOSET AND/OR URINAL TOEXISTING WATER CLOSET AND/OR URINAL TOEXISTING WATER CLOSET AND/OR URINAL TO
REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.REMAIN. PROTECT DURING CONSTRUCTION.
2222 EXISTING LAVATORY TO REMAIN. PROTECTEXISTING LAVATORY TO REMAIN. PROTECTEXISTING LAVATORY TO REMAIN. PROTECTEXISTING LAVATORY TO REMAIN. PROTECT
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
3333 CONNECT NEW 1/2" DCW AND 1/2" DHW TOCONNECT NEW 1/2" DCW AND 1/2" DHW TOCONNECT NEW 1/2" DCW AND 1/2" DHW TOCONNECT NEW 1/2" DCW AND 1/2" DHW TO
EXISTING DCW AND DHW AT APPROXIMATELY THISEXISTING DCW AND DHW AT APPROXIMATELY THISEXISTING DCW AND DHW AT APPROXIMATELY THISEXISTING DCW AND DHW AT APPROXIMATELY THIS
LOCATION. FIELD VERIFY EXACT LOCATION.LOCATION. FIELD VERIFY EXACT LOCATION.LOCATION. FIELD VERIFY EXACT LOCATION.LOCATION. FIELD VERIFY EXACT LOCATION.
4444 MOUNT HOT AND COLD HOSE BIBBS ON WALLMOUNT HOT AND COLD HOSE BIBBS ON WALLMOUNT HOT AND COLD HOSE BIBBS ON WALLMOUNT HOT AND COLD HOSE BIBBS ON WALL
UNDER LAB SINK.UNDER LAB SINK.UNDER LAB SINK.UNDER LAB SINK.
5555 RELOCATE EXISTING REDUCED PRESSURERELOCATE EXISTING REDUCED PRESSURERELOCATE EXISTING REDUCED PRESSURERELOCATE EXISTING REDUCED PRESSURE
PRINCIPLE BACK FLOW PREVENTER ANDPRINCIPLE BACK FLOW PREVENTER ANDPRINCIPLE BACK FLOW PREVENTER ANDPRINCIPLE BACK FLOW PREVENTER AND
ASSOCIATED PRV, VALVING, PIPING ANDASSOCIATED PRV, VALVING, PIPING ANDASSOCIATED PRV, VALVING, PIPING ANDASSOCIATED PRV, VALVING, PIPING AND
CHEMICAL SOAP DISPENSER TO THIS LOCATION.CHEMICAL SOAP DISPENSER TO THIS LOCATION.CHEMICAL SOAP DISPENSER TO THIS LOCATION.CHEMICAL SOAP DISPENSER TO THIS LOCATION.
CONNECT TO NEW WATER PIPING AS REQUIRED.CONNECT TO NEW WATER PIPING AS REQUIRED.CONNECT TO NEW WATER PIPING AS REQUIRED.CONNECT TO NEW WATER PIPING AS REQUIRED.
SEE DETAIL 8/PL501.SEE DETAIL 8/PL501.SEE DETAIL 8/PL501.SEE DETAIL 8/PL501.
NOTE
# DESCRIPTION
6666 CONNECT NEW 1" DCW AND 1" DHW TO EXISTINGCONNECT NEW 1" DCW AND 1" DHW TO EXISTINGCONNECT NEW 1" DCW AND 1" DHW TO EXISTINGCONNECT NEW 1" DCW AND 1" DHW TO EXISTING
DCW AND DHW AT APPROXIMATELY THISDCW AND DHW AT APPROXIMATELY THISDCW AND DHW AT APPROXIMATELY THISDCW AND DHW AT APPROXIMATELY THIS
LOCATION. FIELD VERIFY EXACT LOCATION.LOCATION. FIELD VERIFY EXACT LOCATION.LOCATION. FIELD VERIFY EXACT LOCATION.LOCATION. FIELD VERIFY EXACT LOCATION.
7777 DROP 1/2" DEIONIZED WATER DOWN FROM LEVELDROP 1/2" DEIONIZED WATER DOWN FROM LEVELDROP 1/2" DEIONIZED WATER DOWN FROM LEVELDROP 1/2" DEIONIZED WATER DOWN FROM LEVEL
ABOVE AND ROUTE AS SHOWN.ABOVE AND ROUTE AS SHOWN.ABOVE AND ROUTE AS SHOWN.ABOVE AND ROUTE AS SHOWN.
8888 DROP 1/2" DEIONIZED WATER DOWN IN WALL ANDDROP 1/2" DEIONIZED WATER DOWN IN WALL ANDDROP 1/2" DEIONIZED WATER DOWN IN WALL ANDDROP 1/2" DEIONIZED WATER DOWN IN WALL AND
CONNECT TO DEIONIZED WATER SPOUT.CONNECT TO DEIONIZED WATER SPOUT.CONNECT TO DEIONIZED WATER SPOUT.CONNECT TO DEIONIZED WATER SPOUT.
9999 DEIONIZED WATER PIPING AND ASSOCIATEDDEIONIZED WATER PIPING AND ASSOCIATEDDEIONIZED WATER PIPING AND ASSOCIATEDDEIONIZED WATER PIPING AND ASSOCIATED
FAUCET AND VALVING ARE PART OF ADD.FAUCET AND VALVING ARE PART OF ADD.FAUCET AND VALVING ARE PART OF ADD.FAUCET AND VALVING ARE PART OF ADD.
ALTERNATE #5.ALTERNATE #5.ALTERNATE #5.ALTERNATE #5.
(E)4"
(E)FD
(E)3"
(E) 2"
VENT UP
(E)CO
LEADER DN.
(E)4" RD
K-6716BANNO NC_SINKSCAST IRO N
(E)3" WASTE
DOWN, (E)3" VTR
(E)FD (E)FD
(E)3"VTR
(E)4"VTR
(E)FD
(E)3"VTR(E)4" RD
LEADER DN.
(E)3" VTR
(E)2" VENT
FROM BELOW
(E)2"
K-6716BANNO NC_SINKSCAST IRO N
EEEE
FFFF
4444 5555
136
UNISEX RM
134
MEN'S RM
132
WOMEN'S RM
1111
4444 33335555
PPPP----3333
PPPP----1B1B1B1B
PPPP----3333
PPPP----3333 PPPP----2A2A2A2A
PPPP----2A2A2A2A
PPPP----2B2B2B2B
PPPP----1A1A1A1A
PPPP----1A1A1A1A
PPPP----1A1A1A1A
PPPP----1A1A1A1A
PPPP----1A1A1A1A PPPP----3333
PPPP----3333
5555
5555
4444
5555
3333
3333
55553333
5555
3333
EEEE
FFFF
4444 5555
136
UNISEX RM
134
MEN'S RM
132
WOMEN'S RM
6666
PPPP----3333
PPPP----1B1B1B1B
PPPP----3333
PPPP----3333 PPPP----2A2A2A2A
PPPP----2A2A2A2A
PPPP----2B2B2B2B
PPPP----1A1A1A1A
PPPP----1A1A1A1A
PPPP----1A1A1A1A
PPPP----1A1A1A1A
PPPP----1A1A1A1A PPPP----3333
PPPP----3333
6666
6666 WHAWHAWHAWHA----BBBB
1111----1/2"1/2"1/2"1/2"
1111----1/2"1/2"1/2"1/2"
10101010
9999
6666
10101010
2"2"2"2"
2"2"2"2"
WHAWHAWHAWHA----CCCC
9999
EEEE
FFFF
4444 5555
228
CUST RM
226
MEN'S ROOM
220
WOMEN'S ROOM
2-G
ELEVATOR
1111
4444
PPPP----3333
PPPP----3333
PPPP----2B2B2B2B
PPPP----2A2A2A2A
PPPP----2A2A2A2A
PPPP----1A1A1A1A
PPPP----1A1A1A1A
PPPP----1A1A1A1A
PPPP----1A1A1A1A
PPPP----1A1A1A1A
PPPP----3333
PPPP----3333
NEW 2" VENTNEW 2" VENTNEW 2" VENTNEW 2" VENT
FROM BELOWFROM BELOWFROM BELOWFROM BELOW
NEW 2" VENTNEW 2" VENTNEW 2" VENTNEW 2" VENT
FROM BELOWFROM BELOWFROM BELOWFROM BELOW
NEW 2" VENTNEW 2" VENTNEW 2" VENTNEW 2" VENT
FROM BELOWFROM BELOWFROM BELOWFROM BELOW
2222
NEW 2" VENTNEW 2" VENTNEW 2" VENTNEW 2" VENT
FROM BELOWFROM BELOWFROM BELOWFROM BELOW
2222
2222
2222
11111111
(E) SERVICE
SINK
EEEE
FFFF
4444 5555
228
CUST RM 226
MEN'S ROOM
220
WOMEN'S ROOM
2-G
ELEVATOR
PPPP----3333
PPPP----3333
PPPP----2B2B2B2B
PPPP----2A2A2A2A
PPPP----2A2A2A2A
PPPP----1A1A1A1A
PPPP----1A1A1A1A
PPPP----1A1A1A1A
PPPP----1A1A1A1A
PPPP----1A1A1A1A
PPPP----3333
PPPP----3333
7777
8888
8888
8888
7777
11111111
(E) SERVICE
SINK
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
PL403
Enlarged
Plumbing
Remodel
Plans
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
00002.52.52.52.55555 5555 10101010
DRAWING NOTES
NOTE
# DESCRIPTION
1111 EXISTING ROOF DRAIN TO REMAIN. PROTECTEXISTING ROOF DRAIN TO REMAIN. PROTECTEXISTING ROOF DRAIN TO REMAIN. PROTECTEXISTING ROOF DRAIN TO REMAIN. PROTECT
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
2222 CONNECT NEW 2" VENT TO EXISTING VENTCONNECT NEW 2" VENT TO EXISTING VENTCONNECT NEW 2" VENT TO EXISTING VENTCONNECT NEW 2" VENT TO EXISTING VENT
THROUGH ROOF AT APPROXIMATELY THISTHROUGH ROOF AT APPROXIMATELY THISTHROUGH ROOF AT APPROXIMATELY THISTHROUGH ROOF AT APPROXIMATELY THIS
LOCATION. FIELD VERIFY EXACT LOCATION.LOCATION. FIELD VERIFY EXACT LOCATION.LOCATION. FIELD VERIFY EXACT LOCATION.LOCATION. FIELD VERIFY EXACT LOCATION.
3333 RISE 2" VENT UP TO LEVEL ABOVE.RISE 2" VENT UP TO LEVEL ABOVE.RISE 2" VENT UP TO LEVEL ABOVE.RISE 2" VENT UP TO LEVEL ABOVE.
4444 PROTECT EXISTING VENT RISE DURINGPROTECT EXISTING VENT RISE DURINGPROTECT EXISTING VENT RISE DURINGPROTECT EXISTING VENT RISE DURING
CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.
5555 CONNECT NEW WASTE TO EXISTING WASTE BELOWCONNECT NEW WASTE TO EXISTING WASTE BELOWCONNECT NEW WASTE TO EXISTING WASTE BELOWCONNECT NEW WASTE TO EXISTING WASTE BELOW
FLOOR AT APPROXIMATELY THIS LOCATION. FIELDFLOOR AT APPROXIMATELY THIS LOCATION. FIELDFLOOR AT APPROXIMATELY THIS LOCATION. FIELDFLOOR AT APPROXIMATELY THIS LOCATION. FIELD
VERIFY EXACT LOCATION.VERIFY EXACT LOCATION.VERIFY EXACT LOCATION.VERIFY EXACT LOCATION.
6666 CONNECT NEW DCW AND/OR DHW PIPING TOCONNECT NEW DCW AND/OR DHW PIPING TOCONNECT NEW DCW AND/OR DHW PIPING TOCONNECT NEW DCW AND/OR DHW PIPING TO
EXISTING IN CEILING SPACE AND ROUTE TO NEWEXISTING IN CEILING SPACE AND ROUTE TO NEWEXISTING IN CEILING SPACE AND ROUTE TO NEWEXISTING IN CEILING SPACE AND ROUTE TO NEW
FIXTURE. FIELD VERIFY EXACT LOCATION.FIXTURE. FIELD VERIFY EXACT LOCATION.FIXTURE. FIELD VERIFY EXACT LOCATION.FIXTURE. FIELD VERIFY EXACT LOCATION.
7777 RISE NEW DCW AND DHW PIPING UP FROM LEVELRISE NEW DCW AND DHW PIPING UP FROM LEVELRISE NEW DCW AND DHW PIPING UP FROM LEVELRISE NEW DCW AND DHW PIPING UP FROM LEVEL
BELOW AND CONNECT TO FIXTURE.BELOW AND CONNECT TO FIXTURE.BELOW AND CONNECT TO FIXTURE.BELOW AND CONNECT TO FIXTURE.
8888 RISE NEW DCW PIPING UP FROM LEVEL BELOWRISE NEW DCW PIPING UP FROM LEVEL BELOWRISE NEW DCW PIPING UP FROM LEVEL BELOWRISE NEW DCW PIPING UP FROM LEVEL BELOW
AND CONNECT TO FIXTURE.AND CONNECT TO FIXTURE.AND CONNECT TO FIXTURE.AND CONNECT TO FIXTURE.
9999 SEE ARCHITECTURAL PLAN FOR WATER HAMMERSEE ARCHITECTURAL PLAN FOR WATER HAMMERSEE ARCHITECTURAL PLAN FOR WATER HAMMERSEE ARCHITECTURAL PLAN FOR WATER HAMMER
ARRESTOR ACCESS DOOR IN WALL.ARRESTOR ACCESS DOOR IN WALL.ARRESTOR ACCESS DOOR IN WALL.ARRESTOR ACCESS DOOR IN WALL.
10101010 CONNECT NEW DCW PIPING TO EXISTING DCW INCONNECT NEW DCW PIPING TO EXISTING DCW INCONNECT NEW DCW PIPING TO EXISTING DCW INCONNECT NEW DCW PIPING TO EXISTING DCW IN
CHASE SPACE. FIELD VERIFY EXACT LOCATION.CHASE SPACE. FIELD VERIFY EXACT LOCATION.CHASE SPACE. FIELD VERIFY EXACT LOCATION.CHASE SPACE. FIELD VERIFY EXACT LOCATION.
11111111 NO PLUMBING WORK IN THIS AREA. PROTECTNO PLUMBING WORK IN THIS AREA. PROTECTNO PLUMBING WORK IN THIS AREA. PROTECTNO PLUMBING WORK IN THIS AREA. PROTECT
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
SCALE:SCALE:SCALE:SCALE:PL403PL403PL403PL403 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ENLARGED LEVEL 01 PLUMBING REMODEL PLAN -WASTE & VENT1111
SCALE:SCALE:SCALE:SCALE:PL403PL403PL403PL403 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ENLARGED LEVEL 01 PLUMBING REMODEL PLAN -WATER2222
00002.52.52.52.55555 5555 10101010
SCALE:SCALE:SCALE:SCALE:PL403PL403PL403PL403 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ENLARGED LEVEL 02 PLUMBING REMODEL PLAN -WASTE & VENT3333
SCALE:SCALE:SCALE:SCALE:PL403PL403PL403PL403 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ENLARGED LEVEL 02 PLUMBING REMODEL PLAN -WATER4444
00002.52.52.52.55555 5555 10101010
00002.52.52.52.55555 5555 10101010
1111
CCCC
DDDD
EEEE
2222 3333
272
BIO-CHEMISTRY LAB
PPPP----4D4D4D4D
PPPP----4B4B4B4B
PPPP----7777
FDFDFDFD----1111
2"2"2"2"
2"2"2"2"2"2"2"2"
2"2"2"2"
2"2"2"2"
2"2"2"2"2"2"2"2"
1111 1111 1111
1111
CCCC
DDDD
EEEE
2222 3333
272
BIO-CHEMISTRY LAB
PPPP----4D4D4D4D
PPPP----6666
MVMVMVMV
22221"1"1"1"
PPPP----4B4B4B4B
PPPP----6666
PPPP----7777
2222
3333
4444
1/2"1/2"1/2"1/2"
DIDIDIDI
DI
DIDIDI
1"1"1"1"1"1"1"1"
DI
DIDIDI
DI
DIDIDI
1/2"1/2"1/2"1/2"
4444
CACACACA CACACACA
3/4"3/4"3/4"3/4"
CACACACA
CACACACA
1/2"1/2"1/2"1/2"
1/2"1/2"1/2"1/2"
1111 1111
5555
6666
7777
8888 8888
PPPP----8888
PPPP----9999
CACACACA
GGGG
1/2"1/2"1/2"1/2"
9999
10101010
11111111
12121212
10101010
101010101111----1/4"1/4"1/4"1/4"
1111----1/4"1/4"1/4"1/4"
3/4"3/4"3/4"3/4"
13131313
13131313
13131313 13131313
13131313
13131313
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
PL404
Enlarged
Plumbing
Remodel
Plans
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
DRAWING NOTES
00002.52.52.52.55555 5555 10101010
NOTE
# DESCRIPTION
1111 SEE PL102 FOR CONTINUATION.SEE PL102 FOR CONTINUATION.SEE PL102 FOR CONTINUATION.SEE PL102 FOR CONTINUATION.
2222 CONNECT 1" DCW, 1" DHW AND 1/2" DEIONIZEDCONNECT 1" DCW, 1" DHW AND 1/2" DEIONIZEDCONNECT 1" DCW, 1" DHW AND 1/2" DEIONIZEDCONNECT 1" DCW, 1" DHW AND 1/2" DEIONIZED
WATER AT APPROXIMATELY THIS LOCATION. FIELDWATER AT APPROXIMATELY THIS LOCATION. FIELDWATER AT APPROXIMATELY THIS LOCATION. FIELDWATER AT APPROXIMATELY THIS LOCATION. FIELD
VERIFY EXACT LOCATION AND SIZE OF EXISTING.VERIFY EXACT LOCATION AND SIZE OF EXISTING.VERIFY EXACT LOCATION AND SIZE OF EXISTING.VERIFY EXACT LOCATION AND SIZE OF EXISTING.
3333 DROP 1/2" DEIONIZED WATER DOWN IN WALL TODROP 1/2" DEIONIZED WATER DOWN IN WALL TODROP 1/2" DEIONIZED WATER DOWN IN WALL TODROP 1/2" DEIONIZED WATER DOWN IN WALL TO
LEVEL BELOW. SEE PL402 FOR CONTINUATION.LEVEL BELOW. SEE PL402 FOR CONTINUATION.LEVEL BELOW. SEE PL402 FOR CONTINUATION.LEVEL BELOW. SEE PL402 FOR CONTINUATION.
4444 DROP 1/2" DEIONIZED WATER DOWN IN WALL ANDDROP 1/2" DEIONIZED WATER DOWN IN WALL ANDDROP 1/2" DEIONIZED WATER DOWN IN WALL ANDDROP 1/2" DEIONIZED WATER DOWN IN WALL AND
CONNECT TO DEIONIZED WATER SPOUT.CONNECT TO DEIONIZED WATER SPOUT.CONNECT TO DEIONIZED WATER SPOUT.CONNECT TO DEIONIZED WATER SPOUT.
5555 CONNECT NEW 1/2" GAS AND 1/2" AIR TOCONNECT NEW 1/2" GAS AND 1/2" AIR TOCONNECT NEW 1/2" GAS AND 1/2" AIR TOCONNECT NEW 1/2" GAS AND 1/2" AIR TO
EXISTING BELOW COUNTER. ROUTE UNDEREXISTING BELOW COUNTER. ROUTE UNDEREXISTING BELOW COUNTER. ROUTE UNDEREXISTING BELOW COUNTER. ROUTE UNDER
COUNTER AS SHOWN TO NEW GAS NOZZLES.COUNTER AS SHOWN TO NEW GAS NOZZLES.COUNTER AS SHOWN TO NEW GAS NOZZLES.COUNTER AS SHOWN TO NEW GAS NOZZLES.
FIELD VERIFY.FIELD VERIFY.FIELD VERIFY.FIELD VERIFY.
6666 CONNECT NEW 3/4" COMPRESSED AIR TOCONNECT NEW 3/4" COMPRESSED AIR TOCONNECT NEW 3/4" COMPRESSED AIR TOCONNECT NEW 3/4" COMPRESSED AIR TO
EXISTING IN CEILING SPACE AT APPROXIMATELYEXISTING IN CEILING SPACE AT APPROXIMATELYEXISTING IN CEILING SPACE AT APPROXIMATELYEXISTING IN CEILING SPACE AT APPROXIMATELY
THIS LOCATION. FIELD VERIFY EXACT LOCATION.THIS LOCATION. FIELD VERIFY EXACT LOCATION.THIS LOCATION. FIELD VERIFY EXACT LOCATION.THIS LOCATION. FIELD VERIFY EXACT LOCATION.
7777 DROP 1/2" COMPRESSED AIR DOWN ON WALL TODROP 1/2" COMPRESSED AIR DOWN ON WALL TODROP 1/2" COMPRESSED AIR DOWN ON WALL TODROP 1/2" COMPRESSED AIR DOWN ON WALL TO
48" A.F.F. TERMINATE WITH QUICK DISCONNECT48" A.F.F. TERMINATE WITH QUICK DISCONNECT48" A.F.F. TERMINATE WITH QUICK DISCONNECT48" A.F.F. TERMINATE WITH QUICK DISCONNECT
FOR FUTURE CONNECTION.FOR FUTURE CONNECTION.FOR FUTURE CONNECTION.FOR FUTURE CONNECTION.
8888 DROP 1/2" COMPRESSED AIR, 1/2" NATURAL GASDROP 1/2" COMPRESSED AIR, 1/2" NATURAL GASDROP 1/2" COMPRESSED AIR, 1/2" NATURAL GASDROP 1/2" COMPRESSED AIR, 1/2" NATURAL GAS
AND 1/2" DOMESTIC COLD WATER DOWN IN WALLAND 1/2" DOMESTIC COLD WATER DOWN IN WALLAND 1/2" DOMESTIC COLD WATER DOWN IN WALLAND 1/2" DOMESTIC COLD WATER DOWN IN WALL
AND CONNECT INTO RELOCATED FUME HOODS.AND CONNECT INTO RELOCATED FUME HOODS.AND CONNECT INTO RELOCATED FUME HOODS.AND CONNECT INTO RELOCATED FUME HOODS.
9999 RISE 1/2" COMPRESSED AIR TAKEOFF OFF OF THERISE 1/2" COMPRESSED AIR TAKEOFF OFF OF THERISE 1/2" COMPRESSED AIR TAKEOFF OFF OF THERISE 1/2" COMPRESSED AIR TAKEOFF OFF OF THE
TOP OF THE COMPRESSED AIR LINE.TOP OF THE COMPRESSED AIR LINE.TOP OF THE COMPRESSED AIR LINE.TOP OF THE COMPRESSED AIR LINE.
10101010 ROUTE 1/4" CONTINUOUS FLEXIBLE COPPERROUTE 1/4" CONTINUOUS FLEXIBLE COPPERROUTE 1/4" CONTINUOUS FLEXIBLE COPPERROUTE 1/4" CONTINUOUS FLEXIBLE COPPER
TUBING IN CEILING SPACE AS SHOWN WITHOUTTUBING IN CEILING SPACE AS SHOWN WITHOUTTUBING IN CEILING SPACE AS SHOWN WITHOUTTUBING IN CEILING SPACE AS SHOWN WITHOUT
SEAMS OR JOINTS.SEAMS OR JOINTS.SEAMS OR JOINTS.SEAMS OR JOINTS.
11111111 DROP 1/4" COPPER TUBING DOWN ON WALL.DROP 1/4" COPPER TUBING DOWN ON WALL.DROP 1/4" COPPER TUBING DOWN ON WALL.DROP 1/4" COPPER TUBING DOWN ON WALL.
OWNER TO CONNECT 1/4" COPPER TUBING TOOWNER TO CONNECT 1/4" COPPER TUBING TOOWNER TO CONNECT 1/4" COPPER TUBING TOOWNER TO CONNECT 1/4" COPPER TUBING TO
HYDROGEN, ETHYLENE AND ARGON OWNERHYDROGEN, ETHYLENE AND ARGON OWNERHYDROGEN, ETHYLENE AND ARGON OWNERHYDROGEN, ETHYLENE AND ARGON OWNER
PROVIDED FLOW CONTROL STATION ANDPROVIDED FLOW CONTROL STATION ANDPROVIDED FLOW CONTROL STATION ANDPROVIDED FLOW CONTROL STATION AND
ASSOCIATED TANKS.ASSOCIATED TANKS.ASSOCIATED TANKS.ASSOCIATED TANKS.
12121212 DROP 1/4" COPPER TUBING AND 1/2"DROP 1/4" COPPER TUBING AND 1/2"DROP 1/4" COPPER TUBING AND 1/2"DROP 1/4" COPPER TUBING AND 1/2"
COMPRESSED AIR DOWN ON WALL. OWNER TOCOMPRESSED AIR DOWN ON WALL. OWNER TOCOMPRESSED AIR DOWN ON WALL. OWNER TOCOMPRESSED AIR DOWN ON WALL. OWNER TO
CONNECT HYDROGEN, ETHYLENE, ARGON ANDCONNECT HYDROGEN, ETHYLENE, ARGON ANDCONNECT HYDROGEN, ETHYLENE, ARGON ANDCONNECT HYDROGEN, ETHYLENE, ARGON AND
COMPRESSED AIR TO TUBE FURNACE.COMPRESSED AIR TO TUBE FURNACE.COMPRESSED AIR TO TUBE FURNACE.COMPRESSED AIR TO TUBE FURNACE.
13131313 DEIONIZED WATER PIPING AND ASSOCIATEDDEIONIZED WATER PIPING AND ASSOCIATEDDEIONIZED WATER PIPING AND ASSOCIATEDDEIONIZED WATER PIPING AND ASSOCIATED
FAUCET AND VALVING ARE PART OF ADD.FAUCET AND VALVING ARE PART OF ADD.FAUCET AND VALVING ARE PART OF ADD.FAUCET AND VALVING ARE PART OF ADD.
ALTERNATE #5.ALTERNATE #5.ALTERNATE #5.ALTERNATE #5.
SCALE:SCALE:SCALE:SCALE:PL404PL404PL404PL404 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ENLARGED LEVEL 02 PLUMBING REMODEL PLAN -WASTE & VENT1111
SCALE:SCALE:SCALE:SCALE:PL404PL404PL404PL404 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ENLARGED LEVEL 02 PLUMBING REMODEL PLAN -WATER & GAS2222
00002.52.52.52.55555 5555 10101010
INSERTS OR BEAM /
TRUSS CONNECTION
CINCH ANCHORS
WELDED STEEL
WALL BRACKET
ANGLE
ROD
ADJUSTABLE
PIPE STAND
THRU-BOLT
EYE BOLTS
TURNBUCKLE
U-BOLT
WALL BRACKET
U-BOLTS
STEEL OFFSET
CI
N
C
H
A
N
C
H
O
R
S
EYE BOLT
PIPE CLAMP
ROD
TURNBUCKLE
I-BEAM
STEEL PLATE
BLOCK WALL
CLAMPS
ANGLE
U-BOLTS
ROD
SPLIT RING
CLEVIS HANGER
INSERTS OR BEAM /
TRUSS CONNECTION
C-CLAMP
LOCK NUT
TYP.
STEEL CLEAVIS
TEST TEE
CL
FINISHED WALL SURFACE
PLUG
CLEANOUT
THREADED
COVER PLATE WITH
SECURING SCREW
CENTERLINE
MOUNTING HEIGHT CHART
DESCRIPTION
URINAL
SINK
LAVATORY
GENERAL WALL
LOCATION
NOTE:
12"
12"
48"
HEIGHT
12"
COORDINATE WITH ARCHITECT PRIOR TO
INSTALLING AT A HEIGHT OTHER THAN
THAT LISTED ABOVE.
CLEANOUT TO GRADE (COTG)FLOOR CLEANOUT (FCO)
1/8" BEND IF CLEANOUT
OCCURS AT END OF LINE
LENGTH TO SUIT
CAST IRON WASTE LINE,
1/8" CAST IRON BEND
WASTE LINE
CAST IRON WASTE LINE,
LENGTH TO SUIT
1/8" CAST IRON BEND
OCCURS AT END OF LINE
1/8" BEND IF CLEANOUT
WASTE LINE
COVER. TOP OF COVER
CLEANOUT AND ACCESS
TO BE FLUSH W/ TOP
OF FLOOR
FLOOR LINE
FINISH GRADE
BRASS CLEANOUT PLUG
W/ COUNTER SUNK HEAD.
TROWEL SMOOTH AND EDGE.
16" SQUARE CONCRETE PAD
BODY
SLOPE
NOTE:
GROUT
1-1/4" MIN.
SIMILAR FOR
FLOOR SINKS.
FLOOR DRAIN
SCHEDULE FOR SIZE
DRAIN), SEE PLUMBING
(THREADS INTO FLOOR
DRAINAGE PIPING
FLOOR SLAB
EXISTING 30"x30" 40 MIL. PVC
SHOWER PAN LINER.
TURN DOWN UNDER
DRAIN CLAMP
STRAINER
FLOOR DRAIN
COLLAR
CLAMPING
THAN FIXTURE TOP
OF HOLE 6" LARGER
FINISHED FLOOR. TOP
SLOPE
30"x30"
SLOPE SLOPE
R
W
A
E
T
RT
PA
SEWER
GASES
TRAP PRIMER
VACUUM BREATHER
PORTS.
1/2"
VALVE (TP-1)
COLD WATER MAIN.
1/2"
FIN. FLOOR
FLOOR DRAIN
2X6 BLOCKING IN
WALL FOR WATER
LINE SUPPORT.
PLUMBING FIXTURE
ESCUTCHEON RING
PIPING TO
15101
WALL STUDS
15105
WATER PIPING
GRAVEL
HOT OR COLD
ALL AROUND)
SAND (3" MIN.
CONCRETE FLOOR
"THERMA-CEL"
COMPACTED
PIPE INSULATION
DIRT FILL
3'-0"
5'-0"
6'-0"
SERVICE SINK
SERVICE SINK FAUCET
3/4" DHW AND DCW
FLOOR
1/2" REDUCED PRESSURE
PRINCIPLE BACKFLOW
PREVENTER.
1/2"
PRV SET @ 35
PSI AND 5 GPM.
PRESSURE GUAGE.
1/2" SUPPLY BRANCH,
TYPICAL EACH FLOOR.
HB-2, CONSISTING OF A 1/2"
BALL VALVE, AND 3/4" HOSE
CONNECTION FOR SUPPLY
TO "CUSTODIAL SOLUTION
STATION (N.I.C.)".
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : ????
PL501
Plumbing
Details
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
Bid Set
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
TYPICAL PIPE SUPPORTS DETAIL1111
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
WALL CLEANOUT DETAIL2222
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
CLEANOUT DETAILS3333
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
FLOOR DRAIN IN EXISTING FLOOR DETAIL4444
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
TRAP PRIMER DETAIL5555
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
PIPE SUPPORT DETAIL6666
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
UNDERGROUND PIPE DETAIL7777
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
SERVICE SINK DETAIL8888
CIRCUITING & GENERAL SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
KEYED NOTE REFERENCE1
BRANCH CIRCUIT HOME-RUN TO PANEL INDICATED
A-1,3,5
3/4"C.-6#12,1#12G
QTY & SIZE OF EQUIPMENT GROUND CONDUCTOR
QTY & SIZE OF NEUTRAL AND PHASE CONDUCTOR(S)
SIZE OF CONDUIT
A-1,3,5
3/4"C.-6#12,1#12G
PANEL AND CIRCUIT DESIGNATIONS
EQUIPMENT GROUNDING CONDUCTOR
TICK MARKS
NEUTRAL CONDUCTOR(S)
PHASE AND/OR SWITCH-LEG CONDUCTOR(S)
BRANCH CIRCUIT/FEEDER CONCEALED IN CEILING OR WALL
BRANCH CIRCUIT/FEEDER CONCEALED UNDERGROUND OR FLOOR
NEW EQUIPMENT, DEVICES, ETC.
EXISTING EQUIPMENT, DEVICES, ETC.
DEMOLITION EQUIPMENT, DEVICES, ETC.
DETAIL # / SHEET REFERENCE1 / ES101
*25,000A CALCULATED AVAILABLE FAULT CURRENT AT EQUIPMENT(SEE POWER RISER)
FIRE ALARM SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
DETECTOR SUBSCRIPTS
P PHOTOELECTRIC SMOKE DETECTOR D DUCT SMOKE DETECTOR
ID IN-DUCT SMOKE DETECTOR H HEAT DETECTOR
M MULTI-STATION SMOKE DETECTOR (120V W/BATTERY BACKUP)
M/S MULTI-STATION SMOKE DETECTOR W/VISIBLE STROBE (120V W/BATTERY BACKUP)
M/C MULTI-STATION SMOKE / CARBON MONOXIDE DETECTOR (120V W/BATTERY BACKUP)
FIRE ALARM CONTROL PANEL (WALL MOUNTED, TOP AT 6'-0' AFF)
F
FACP
NOTIFICATION DEVICE EXTENDER PANEL. PROVIDE QTY AS REQUIRED BASED ON DEVICE
VOLTAGE DROP CALC'S PER NFPA 72 REQUIREMENTS. (WALL MOUNTED, TOP AT 5'-0' AFF)
REMOTE ANNUCIATOR PANEL (FLUSH MOUNTED IN WALL AT 5'-0' AFF)
NAC
RA
MANUAL PULL STATION (MOUNTING HEIGHT PER ADA & NFPA 72)
MAGNETIC DOOR HOLD OPEN
ADDRESSABLE CONTROL/RELAY MODULE
MM
CM
ADDRESSABLE MONITORING MODULE
FIRE ALARM FLOW SWITCH
FIRE ALARM TAMPER SWITCH
FS
TS
WALL OR CEILING MOUNTED FIRE ALARM HORN ONLY
WALL MOUNTED FIRE ALARM STROBE OR HORN/STROBE
PROVIDE CANDELA RATING AS REQUIRED BY NFPA 72
#
ADDRESSABLE DETECTOR WITH BASE
EXTERIOR 120V FIRE BELL, INSTALL NEXT TO FDC.
FIRE/SMOKE DAMPER; COORDINATE LOCATIONS WITH MECH. DRAWINGSSD
A. DO NOT INSTALL MORE THAN (10) NOTIFICATION APPLIANCES ON ANY SINGLE CLASS "A" SIGNAL CIRCUIT.
DO NOT EXCEED 400 FT. OF NO. 14 WIRE IN THE TOTAL LOOP.
B. NFPA ALLOWS NOTIFICATION APPLIANCES TO BE MOUNTED AT A HEIGHT RANGE BETWEEN 80" TO 96"
ABOVE FINISH FLOOR. THE PREFERRED HEIGHT IS 80". IF THIS CONFLICTS WITH OTHER TRADES OR ROOM
FURNISHINGS, LOCATE AS CLOSE TO 80" AS POSSIBLE, NOT EXCEEDING 96". ALL NOTIFICATION
APPLIANCES IN A COMMON ROOM OR LINE OF SIGHT SHALL BE LOCATED AT A COMMON HEIGHT.
C. MOUNT PULL STATIONS AT 46-48" A.F.F. TO THE OPERATING HANDLE TO MEET ADA REQUIREMENTS.
D. DO NOT CONNECT THE FIRE ALARM SYSTEM TO ANY DEVICE WHICH HAS A POWER HELD
CONTACTS.(FLOW, TAMPER, HOOD SYSTEM, DUCT DETECTOR, ETC..FALSE ALARM WILL OCCUR.
E. ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALL CONDUCTOR QUANTITIES PER FIRE ALARM
SYSTEM SUPPLIER, AND AS PER NFPA AND NEC REQUIREMENTS.
F. DO NOT INSTALL ANY SMOKE OR HEAT DETECTORS WITHIN 3 FEET OF ANY AIR DIFFUSER.
G. DO NOT EXCEED 2500 FEET ON ANY ADDRESSABLE DEVICE RUN. DO NOT EXCEED 120 DEVICES ON ANY
ONE ADDRESSABLE DEVICE RUN.
H. ALL AIR HANDLING EQUIPMENT 2000 CFM OR MORE MUST BE SHUT DOWN UPON FIRE ALARM AS PER LIFE
SAFETY CODES.
I. ALL CLASS "B" INITIATING CIRCUITS WITH ADDRESSABLE DEVICES NEED EOLR. (END OF LINE RESISTORS).
J. IN CORRIDORS, NOTIFICATION APPLIANCES MUST BE LOCATED WITHIN 15' FROM ENDS OF CORRIDORS
AND A MAXIMUM OF 100' SPACING.
K. NOTIFICATION APPLIANCES TO BE SYNCHRONIZED TO PROVIDE A 3-3-3 TEMPORAL PATTERN.
L. ALL WIRING AND CONDUIT ROUTING TO BE AS DESCRIBED ON SUPPLIED SHOP DRAWINGS. FIRE ALARM
PLAN IS SHOWN FOR GENERAL LOCATION AND LAYOUT ONLY.
M. THE FIRE ALARM SYSTEM TO BE IN COMPLIANCE WITH ALL APPLICABLE LOCAL, STATE AND ADA
REQUIREMENTS.
N. ELECT. CONTR. TO CONNECT SPRINKLER SYSTEM TAMPER SWITCHES AND FLOW VALVES TO FIRE ALARM
SYSTEM AS REQUIRED. SEE FIRE SPRINKLER SYSTEM DRAWINGS FOR EXACT LOCATIONS AND
QUANTITIES.
GENERAL FIRE ALARM SYSTEM NOTES
FIRE ALARM SMOKE DAMPERSD
CEILING MOUNTED FIRE ALARM STROBE OR HORN/STROBE
PROVIDE CANDELA RATING AS REQUIRED BY NFPA 72
LIGHTING SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
PARKING AREA POLE LIGHT, SINGLE OR DOUBLE HEAD AS INDICATED ON
DRAWINGS. REFER TO LIGHT POLE DETAIL FOR POLE INFORMATION.
2X4 FLUORESCENT OR LED FIXTURE
2X2 FLUORESCENT OR LED FIXTURE
SURFACE MOUNTED FLUORESCENT OR LED FIXTURE
STRIP FLUORESCENT OR LED FIXTURE
WALL MOUNTED FLUORESCENT OR LED FIXTURE
EXTERIOR WALL MOUNTED FIXTURE
ROUND RECESSED FIXTURE
SURFACE OR PENDANT FIXTURE
LIGHT FIXTURE SUBSCRIPTS
NL NIGHT-LIGHT(CONNECT TO UNSWITCHED LEG OF CIRCUIT)
EXIT SIGN, WALL OR CEILING MOUNTING AS REQUIRED (SINGLE OR DOUBLE FACE)
DIRECTIONAL CHEVRONS AS INDICATED; CONNECT TO UNSWITCHED LEG OF LIGHTING
CIRCUIT THAT IS IN THE SAME AREA AS THE EXIT SIGNS.
SHADED FIXTURE INDICATES AN EMERGENCY FIXTURE. PROVIDE WITH EMERG. BATTERY
PACK OR CONNECT TO EMERGENCY POWER SYSTEM (WHERE APPLICABLE). CONNECT
BATTERY PACK TO UNSWITCHED LEG OF LIGHTING CIRCUIT THAT SERVES THE SAME
AREA AS THE EMERGENCY FIXTURE. PROVIDE WITH TEST LIGHT AND SWITCH.
CEILING MOUNTED OCCUPANCY SENSOR, REFER TO OCCUPANCY SENSOR/SWITCH
SCHEDULE FOR SENSOR TYPE AND ADDITIONAL INFORMATION.
SWITCH MOUNTED OCCUPANCY SENSOR, LOW VOLTAGE SWITCHPOD OR DIMMER
SWITCH, REFER TO OCCUPANCY SENSOR/SWITCH SCHEDULE FOR TYPE AND
ADDITIONAL INFORMATION.
SINGLE-POLE SWITCH (SEE SUB-SCRIPTS BELOW FOR ADDITIONAL INFORMATION)
SWITCH SUBSCRIPTS
3 3-WAY SWITCH
4 4-WAY SWITCH
D DIMMER SWITCH (COMPATIBLE W/ LOAD & LTG TYPES)
F 7-DAY PROGRAMMABLE TIMER SWITCH
(INTERMATIC MODEL EI500WC SERIES)
P PILOT LIGHTED SWITCH
F1 LIGHT FIXTURE TYPE DESIGNATION
S
###
WALL OR CEILING MOUNTED EMERGENCY LIGHTING UNIT W/BATTERY PACK
CONNECT TO UNSWITCHED LEG OF LIGHTING CIRCUIT THAT IS IN THE SAME AREA AS
THE EMERGENCY LIGHT.
LV LOW-VOLTAGE SWITCH (PER DWG'S)
T THERMAL-OVERLOAD SWITCH
M SWITCH SUPPLIED WITH EQUIPMENT,
INSTALLED BY E.C.
WP WEATHERPROOF
2P DOUBLE POLE, SINGLE THROW SWITCH
GENERAL LIGHTING NOTES:
A. SYMBOLS SHOWN ABOVE MAY NOT REPRESENT ALL LIGHT FIXTURES USED ON PROJECT, REFER TO
LIGHT FIXTURE SCHEDULE FOR ACTUAL FIXTURE INFORMATION INCLUDING FIXTURE TYPE, LAMPING,
MOUNTING AND ETC.
B. JUNCTION BOXES FOR LIGHTING CIRCUITING ARE NOT SHOWN FOR CLARITY. THE E.C. IS RESPONSIBLE
FOR PROVIDING AND INSTALLING ALL JUNCTION BOXES REQUIRED FOR CIRCUITING OF ALL LIGHT
FIXTURES THAT ARE NOT LISTED FOR "THROUGH-BRANCH CIRCUIT WIRING".
C. IN GENERAL ALL SWITCH-LEG CONDUCTORS MAY NOT BE SHOWN ON DRAWINGS; E.C. SHALL PROVIDE
AND INSTALL CONDUCTORS AS REQUIRED TO ACHIEVE CONTROL SCHEMES INDICATED AND
DESCRIBED ON DRAWINGS. INCLUDING ALL 0 -10V DIMMING CONTROLS BETWEEN SWITCH AND
FIXTURES.
D. ALL BATTERY EXIT SIGNS AND EMERGENCY LIGHTING TO BE CONNECTED TO THE UNSWITCHED LEG OF
THE LIGHTING CIRCUIT IN THE AREA.
###
F
M
POW ER SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
ELECTRICAL SWITCHBOARD EQUIPMENT, (SEE POWER RISER AND PANEL SCHEDULES
FOR ADDITIONAL INFORMATION)
'MSB'
'T##'DRY-TYPE TRANSFORMER, (SEE POWER RISER FOR ADDITIONAL INFORMATION)
'LA'
ELECTRICAL PANELBOARD, (SEE POWER RISER AND PANEL SCHEDULES
FOR ADDITIONAL INFORMATION)
DISCONNECT SWITCH, SIZE/POLES/TYPE AS INDICATED
TYPES: 1=NEMA 1, 3R=NEMA 3R, 4X=NEMA 4X
FUSED DISCONNECT SWITCH, SIZE/POLES/TYPE AS INDICATED
TYPES: 1=NEMA 1, 3R=NEMA 3R, 4X=NEMA 4X
COMBINATION STARTER & FUSED DISCONNECT SWITCH, SIZE/POLES/TYPE AS INDICATED.
TYPES: 1=NEMA 1, 3R=NEMA 3R, 4X=NEMA 4X
J
JUNCTION BOX
CR = CORD REEL; SEE DRAWINGS FOR INFORMATION
CD = CORD DROP; SEE DRAWINGS FOR INFORMATION
EQUIPMENT CONNECTION; COORDINATE CONNECTION WITH EQUIPMENT
PRIOR TO ROUGH-IN
MOTOR CONNECTION
POWER AND/OR DATA SERVICE POLE
FLOORBOX (SEE FLOORBOX SCHEDULE FOR ADDITIONAL INFORMATION)
PUSHBUTTON STATION
FB#
SPECIAL RECEPTACLE (COORDINATE NEMA TYPE WITH EQUIP.)
(REFER TO PANEL SCHEDULES FOR AMPS)
CEILING MOUNTED DUPLEX RECEPTACLE (COORDINATE PLACEMENT WITH
CEILING EQUIPMENT PRIOR TO ROUGH-IN)
DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE REQUIRED BY NEC
GFCI-TYPE DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE REQUIRED BY NEC
DOUBLE-DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE REQUIRED BY NEC
GFCI-TYPE DOUBLE-DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE REQUIRED BY
NEC
RECEPTACLE AND EQUIPMENT SUBSCRIPTS
AC ABOVE COUNTER
W P W EATHERPROOF (UL LISTED W EATHER-RESISTANT)
42"MOUNTING HEIGHT AFF OR AFG
REF REFRIGERATOR
M MICROWAVE
M/R MICROWAVE/RANGE HOOD (LOCATE ABOVE RANGE)
USB DUPLEX RECPT. W ITH (2) USB CHARGING PORTS
DW DISHWASHER, INSTALL PER NEC 422.16(B)(2)
D/DW DISPOSAL/DISHWASHER, INSTALL PER NEC 422.16(B)(2)
TV RECEPT. DEDICATED TO TV;
FIELD VERIFY HEIGHT W/ TV PRIOR TO ROUGH-IN.
EW C ELECTRIC W ATER COOLER;
PROVIDE GFCI PROTECTION PER NEC 422.5(A)
HVAC THERMOSTAT OR SENSOR; PROVIDE & INSTALL BACKBOX,3/4" CONDUIT AND
CONDUCTORS TO ASSOCIATED HVAC UNIT. COORDINATE EXACT LOCATION & SIZE AND
NUMBER OF CONDUCTORS WITH M.C.
T SOR
EXHAUST FAN CONNECTION
D CLOTHES DRYER (NEMA 14-30R)
R ELECTRIC RANGE (NEMA 14-50R)
W W ELDER RECEPTACLE
208/240V -NEMA 6-50R
GENERAL SPECIAL SYSTEM NOTES:
A. ALL DEVICES SHOWN AT OR NEAR MILLWORK/CASEWORK SHALL BE COORDINATED WITH THE
ARCHITECTURAL ELEVATION DRAWINGS AND MILLWORK INSTALLER TO INSURE PROPER MOUNTING
HEIGHTS. CONTRACTOR SHALL ADJUST DEVICES AS NECESSARY IN ORDER TO POSITION DEVICES SUCH
THAT THEY WILL NOT FALL BEHIND MILLWORK, CABINETS OR BE DIRECTLY ABOVE SINKS OR MIDWAY
BETWEEN TILEWORK/WALL OR WAINSCOATING, ETC.
B. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL A GFCI TYPE RECEPTACLE FOR ALL
RECPTACLES SHOWN IN TOILET RMS, BATHROOMS, KITCHENS/SERVING AREAS, ROOFTOP, OUTDOORS
OR WITHIN 6FT OF ANY SINK, BASIN, TUB OR FLOOR SINK AND ALL OTHER AREAS DEFINED BY THE NEC.
SPLIT-WIRED RECEPTACLE, HALF OF RECEPT. SHALL BE SWITCHED OTHER HALF SHALL
HAVE CONSTANT POWER.
SPECIAL SYSTEMS SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
DATA OUTLET; _= # OF DATA CABLES, X=CONDUIT SIZE (SEE NOTES 1,2,3 BELOW)_D-X
TELEPHONE OUTLET; _= # OF TELEPHONE CABLES, X=CONDUIT SIZE
(SEE NOTES 1,2,3 BELOW)
_T-X
TELEPHONE/DATA OUTLET; _= # OF TELEPHONE/DATA CABLES, X=CONDUIT SIZE
(SEE NOTES 1,2,3 BELOW)
_T/_D-X
CEILING MOUNTED DATA OUTLET; _= # OF DATA CABLES, X=CONDUIT SIZE
(SEE NOTES 1,2,3 BELOW)
_D-X
A. COMMUNICATIONS CABLES SHALL HAVE BENDS NO GREATER THAN 90 DEG.
B. CONDUITS FOR COMMUNICATIONS CABLING SHALL HAVE A MAXIMUM BEND RADIUS NOT MORE THAN 10X
THE DIAMETER OF THE CONDUIT.
C. ALL COMMUNICATIONS CONDUITS SHALL BE TERMINATED WITH AN INSULATED NON-METALLIC BUSHING
AT BOTH ENDS.
D. COMMUNICATIONS CONDUITS SHALL HAVE NO MORE THAN (2) 90'S WITHOUT A PULLBOX. PULL BOXES
SHALL BE LOCATED IN ACCESSIBLE LOCATIONS AND SHALL BE SIZED AT LEASED 12X THE LARGEST
CONDUIT DIAMETER IN LENGTH AND MIN, 4" DEEP AND 8" WIDE.
E. IT SHALL BE THE RESPONSIBILITY OF THE E.C. TO INSURE THAT THE PATHWAY FOR THE DATA CABLING
DOES NOT CREATE CABLE LENGTHS TO EXCEEDS THE LENGTH OF 295FT FROM OUTLET TO PATCH
PANEL, THIS INCLUDES SERVICE LOOPS AND PATCH CORDS.
F. WHERE CABLE TRAY IS UTILIZED IN THE PROJECT. COMMUNICATION CONDUITS ENDING AT THE CABLE
TRAY SHALL EXTEND 1" OVER THE SIDE INTO THE TRAY.
GENERAL SPECIAL SYSTEM NOTES:
###
_D-X
SPECIAL SYSTEMS NOTES:
1. UTILIZE 4 11/16" DEEP BOX WITH REQUIRED MUDRING AND CONDUIT TO ABOVE NEAREST ACCESSIBLE
CEILING OR DATA RACK, TERMINATE WITH INSULATED THROAT BUSHING. PROVIDE QTY OF CABLES
INDICATED FROM OUTLET TO NEAREST TELE/DATA ROOM. SEE DWGS FOR ADDITIONAL INFORMATION.
UTILIZE J-HOOKS 3FT ON CENTER FOR SUPPORT OF CABLING WHERE CABLE TRAY IS NOT
INSTALLED/SPECIFIED.
2. CONDUIT SIZE ('X' FROM ABOVE); 2=1/2", 3=3/4", 4=1", 5=1-1/4", 6=1-1/2"
3. BLANK (NO LABEL) = 4-11/16" DEEP BOX WITH REQUIRED MUDRING AND 1" CONDUIT TO ABOVE NEAREST
ACCESSIBLE CEILING/CABLE TRAY, TERMINATE WITH INSULATED
THROAT BUSHING, PROVIDE PULL STRING. (UNLESS OTHERWISE NOTED)
WALL/FLOOR ELECTRICAL PATHWAY SLEEVE;
INSTALL THROUGH WALL OR FLOOR AS INDICATED. SLEEVES SHALL BE ABOVE
ACCESSIBLE CEILINGS IN ACCESSIBLE LOCATION, FIELD VERIFY EXACT LOCATION TO
AVOID CONFLICT WITH OTHER TRADES AND UTILITIES. IF WALL/FLOOR IS NOT FIRE RATED
E.C. MAY UTILIZED EMT CONDUIT SLEEVES OF EQUAL SIZE. REFER TO ARCHITECTURAL
DRAWINGS FOR FIRE RATINGS.
(qty) = QUANTITY OF SLEEVES AT LOCATION
EP2 = 2" HILTI SPEED SLEEVE CP-653-BA
EP4 = 4" HILTI SPEED SLEEVE CP-653-BA
###
FB#
_D-X
ELECTRICAL FLOORBOX
REFER TO "ELECTRICAL FLOORBOX SCHEDULE" FOR INFORMATION.
_= # OF DATA CABLES, X=CONDUIT SIZE (SEE NOTES 1,2,3 BELOW)
TV AND/OR AV BOX; WITH POWER, DATA AND/OR AV CONNECTIVITY
### = BOX ID: REFER TO "ELECTRICAL AV/TV BOX SCHEDULE" FOR INFORMATION.
_= # OF DATA CABLES, X=CONDUIT SIZE (SEE NOTE #2 BELOW)
INSTALL CONDUIT (SIZE AS INDICATED) FROM BOX TO NEAREST ACCESSIBLE CEILING
SPACE W/ DATA CABLING/TERMINATIONS AS INDICATED ON DRAWINGS.
W ALL
###
FLOOR
(qty)
(qty)
P
1PH
2/C
3/C
3P
3PH
3W
4W
AC
ADA
AFF
AFG
AIC
AL
A or
AMP
ANN
AP
ATS
AV
AWG
BFG
C
CATV
CB
CCTV
CKT
C
CP
CT
CU
DS
EA
E.C.
EM
EMT
ENT
EPO
EQUIP
EX
FA
FACP
FLA
FMC
GND
G.C.
GEN
GFI
GFP
HD
HID
HOA
HP
HPS
HV
HZ
IG
IMC
J-BOX
ABBREVIATIONS
SINGLE POLE
SINGLE-PHASE
TWO-CONDUCTOR
THREE-CONDUCTOR
THREE POLE
THREE-PHASE
THREE-WIRE
FOUR-WIRE
ABOVE COUNTER
AMERICANS WITH DISABILITIES ACT
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMPERE
ANNUNCIATOR
ACCESS POINT
(WIRELESS DATA)
AUTOMATIC TRANSFER SWITCH
AUDIO VISUAL
AMERICAN WIRE GAGE
BELOW FINISHED GRADE
CEILING MOUNTED
CABLE TELEVISION
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CONDUIT
CONTROL PANEL
CURRENT TRANSFORMER
COPPER
DISCONNECT SWITCH
EACH
ELECTRICAL CONTRACTOR
EMERGENCY
ELECTRICAL METALLIC TUBING
ELECTRICAL NONMETALLIC TUBING
EMERGENCY POWER OFF
EQUIPMENT
EXISTING
FIRE ALARM
FIRE ALARM CONTROL PANEL
FULL LOAD AMPS
FLEXIBLE METAL CONDUIT
GROUND
GENERAL CONTRACTOR
GENERATOR
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT PROTECTION
HEAVY DUTY
HIGH INTENSITY DISCHARGE
HAND-OFF-AUTOMATIC
HORSE POWER
HIGH PRESSURE SODIUM
HIGH VOLTAGE
HERTZ
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
JUNCTION BOX
V
KVA
kW
kWh
LED
LFMC
LFNC
LTG
LV
MAX
M.C.
MCA
MCB
MCC
MDP
MH
MIN
MLO
MOCP
NA
NC
NEC
NEMA
NFPA
NIC
NL
NO
NTS
OC
OH DR
OL
PB
P
PNL
PT
PTZ
QTY
RCP
RMC
RNC
SCA
SCBA
SF
SPD
SPEC
SWBD
SWGR
TL
TP
TTB
TV
TYP
UG
UPS
V
VA
V.I.F.
VFD
WAP
W/
W/O
WP
XFMR
KILOVOLT
KILOVOLT AMPERE
KILOWATT
KILOWATT HOUR
LIGHT EMITTING DIODE
LIQUID TIGHT FLEXIBLE METAL CONDUIT
LIQUID TIGHT FLEXIBLE NONMETALLIC
CONDUIT
LIGHTING
LOW VOLTAGE
MAXIMUM
MECH. CONTRACTOR
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION PANEL
MANHOLE
MINIMUM
MAIN LUGS ONLY
MAXIMUM OVERCURRENT PROTECTION
NOT APPLICABLE
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NATIONAL FIRE PROTECTION
ASSOCIATION
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
ON CENTER
OVERHEAD DOOR
OVERLOAD
PUSHBUTTON
PHASE
PANEL
POTENTIAL TRANSFORMER
PAN/TILT/ZOOM
QUANTITY
REFLECTED CEILING PLAN
RIGID METAL CONDUIT
RIGID NONMETALLIC CONDUIT
SHORT CIRCUIT AMPS
STANDARD COLOR BY ARCHITECT
SQUARE FOOT (FEET)
SURGE PROTECTION DEVICE
SPECIFICATION
SWITCHBOARD
SWITCHGEAR
TWIST LOCK
TWISTED PAIR
TELEPHONE TERMINAL BOARD
TELEVISION
TYPICAL
UNDERGROUND
UNINTERRUPTIBLE POWER SUPPLY
VOLTS
VOLT AMPERE
VERIFY IN FIELD
VARIABLE FREQUENCY DRIVE
WIRELESS ACCESS POINT
WITH
WITHOUT
WEATHERPROOF
TRANSFORMER
A. E.C. SHALL REFER TO THE MECHANICAL DRAWINGS FOR EXACT LOCATIONS OF ALL MECHANICAL
EQUIPMENT AND ELECTRICAL CONNECTIONS.
B. E.C. SHALL PROVIDE MINIMUM WORKING CLEARANCE AS PER NEC BEFORE INSTALLING ANY ELECTRICAL
PANELS OR CABINETS. SEE ELECTRICAL EQUIPMENT CLEARANCE DETAIL.
C. INSTALL ALL LIGHT FIXTURES IN MECHANICAL ROOM AFTER THE MECHANICAL EQUIPMENT IS IN PLACE.
ADJUST AS NECESSARY. PROVIDE CHAIN SUSPENSION KITS AS REQUIRED.
D. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN(S) FOR EXACT FIXTURE LOCATIONS, CEILING
TYPES, ETC.
E. E.C. SHALL PROVIDE ALL CONCRETE PADS AS REQUIRED FOR ALL ELECTRICAL EQUIPMENT.
F. CONFIRM EXACT LOCATIONS OF ALL TELEPHONE/DATA OUTLETS WITH OWNER PRIOR TO ROUGH-IN.
G. LOCATE SWITCHES, OUTLETS, ETC., SHOWN AT ROOM ENTRY DOORWAYS, AS CLOSE TO DOOR FRAME AS
POSSIBLE, SO AS NOT RO INTERFERE WITH ROOM CABINETS, ETC.
H. SUPPORT ALL LIGHT FIXTURES INDEPENDENT OF CEILING.
I. ELECTRICAL CONTRACTOR SHALL OBTAIN ALL APPLICABLE PERMITS FOR WORK AND PAY ASSOCIATED
FEES.
J. MAINTAIN 24" MIN. CLEARANCE FROM ALL COMMUNICATIONS CABLING AND ELECTRONIC BALLASTS.
K. UNLESS SPECIFICALLY INDICATED OTHERWISE, E.C. SHALL COORDINATE WITH ANY SPECIAL SYSTEMS
SUPPLIER/SHOP DRAWINGS; DENTAL, MEDICAL, KITCHEN, SPECIALIZED EQUIPMENT, ETC. FOR THE EXACT
ROUGH-IN REQUIREMENTS FOR THEIR EQUIPMENT. ALSO UNLESS INDICATED OTHERWISE, THE E.C. TO
BE RESPONSIBLE FOR FINAL ELECTRICAL CONNECTIONS TO ALL SPECIAL EQUIPMENT.
L. ALL CONDUIT/RACEWAY/CABLES TO BE CONCEALED IN WALLS OR ABOVE CEILINGS. IF ANY SURFACE
WORK IS NECESSARY, IT SHALL BE APPROVED BY THE ARCHITECT/ENGINEER PRIOR TO INSTALLATION.
M. ELECTRICAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND THOROUGHLY INVESTIGATE THE
EXISTING CONDITIONS, AS THEY RELATE TO THE SCOPE OF WORK DESCRIBED. MAKE NECESSARY
PROVISIONS IN THE BASE BID TO ADEQUATELY ACCOMMODATE THESE CONDITIONS.
N. DATA CABLING SYSTEM PRE-INSTALLATION CONFERENCE:
1. E.C. SHALL SCHEDULE A MEETING A MINIMUM OF FIVE CALENDAR DAYS PRIOR TO BEGINNING DATA
CABLING INSTALLATION . ATTENDEES SHOULD INCLUDE OWNER’S REP., ENGINEER, GC, EC AND
CABLING SUB. REFER TO SECTION 26 6210(1.4)(E)FOR ADDITIONAL INFORMATION.
PROJECT GENERAL NOTES:
CONTACT:Jarom Taylor Nexant (Rocky Mountain Power)
(801) 746-1623
For Assistance
UTILITY LIGHTING REBATES & INCENTIVES:
IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PREPARE ALL REQUIRED
APPLICATIONS AND INFORMATION REQUIRED TO PROVIDE THE OWNER WITH THE MAXIMUM AMOUNT OF
REBATE DOLLARS FROM THE LOCAL UTILITY COMPANY. THE ELECTRICAL CONTRACTOR SHALL SUBMIT
VERIFICATION OF THE UTILITY COMPANY PRE-APPLICATION APPROVAL PRIOR TO ORDERING ANY MATERIALS.
VISIT THE FOLLOWING UTILITY CO. WEBSITES FOR INFORMATION:
TYPICAL DEVICE MOUNTING HEIGHTS:
GENERAL COORDINATION NOTE:
GENERAL DETAIL NOTES:
FINISH FLOOR
1' -6''
THERMOSTAT OR SENSOR
VERIFY WITH M.C. PRIOR TO
LIGHT SW.
(OR AS NOTED)
* 4' -0''
* 3' -6''
(OR AS NOTED)
RECEPTACLE
@ MILLWORK
BACKSPLASH
CAB. DIMENSIONS
PER ARCH. DETAIL
6"
CABINET
*E.C. SHALL COORDINATE ALL DEVICE
MOUNTING HGTS. AND EXACT LOCATION
WITH ARCHITECTURAL INTERIOR
ELEVATIONS REPORT CONFLICTS TO
ARCHITECT **PRIOR TO ROUGH-IN**
ROUGH-IN.
TYPICAL FOR ALL DEVICES
MOUNTED ABOVE COUNTER
(ie C.O.'S, DATA, PHONE etc.)
A.
B.
C.
D.
ALL MOUNTING HEIGHTS TYPICAL UNLESS
NOTED OTHERWISE.
COORDINATE OUTLET HEIGHTS WITH
ARCHITECTS MILLWORK DWGS. TO INSURE
THAT OUTLETS WILL NOT FALL BEHIND
CABINETS, BACKSPLASHES, OR INTERFERE
WITH WAINSCOTING, ETC.
ALL SWITCHES AND THERMOSTATS TO BE
MOUNTED AS CLOSE TO DOOR JAMS AS
POSSIBLE. COORDINATE ALL DEVICES WITH
ARCHITECTURAL PLANS AND DETAILS.
COORDINATE LIGHT SWITCH & OUTLET
HEIGHTS WITH ARCHITECTURAL
WAINSCOTING AND OR TILE WORK SO AS
NOT TO FALL MIDWAY IN THESE FINISHES.
FIRE
6' -8''
FIRE ALARM NOTIFICATION
DEVICE
FIRE
MANUAL PULL STATION
HANDLE SHALL BE
BETWEEN 42" & 48" AFF CABINET
RECEPT.
TELE/DATA
OUTLET
TV
OUTLET
ELECTRICAL EQUIP. CLEARANCE
ELECTRICAL
EQUIPMENT
NOTE #1
N O T E #4
NOTE#3
NOTE#2
NOTES:
1. THE MINIMUM HEADROOM OF WORKING SPACE SHALL BE 6 1/2FT.
2. THE WIDTH OF THE WORKING SPACE SHALL BE THE WIDTH OF THE EQUIPMENT OR 30", WHICHEVER IS
GREATER. THE PANEL DOOR SHALL OPEN AT LEAST 90 DEGREES.
3. ALL CIRCUIT BREAKERS, WHEN IN THIER HIGHEST POSITION, SHALL NOT BE MORE THAN 6FT 7 IN. ABOVE
THE FINISHED FLOOR.
4. 3FT CLEARANCE IF 0-150V TO GROUND, 3.5FT CLEARANCE IF 151-600V TO GROUND. 4FT IF EXPOSED LIVE
PARTS ON BOTH SIDES OF THE WORKING SPACE.
GENERAL NOTES:
A. ALL WORKING SPACE CLEARANCES ARE FROM THE FACE OF THE EQUIPMENT.
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:22127
04-28-2023 EG0.0
ELECTRICAL
SYMBOLS &
DETAILS
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
SECURITY & ACCESS CONTROL SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
CARD READER/KEYPAD LOCATION; UTILIZE 4SQ. BOX W/1-GANG MUDRING AND 3/4"C. W/
PULL STRING TO NEAREST ACCESSIBLE CEILING SPACE. CR
CAM SECURITY CAMERA: PROVIDE AND INSTALL A 4SQ. BOX W/3/4"C., TO NEAREST
ACCESSIBLE CEILING SPACE & 1-CAT6A CABLE TO IT ROOM. TERMINATE JACK ON THE
CABLE FOR CAMERA. CAMERA TO BE PROVIDED AND INSTALLED BY OWNER OVER BOX;
COORDINATE ROUGH-IN WITH OWNER CAMERA SPEC.
CONNECTION TO DOOR FRAME FOR ACCESS CONTROL. PROVIDE (1)3/4"C W/PULLSTRING
FROM DOOR TO NEAREST ACCESSSIBLE CEILING SPACE.
• E.C. IS RESPONSIBLE FOR ROUGH-IN FOR ACCESS CONTROL SYSTEM; EQUIPMENT AND CABLING TO BE
PROVIDED AND INSTALLED BY OWNER. E.C. SHALL COORDINATE ROUGH-IN OF ACCESS CONTROL
SYSTEM WITH BYU-I PRIOR TO ROUGH-IN.
• E.C. IS RESPONSIBLE FOR ROUGH-IN, CABLING AND TERMINATIONS FOR SECURITY CAMERA'S. CAMERAS
WILL BE PROVIDED AND INSTALLED BY BYU-I. E.C. SHALL COORINATE LOCATIONS AND ROUGH-IN WITH
BYU-I PRIOR TO WORK BEING DONE.
GENERAL SECURITY & ACCESS CONTROL NOTES:
F
C
12" SQUARE, SEMI-RECESSED 60HZ. SYNCHRONOUS, 4-WIRE CLOCK WITH ALUMINUM
FRAME AND WHITE FACE.
SIMPLEX #2310-9271 W/ SIMPLEX #2975-9038 RECESSED BACKBOX. (UNO)
M -MASTER CLOCK (AMERICAN TIME & STANDARD #ASQMSTR-002XE)
D -DIGITAL CLOCK (AMERICAN TIME & STANDARD #CC4SE)
PROVIDE AND INSTALL A 3/4"C., 4#12 THHN (BLK,WHT,RED,GRN) FROM EACH CLOCK BACK
TO NEAREST MASTER CLOCK OR SYSTEM J-BOX. PROVIDE ALL REQUIRED CONNECTIONS
BETWEEN MASTER CLOCK AND CLOCKS FOR A COMPLETE AND FUNCTIONAL SYSTEM.
2 __ÑW _W U hI[U S _Ñl c I] Ñhc ÑU c C d _n Ñl [hZ ѽ ¤ Á ÑA 6 4
A
B
C
D
E
F
GH
3 4 5 6 7 8
1 2 1 2 1 12 2
3
1
1
2
2
1
1
2
21122
4
4
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:22127
04-28-2023 ED1.0
LEVEL 0
EXISTING
LIGHTING
PLAN
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
1 DISCONNECT AND REMOVE EXISTING RECESSED CAN
MAINTAIN CIRCUIT FOR NEW LIGHT.
2 PROVIDE AND INSTALL A METAL PLATE TO COVER EXISTING
OPENING. PLATE SHALL BE CUT TO ACCEPT NEW SYLVANIA
LED/RT8/2000/840 LED DOWN LIGHT. METAL PLATE FINISH TO
MATCH SOFFIT. PROVIDE AND INSTALL LIGHT FIXTURE
CONNECT TO EXISTING CIRCUIT AND CONTROLS.
3 NEW LIGHTING FIXTURE. CUT EXISTING SOFFIT TO ACCEPT
NEW SYLVANIA LED/RT8/2000/840 CONNECT TO EXISTING
EXTERIOR LIGHTING CIRCUIT AND CONTROLS.
4 DISCONNECT AND REMOVE EXISTING LIGHTING IN AREA.
REMOVE ALL ASSOCIATED CONDUIT, CABLE, AND CONTROLS.
KEY NOTES:#
NORTH
16'8'0"
SCALE: 1/8" = 1'-0"1 LEVEL 0 EXISTING LIGHTING PLAN
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
SPECIAL DEMOLITION NOTES:
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
GENERAL NOTES:
FB
FB FB
FB
P P
P
P
P
P
P P
P
P
F
F
A
B
C
D
E
F
GH
J
3 4 5 6 7 8
'RR'
'S'
'R'
'FACP'
1
2
2
3
3
4
4
2 2
11
1
1
1
1
5
5
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:22127
04-28-2023 ED1.1
LEVEL 0
EXISTING
POWER
PLAN
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
1 EXISTING DEVICE LOCATION TO REMAIN. RELACE DEVICE AND
FACEPLATE. PROVIDE NEW CIRCUIT AS SHOWN.
2 CAREFULLY DISCONNECT, REMOVE, AND CLEAN EXISTING
SECURITY CAMERA. REMOVE ALL ASSOCIATED CONDUIT AND
CABLE. RETURN CAMERA TO OWNER.
3 CAREFULLY DISCONNECT, REMOVE, CLEAN AND STORE
EXISTING CLOCK TO BE USED IN REMODEL. RETURN ALL
UNUSED CLOCKS TO OWNER.
4 CAREFULLY REMOVE EXISTING PANEL. PROTECT AND STORE
PANEL INTERIOR FOR POSSIBLE USE IN NEW DESIGN, IF NEW
PANELS ARE NOT AVAILABLE TO MEET CONSTRUCTION
TIMELINES. DISCONNECT AND REMOVE EXISTING FEEDER
CONDUCTORS AND CONDUIT WHERE ACCESSIBLE. SEE
SPECIAL DEMO NOTE FOR FURTHER INSTRUCTION.
5 E.C. SHALL INTERCEPT ALL EXISTING CIRCUITS TO REMAIN.
SLICE AND EXTEND TO NEW PANEL LOCATION AND
TERMINATE ON NEW BREAKERS LABEL EACH SPLICED
CIRCUIT.
KEY NOTES:#
SCALE: 1/8" = 1'-0"1 LEVEL 0 EXISTING POWER PLAN
NORTH
16'8'0"
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
GENERAL NOTES:
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
SPECIAL DEMOLITION NOTES:
C
A
1
B
C
D
E
F
2 3 4 5
HAZ.
STORAGE
[167]
HAZ.
STORAGE
[166]
ROCK
LABORATORY
[164]
MEN'S T.R.
[162]
WOMEN'S
T.R.
[160]
PIPE
CHASE
[I-Q]
HALLWAY
[1-T]
LAB PREP
ROOM
[161]
ELEVATOR
[1-M]
CUST.
[147]
STAIRWELL
[1-P]
PHYSICAL
GEOLOGY
ROOM
[158]
WOMEN'S
RM
[132]
MEN'S RM
[134]
LECTURE
HALL
[145]PREP/STORAGE
RM
[143]
MINEROLOGY
LAB
[149]
HALLWAY
[I-N]
HALLWAY
[I-L]
HALLWAY
[I-K]
UNISEX RM
[136]
HALLWAY
[1-U]
STAIRWELL
[1-V]
BDF
[138]
STAIRWELL
[1-S]
ELEVATOR
[1-J]
1 1
1 1
2 2
2 2
3
33
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:22127
04-28-2023 ED1.2
LEVEL 1
EXISTING
ELECTRICAL
PLAN
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
1 DISCONNECT AND REMOVE EXISTING RECESSED CAN
MAINTAIN CIRCUIT FOR NEW LIGHT.
2 PROVIDE AND INSTALL A METAL PLATE TO COVER EXISTING
OPENING. PLATE SHALL BE CUT TO ACCEPT NEW SYLVANIA
LED/RT8/2000/840 LED DOWN LIGHT. METAL PLATE FINISH TO
MATCH SOFFIT. PROVIDE AND INSTALL LIGHT FIXTURE
CONNECT TO EXISTING CIRCUIT AND CONTROLS.
3 E.C. SHALL PROTECT, MAINTAIN AND/OR RE-ESTABLISH ALL
EXISTING LIGHTING, CONTROLS, FIRE ALARM AND POWER IN
THIS AREA.
KEY NOTES:#
SCALE: 1/8" = 1'-0"1 LEVEL 1 EXISTING PLAN
16'8'0"
NORTH
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
GENERAL NOTES:
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
SPECIAL DEMOLITION NOTES:
S
nD1
S
nD1
S
nD1
S
nD1
1
C
D
E
F
2 3 4 5
3 3
3
(TYP)(TYP)
(TYP)
3
(TYP)
444
1
C
D
E
F
2 3 4 5
1
1
1
111
1
1
1
2
5 6
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:22127
04-28-2023 ED2.2
LEVEL 2
EXISTING
ELECTRICAL
PLAN
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
1 EXISTING DEVICE LOCATION TO REMAIN. RELACE DEVICE AND
FACEPLATE. PROVIDE NEW CIRCUIT AS SHOWN.
2 CAREFULLY DISCONNECT, REMOVE, CLEAN AND STORE
EXISTING CLOCK TO BE USED IN REMODEL. RETURN ALL
UNUSED CLOCKS TO OWNER.
3 CAREFULLY DISCONNECT, REMOVE, AND CLEAN EXISTING
LIGHTING IN THIS AREA; REMOVE ALL ASSOCIATED
CONTROLS, WIRE AND CONDUIT, MAINTAIN EXISTING NORMAL
AND EMERGENCY LIGHTING CIRCUITS FOR NEW LIGHTING.
MAINTAIN AND/OR RE-ESTABLISH ELECTRICAL CONTINUITY TO
DOWNSTREAM DEVICES TO REMAIN. LIGHTING CONTROL
DEVICES THAT ARE COMPATIBLE WITH NEW DESIGN MAY BE
REUSED. RETURN ANY LIGHTING FIXTURE THAT IS NOT
RE-INSTALLED TO OWNER.
4 E.C. SHALL PROTECT, MAINTAIN AND/OR RE-ESTABLISH ALL
EXISTING LIGHTING, CONTROLS, FIRE ALARM AND POWER IN
THIS AREA.
5 CAREFULLY REMOVE EXISTING PANEL. PROTECT AND STORE
PANEL INTERIOR FOR POSSIBLE USE IN NEW DESIGN, IF NEW
PANELS ARE NOT AVAILABLE TO MEET CONSTRUCTION
TIMELINES. DISCONNECT AND REMOVE EXISTING FEEDER
CONDUCTORS AND CONDUIT WHERE ACCESSIBLE. SEE
SPECIAL DEMO NOTE FOR FURTHER INSTRUCTION.
6 E.C. SHALL INTERCEPT ALL EXISTING CIRCUITS TO REMAIN.
SLICE AND EXTEND TO NEW PANEL LOCATION AND
TERMINATE ON NEW BREAKERS LABEL EACH SPLICED
CIRCUIT.
KEY NOTES:#
SCALE: 1/8" = 1'-0"1 LEVEL 2 EXISTING LIGHTING PLAN
SCALE: 1/8" = 1'-0"2 LEVEL 2 EXISTING POWER PLAN
16'8'0"
NORTH
16'8'0"
NORTH
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
SPECIAL DEMOLITION NOTES:
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
GENERAL NOTES:
C
SnD1
SnD1
nD
nDCnDC
S
CD1S
CD1
SCD1S
CD1
nD
n1
nD nD
nD
SnD1
SnD1
S
nD1
WD1 WD1
n2D
n2
D
S
nD1
SnD1
R
nPS80
R
nPS80
WD1
nD
S
nD1
nD
O
n2
D
S
nD1
S
nD1
S
nD1
S
nD1
S
nD1
SnD1SnD1SnD1S
nD1
S
nD1
nD
S
nD1
S
nD1
WD
1
S
CD1
S
CD2
S
CD2
WD
1
nD
D
R
nP
P
1
6
nD
R
nPP16
S
nD1
A
B
C
D
E
F
G
3 4 5 6 7
MEN'S RM
[66]
WOMEN'S
RM
[64]
MECHANICAL
ROOM
[69]
VESTIBULE
[O-A]
HALLWAY
[O-C]
STORAGE
[63]
STAIRWELL
[O-B]
PIPE
CHASE
[O-Q]
ELEVATOR
[O-D]MECH RM
[67]
CUST RM
[68]
CLASSROOM
[50]
DARK
ROOM
[59D]
COMPUTER
LAB
[59]
PHOTO
STUDIO
[51]
VESTIBULE
[59C]
OFFICE
[57]
EQUIP /
CHECK OUT
[59A]
STORAGE
[59B]
OFFICE
[55]
FILM
[59E]
ACOUSTICS
STUDIO
[52B]
STORAGE
[51A]
CHANGING
[51B]
VESTIBULE
[0-H]
OPTICS LAB
[52A]
PHYSICS
LAB
[52]
STORAGE
[52C]
(TYP)
F3 (TYP)
F3
(TYP)
F4 (TYP)
F4
b b
b
bb
b b
aa
a
a
a a
aaa
(TYP)
F12
(TYP)
F3
(TYP)
F3
(TYP)
(TYP)
F3
(TYP)
F3 (TYP)
F3
(TYP)
F3
F3 F3
(TYP)
F3
F3F3F3
F3
F3F3
F3F3F3F6
F4
'S'
'R'
'R(SEC 2)'
S-29
S-27
R-53
(TYP)
F3
(TYP)
F3
F3E
F3E
F3EF3E
F3EF3E
(TYP)
F3
F3E
F3E
F3E F3E
F3E
F3E
F3E
F3E
F3E
F3E
F3E
F3E
F3E
F3E
F10
F10
F3
A
EE1.0
1
F10
F10
F12
F12
F12
F12
F3 F3
F1F1
F12 F12
F1
R-52F11
F11
R-54
S-32
(TYP)
F9
F9
F12E F12E
F12E
F12E
F12E
F12E
F12E
F12E R-51
(TYP)
F12
(TYP)
F12
2
3 3
(TYP)(TYP)F13
F13
F7 F8F8
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:22127
04-28-2023 EE1.0
LEVEL 0
LIGHTING
PLAN
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
1 DIMMING SWITCH TO CONTROL VANITY LIGHTS. CIRCUIT
DOWN STREAM FROM WALL OCC SENSOR.
2 SUSPEND 1" UNISTRUT TO HEIGHT SPECIFIED BY ARCHITECT
AND MOUNT TRACK TO SUSPENDED STRUT.
3 SUSPEND FIXTURE WITH AIRCRAFT CABLE. COORDINATE
SUSPENSION HEIGH AND LIGHT LOCATION WITH OTHER
CEILING DEVICES AND WITH OWNER AND ARCHITECT PRIOR
TO ROUGH IN.
KEY NOTES:#
NORTH
16'8'0"
SCALE: 1/8" = 1'-0"1 LEVEL 0 OVERALL LIGHTING PLAN
LIGHTING CONTROL (nLIGHT) SYSTEM SCHEDULE
TYPE DESCRIPTION MFGR. CATALOG # NOTES
CEILING SENSORS
nD1 DUAL-TECHNOLOGY, SMALL MOTION, CEILING
OCCUPANCY SENSOR W/ AUTO DIMMING CONTROL
PHOTOCELL
SENSOR SWITCH nCM-PDT-9-RJB-
ADCX
RELAY PACKS/POWER SUPPLIES & INTERFACE DEVICES
nPP16 RELAY POWER PACK SENSOR SWITCH nPP16 2
nPS80 RELAY POWER PACK SENSOR SWITCH nPS80 2
WALL SWITCHES
nLIGHT ON/OFF PUSHBUTTON SENSOR SWITCH nPODM 3
n1 nLIGHT ON/OFF PUSHBUTTON SENSOR SWITCH nPODM 3
n2D nLIGHT ON/OFF PUSHBUTTON W/DIMMING,
2-CHANNEL
SENSOR SWITCH nPODM-2PDX-X 3
nD nLIGHT ON/OFF PUSHBUTTON W/DIMMING SENSOR SWITCH nPODM-DX 3
nDC nLIGHT ON/OFF PUSHBUTTON W/DIMMING, COLOR
CORRECTION
SENSOR SWITCH nPODM-DX-CCT 3
nDO nLIGHT DUAL-TECH OCCUPANCY SENSOR, ON/OFF
PUSHBUTTON W/DIMMING
SENSOR SWITCH nWSX PDT LV-DX 3
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MOUNTING VOLTS LUMENS
COLOR
TEMP.(K)MFGR. CATALOG # NOTES
F1 EXIT SIGN WALL OR
CEILING
120-277 N/A N/A LITHONIA LQM-S-W-3-G-120/277-AC 11
F2 EXISTING 2X2 LAY-IN FIXTURE RECESSED 120-277 4000 4000 12
F3 2X2 LAY-IN LED, 0-10V DIMMING RECESSED 120-277 4000 4000 LITHONIA EPANL-2X2-4800-LM-80CRI-40K-MIN1-NLIGHT-MVO
LT
F4 2X2 LAY-IN LED COLOR CORRECTING RECESSED 120-277 4000 4000 LITHONIA 2BLT2-TUWH-PROP-48L-ADSM-MVOLT-NLT
F5 6" ROUND RECESSED LED CAN, 0-10V
DIMMING
RECESSED 120-277 1500 4000 LITHONIA LDN6-40/15-LO6AR-LSS-MVOLT-EZ10
F6 "IN USE" LIGHT WALL 120-277 RT TECHNOLOGIES LEDS-SJ-110-R-1U
F7 24" VANITY MAKEUP LIGHT SURFACE 120-277 KICHLER 624NI
F8 36" VANITY MAKEUP LIGHT SURFACE 120-277 KICHLER 626NI
F9 RECESSED CAN W/ INCADESCENT BULB RECESSED 120-277 LITHONIA L7XR6/CO1 R6 100W R40 INC
F10 4FT LED STRIP, 0-10V DIMMING SURFACE/
SUSPENDED
120-277 4000 4000 LITHONIA CLX-L48-4000LM-SEF-RDL-MVOLT-GZ10-40K-80CRI
F11 LED TRACK LIGHT SURFACE 120 1500 4000 LSI TRACK: TRK-SC-XX1-120-CBA HEAD SEE NOTE 9 10
F12 1X4 SURFACE FIXTURE SURFACE 120-277 4000 4000 LITHONIA BLWP4-40L-ADP-EZ1-LP840-N100
F13 HAIR LIGHT FLASH UNIT 120 EINSTEIN E640 8
LIGHTING CONTROL/OCCUPANCY SENSOR SCHEDULE
TYPE DESCRIPTION MFGR. CATALOG #
APPROVED
EQUALS NOTES
OCC. SENSORS - CEILING (LINE VOLTAGE)
CD2 DUAL-TECHNOLOGY, LINE VOLTAGE, SMALL MOTION 800W MAX
LOAD
SENSOR SWITCH CMR PDT 9 COOPER,
WATTSOPPER,
HUBBELL
OCC. SENSORS - CEILING (LOW VOLTAGE)
CD1 DUAL-TECHNOLOGY, SMALL MOTION 360 DEGREE COVERAGE,
LOW VOLTAGE, W/ISOLATED RELAY
SENSOR SWITCH CM PDT 9 R COOPER,
WATTSTOPPER,
HUBBELL
1
OCC. SENSORS - WALL MOUNTED
WD1 DUAL-TECHNOLOGY, 1-POLE, NEUTRAL REQUIRED SENSOR SWITCH WSX PDT-** COOPER,
WATTSTOPPER,
HUBBELL
2
1. REFER TO DRAWINGS FOR FIXTURES REQUIRED TO HAVE 0-10V OR STEP-LEVEL DIMMING CONTROL. PROVIDE FIXTURE(S) WITH LED DRIVER(S)
AND REQUIRED DIMMING/SWITCH-LEG CONDUCTORS BETWEEN SWITCH(ES) AND FIXTURE(S) TO PROVIDE CONTROL AS INDICATED ON
DRAWINGS.
2. FIXTURE TO BE CONTINUOUS ROW MOUNTED, LENGTH AS INDICATED ON DRAWINGS. PROVIDE REQUIRED ACCESSORIES/CONNECTORS FOR
CONTINUOUS ROW MOUNTING.
3. SCBA - STANDARD COLOR BY ARCHITECT/OWNER (COORDINATE COLOR WITH ARCHITECT/OWNER PRIOR TO ORDERING.)
4. FIELD ADJUST PENDANT LENGTH AS REQUIRED, VERIFY LENGTH WITH COUNTER AS DIRECTED BY ARCHITECT.
5. REFER TO ARCHITECTURAL ELEVATION DRAWINGS FOR PLACEMENT AND MOUNTING HEIGHT OF FIXTURES.
6. PROVIDE AND INSTALL 120V FACTORY APPROVED DIMMER SWITCH FOR TRACK: ACUITY P/N: SYNERGY ISD 400 ELV 120.
7. PROVIDE ALL COMPONENTS FOR COMPLETE INSTALLATION, INCLUDING BUT NOT LIMITED TO: END FEEDS, CONNECTORS AND ETC.
8. MOUNT PER MANUFACTURE AND OWNER. MAKE ALL REQUIRED CONNECTIONS.
9. E.C. SHALL PROVIDE AND INSTALL (20) LZ-15-90-40-ZM-CT2-10-120-CBA. LOCATED, AIM, AND FOCUS TO SATISFACTION OF OWNER.
10. REFER TO PLANS FOR TRACK LENGTH AND CONFIGURATION. E.C. SHALL PROVIDE AND INSTALL ALL REQUIRED POWER FEEDS, CORNERS,
CONNECTIONS ETC. FOR A COMPLETE TRACK SYSTEM.
11. CONNECT ALL EXIT SIGNS TO EXISTING EMERGENCY LIGHTING CIRCUIT.
12. CAREFULLY REMOVE, CLEAN, AND REINSTALL AS SHOWN IN NEW DESIGN.
LIGHT FIXTURE SCHEDULE NOTES:
• LIGHTING FIXTURES INDICATED IN SCHEDULE ARE BASIS OF DESIGN, ALTERNATE MANUFACTURERS SHALL BE PRE-APPROVED BY ADDENDUM.
ALTERNATE MANUFACTURERS SHALL SUBMIT PER-APPROVALS TO ENGINEER A MINIMUM OF 10 DAYS PRIOR TO PROJECT BID DATE.
• THE SUFFIX 'E' DENOTES A FIXTURE SUPPLIED WITH AN EMERGENCY TRANSFER DEVICE. PROVIDE A NORMAL POWER SENSING CIRCUIT.
CONTROL FIXTURE WITH SURROUNDING FIXTURES. CONNECT TO EXISTING EMERGENCY LIGHTING CIRCUIT IN AREA. CONNECT SUCH THAT
FIXTURE WILL ILLUMINATE UPON NORMAL POWER FAILURE.
GENERAL LIGHTING SCHEDULE NOTES:
1. PROVIDE 0-10V DIMMING CONDUCTORS (GREY & VIOLET) BETWEEN DEVICE AND LIGHT FIXTURE(S) FOR DIMMING AS INDICATED ON DWGS.
2. ROUTE ASSOCIATED ROOM LTG CIRCUIT THROUGH RELAY FOR CONTROL, PROVDE 0-10V DIMMING AND LOW VOLTAGE CONNECTIONS AS
INDICATED ON DRAWINGS AND DETAILS.
3. DEVICE COLOR SHALL MATCH WIRING DEVICES; REFER TO SPECIFICATIONS.
4. MOUNT DEVICE TO BOTTOM OF STRUCTURE.
nLIGHT LIGHTING CONTROL SCHEDULE NOTES:
nLIGHT LIGHTING CONTROL SCHEDULE GENERAL NOTES:
• E.C. SHALL BE RESPONSIBLE FOR PROVIDING ALL LIGHTING CONTROL COMMISSIONING/PROGRAMMING OF ALL nLIGHT COMPONENTS. THE
COMMISSIONING/PROGRAMMING SHALL BE DONE BY A nLIGHT CERTIFIED TECHNICIAN.
• E.C. SHALL NOTIFY OWNER 1-WEEK PRIOR TO COMMISSIONING/PROGRAMMING OF THE SYSTEM SO THAT THE OWNER CAN PROVIDE
REPRESENTATIVES DURING THE COMMISSIONING/PROGRAMMING PERIOD.
1. PROVIDE ADDITIONAL POWER PACKS; SENSOR SWITCH PP20 AS NEED FOR QTY OF OCCUPANCY SENSORS/SWITCHES.
2. DEVICE COLOR SHALL MATCH WIRING DEVICES; REFER TO SPECIFICATIONS.
3. REFER TO MANUFACTURER DOCUMENTATION FOR QTY AND SIZE OF CONDUCTORS BETWEEN LOW VOLTAGE SWITCH, SENSOR(S) AND
POWER/RELAY PACKS.
4. PROVIDE SECONDARY RELAY PACK; SENSOR SWITCH SP20 AS NEEDED TO PROVIDE DUAL-LEVEL SWITCHING OF FIXTURES.
5. PROVIDE 0-10V DIMMING CONDUCTORS (GRAY & VIOLET) BETWEEN SWITCH AND LIGHT FIXTURES FOR DIMMING CONTROL.
6. PROGRAM ON/OFF TIMES OF RELAY'S AS DIRECTED BY OWNER. PROVIDE COMMISSIONING AS INDICATED IN GENERAL NOTES BELOW.
7. CUSTOM WALL STATION ENGRAVINGS IS REQUIRED FOR WALL STATION(S) AND SHALL BE SPECIFIED/COORDINATED WITH OWNER AFTER
PROGRAMING OF SYSTEM.
CONTROL & OCCUPANCY SENSOR SCHEDULE NOTES:
• E.C. SHALL BE RESPONSIBLE FOR THE PROGRAMMING/COMMISSIONING OF THE LIGHTING CONTROL SYSTEMS TO FUNCTION AS INDICATED ON
THE DRAWINGS AND SHALL INCLUDE ALL REQUIRED COST IN THE BASE BID. FOR AREAS WITH DAYLIGHTING CONTROL, THE DAYLIGHTING SET-
POINTS SHALL BE COORDINATED WITH THE OWNER FOR EACH AREA PRIOR TO FINAL PROGRAMMING OF THE DAYLIGHTING SENSOR(S). ALL
PROGRAMMING/COMMISSIONING SHALL BE DONE BY A FACTORY CERTIFIED OR TRAINED PERSON.
• LIGHTING IS SPACES WITH WIRELESS CONTROLS SHALL BE FIELD TUNED TO FOOTCANDLE LEVELS THAT ARE SATISFACTORY TO THE OWNER
DURING PROGRAMMING AND COMMISSIONING OF THE WIRELESS CONTROL SYSTEM.
GENERAL LIGHTING CONTROL NOTES:
SCALE: 3/4" = 1'-0"A CHANGING ROOM VANITY ELEVATION
J
J
FB
FBFB
J J
F
F
F
F F
CR
CR
FF
M
RM
R
M
RM
A
B
C
D
E
F
GH
J
K
3 4 5 6 7 8
MEN'S RM
[66]
WOMEN'S
RM
[64]
MECHANICAL
ROOM
[69]
VESTIBULE
[O-A]
HALLWAY
[O-C]
STORAGE
[63]
STAIRWELL
[O-B]
PIPE
CHASE
[O-Q]
ELEVATOR
[O-D]
MECH RM
[67]
CUST RM
[68]
CLASSROOM
[50]
DARK
ROOM
[59D]
COMPUTER
LAB
[59]
PHOTO
STUDIO
[51]
VESTIBULE
[59C]
OFFICE
[57]
EQUIP /
CHECK OUT
[59A]
STORAGE
[59B]
OFFICE
[55]
FILM
[59E]
ACOUSTICS
STUDIO
[52B]
STORAGE
[51A]
CHANGING
[51B]
VESTIBULE
[0-H]
OPTICS LAB
[52A]
PHYSICS
LAB
[52]
STORAGE
[52C]
6D-5
AC
AC
AC
AC AC
CD CD
6D-5
'S'
'R(SEC 2)'
'R'
6D-5
1
1
1
3D-4
2D-4
2D-4
3D-4
3D-4
1D-4
1D-4
1D-4
1D-4 1D-4
1D-4
1D-41D-41D-41D-4
1D-4
6D-5
AC
AC AC
AC
AC
AC
AC
2
2
2D-4
2D-4
2D-4
AC AC
2D-4
IEF-1
(A/EE2.0)(A/EE2.0)
R-27R-25R-25R-25
R-24
R-24
R-22
R-22
R-28 R-28 R-28
R-29
R-29
R-26
R-26
R-26R-29
R-40
R-40
R-40 R-40
R-40
R-42
R-43 R-43
R-45,47
R-39,41R-38 R-38
R-48 R-44,46 R-30 R-30
R-30
R-31
R-31
R-33,35R-32R-32R-32R-37R-37R-37 R-34,36
S-17S-17 S-17
S-15
S-14
S-14
S-16
S-16
S-23
S-23
S-18 S-18 S-19
S-21
S-21
S-21
S-20
R-18
R-20
R-18
R-18
R-18
R-18 R-19
R-19
R-19
R-20R-20
R-21
R-21
R-20
R-23
R-23
R-16
R-14
R-14
R-14
R-15
R-15
R-15
R-17
R-17R-17
S-20 S-20
S-19
S-22
S-22
S-22
S-22
S-24
S-24 S-24
S-20
R-22
R-15
R-24
R-24
R-22
R-22
R-21
R-23
R-48
S-25
R-49
S-20 R-13
R-49 R-49
S-26 S-28
S-30 S-31
S-33 S-35
R-19
R-21 R-23
R-30R-30
R-31 R-31R-42
R-42
R-42
R-13
S-19
S-18
S-16
S-14 1D-4 1D-4 1D-4 1D-4 1D-4 1D-4
1D-41D-41D-41D-41D-41D-4
1D-41D-41D-41D-41D-41D-4
33
3
3
3
4
4
4
R-57 R-57
R-55 R-55
5
EXISTING PANEL M
6 7 8
EXISTING FACP
7
7
9
10
1011
11
11
Bottom of Cable Tray
Power Source/J-box
5'
-
0
A
F
F
±
Heavy Duty #12 AWG Power Cord
(2) GFI NEMA Recptacles
Kellems Strain Relief
Daniel Woodhead 3085-10x-a-123-GFI
WORK TABLE
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:22127
04-28-2023 EE2.0
LEVEL 0
ELECTRICAL
PLAN
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
1 SLIM LINE AV SYSTEM CABINET. PROVIDE (2) DUPLEX
OUTLETS IN CABINET, EXTRA-DEEP BOX WITH 1 1/2" CONDUIT
TO ABOVE ACCESSIBLE CEILING FOR DATA/AV CABLING.
COORDINATE EXACT PLACEMENT OF BOXES WITH CABINET
AND KENDEN JENSEN (CAMPUS AV) PRIOR TO ROUGH IN.
PROVIDE A #10 GREEN INSULATED GROUND CONDUCTOR
FROM CABINET TO NEAREST ELECTRICAL ROOM GROUND
BAR. FIELD VERIFY FINAL LOCATION PRIOR TO ROUGH-IN.
2 MOUNT BEHIND TV, COORDINATE MOUNTING W/ TV MOUNTING
BRACKET PRIOR TO ROUGH IN. PROVIDE EXTRA DEEP BOX
SUCH AS, HUBBELL HBL260, W/ SINGLE GANG MUD RING W/ 1
1/4" C., TO ABOVE ACCESSIBLE CEILING. COORDINATE W/
KENDEN JENSEN (CAMPUS AV) PRIOR TO ROUGH IN.
3 MAINTAIN AND/OR RE-ESTABLISH EXISTING CIRCUITING TO
ELECTRICAL DEVICE.
4 NEW JUMBO 10FT. TELE POWER POLE SUCH AS WIREMOLD
N'800. PROVIDE ALL NECESSARY ACCESSORIES AND
COMPONENTS FOR ACCOMMODATING FURNITURE
CONNECTIONS FOR THE CABLING AND DEVICES SHOWN.
FINISH PER ARCHITECT.
5 ADD ALT. #6 PROVIDE AND INSTALL A PRO STUDIO RAIL
SYSTEM: MANFROTTO #FF3033 WITH TWO TELESCOPIC POSTS
AND ONE PANTOGRAPH EXTENSION ARM. INSTALL PER
MANUFACTURER'S INSTRUCTION. EXACT LOCATION PER
OWNER IN FIELD.
6 PROVIDE AND INSTALL (3) NEW 225A 3P BREAKERS IN
EXISTING MAIN PANEL. FOR NEW PANELS L, R, AND S.
REPLACE (3) EXISTING SPARE BREAKERS.
7 PROVIDE AND INSTALL A 2 1/2" C., 4-#4/0 CU + GND FROM EACH
NEW BREAKER TO EACH OF PANELS L, R, AND S. ROUTE
CONCEALED ABOVE LAY IN CEILINGS. DORE DRILL ALL WALL
AND FLOOR PENETRATIONS.
8 IT IS VERY CONGESTED ABOVE PANEL M WITH EXISTING
CONDUIT. E.C. SHALL VISIT SITE AND OBSERVER EXISTING
CONDITIONS AND INCLUDE THESE CONDITIONS IN BASE BID.
9 ADD ALT. #3 E.C. SHALL PROVIDE AND INSTALL A NEW RG-8U
COAX CABLE FROM THIS SPACE TO ROOF. COIL 50FT OF
CABLE ABOVE CEILING FOR OWNERS USE.
10 COORDINATE EXACT OUTLET LOCATION WITH OWNER PRIOR
TO ROUGH IN. LOCATE ACCESSIBLE TO LIGHT RAIL.
11 FIRE/SMOKE DAMPER. E.C. SHALL PROVIDE A 120V CIRCUIT TO
RELAY MODULE. DAMPER TO CLOSE UPON DETECTION.
KEY NOTES:#
SCALE: 1/8" = 1'-0"1 LEVEL 0 POWER PLAN OVERALL
NORTH
16'8'0"
ELECTRICAL FLOORBOX SCHEDULE
ID DESCRIPTION MFGR. FLOORBOX p/n COVERPLATE p/n
POWER
DEVICES
DATA
DEVICES NOTES
FB 2-GANG, MULTI-SERVICE CONCRETE
FLOORBOX, W/SURFACE STYLE
RECTANGULAR COVER, 3" MIN. POUR
HUBBELL CFB2G30CR 24GCCVRXXX (2) DUPLEX
RECPT.
1,2,3
1. PROVIDE REQUIRED SUB-PLATES FOR INSTALLATION OF POWER, DATA AND AV DEVICES.
2. E.C. SHALL FIELD LOCATE EXACT PLACEMENT OF FLOORBOX WITH ARCHITECT/OWNER PRIOR TO INSTALLATION.
3. PROVIDE CONDUIT (SIZE AS INDICATED ON DRAWINGS) TO ACCESSIBLE CEILING SPACE FOR ROUTING OF DATA AND/OR
LOW VOLTAGE CABLING.
FLOORBOX SCHEDULE NOTES:
SCALE: NONEACORD DROP DETAIL
A. PROVIDE ALL EQUIPMENT, MATERIALS AND LABOR NECESSARY TO EXPAND
THE EXISTING FCI FIRE ALARM SYSTEM. THE SYSTEM ADDITION SHALL
BE CONNECTED DIRECTLY TO THE EXISTING MAIN FIRE ALARM PANEL.
THE INSTALLATION SHALL BE AS RECOMMENDED BY THE MANUFACTURER
AND ACCEPTED BY THE LOCAL AHJ. WHEN THE SYSTEM IS COMPLETE, A
FACTORY REPRESENTATIVE SHALL TEST THE SYSTEM, MAKE
ADJUSTMENTS AND PLACE THE SYSTEM IN OPERATING ORDER.
B. WITHIN 30 DAYS AFTER THE CONTRACT AWARD AND PRIOR TO THE
PURCHASE OF ANY EQUIPMENT, THE FIRE ALARM SYSTEM CONTRACTOR
SHALL SUBMIT FOR APPROVAL SIX (6) COPIES OF THE FOLLOWING:
a. A LIST OF MATERIALS THAT ARE TO BE USED ON THE PROJECT,
INCLUDING MANUFACTURER, MODEL NUMBER AND TECHNICAL
INFORMATION.
b. PRELIMINARY CIRCUIT DIAGRAMS SHOWING INTERCONNECTION OF
ALL MONITORING, NOTIFICATION AND ANNUNCIATION DEVICES,
PANELS AND WIRING COUNTS. DIAGRAMS ARE TO BE 11"X17", DONE
IN A GOOD WORKMAN LIKE MANNER.
c. TECHNICAL MANUALS FOR ALL OF THE EQUIPMENT THAT IS TO BE
USED ON THE PROJECT.
d. SUBMIT SHOP DRAWINGS AND REQUIRED CALCULATIONS TO THE
LOCAL AHJ.
e. OBTAIN A WRITTEN LETTER OF ACCEPTANCE OF THE PROPOSED
SYSTEM AND INCLUDE WITH THE SHOP DRAWING SUBMITTAL TO THE
ENGINEER.
C. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED POWER
SUPPLIES, ELECTRONICS AND CONNECTIONS TO MODIFY EXISTING SYSTEM
TO ACCEPT NEW ADDITION. THE COMPLETE SYSTEM SHALL MAINTAIN A UL
LISTING.
D. ELECTRICAL CONTRACTOR SHALL INCLUDE A $2,000.00 CASH ALLOWANCE IN
THE BID FOR MISCELLANEOUS ADDITIONS AND/OR REQUIREMENTS
IMPOSED BY THE LOCAL AHJ.
FIRE ALARM EXPANSION NOTES:
MECHANICAL - INLINE EXHAUST FAN SCHEDULE
EQUIP. ID VOLTS/PH. HP CIRCUIT FEEDER NOTES
IEF-1 120 V/1 1/3 R-50 3/4"C.,2#12+1#12G
1. CIRCUIT AND CONTROL EXHAUST FAN WITH ROOM LIGHTING CIRCUIT.
2. E.C. SHALL PROVIDE LOCAL DISCONNECT RATED, THERMAL-OVERLOAD SWITCH FOR EQUIPMENT; SWITCH RATING SHALL NOT BE LESS THEN
CIRCUIT BREAKER SUPPLYING EQUIPMENT.
3. E.C. SHALL PROVIDE LOCAL DISCONNECT SWITCH FOR EQUIPMENT; SIZE AND TYPE AS INDICATED IN SCHEDULE. IF FUSED DISCONNECT IS
SPECIFIED FOR EQUIPMENT, FUSE PER EQUIPMENT NAMEPLATE RATING.
4. EQUIPMENT IS FACTORY SUPPLYED WITH DISCONNECT AND CONVIENENCE OUTLET; E.C. SHALL PROVIDE ALL NECESSARY CONNECTIONS.
5. INDOOR UNIT IS POWERED FROM OUTDOOR UNIT; COORDINATE EXACT NUMBER OF CONDUCTORS BETWEEN UNITS WITH M.C. PRIOR TO
ROUGH-IN.
6. PROVIDE 1/2" CONDUIT AND CONDUCTORS BETWEEN FURNACE AND CORRESPONDING OUTDOOR CONDENSING UNIT. COORDINATE SIZE AND
NUMBER OF CONDUCTORS WITH M.C. PRIOR TO ROUGH-IN. PROVIDE CONNECTION BETWEEN FURNACE AND ASSOCIATED OUTSIDE AIR
MOTORIZED DAMPER, COORDINATE WITH M.C.
7. E.C. SHALL PROVIDE COMBINATION STARTER/DISCONNECT SWITCH FOR EQUIPMENT; SIZE AND TYPE AS INDICATED IN SCHEDULE. PROVIDE
WITH CONTROL XFMR (2) SETS OF NO/NC CONTACTS, CONTROLS WITH M.C. PRIOR TO ROUGH-IN. FUSE DISCONNECT PER EQUIPMENT
NAMEPLATE RATING.
MECHANICAL SCHEDULE NOTES:
C
A
B
C
D
E
F
4 5
6 7
STAIRWELL
[1-P]PHYSICAL
GEOLOGY
ROOM
[158]
SEISMOGRAPH
ROOM
[154]
RESOURCE
ROOM
[150A]
LABORATORY
[141]
OFFICE
[150]
OFFICE
[148]
OFFICE
[146]
OFFICE
[144]
WOMEN'S
RM
[132]
MEN'S RM
[134]
LECTURE
HALL
[145]PREP/STORAGE
RM
[143]
HALLWAY
[I-N]
HALLWAY
[I-L]
HALLWAY
[I-G]
UNISEX RM
[136]
OFFICE
[142]
STAIRWELL
[1-H]ELEVATOR
[1-J]
AC
AC
AC
111111
2
3
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:22127
04-28-2023 EE2.1
LEVEL 1
ELECTRICAL
PLAN
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
1 DISCONNECT POWER TO EXISTING LAB TABLES. INTERCEPT
CONDUIT AND CONDUCTORS AND EXTEND UP TO J-BOX ON
BOTTOM OF NEW OWNER FURNISHED TABLES. E.C. SHALL
REFER TO SIMILAR WORK DONE IN ROOM 149 AS A MODEL
FOR WORK HERE. MAKE CONNECTIONS TO NEW TABLES.
2 E.C. SHALL PROTECT AND MAINTAIN ALL EXISTING LIGHTING
AND ELECTRICAL SERVICES IN THIS ROOM EXCEPT AS NOTED.
3 ADD ALT. #3 E.C. TO CORD DRILL ANY WALL OR CEILING
PENETRATIONS. E.C. TO PROVIDE AND INSTALL WIREMOLD
V2400 WITH ALL APPROPRIATED FITTINGS IN ALL FINISHED
SPACES.
KEY NOTES:#
NORTH
16'8'0"SCALE: 1/8" = 1'-0"1 LEVEL 1 POWER PLAN OVERALL
nD
nD
S
nD1
S
nD1
S
nD1
J
J
J
J
J
J
F
F
1
C
D
E
F
2 3 4 5
CLASSROOM
[277]
OFFICE
[259]
OFFICE
[261]
OFFICE
[263]
OFFICE
[265]
MEN'S
ROOM
[226]
WOMEN'S
ROOM
[220]
CLASSROOM
[276]
CUST RM
[267]
BDF RM
[280]
CUST RM
[228]
STORAGE
RM
[277A]
HALLWAY
[2-S]
ELEVATOR
[2-G]
STAIRWELL
[2-T]
BIO-CHEMISTRY
LAB
[272]
F3 F3 F3
F2
(TYP)
F2
(TYP)
F2
F3E
F2E
F2E
F2E
F2EF2E
'L''L (SEC 2)'
L-70
A
1
B
C
D
E
F
2 3 4 5 6 7 8
CLASSROOM
[270]
CLASSROOM
[268]
MEN'S RM
[266]
WOMEN'S
RM
[264]
OFFICE
[252]
OFFICE
[253]
OFFICE
[250]
OFFICE
[248]
OFFICE
[246]OFFICE
[244]
OFFICE
[242]
OFFICE
[240]
OFFICE
[238]
WORK
ROOM
[243]
OFFICE
[236]
OFFICE
[234]
OFFICE
[239]
OFFICE
[237]
OFFICE
[235]
OFFICE
[233]
OFFICE
[232]
CLASSROOM
[255]
CLASSROOM
[277]
OFFICE
[259]
OFFICE
[261]
OFFICE
[263]
OFFICE
[265]
MEN'S
ROOM
[226]WOMEN'S
ROOM
[220]
CLASSROOM
[276]
CUST RM
[267]
BDF RM
[280]
CUST RM
[228]
STORAGE
[258]
STORAGE
RM
[277A]
HALLWAY
[2-S]
LOUNGE
[2-V]
HALLWAY
[2-J]
SECRETARY/RECEPTION
RM
[230]
HALLWAY
[2-K]
CLASSROOM
[260]
CLASSROOM
[262]
HALLWAY
[2-L]
CUST STOR
[216]
STAIRWELL
[2-H]ELEVATOR
[2-G]
STAIRWELL
[2-T]
BIO-CHEMISTRY
LAB
[272]
AC AC
AC
AC
'L''L (SEC 2)'
6D-5
1
2D-4
2D-4
2D-4
1D-4
2D-4
2D-4
2D-4
1D-4
2D-4 2D-4
2D-42D-4
2
2
22
2
2 2D-4
AC
AC
ACACACACACAC
3 3
2D-3 2D-3
2D-3
4
4 (A/EE2.2)
5
5
5
5
6
L-68
L-49
L-49
L-48
L-48
L-50 L-50
L-53 L-53
L-71,73,75
L-64,66
L-44
L-44
L-46
L-46
L-46L-43
L-43
L-43
L-69 L-67
L-45
L-45
L-44
L-44
L-47
L-47
L-47L-47L-45
L-45
77
L-50 L-50
L-51
L-51
L-57 L-59
L-56
L-61
L-58 L-60
L-52 L-55
L-54
WEATHER HEAD
COIL 48" OF EXCESS
CABLE ON MAST
FOR USE BY OWNER
SEAL ROOF
PENETRACTIONS AS
DIRECTED BY ROOFING
CONTRACTOR
2" RIGID CONDUIT ANCHOR TO
STRUCTURE
RG-86 COAX CABLE
TO PHYSICS LAB
ROOM 52
2'
-
0
"
ROOF
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:22127
04-28-2023 EE2.2
LEVEL 2
ELECTRICAL
PLAN
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
1 SLIM LINE AV SYSTEM CABINET. PROVIDE (2) DUPLEX
OUTLETS IN CABINET, EXTRA-DEEP BOX WITH 1 1/2" CONDUIT
TO ABOVE ACCESSIBLE CEILING FOR DATA/AV CABLING.
COORDINATE EXACT PLACEMENT OF BOXES WITH CABINET
AND KENDEN JENSEN (CAMPUS AV) PRIOR TO ROUGH IN.
PROVIDE A #10 GREEN INSULATED GROUND CONDUCTOR
FROM CABINET TO NEAREST ELECTRICAL ROOM GROUND
BAR. FIELD VERIFY FINAL LOCATION PRIOR TO ROUGH-IN.
2 LOCATE DEVICES IN CEILING BEHIND T.V. ADJACENT TO
MOUNTING POST. PROVIDE EXTRA DEEP BOX SUCH AS;
HUBBELL HBL260, WITH SINGLE GANG MUD RING AND BRUSH
STYLE PLATE, MOUNTED FLUSH WITH CEILING.
3 MOUNT RECEPTACLES UNDER THE COUNTER RECESSED IN
CASE WORK. COORDINATE EXACT LOCATION WITH
CASEWORK SHOP DRAWINGS.
4 ADD ALT. #3 E.C. TO CORD DRILL ANY WALL OR CEILING
PENETRATIONS. E.C. TO PROVIDE AND INSTALL WIREMOLD
V2400 WITH ALL APPROPRIATED FITTINGS IN ALL FINISHED
SPACES.
5 SERVICE PANEL SUCH AS LAB LINK #CP24X24-CP-6S-2C W/ SIX
120V, 20A SINGLE RECEPTACLES. PROVIDE ALL NECESSARY
COMPONENTS, DEVICES, AND CONNECTIONS FOR A
COMPLETE SYSTEM.
6 PROVIDE AND INSTALL A 2 1/2" C., 4-#4/0 CU + GND FROM EACH
NEW BREAKER TO EACH OF PANELS L, R, AND S. ROUTE
CONCEALED ABOVE LAY IN CEILINGS. DORE DRILL ALL WALL
AND FLOOR PENETRATIONS.
7 FUME HOODS - MAKE ALL REQUIRED CONNECTIONS TO FUME
HOOD AND FUME HOOD CONTROLS.
KEY NOTES:#
SCALE: 1/8" = 1'-0"1 LEVEL 2 OVERALL LIGHTING PLAN
SCALE: 1/8" = 1'-0"2 LEVEL 2 OVERALL PLAN
16'8'0"
NORTH
16'8'0"
NORTH
A. PROVIDE ALL EQUIPMENT, MATERIALS AND LABOR NECESSARY TO EXPAND
THE EXISTING FCI FIRE ALARM SYSTEM. THE SYSTEM ADDITION SHALL
BE CONNECTED DIRECTLY TO THE EXISTING MAIN FIRE ALARM PANEL.
THE INSTALLATION SHALL BE AS RECOMMENDED BY THE MANUFACTURER
AND ACCEPTED BY THE LOCAL AHJ. WHEN THE SYSTEM IS COMPLETE, A
FACTORY REPRESENTATIVE SHALL TEST THE SYSTEM, MAKE
ADJUSTMENTS AND PLACE THE SYSTEM IN OPERATING ORDER.
B. WITHIN 30 DAYS AFTER THE CONTRACT AWARD AND PRIOR TO THE
PURCHASE OF ANY EQUIPMENT, THE FIRE ALARM SYSTEM CONTRACTOR
SHALL SUBMIT FOR APPROVAL SIX (6) COPIES OF THE FOLLOWING:
a. A LIST OF MATERIALS THAT ARE TO BE USED ON THE PROJECT,
INCLUDING MANUFACTURER, MODEL NUMBER AND TECHNICAL
INFORMATION.
b. PRELIMINARY CIRCUIT DIAGRAMS SHOWING INTERCONNECTION OF
ALL MONITORING, NOTIFICATION AND ANNUNCIATION DEVICES,
PANELS AND WIRING COUNTS. DIAGRAMS ARE TO BE 11"X17", DONE
IN A GOOD WORKMAN LIKE MANNER.
c. TECHNICAL MANUALS FOR ALL OF THE EQUIPMENT THAT IS TO BE
USED ON THE PROJECT.
d. SUBMIT SHOP DRAWINGS AND REQUIRED CALCULATIONS TO THE
LOCAL AHJ.
e. OBTAIN A WRITTEN LETTER OF ACCEPTANCE OF THE PROPOSED
SYSTEM AND INCLUDE WITH THE SHOP DRAWING SUBMITTAL TO THE
ENGINEER.
C. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED POWER
SUPPLIES, ELECTRONICS AND CONNECTIONS TO MODIFY EXISTING SYSTEM
TO ACCEPT NEW ADDITION. THE COMPLETE SYSTEM SHALL MAINTAIN A UL
LISTING.
D. ELECTRICAL CONTRACTOR SHALL INCLUDE A $2,000.00 CASH ALLOWANCE IN
THE BID FOR MISCELLANEOUS ADDITIONS AND/OR REQUIREMENTS
IMPOSED BY THE LOCAL AHJ.
FIRE ALARM EXPANSION NOTES:
SCALE: NONEAROOF CONDUIT DETAIL - HAM RADIO ANTENNA
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:22127
04-28-2023 EE3.0
PANEL
SCHEDULES
22.0540
04/28/2023
[ SET PROJECT INFORMATION
ADDRESS TEXT FIELD AND SET
LOCATION UNDER ENERGY
SETTINGS IF APPLICABLE ]
Romney 2023
Remodel
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:44 A
TOTAL AMPS:160 A 180 A 167 A
TOTAL LOAD:19.2 kVA 21.5 kVA 19.9 kVA
83 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 84
81 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 82
79 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 80
77 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 78
75 167 0 1 20 A -- SPARE 76
73 167 0 1 20 A -- SPARE 74
71
Lab Equipment 20 A 3
167 0 1 20 A -- SPARE 72
69 Fume Hood 20 A 1 500 1280 1 20 A Lighting 70
67 Fume Hood 20 A 1 500 360 1 20 A Receptacle 68
65 Receptacle 20 A 1 360 2500 66
63 Receptacle 20 A 1 360 2500 2 20 A Lab Equipment
64
61 Receptacle 20 A 1 360 360 1 20 A Receptacle 62
59 Receptacle 20 A 1 360 360 1 20 A Receptacle 60
57 Receptacle 20 A 1 360 360 1 20 A Receptacle 58
55 Receptacle 20 A 1 360 360 1 20 A Receptacle 56
53 Receptacle 20 A 1 360 360 1 20 A Receptacle 54
51 Receptacle 20 A 1 360 360 1 20 A Receptacle 52
49 Receptacle 20 A 1 720 720 1 20 A Receptacle 50
47 Receptacle 20 A 1 720 720 1 20 A Receptacle 48
45 Receptacle 20 A 1 720 540 1 20 A Receptacle 46
43 Receptacle 20 A 1 540 720 1 20 A Receptacle 44
41 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 42
39 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 40
37 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 38
35 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 36
33 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 34
31 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 32
29 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 30
27 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 28
25 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 26
23 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 24
21 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 22
19 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 20
17 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 18
15 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 16
13 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 14
11 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 12
9 1000 1000 1 20 A -- Existing Circuit 10
7 1000 1000 8
5
Existing Circuit -- 30 A 3
1000 1000 2 30 A -- Existing Circuit
6
3 1000 1000 4
1 Existing Circuit -- 20 A 2
1000 1000 2 20 A -- Existing Circuit
2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:Recessed WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO Romney 2023 Remodel
LOCATION: VOLTAGE:120/208 Wye A.I.C. RATING:10K PROJECT:
PANEL: L
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:103 A
TOTAL AMPS:128 A 210 A 201 A
TOTAL LOAD:15.4 kVA 24.0 kVA 23.0 kVA
83 SPARE -- 20 A 1 0 -- 1 -- -- PREPARED SPACE 84
81 SPARE -- 20 A 1 0 -- 1 -- -- PREPARED SPACE 82
79 SPARE -- 20 A 1 0 -- 1 -- -- PREPARED SPACE 80
77 SPARE -- 20 A 1 0 -- 1 -- -- PREPARED SPACE 78
75 SPARE -- 20 A 1 0 -- 1 -- -- PREPARED SPACE 76
73 SPARE -- 20 A 1 0 -- 1 -- -- PREPARED SPACE 74
71 SPARE -- 20 A 1 0 -- 1 -- -- PREPARED SPACE 72
69 SPARE -- 20 A 1 0 -- 1 -- -- PREPARED SPACE 70
67 SPARE -- 20 A 1 0 -- 1 -- -- PREPARED SPACE 68
65 SPARE -- 20 A 1 0 -- 1 -- -- PREPARED SPACE 66
63 SPARE -- 20 A 1 0 -- 1 -- -- PREPARED SPACE 64
61 SPARE -- 20 A 1 0 -- 1 -- -- PREPARED SPACE 62
59 SPARE -- 20 A 1 0 -- 1 -- -- PREPARED SPACE 60
57 Receptacle 20 A 1 360 -- 1 -- -- PREPARED SPACE 58
55 Receptacle 20 A 1 360 -- 1 -- -- PREPARED SPACE 56
53 Lighting 20 A 1 1556 2000 1 20 A Track Lighting 54
51 Lighting 20 A 1 1437 1250 1 20 A Track Lighting 52
49 Receptacle 20 A 1 540 864 1 20 A IEF-1 50
47 2500 360 1 20 A Receptacle 48
45 Electric Clothes Dryer 20 A 2
2500 2500 46
43 Receptacle 20 A 1 720 2500 2 20 A Receptacle
44
41 2500 720 1 20 A Receptacle 42
39 Receptacle 20 A 2
2500 900 1 20 A Receptacle 40
37 Receptacle 20 A 1 540 360 1 20 A Receptacle 38
35 2500 2500 36
33 Receptacle 20 A 2
2500 2500 2 20 A Receptacle
34
31 Receptacle 20 A 1 1360 540 1 20 A Receptacle 32
29 Receptacle 20 A 1 540 900 1 20 A Receptacle 30
27 Receptacle 20 A 1 360 540 1 20 A Receptacle 28
25 Receptacle 20 A 1 540 540 1 20 A Receptacle 26
23 Receptacle 20 A 1 720 720 1 20 A Receptacle 24
21 Receptacle 20 A 1 720 900 1 20 A Receptacle 22
19 Receptacle 20 A 1 900 720 1 20 A Receptacle 20
17 Receptacle 20 A 1 540 900 1 20 A Receptacle 18
15 Receptacle 20 A 1 720 360 1 20 A Receptacle 16
13 Receptacle 20 A 1 360 540 1 20 A Receptacle 14
11 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 12
9 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 10
7 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 8
5 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 6
3 1000 1000 4
1 Existing Circuit -- 30 A 2
1000 1000 2 30 A -- Existing Circuit
2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:Recessed WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO Romney 2023 Remodel
LOCATION: VOLTAGE:120/208 Wye A.I.C. RATING:10K PROJECT:
PANEL: R
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:39 A
TOTAL AMPS:84 A 75 A 71 A
TOTAL LOAD:10.0 kVA 8.9 kVA 8.5 kVA
41 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 42
39 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 40
37 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 38
35 Receptacle 20 A 1 540 0 1 20 A -- SPARE 36
33 Receptacle 20 A 1 720 0 1 20 A -- SPARE 34
31 Receptacle 20 A 1 540 1260 1 20 A Lighting 32
29 Lighting 20 A 1 860 720 1 20 A Receptacle 30
27 Lighting 20 A 1 1510 540 1 20 A Receptacle 28
25 Receptacle 20 A 1 180 720 1 20 A Receptacle 26
23 Receptacle 20 A 1 720 540 1 20 A Receptacle 24
21 Receptacle 20 A 1 540 720 1 20 A Receptacle 22
19 Receptacle 20 A 1 900 900 1 20 A Receptacle 20
17 Receptacle 20 A 1 540 540 1 20 A Receptacle 18
15 Receptacle 20 A 1 360 540 1 20 A Receptacle 16
13 Existing Circuit -- 20 A 1 1000 540 1 20 A Receptacle 14
11 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 12
9 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 10
7 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 8
5 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 6
3 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 4
1 Existing Circuit -- 20 A 1 1000 1000 1 20 A -- Existing Circuit 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:Recessed WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO Romney 2023 Remodel
LOCATION: VOLTAGE:120/208 Wye A.I.C. RATING:10K PROJECT:
PANEL: S
PAYNE ENGINEERING