HomeMy WebLinkAboutLOAD SHORT FORM - 23-00640 - 494 S Teton Ave - New Shop MechanicalBold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:03:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 1 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Load Short Form Date:Entire House By: Project Information For: Design Information InfiltrationClgHtg SimplifiedMethod88-6Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1376Design TD (°F) H-Daily range 5030Inside humidity (%) -2835Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make York Make York Trade YORK BY JOHNSON CONTROLS Trade YORK Model TG9S080C16MP11 Cond YCD24B21 AHRI ref 2008575 Coil AD-36M*****1++TXV+TD AHRI ref 10276577 Efficiency 95.5 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh80000 Sensible cooling Btuh16520 Heating output Btuh78000 Latent cooling Btuh7080 Temperature rise °F61 Total cooling Btuh23600 Actual air flow cfm1400 Actual air flow cfm787 Air flow factor cfm/Btuh0.034 Air flow factor cfm/Btuh0.047 Static pressure in H2O0.50 Static pressure in H2O0.50 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) zone 1 756 17152 5641 578 267 zone 3 main 1757 0 3162 0 150 zone 2 1229 24404 9245 822 437 Entire House 3742 41556 16647 1400 787 Other equip loads 0 0 Equip. @ 1.00 RSM 16647 Latent cooling 0 TOTALS 3742 41556 16647 1400 787 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:03:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 2 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Load Short Form Date:zone 1 By: Project Information For: Design Information InfiltrationClgHtg SimplifiedMethod88-6Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1376Design TD (°F) H-Daily range 5030Inside humidity (%) -2835Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) bed 1 2nd 208 5853 1559 197 74 1 bath 2nd 66 1982 346 67 16 1 kit living 2nd 482 9316 3737 314 177 zone 1 756 17152 5641 578 267 Other equip loads 0 0 Equip. @ 1.00 RSM 5641 Latent cooling 0 TOTALS 756 17152 5641 578 267 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:03:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 3 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Load Short Form Date:zone 2 By: Project Information For: Design Information InfiltrationClgHtg SimplifiedMethod88-6Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1376Design TD (°F) H-Daily range 5030Inside humidity (%) -2835Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) mech rm 2nd 52 1485 257 50 12 2 kit living 2nd 475 5812 2997 196 142 3 bed 2nd 310 7474 2826 252 134 2 bed 2nd 320 7591 2812 256 133 2bath 2nd 72 2041 353 69 17 zone 2 1229 24404 9245 822 437 Other equip loads 0 0 Equip. @ 1.00 RSM 9245 Latent cooling 0 TOTALS 1229 24404 9245 822 437 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:03:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 4 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Load Short Form Date:zone 3 main By: Project Information For: Design Information InfiltrationClgHtg SimplifiedMethod88-6Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1376Design TD (°F) H-Daily range 5030Inside humidity (%) -2835Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) bath main 83 0 37 0 2 living room main 1103 0 2206 0 104 shower main 85 0 48 0 2 kitchen main 384 0 872 0 41 Storage 1 104 0 0 0 0 zone 3 main 1757 0 3162 0 150 Other equip loads 0 0 Equip. @ 1.00 RSM 3162 Latent cooling 0 TOTALS 1757 0 3162 0 150 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:03:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 1 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Loads for Multiple Orientations Date:Entire House By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) )H(33-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh)17902 18008 16667 16841 16647 17202 16963 17929 Latent Load (Btuh)0 0 0 0 0 0 0 0 Total Load (Btuh)17902 18008 16667 16841 16647 17202 16963 17929 Heating AVF (cfm)1400 1400 1400 1400 1400 1400 1400 1400 Cooling AVF (cfm)787 787 787 787 787 787 787 787 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction Front Door faces 0 5000 10000 15000 20000 N NE E SE S SW W NW Front Door faces SouthCurrent Orientation: Front Door faces NortheastHighest Cooling Load: Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:03:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 2 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Loads for Multiple Orientations Date:zone 1 By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) )H(33-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh)7144 7930 8401 6632 5641 6459 7484 6937 Latent Load (Btuh)0 0 0 0 0 0 0 0 Total Load (Btuh)7144 7930 8401 6632 5641 6459 7484 6937 Heating AVF (cfm)578 578 578 578 578 578 578 578 Cooling AVF (cfm)311 347 369 303 267 295 337 295 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction Front Door faces 0 2000 4000 6000 8000 10000 N NE E SE S SW W NW Front Door faces SouthCurrent Orientation: Front Door faces EastHighest Cooling Load: Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:03:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 3 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Loads for Multiple Orientations Date:zone 3 main By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) )H(33-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh)3517 2680 1968 2491 3162 3223 3294 3742 Latent Load (Btuh)0 0 0 0 0 0 0 0 Total Load (Btuh)3517 2680 1968 2491 3162 3223 3294 3742 Heating AVF (cfm)0 0 0 0 0 0 0 0 Cooling AVF (cfm)153 117 87 114 150 147 148 159 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction Front Door faces 0 1000 2000 3000 4000 N NE E SE S SW W NW Front Door faces SouthCurrent Orientation: Front Door faces NorthwestHighest Cooling Load: Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:03:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 4 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Loads for Multiple Orientations Date:zone 2 By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) )H(33-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh)8824 7880 7989 8516 9245 9087 9637 9380 Latent Load (Btuh)0 0 0 0 0 0 0 0 Total Load (Btuh)8824 7880 7989 8516 9245 9087 9637 9380 Heating AVF (cfm)822 822 822 822 822 822 822 822 Cooling AVF (cfm)384 344 351 389 437 416 434 399 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction Front Door faces 0 2000 4000 6000 8000 10000 N NE E SE S SW W NW Front Door faces SouthCurrent Orientation: Front Door faces WestHighest Cooling Load: Bold/italic values have been manually overridden 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 1 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Building Analysis Date:Entire House By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 16.870023.2Walls 5.2215813.7Glazing 000Doors 8.033181.7Ceilings 5.823940.70.7Floors 22.392514.0Infiltration 41.917432Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.041556Total Cooling Walls Glazing Ceilings FloorsInfiltration Ducts % of loadBtuhBtuh/ft²Component 5.89590.4Walls 26.1434627.6Glazing 000Doors 10.918120.9Ceilings 2.54130.1Floors 6.911420.5Infiltration 47.97975Ducts 00Ventilation 00Internal gains 00Blower 0Adjustments 100.016647Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 53 Btuh/ft²-°F WARNING: window to floor area ratio = 4.2% - less than 5%. Bold/italic values have been manually overridden 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 2 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Building Analysis Date:zone 1 By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 16.929064.9Walls 6.3108722.8Glazing 000Doors 7.412641.7Ceilings 4.78081.31.3Floors 22.738916.1Infiltration 41.97195Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.017152Total Cooling Walls Glazing Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 4.62600.4Walls 17.9101121.2Glazing 000Doors 12.26900.9Ceilings 2.51390.2Floors 5.53120.5Infiltration 57.23229Ducts 00Ventilation 00Internal gains 00Blower 0Adjustments 100.05641Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 49 Btuh/ft²-°F Data entries checked. Bold/italic values have been manually overridden 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 3 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Building Analysis Date:zone 2 By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 16.840954.9Walls 4.4107222.8Glazing 000Doors 8.420541.7Ceilings 6.515861.31.3Floors 22.053606.1Infiltration 41.910237Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.024404Total Cooling Walls Glazing Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 4.03660.4Walls 19.1176237.5Glazing 000Doors 12.111220.9Ceilings 3.02730.2Floors 4.74300.5Infiltration 57.25291Ducts 00Ventilation 00Internal gains 00Blower 0Adjustments 100.09245Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 47 Btuh/ft²-°F WARNING: window to floor area ratio = 3.8% - less than 5%. Bold/italic values have been manually overridden 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 4 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Building Analysis Date:zone 3 main By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating % of loadBtuhBtuh/ft²Component 000Walls 000Glazing 000Doors 000Ceilings 0000Floors 000Infiltration 00Ducts 00Piping 00Humidification 00Ventilation0Adjustments 00Total Cooling Walls Glazing Infiltration % of loadBtuhBtuh/ft²Component 10.53330.4Walls 76.8242938.6Glazing 000Doors 000Ceilings 000Floors 12.74000.5Infiltration 00Ducts 00Ventilation 00Internal gains 00Blower 0Adjustments 100.03162Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 66 Btuh/ft²-°F WARNING: window to floor area ratio = 3.6% - less than 5%. 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 1 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:Entire House By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 970.4410884.9421.00.065220n 2020.4422544.9421.00.065456e 1050.4411694.9421.00.065237s 2230.4424904.9421.00.065504w 6260.4470024.9421.00.0651417all 12F-0sw: Frm wall, mtl ext, 1/2" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 410.440021.00.06592n 1880.440021.00.065425e 1040.440021.00.065236s 3330.440021.00.065753all Partitions (none) Windows 4A4-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.31); 6.67 ft head ht 38112.072222.800.30032n 167535.1108722.800.30048e 166435.10000.30047e 31020.235022.800.30015s 31720.20000.30016s 434627.6215813.700.300158all Doors (none) Ceilings 16B-44md: Attic ceiling, mtl roof mat, r-5 roof ins, r-44 ceil ins, 1/2" gypsum board int fnsh 18120.9133181.6744.00.0221985 Floors 19C-19cscp: Flr floor, frm flr, 6" thkns, carpet flr fnsh, r-2 ext ins, r-19 cav ins, tight crwl ovr, r-11 wall insul 4130.2223941.2930.00.0491855 22A-tpl: Bg floor, light dry soil, on grade depth 0.989102 00000 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 2 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:zone 1 By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 970.4410884.9421.00.065220n 780.448694.9421.00.065176e 850.449484.9421.00.065192w 2600.4429064.9421.00.065588all Partitions (none) Windows 4A4-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.31); 6.67 ft head ht 38112.072222.800.30032n 56235.136522.800.30016e 94319.8108722.800.30048all Doors (none) Ceilings 16B-44md: Attic ceiling, mtl roof mat, r-5 roof ins, r-44 ceil ins, 1/2" gypsum board int fnsh 6900.9112641.6744.00.022756 Floors 19C-19cscp: Flr floor, frm flr, 6" thkns, carpet flr fnsh, r-2 ext ins, r-19 cav ins, tight crwl ovr, r-11 wall insul 1390.228081.2930.00.049626 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 3 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:zone 3 main By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 1/2" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 410.440021.00.06592n 1880.440021.00.065425e 1040.440021.00.065236s 3330.440021.00.065753all Partitions (none) Windows 4A4-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.31); 6.67 ft head ht 166435.10000.30047e 31720.20000.30016s 198031.40000.30063all Doors (none) Ceilings (none) Floors 22A-tpl: Bg floor, light dry soil, on grade depth 0.989102 00000 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 4 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:zone 2 By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 1240.4413854.9421.00.065280e 1050.4411694.9421.00.065237s 1380.4415414.9421.00.065312w 3660.4440954.9421.00.065829all Partitions (none) Windows 4A4-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.31); 6.67 ft head ht 111335.172222.800.30032e 31020.235022.800.30015s 142330.3107222.800.30047all Doors (none) Ceilings 16B-44md: Attic ceiling, mtl roof mat, r-5 roof ins, r-44 ceil ins, 1/2" gypsum board int fnsh 11220.9120541.6744.00.0221229 Floors 19C-19cscp: Flr floor, frm flr, 6" thkns, carpet flr fnsh, r-2 ext ins, r-19 cav ins, tight crwl ovr, r-11 wall insul 2730.2215861.2930.00.0491229 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 5 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:bath main By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 1/2" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 180.440021.00.06540n Partitions (none) Windows (none) Doors (none) Ceilings (none) Floors 22A-tpl: Bg floor, light dry soil, on grade depth 0.9895 00000 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 6 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:shower main By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 1/2" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 230.440021.00.06552n Partitions (none) Windows (none) Doors (none) Ceilings (none) Floors 22A-tpl: Bg floor, light dry soil, on grade depth 0.9897 00000 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 7 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:kitchen main By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 1/2" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 780.440021.00.065176e Partitions (none) Windows 4A4-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.31); 6.67 ft head ht 56235.10000.30016e Doors (none) Ceilings (none) Floors 22A-tpl: Bg floor, light dry soil, on grade depth 0.98924 00000 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 8 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:Storage 1 By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls (none) Partitions (none) Windows (none) Doors (none) Ceilings (none) Floors (none) 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 9 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:living room main By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 1/2" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 1100.440021.00.065249e 1040.440021.00.065236s 2140.440021.00.065485all Partitions (none) Windows 4A4-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.31); 6.67 ft head ht 110135.10000.30031e 31720.20000.30016s 141830.20000.30047all Doors (none) Ceilings (none) Floors 22A-tpl: Bg floor, light dry soil, on grade depth 0.98967 00000 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 10 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:bed 1 2nd By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 500.445534.9421.00.065112n 460.445144.9421.00.065104w 950.4410674.9421.00.065216all Partitions (none) Windows 4A4-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.31); 6.67 ft head ht 19312.036522.800.30016n Doors (none) Ceilings 16B-44md: Attic ceiling, mtl roof mat, r-5 roof ins, r-44 ceil ins, 1/2" gypsum board int fnsh 1900.913481.6744.00.022208 Floors 19C-19cscp: Flr floor, frm flr, 6" thkns, carpet flr fnsh, r-2 ext ins, r-19 cav ins, tight crwl ovr, r-11 wall insul 340.221991.2930.00.049154 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 11 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:1 bath 2nd By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 390.444354.9421.00.06588w Partitions (none) Windows (none) Doors (none) Ceilings 16B-44md: Attic ceiling, mtl roof mat, r-5 roof ins, r-44 ceil ins, 1/2" gypsum board int fnsh 600.911101.6744.00.02266 Floors 19C-19cscp: Flr floor, frm flr, 6" thkns, carpet flr fnsh, r-2 ext ins, r-19 cav ins, tight crwl ovr, r-11 wall insul 120.22671.2930.00.04952 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 12 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:1 kit living 2nd By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 480.445354.9421.00.065108n 780.448694.9421.00.065176e 1260.4414054.9421.00.065284all Partitions (none) Windows 4A4-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.31); 6.67 ft head ht 18912.035722.800.30016n 56235.136522.800.30016e 75123.772222.800.30032all Doors (none) Ceilings 16B-44md: Attic ceiling, mtl roof mat, r-5 roof ins, r-44 ceil ins, 1/2" gypsum board int fnsh 4400.918061.6744.00.022482 Floors 19C-19cscp: Flr floor, frm flr, 6" thkns, carpet flr fnsh, r-2 ext ins, r-19 cav ins, tight crwl ovr, r-11 wall insul 930.225421.2930.00.049420 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 13 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:mech rm 2nd By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 280.443164.9421.00.06564w Partitions (none) Windows (none) Doors (none) Ceilings 16B-44md: Attic ceiling, mtl roof mat, r-5 roof ins, r-44 ceil ins, 1/2" gypsum board int fnsh 470.91871.6744.00.02252 Floors 19C-19cscp: Flr floor, frm flr, 6" thkns, carpet flr fnsh, r-2 ext ins, r-19 cav ins, tight crwl ovr, r-11 wall insul 120.22671.2930.00.04952 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 14 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:2bath 2nd By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 390.444354.9421.00.06588w Partitions (none) Windows (none) Doors (none) Ceilings 16B-44md: Attic ceiling, mtl roof mat, r-5 roof ins, r-44 ceil ins, 1/2" gypsum board int fnsh 650.911201.6744.00.02272 Floors 19C-19cscp: Flr floor, frm flr, 6" thkns, carpet flr fnsh, r-2 ext ins, r-19 cav ins, tight crwl ovr, r-11 wall insul 160.22921.2930.00.04972 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 15 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:2 bed 2nd By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 500.445574.9421.00.065113s 710.447904.9421.00.065160w 1210.4413474.9421.00.065273all Partitions (none) Windows 4A4-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.31); 6.67 ft head ht 31020.235022.800.30015s Doors (none) Ceilings 16B-44md: Attic ceiling, mtl roof mat, r-5 roof ins, r-44 ceil ins, 1/2" gypsum board int fnsh 2920.915351.6744.00.022320 Floors 19C-19cscp: Flr floor, frm flr, 6" thkns, carpet flr fnsh, r-2 ext ins, r-19 cav ins, tight crwl ovr, r-11 wall insul 710.224131.2930.00.049320 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 16 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:3 bed 2nd By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 640.447134.9421.00.065144e 550.446134.9421.00.065124s 1190.4413264.9421.00.065268all Partitions (none) Windows 4A4-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.31); 6.67 ft head ht 55135.135722.800.30016e Doors (none) Ceilings 16B-44md: Attic ceiling, mtl roof mat, r-5 roof ins, r-44 ceil ins, 1/2" gypsum board int fnsh 2830.915181.6744.00.022310 Floors 19C-19cscp: Flr floor, frm flr, 6" thkns, carpet flr fnsh, r-2 ext ins, r-19 cav ins, tight crwl ovr, r-11 wall insul 690.224001.2930.00.049310 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 17 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Date:2 kit living 2nd By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) SimplifiedMethod)H(33-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, mtl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud, r-1 int bd ins 600.446724.9421.00.065136e Partitions (none) Windows 4A4-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.31); 6.67 ft head ht 56235.136522.800.30016e Doors (none) Ceilings 16B-44md: Attic ceiling, mtl roof mat, r-5 roof ins, r-44 ceil ins, 1/2" gypsum board int fnsh 4340.917941.6744.00.022475 Floors 19C-19cscp: Flr floor, frm flr, 6" thkns, carpet flr fnsh, r-2 ext ins, r-19 cav ins, tight crwl ovr, r-11 wall insul 1060.226131.2930.00.049475 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 1 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Project Summary Date:Entire House By: Project Information For: Notes: Design Information Rexburg Madison Co, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F88Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F13Daily range H Relative humidity %50Moisture difference gr/lb-28 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh24124 Structure Btuh8673 Ducts Btuh17432 Ducts Btuh7975Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none)Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh41556 Use manufacturer's data y Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh16647 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh-1506 Ducts Btuh-110Central vent (0 cfm)Btuh0 CoolingHeating (none)37421985Area (ft²)Equipment latent load Btuh0 2993215876Volume (ft³)Air changes/hour 0.190.50 Equipment Total Load (Sen+Lat)Btuh16647 Equiv. AVF (cfm)95132 Req. total capacity at 0.70 SHR ton2.0 Heating Equipment Summary Cooling Equipment Summary Make York Make YorkTradeYORK BY JOHNSON CONTROLS Trade YORK Model TG9S080C16MP11 Cond YCD24B21AHRI ref 2008575 Coil AD-36M*****1++TXV+TD AHRI ref 10276577Efficiency95.5 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh80000 Sensible cooling Btuh16520Heating output Btuh78000 Latent cooling Btuh7080 Temperature rise °F61 Total cooling Btuh23600Actual air flow cfm1400 Actual air flow cfm787 Air flow factor cfm/Btuh0.034 Air flow factor cfm/Btuh0.047Static pressure in H2O0.50 Static pressure in H2O0.50 Space thermostat Load sensible heat ratio 1.00 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 2 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Project Summary Date:zone 1 By: Project Information For: Notes: Design Information Rexburg Madison Co, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F88Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F13Daily range H Relative humidity %50Moisture difference gr/lb-28 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh9957 Structure Btuh2413 Ducts Btuh7195 Ducts Btuh3229Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh17152 Use manufacturer's data y Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh5641 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh-411 Ducts Btuh-42Central vent (0 cfm)Btuh0 CoolingHeating756756Area (ft²)Equipment latent load Btuh0 60486048Volume (ft³)Air changes/hour 0.260.55 Equipment Total Load (Sen+Lat)Btuh5641 Equiv. AVF (cfm)2656 Req. total capacity at 0.70 SHR ton0.7 Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/aTraden/a Trade n/a Model n/a Cond n/aAHRI ref n/a Coil n/a AHRI ref n/aEfficiencyn/a Efficiency n/a Heating input Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 3 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Project Summary Date:zone 2 By: Project Information For: Notes: Design Information Rexburg Madison Co, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F88Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F13Daily range H Relative humidity %50Moisture difference gr/lb-28 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh14167 Structure Btuh3954 Ducts Btuh10237 Ducts Btuh5291Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh24404 Use manufacturer's data y Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh9245 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh-567 Ducts Btuh-68Central vent (0 cfm)Btuh0 CoolingHeating12291229Area (ft²)Equipment latent load Btuh0 98289828Volume (ft³)Air changes/hour 0.220.47 Equipment Total Load (Sen+Lat)Btuh9245 Equiv. AVF (cfm)3677 Req. total capacity at 0.70 SHR ton1.1 Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/aTraden/a Trade n/a Model n/a Cond n/aAHRI ref n/a Coil n/a AHRI ref n/aEfficiencyn/a Efficiency n/a Heating input Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:03 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 4 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Project Summary Date:zone 3 main By: Project Information For: Notes: Design Information Rexburg Madison Co, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F88Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F13Daily range H Relative humidity %50Moisture difference gr/lb-28 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh0 Structure Btuh3162 Ducts Btuh0 Ducts Btuh0Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh0 Use manufacturer's data y Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh3162 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh-528 Ducts Btuh0Central vent (0 cfm)Btuh0 CoolingHeating17570Area (ft²)Equipment latent load Btuh0 140560Volume (ft³)Air changes/hour 0.140 Equipment Total Load (Sen+Lat)Btuh3162 Equiv. AVF (cfm)330 Req. total capacity at 0.70 SHR ton0.4 Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/aTraden/a Trade n/a Model n/a Cond n/aAHRI ref n/a Coil n/a AHRI ref n/aEfficiencyn/a Efficiency n/a Heating input Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:04Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 1C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J® W or ksheet Date:Entire House By: 1 Room name Entire House zone 1 2 Exposed wall 291.0 ft 79.5 ft 3 Room height 8.0 ft 8.0 ft 4 Room dimensions 5 Room area 3741.5 f t²756.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.440.44 252 220 1088 97 252 220 1088 97 .GG 4A4-2ov4A4-2ov 0.3000.300 nn 22.8022.80 12.0312.03 32 0 722 381 32 0 722 381 .WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.440.44 92 92 0 41 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.440.44 504 456 2254 202 192 176 869 78 1 1 GG 4A4-2ov4A4-2ov 0.3000.300 ee 22.8022.80 35.1435.14 48 0 1087 1675 16 0 365 562 WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.440.44 472 425 0 188 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ee 0.000.00 35.1435.14 47 0 0 1664 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.440.44 252 237 1169 105 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 22.8022.80 20.2120.21 15 0 350 310 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.440.44 252 236 0 104 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 0.000.00 20.2120.21 16 0 0 317 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.440.44 504 504 2490 223 192 192 948 85 CC 16B-44md16B-44md 0.0220.022 --1.671.67 0.910.91 1985 1985 3318 1812 756 756 1264 690 FF 19C-19cscp19C-19cscp 0.0490.049 --1.291.29 0.220.22 1855 1855 2394 413 626 626 808 139 FF 22A-tpl22A-tpl 0.9890.989 --0.000.00 0.000.00 1757 102 0 0 0 0 0 0 6 c) AED excursion 0 68 Envelope loss/gain 14872 7530 6065 2101 12 a)Infiltration 9251 1142 3891 312 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)24124 8673 9957 2413 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 24124 8673 9957 2413 15 Duct loads 72%92%17432 7975 72%134%7195 3229 Total room load 41556 16647 17152 5641 Air required (cfm)Air required (cfm)1400 787 578 267 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:04Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 2C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J® W or ksheet Date:Entire House By: 1 Room name zone 3 main zone 2 2 Exposed wall 102.0 ft 109.5 ft 3 Room height 8.0 ft 8.0 ft 4 Room dimensions 5 Room area 1757.0 f t²1228.5 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.440.44 0 0 0 0 0 0 0 0 .GG 4A4-2ov4A4-2ov 0.3000.300 nn 22.8022.80 12.0312.03 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.440.44 92 92 0 41 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.440.44 0 0 0 0 312 280 1385 124 1 1 GG 4A4-2ov4A4-2ov 0.3000.300 ee 22.8022.80 35.1435.14 0 0 0 0 32 0 722 1113 WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.440.44 472 425 0 188 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ee 0.000.00 35.1435.14 47 0 0 1664 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.440.44 0 0 0 0 252 237 1169 105 GG 4A4-2ov4A4-2ov 0.3000.300 ss 22.8022.80 20.2120.21 0 0 0 0 15 0 350 310 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.440.44 252 236 0 104 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 0.000.00 20.2120.21 16 0 0 317 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.440.44 0 0 0 0 312 312 1541 138 CC 16B-44md16B-44md 0.0220.022 --1.671.67 0.910.91 0 0 0 0 1229 1229 2054 1122 FF 19C-19cscp19C-19cscp 0.0490.049 --1.291.29 0.220.22 0 0 0 0 1229 1229 1586 273 FF 22A-tpl22A-tpl 0.9890.989 --0.000.00 0.000.00 1757 102 0 0 0 0 0 0 6 c) AED excursion 449 340 Envelope loss/gain 0 2762 8807 3524 12 a)Infiltration 0 400 5360 430 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)0 3162 14167 3954 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 0 3162 14167 3954 15 Duct loads 0%0%0 0 72%134%10237 5291 Total room load 0 3162 24404 9245 Air required (cfm)Air required (cfm)0 150 822 437 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:04Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 3C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J® W or ksheet Date:zone 1 By: 1 Room name zone 1 bed 1 2nd 2 Exposed wall 79.5 ft 29.0 ft 3 Room height 8.0 ft 8.0 heat/coolft 4 Room dimensions ft13.0x16.0 5 Room area 756.0 f t²208.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.440.44 252 220 1088 97 128 112 553 50 .GG 4A4-2ov4A4-2ov 0.3000.300 nn 22.8022.80 12.0312.03 32 0 722 381 16 0 365 193 .WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.440.44 192 176 869 78 0 0 0 0 1 1 GG 4A4-2ov4A4-2ov 0.3000.300 ee 22.8022.80 35.1435.14 16 0 365 562 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.440.44 192 192 948 85 104 104 514 46 CC 16B-44md16B-44md 0.0220.022 --1.671.67 0.910.91 756 756 1264 690 208 208 348 190 FF 19C-19cscp19C-19cscp 0.0490.049 --1.291.29 0.220.22 626 626 808 139 154 154 199 34 FF 22A-tpl22A-tpl 0.9890.989 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 68 41 Envelope loss/gain 6065 2101 1978 553 12 a)Infiltration 3891 312 1420 114 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)9957 2413 3398 667 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 9957 2413 3398 667 15 Duct loads 72%134%7195 3229 72%134%2455 892 Total room load 17152 5641 5853 1559 Air required (cfm)Air required (cfm)578 267 197 74 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:04Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 4C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J® W or ksheet Date:zone 1 By: 1 Room name 1 bath 2nd 1 kit living 2nd 2 Exposed wall 11.0 ft 39.5 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft11.0x6.0 ft482.0x1.0 5 Room area 66.0 f t²482.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.440.44 0 0 0 0 124 108 535 48 .GG 4A4-2ov4A4-2ov 0.3000.300 nn 22.8022.80 12.0312.03 0 0 0 0 16 0 357 189 .WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.440.44 0 0 0 0 192 176 869 78 1 1 GG 4A4-2ov4A4-2ov 0.3000.300 ee 22.8022.80 35.1435.14 0 0 0 0 16 0 365 562 WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.440.44 88 88 435 39 0 0 0 0 CC 16B-44md16B-44md 0.0220.022 --1.671.67 0.910.91 66 66 110 60 482 482 806 440 FF 19C-19cscp19C-19cscp 0.0490.049 --1.291.29 0.220.22 52 52 67 12 420 420 542 93 FF 22A-tpl22A-tpl 0.9890.989 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -6 33 Envelope loss/gain 612 105 3475 1443 12 a)Infiltration 538 43 1933 155 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1151 148 5408 1598 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1151 148 5408 1598 15 Duct loads 72%134%831 198 72%134%3908 2139 Total room load 1982 346 9316 3737 Air required (cfm)Air required (cfm)67 16 314 177 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:04Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 5C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J® W or ksheet Date:zone 2 By: 1 Room name zone 2 mech rm 2nd 2 Exposed wall 109.5 ft 8.0 ft 3 Room height 8.0 ft 8.0 heat/coolft 4 Room dimensions ft8.0x6.5 5 Room area 1228.5 f t²52.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 4A4-2ov4A4-2ov 0.3000.300 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.440.44 312 280 1385 124 0 0 0 0 1 1 GG 4A4-2ov4A4-2ov 0.3000.300 ee 22.8022.80 35.1435.14 32 0 722 1113 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.440.44 252 237 1169 105 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 22.8022.80 20.2120.21 15 0 350 310 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.440.44 312 312 1541 138 64 64 316 28 CC 16B-44md16B-44md 0.0220.022 --1.671.67 0.910.91 1229 1229 2054 1122 52 52 87 47 FF 19C-19cscp19C-19cscp 0.0490.049 --1.291.29 0.220.22 1229 1229 1586 273 52 52 67 12 FF 22A-tpl22A-tpl 0.9890.989 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 340 -9 Envelope loss/gain 8807 3524 470 78 12 a)Infiltration 5360 430 392 31 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)14167 3954 862 110 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 14167 3954 862 110 15 Duct loads 72%134%10237 5291 72%134%623 147 Total room load 24404 9245 1485 257 Air required (cfm)Air required (cfm)822 437 50 12 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:04Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 6C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J® W or ksheet Date:zone 2 By: 1 Room name 2 kit living 2nd 3 bed 2nd 2 Exposed wall 19.0 ft 35.5 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft19.0x25.0 ft20.0x15.5 5 Room area 475.0 f t²310.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 4A4-2ov4A4-2ov 0.3000.300 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.440.44 152 136 672 60 160 144 713 64 1 1 GG 4A4-2ov4A4-2ov 0.3000.300 ee 22.8022.80 35.1435.14 16 0 365 562 16 0 357 551 WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.440.44 0 0 0 0 124 124 613 55 GG 4A4-2ov4A4-2ov 0.3000.300 ss 22.8022.80 20.2120.21 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.440.44 0 0 0 0 0 0 0 0 CC 16B-44md16B-44md 0.0220.022 --1.671.67 0.910.91 475 475 794 434 310 310 518 283 FF 19C-19cscp19C-19cscp 0.0490.049 --1.291.29 0.220.22 475 475 613 106 310 310 400 69 FF 22A-tpl22A-tpl 0.9890.989 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 45 48 Envelope loss/gain 2444 1207 2601 1069 12 a)Infiltration 930 75 1738 139 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3374 1282 4339 1209 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 3374 1282 4339 1209 15 Duct loads 72%134%2438 1715 72%134%3135 1617 Total room load 5812 2997 7474 2826 Air required (cfm)Air required (cfm)196 142 252 134 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:04Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 7C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J® W or ksheet Date:zone 2 By: 1 Room name 2 bed 2nd 2bath 2nd 2 Exposed wall 36.0 ft 11.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft20.0x16.0 ft11.0x6.5 5 Room area 320.0 f t²71.5 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 4A4-2ov4A4-2ov 0.3000.300 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.440.44 0 0 0 0 0 0 0 0 1 1 GG 4A4-2ov4A4-2ov 0.3000.300 ee 22.8022.80 35.1435.14 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.440.44 128 113 557 50 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 22.8022.80 20.2120.21 15 0 350 310 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.440.44 160 160 790 71 88 88 435 39 CC 16B-44md16B-44md 0.0220.022 --1.671.67 0.910.91 320 320 535 292 72 72 120 65 FF 19C-19cscp19C-19cscp 0.0490.049 --1.291.29 0.220.22 320 320 413 71 72 72 92 16 FF 22A-tpl22A-tpl 0.9890.989 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 268 -12 Envelope loss/gain 2645 1061 647 108 12 a)Infiltration 1762 141 538 43 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)4407 1203 1185 151 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 4407 1203 1185 151 15 Duct loads 72%134%3184 1609 72%134%856 202 Total room load 7591 2812 2041 353 Air required (cfm)Air required (cfm)256 133 69 17 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:04Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 8C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J® W or ksheet Date:zone 3 main By: 1 Room name zone 3 main bath main 2 Exposed wall 102.0 ft 5.0 ft 3 Room height 8.0 ft 8.0 cool onlyft 4 Room dimensions ft16.5x5.0 5 Room area 1757.0 f t²82.5 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 4A4-2ov4A4-2ov 0.3000.300 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.440.44 92 92 0 41 40 40 0 18 .WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 1 1 GG 4A4-2ov4A4-2ov 0.3000.300 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.440.44 472 425 0 188 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ee 0.000.00 35.1435.14 47 0 0 1664 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.440.44 252 236 0 104 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 0.000.00 20.2120.21 16 0 0 317 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC 16B-44md16B-44md 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 19C-19cscp19C-19cscp 0.0490.049 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 22A-tpl22A-tpl 0.9890.989 --0.000.00 0.000.00 1757 102 0 0 83 5 0 0 6 c) AED excursion 449 0 Envelope loss/gain 0 2762 0 17 12 a)Infiltration 0 400 0 20 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)0 3162 0 37 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 0 3162 0 37 15 Duct loads 0%0%0 0 0%0%0 0 Total room load 0 3162 0 37 Air required (cfm)Air required (cfm)0 150 0 2 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:04Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 9C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J® W or ksheet Date:zone 3 main By: 1 Room name living room main shower main 2 Exposed wall 66.5 ft 6.5 ft 3 Room height 8.0 cool onlyft 8.0 cool onlyft 4 Room dimensions ft35.0x31.5 ft13.0x6.5 5 Room area 1102.5 f t²84.5 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 4A4-2ov4A4-2ov 0.3000.300 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.440.44 0 0 0 0 52 52 0 23 .WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 1 1 GG 4A4-2ov4A4-2ov 0.3000.300 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.440.44 280 249 0 110 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ee 0.000.00 35.1435.14 31 0 0 1101 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.440.44 252 236 0 104 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 0.000.00 20.2120.21 16 0 0 317 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC 16B-44md16B-44md 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 19C-19cscp19C-19cscp 0.0490.049 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 22A-tpl22A-tpl 0.9890.989 --0.000.00 0.000.00 1103 67 0 0 85 7 0 0 6 c) AED excursion 313 -1 Envelope loss/gain 0 1945 0 22 12 a)Infiltration 0 261 0 26 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)0 2206 0 48 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 0 2206 0 48 15 Duct loads 0%0%0 0 0%0%0 0 Total room load 0 2206 0 48 Air required (cfm)Air required (cfm)0 104 0 2 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:04Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 10C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J® W or ksheet Date:zone 3 main By: 1 Room name kitchen main Storage 1 2 Exposed wall 24.0 ft 0 ft 3 Room height 8.0 cool onlyft 8.0 cool onlyft 4 Room dimensions ft24.0x16.0 ft11.5x9.0 5 Room area 384.0 f t²103.5 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 4A4-2ov4A4-2ov 0.3000.300 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.440.44 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 1 1 GG 4A4-2ov4A4-2ov 0.3000.300 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 0.000.00 0.440.44 192 176 0 78 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ee 0.000.00 35.1435.14 16 0 0 562 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.440.44 0 0 0 0 0 0 0 0 GG 4A4-2ov4A4-2ov 0.3000.300 ss 0.000.00 20.2120.21 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC 16B-44md16B-44md 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 19C-19cscp19C-19cscp 0.0490.049 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 22A-tpl22A-tpl 0.9890.989 --0.000.00 0.000.00 384 24 0 0 104 0 0 0 6 c) AED excursion 137 0 Envelope loss/gain 0 777 0 0 12 a)Infiltration 0 94 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)0 872 0 0 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 0 872 0 0 15 Duct loads 0%0%0 0 0%0%0 0 Total room load 0 872 0 0 Air required (cfm)Air required (cfm)0 41 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:05Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 1C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J8® For m J1 Date:Entire House By: 1 Name of Room Entire House zone 1 2 Running Feet of Exposed Wall 291.0 ft 79.5 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²6116.2ft 8.0 f t²1423.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)f t²3741.5 f t²756.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²3741.5°0 f t²756.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.944.94 0.440.44 252 1088 97 252 1088 97 .GlazGlaz 4A4-2ov4A4-2ov nn 22.8022.80 12.0312.03 32 722 381 32 722 381 .WallWall 12F-0sw12F-0sw nn 0.000.00 0.440.44 92 0 41 0 0 0 .WallWall 12F-0sw12F-0sw ee 4.944.94 0.440.44 504 2254 202 192 869 78 1 1 GlazGlaz 4A4-2ov4A4-2ov ee 22.8022.80 35.1435.14 48 1087 1675 16 365 562 WallWall 12F-0sw12F-0sw ee 0.000.00 0.440.44 472 0 188 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ee 0.000.00 35.1435.14 47 0 1664 0 0 0 WallWall 12F-0sw12F-0sw ss 4.944.94 0.440.44 252 1169 105 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 22.8022.80 20.2120.21 15 350 310 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.440.44 252 0 104 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 0.000.00 20.2120.21 16 0 317 0 0 0 WallWall 12F-0sw12F-0sw ww 4.944.94 0.440.44 504 2490 223 192 948 85 CeilCeil 16B-44md16B-44md --1.671.67 0.910.91 1985 3318 1812 756 1264 690 FlorFlor 19C-19cscp19C-19cscp --1.291.29 0.220.22 1855 2394 413 626 808 139 FlorFlor 22A-tpl22A-tpl --0.000.00 0.000.00 1757 0 0 0 0 0 Infiltration Heating Load (Btuh)0.500.50 9251 3891 Effect WAR WAR 12 Sensible Load (Btuh)ACH 1.00 1142 1.00 312 0.190.19 Latent Load (Btuh)-1506 -411 Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 24124 8673 -1506 9957 2413 -411 Duct EHLF & ESGF 0.7230.723 1.3380.920 17432 7975 7195 3229 15 Loads ELG -110 -42 Vent CfmVent Cfm16Ventilation Loads 00 E CfmE Cfm 00 0 0 0 0 0 0 17 Winter Humidification Load Gal/Day 00 0 0 18 Piping Load 0 0 19 Blower Heat 0 0 20 AED Excursion & Latent Moisture Migration Load 0 68 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 41556 16647 0 17152 5641 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:05Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 2C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J8® For m J1 Date:Entire House By: 1 Name of Room zone 3 main zone 2 2 Running Feet of Exposed Wall 102.0 ft 109.5 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²2519.8ft 8.0 f t²2173.3ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)f t²1757.0 f t²1228.5 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²1757.0°0 f t²1228.5° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.944.94 0.440.44 0 0 0 0 0 0 .GlazGlaz 4A4-2ov4A4-2ov nn 22.8022.80 12.0312.03 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw nn 0.000.00 0.440.44 92 0 41 0 0 0 .WallWall 12F-0sw12F-0sw ee 4.944.94 0.440.44 0 0 0 312 1385 124 1 1 GlazGlaz 4A4-2ov4A4-2ov ee 22.8022.80 35.1435.14 0 0 0 32 722 1113 WallWall 12F-0sw12F-0sw ee 0.000.00 0.440.44 472 0 188 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ee 0.000.00 35.1435.14 47 0 1664 0 0 0 WallWall 12F-0sw12F-0sw ss 4.944.94 0.440.44 0 0 0 252 1169 105 GlazGlaz 4A4-2ov4A4-2ov ss 22.8022.80 20.2120.21 0 0 0 15 350 310 WallWall 12F-0sw12F-0sw ss 0.000.00 0.440.44 252 0 104 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 0.000.00 20.2120.21 16 0 317 0 0 0 WallWall 12F-0sw12F-0sw ww 4.944.94 0.440.44 0 0 0 312 1541 138 CeilCeil 16B-44md16B-44md --1.671.67 0.910.91 0 0 0 1229 2054 1122 FlorFlor 19C-19cscp19C-19cscp --1.291.29 0.220.22 0 0 0 1229 1586 273 FlorFlor 22A-tpl22A-tpl --0.000.00 0.000.00 1757 0 0 0 0 0 Infiltration Heating Load (Btuh)0.500.50 0 5360 Effect WAR WAR 12 Sensible Load (Btuh)ACH 1.00 400 1.00 430 0.190.19 Latent Load (Btuh)-528 -567 Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 0 3162 -528 14167 3954 -567 Duct EHLF & ESGF 0.7230 1.3380 0 0 10237 5291 15 Loads ELG 0 -68 Vent CfmVent Cfm16Ventilation Loads 00 E CfmE Cfm 00 0 0 0 0 0 0 17 Winter Humidification Load Gal/Day 00 0 0 18 Piping Load 0 0 19 Blower Heat 0 0 20 AED Excursion & Latent Moisture Migration Load 449 340 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 0 3162 0 24404 9245 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:05Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 3C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J8® For m J1 Date:zone 1 By: 1 Name of Room zone 1 bed 1 2nd 2 Running Feet of Exposed Wall 79.5 ft 29.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²1423.0ft 8.0 f t²443.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)f t²756.0 16.0 x 13.0 ft f t²208.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²756.0°0 f t²208.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.944.94 0.440.44 252 1088 97 128 553 50 .GlazGlaz 4A4-2ov4A4-2ov nn 22.8022.80 12.0312.03 32 722 381 16 365 193 .WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw ee 4.944.94 0.440.44 192 869 78 0 0 0 1 1 GlazGlaz 4A4-2ov4A4-2ov ee 22.8022.80 35.1435.14 16 365 562 0 0 0 WallWall 12F-0sw12F-0sw ee 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.944.94 0.440.44 192 948 85 104 514 46 CeilCeil 16B-44md16B-44md --1.671.67 0.910.91 756 1264 690 208 348 190 FlorFlor 19C-19cscp19C-19cscp --1.291.29 0.220.22 626 808 139 154 199 34 FlorFlor 22A-tpl22A-tpl --0.000.00 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.550.55 3891 1420 Effect WAR WAR 12 Sensible Load (Btuh)ACH 1.00 312 0.36 114 0.260.26 Latent Load (Btuh)-411 Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 9957 2413 -411 3398 667 Duct EHLF & ESGF 0.7230.723 1.3381.338 7195 3229 2455 892 15 Loads ELG -42 -11 Vent CfmVent Cfm16Ventilation Loads 00 E CfmE Cfm 00 0 0 0 17 Winter Humidification Load Gal/Day 00 0 18 Piping Load 0 19 Blower Heat 0 20 AED Excursion & Latent Moisture Migration Load 68 41 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 17152 5641 0 5853 1559 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:05Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 4C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J8® For m J1 Date:zone 1 By: 1 Name of Room 1 bath 2nd 1 kit living 2nd 2 Running Feet of Exposed Wall 11.0 ft 39.5 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²251.0ft 8.0 f t²729.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)6.0 x 11.0 ft f t²66.0 1.0 x 482.0 ft f t²482.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²66.0°0 f t²482.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.944.94 0.440.44 0 0 0 124 535 48 .GlazGlaz 4A4-2ov4A4-2ov nn 22.8022.80 12.0312.03 0 0 0 16 357 189 .WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw ee 4.944.94 0.440.44 0 0 0 192 869 78 1 1 GlazGlaz 4A4-2ov4A4-2ov ee 22.8022.80 35.1435.14 0 0 0 16 365 562 WallWall 12F-0sw12F-0sw ee 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.944.94 0.440.44 88 435 39 0 0 0 CeilCeil 16B-44md16B-44md --1.671.67 0.910.91 66 110 60 482 806 440 FlorFlor 19C-19cscp19C-19cscp --1.291.29 0.220.22 52 67 12 420 542 93 FlorFlor 22A-tpl22A-tpl --0.000.00 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.550.55 538 1933 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.14 43 0.50 155 0.260.26 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 1151 148 5408 1598 Duct EHLF & ESGF 0.7230.723 1.3381.338 831 198 3908 2139 15 Loads ELG -4 -27 Vent CfmVent Cfm16Ventilation Loads 00 E CfmE Cfm 00 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -6 33 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 1982 346 9316 3737 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:05Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 5C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J8® For m J1 Date:zone 2 By: 1 Name of Room zone 2 mech rm 2nd 2 Running Feet of Exposed Wall 109.5 ft 8.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²2173.3ft 8.0 f t²211.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)f t²1228.5 6.5 x 8.0 ft f t²52.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²1228.5°0 f t²52.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .GlazGlaz 4A4-2ov4A4-2ov nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw ee 4.944.94 0.440.44 312 1385 124 0 0 0 1 1 GlazGlaz 4A4-2ov4A4-2ov ee 22.8022.80 35.1435.14 32 722 1113 0 0 0 WallWall 12F-0sw12F-0sw ee 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.944.94 0.440.44 252 1169 105 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 22.8022.80 20.2120.21 15 350 310 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.944.94 0.440.44 312 1541 138 64 316 28 CeilCeil 16B-44md16B-44md --1.671.67 0.910.91 1229 2054 1122 52 87 47 FlorFlor 19C-19cscp19C-19cscp --1.291.29 0.220.22 1229 1586 273 52 67 12 FlorFlor 22A-tpl22A-tpl --0.000.00 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.470.47 5360 392 Effect WAR WAR 12 Sensible Load (Btuh)ACH 1.00 430 0.07 31 0.220.22 Latent Load (Btuh)-567 Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 14167 3954 -567 862 110 Duct EHLF & ESGF 0.7230.723 1.3381.338 10237 5291 623 147 15 Loads ELG -68 -3 Vent CfmVent Cfm16Ventilation Loads 00 E CfmE Cfm 00 0 0 0 17 Winter Humidification Load Gal/Day 00 0 18 Piping Load 0 19 Blower Heat 0 20 AED Excursion & Latent Moisture Migration Load 340 -9 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 24404 9245 0 1485 257 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:05Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 6C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J8® For m J1 Date:zone 2 By: 1 Name of Room 2 kit living 2nd 3 bed 2nd 2 Running Feet of Exposed Wall 19.0 ft 35.5 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²600.2ft 8.0 f t²547.6ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)25.0 x 19.0 ft f t²475.0 15.5 x 20.0 ft f t²310.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²475.0°0 f t²310.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .GlazGlaz 4A4-2ov4A4-2ov nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw ee 4.944.94 0.440.44 152 672 60 160 713 64 1 1 GlazGlaz 4A4-2ov4A4-2ov ee 22.8022.80 35.1435.14 16 365 562 16 357 551 WallWall 12F-0sw12F-0sw ee 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.944.94 0.440.44 0 0 0 124 613 55 GlazGlaz 4A4-2ov4A4-2ov ss 22.8022.80 20.2120.21 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.944.94 0.440.44 0 0 0 0 0 0 CeilCeil 16B-44md16B-44md --1.671.67 0.910.91 475 794 434 310 518 283 FlorFlor 19C-19cscp19C-19cscp --1.291.29 0.220.22 475 613 106 310 400 69 FlorFlor 22A-tpl22A-tpl --0.000.00 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.470.47 930 1738 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.17 75 0.32 139 0.220.22 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 3374 1282 4339 1209 Duct EHLF & ESGF 0.7230.723 1.3381.338 2438 1715 3135 1617 15 Loads ELG -26 -17 Vent CfmVent Cfm16Ventilation Loads 00 E CfmE Cfm 00 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 45 48 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 5812 2997 7474 2826 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:05Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 7C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J8® For m J1 Date:zone 2 By: 1 Name of Room 2 bed 2nd 2bath 2nd 2 Running Feet of Exposed Wall 36.0 ft 11.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²555.6ft 8.0 f t²259.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)16.0 x 20.0 ft f t²320.0 6.5 x 11.0 ft f t²71.5 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²320.0°0 f t²71.5° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .GlazGlaz 4A4-2ov4A4-2ov nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw ee 4.944.94 0.440.44 0 0 0 0 0 0 1 1 GlazGlaz 4A4-2ov4A4-2ov ee 22.8022.80 35.1435.14 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ee 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.944.94 0.440.44 128 557 50 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 22.8022.80 20.2120.21 15 350 310 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.944.94 0.440.44 160 790 71 88 435 39 CeilCeil 16B-44md16B-44md --1.671.67 0.910.91 320 535 292 72 120 65 FlorFlor 19C-19cscp19C-19cscp --1.291.29 0.220.22 320 413 71 72 92 16 FlorFlor 22A-tpl22A-tpl --0.000.00 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.470.47 1762 538 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.33 141 0.10 43 0.220.22 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 4407 1203 1185 151 Duct EHLF & ESGF 0.7230.723 1.3381.338 3184 1609 856 202 15 Loads ELG -18 -4 Vent CfmVent Cfm16Ventilation Loads 00 E CfmE Cfm 00 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 268 -12 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 7591 2812 2041 353 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:05Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 8C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J8® For m J1 Date:zone 3 main By: 1 Name of Room zone 3 main bath main 2 Running Feet of Exposed Wall 102.0 ft 5.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²2519.8ft 8.0 f t²344.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)f t²1757.0 5.0 x 16.5 ft f t²82.5 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²1757.0°0 f t²82.5° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .GlazGlaz 4A4-2ov4A4-2ov nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw nn 0.000.00 0.440.44 92 0 41 40 0 18 .WallWall 12F-0sw12F-0sw ee 0.000.00 0.000.00 0 0 0 0 0 0 1 1 GlazGlaz 4A4-2ov4A4-2ov ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ee 0.000.00 0.440.44 472 0 188 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ee 0.000.00 35.1435.14 47 0 1664 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.440.44 252 0 104 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 0.000.00 20.2120.21 16 0 317 0 0 0 WallWall 12F-0sw12F-0sw ww 0.000.00 0.000.00 0 0 0 0 0 0 CeilCeil 16B-44md16B-44md --0.000.00 0.000.00 0 0 0 0 0 0 FlorFlor 19C-19cscp19C-19cscp --0.000.00 0.000.00 0 0 0 0 0 0 FlorFlor 22A-tpl22A-tpl --0.000.00 0.000.00 1757 0 0 83 0 0 Infiltration Heating Load (Btuh)00 0 0 Effect WAR WAR 12 Sensible Load (Btuh)ACH 1.00 400 0 20 0.140.14 Latent Load (Btuh)-528 Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 0 3162 -528 0 37 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 00 E CfmE Cfm 00 0 0 0 17 Winter Humidification Load Gal/Day 00 0 18 Piping Load 0 19 Blower Heat 0 20 AED Excursion & Latent Moisture Migration Load 449 0 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 0 3162 0 0 37 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:05Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 9C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J8® For m J1 Date:zone 3 main By: 1 Name of Room living room main shower main 2 Running Feet of Exposed Wall 66.5 ft 6.5 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²975.0ft 8.0 f t²312.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)31.5 x 35.0 ft f t²1102.5 6.5 x 13.0 ft f t²84.5 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²1102.5°0 f t²84.5° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .GlazGlaz 4A4-2ov4A4-2ov nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw nn 0.000.00 0.440.44 0 0 0 52 0 23 .WallWall 12F-0sw12F-0sw ee 0.000.00 0.000.00 0 0 0 0 0 0 1 1 GlazGlaz 4A4-2ov4A4-2ov ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ee 0.000.00 0.440.44 280 0 110 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ee 0.000.00 35.1435.14 31 0 1101 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.440.44 252 0 104 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 0.000.00 20.2120.21 16 0 317 0 0 0 WallWall 12F-0sw12F-0sw ww 0.000.00 0.000.00 0 0 0 0 0 0 CeilCeil 16B-44md16B-44md --0.000.00 0.000.00 0 0 0 0 0 0 FlorFlor 19C-19cscp19C-19cscp --0.000.00 0.000.00 0 0 0 0 0 0 FlorFlor 22A-tpl22A-tpl --0.000.00 0.000.00 1103 0 0 85 0 0 Infiltration Heating Load (Btuh)00 0 0 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0 261 0 26 0.140.14 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 0 2206 0 48 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 00 E CfmE Cfm 00 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 313 -1 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 0 2206 0 48 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:05Right-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 10C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Right-J8® For m J1 Date:zone 3 main By: 1 Name of Room kitchen main Storage 1 2 Running Feet of Exposed Wall 24.0 ft 0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²560.8ft 8.0 f t²328.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)16.0 x 24.0 ft f t²384.0 9.0 x 11.5 ft f t²103.5 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²384.0°0 f t²103.5° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0 .GlazGlaz 4A4-2ov4A4-2ov nn 0.000.00 0.000.00 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw nn 0.000.00 0.440.44 0 0 0 0 0 0 .WallWall 12F-0sw12F-0sw ee 0.000.00 0.000.00 0 0 0 0 0 0 1 1 GlazGlaz 4A4-2ov4A4-2ov ee 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ee 0.000.00 0.440.44 192 0 78 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ee 0.000.00 35.1435.14 16 0 562 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 0.000.00 0.440.44 0 0 0 0 0 0 GlazGlaz 4A4-2ov4A4-2ov ss 0.000.00 20.2120.21 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 0.000.00 0.000.00 0 0 0 0 0 0 CeilCeil 16B-44md16B-44md --0.000.00 0.000.00 0 0 0 0 0 0 FlorFlor 19C-19cscp19C-19cscp --0.000.00 0.000.00 0 0 0 0 0 0 FlorFlor 22A-tpl22A-tpl --0.000.00 0.000.00 384 0 0 104 0 0 Infiltration Heating Load (Btuh)00 0 0 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0 94 0 0 0.140.14 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 0 872 0 0 Duct EHLF & ESGF 00 00 0 0 0 0 15 Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 00 E CfmE Cfm 00 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 137 0 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 0 872 0 0 Bold/italic values have been manually overridden 2023-Sep-11 18:04:07 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 1 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Load Multizone Summary Report Date: By: Infiltration Summary Heating Cooling ZONE NAME Volume ACH AVF HTM Volume ACH AVF HTM f t³cfm Btu h/f t²f t³cfm Btu h/f t² 0.5 26 0.26 6048 6.1 56 0.55 6048zone 1 0.5 33 0.14 14056 0 0 0 0zone 3 main 0.5 36 0.22 9828 6.1 77 0.47 9828zone 2 Entire House 15876 0.50 132 6.1 29932 0.19 95 0.5 Load and AVF Summary ROOM NAME Area Htg load Clg load Htg AVF Clg AVF f t²Btuh Btuh cfm cfm 74 197 1559 5853 208bed 1 2nd 16 67 346 1982 661 bath 2nd 177 314 3737 9316 4821 kit living 2nd 267 578 5641 17152 756zone 1 2 0 37 0 83bath main 104 0 2206 0 1103living room main 2 0 48 0 85shower main 41 0 872 0 384kitchen main 0 0 0 0 104Storage 1 150 0 3162 0 1757zone 3 main 12 50 257 1485 52mech rm 2nd 142 196 2997 5812 4752 kit living 2nd 134 252 2826 7474 3103 bed 2nd 133 256 2812 7591 3202 bed 2nd 17 69 353 2041 722bath 2nd 437 822 9245 24404 1229zone 2 Entire House 3742 41556 16647 1400 787 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:07 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 1 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:J1 Form - Worksheet A Date:Entire House By: Supporting Detail Project Name:Shawn galbraith Date: Address: Phone:Job ID: Worksheet A Location and Design Conditions Weather Location:Rexburg Madison Co, ID, US 444859Latitude =Elevation = Indoor Conditions, Heating:70 °FDB =%50°F75%30 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB =-6 °F Hgr/lb-28°F88 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F13°F76 CTD =HTD = Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:07 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 2 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:J1 Form - Worksheet A Date:zone 1 By: Supporting Detail Project Name:Shawn galbraith Date: Address: Phone:Job ID: Worksheet A Location and Design Conditions Weather Location:Rexburg Madison Co, ID, US 444859Latitude =Elevation = Indoor Conditions, Heating:70 °FDB =%50°F75%30 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB =-6 °F Hgr/lb-28°F88 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F13°F76 CTD =HTD = Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:07 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 3 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:J1 Form - Worksheet A Date:zone 2 By: Supporting Detail Project Name:Shawn galbraith Date: Address: Phone:Job ID: Worksheet A Location and Design Conditions Weather Location:Rexburg Madison Co, ID, US 444859Latitude =Elevation = Indoor Conditions, Heating:70 °FDB =%50°F75%30 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB =-6 °F Hgr/lb-28°F88 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F13°F76 CTD =HTD = Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-11 18:04:07 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 4 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:J1 Form - Worksheet A Date:zone 3 main By: Supporting Detail Project Name:Shawn galbraith Date: Address: Phone:Job ID: Worksheet A Location and Design Conditions Weather Location:Rexburg Madison Co, ID, US 444859Latitude =Elevation = Indoor Conditions, Heating:70 °FDB =%50°F75%30 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB =-6 °F Hgr/lb-28°F88 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F13°F76 CTD =HTD = Bold/italic values have been manually overridden 2023-Sep-11 18:04:07 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 1 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:AED Assessment Date:Entire House By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) )H(33-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gl a z i n g l o a d ( B t u h ) Hour of Day 0 500 1,000 1,500 2,000 2,500 3,000 3,500 4,000 4,500 5,000 5,500 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 23.0%. House has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 0 Btuh Bold/italic values have been manually overridden 2023-Sep-11 18:04:07 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 2 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:AED Assessment Date:zone 1 By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) )H(33-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gl a z i n g l o a d ( B t u h ) Hour of Day 0 100 200 300 400 500 600 700 800 900 1,000 1,100 1,200 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 15.4%. Zone has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 68 Btuh (PFG - ALP) Bold/italic values have been manually overridden 2023-Sep-11 18:04:07 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 3 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:AED Assessment Date:zone 2 By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) )H(33-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gl a z i n g l o a d ( B t u h ) Hour of Day 0 200 400 600 800 1,000 1,200 1,400 1,600 1,800 2,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 23.9%. Zone has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 340 Btuh (PFG - ALP) Bold/italic values have been manually overridden 2023-Sep-11 18:04:07 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 4 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:AED Assessment Date:zone 3 main By: Project Information For: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Rexburg Madison Co, ID, US 1376Design TD (°F)ft4859Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-27.935.3Moisture difference (gr/lb)CoolingHeating Infiltration:88-6Dry bul b (°F) )H(33-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gl a z i n g l o a d ( B t u h ) Hour of Day 0 200 400 600 800 1,000 1,200 1,400 1,600 1,800 2,000 2,200 2,400 2,600 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 26.7%. Zone has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 449 Btuh (PFG - ALP) 2023-Sep-11 18:04:07 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 1 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Duct system multi orientation report Date:Entire House By: Project Information For: Group 1: ( N, S, SW, W, NW) Group 2: (NE, E, SE) Duct Name (SE)(E)(NE)(N) Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 1 bath 2nd 64x1233 h64x1233 h64x1233 h64x1233 h 1 bath 2nd-A 64x1233 h64x1233 h64x1233 h64x1233 h 1 kit living 2nd 84x12157 h84x12157 h84x12157 h84x12157 h 1 kit living 2nd-A 84x12157 h84x12157 h84x12157 h84x12157 h 2 bed 2nd 104x12256 h104x12256 h104x12256 h104x12256 h 2 kit living 2nd 94x12196 h94x12196 h94x12196 h94x12196 h 2bath 2nd 64x1269 h64x1269 h64x1269 h64x1269 h 3 bed 2nd 104x12252 h104x12252 h104x12252 h104x12252 h Storage 1 04x120 c04x120 c04x120 c04x120 c bath main 64x122 c64x122 c64x122 c64x122 c bed 1 2nd 94x12197 h94x12197 h94x12197 h94x12197 h kitchen main 64x1232 c64x1219 c64x1226 c64x1241 c living room main 64x1240 c64x1232 c64x1242 c64x1252 c living room main-A 64x1240 c64x1232 c64x1242 c64x1252 c mech rm 2nd 64x1250 h64x1250 h64x1250 h64x1250 h shower main 64x122 c64x122 c64x122 c64x122 c Supply Trunks st1 14x8117 c14x887 c14x8114 c14x8150 c st4 14x881 c14x864 c14x884 c14x8104 c st5 14x836 c14x823 c14x829 c14x845 c st2A 14x8252 h14x8252 h14x8252 h14x8252 h st2 20x8822 h20x8822 h20x8822 h20x8822 h st3 14x8578 h14x8578 h14x8578 h14x8578 h st3A 14x8197 h14x8197 h14x8197 h14x8197 h Return Branches rb3 68x24117 c68x2487 c68x24114 c78x24150 c rb1 108x24325 h108x24325 h108x24325 h108x24325 h rb2 108x24314 h108x24314 h108x24314 h108x24314 h rb4 128x24448 h128x24448 h128x24448 h128x24448 h rb5 68x2483 h68x2483 h68x2483 h68x2483 h rb6 88x24231 h88x24231 h88x24231 h88x24231 h Return Trunks rt2A 14x8314 h14x8314 h14x8314 h14x8314 h rt2 22x81086 h22x81086 h22x81086 h22x81086 h rt3 14x8314 h14x8314 h14x8314 h14x8314 h Friction Rates Heating FR 0.0830.0830.0790.079 Cooling FR 0.0830.0830.0790.079 2023-Sep-11 18:04:07 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 2 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Project Information For: Duct Name (NW)(W)(SW)(S) Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 1 bath 2nd 64x1233 h64x1233 h64x1233 h64x1233 h 1 bath 2nd-A 64x1233 h64x1233 h64x1233 h64x1233 h 1 kit living 2nd 84x12157 h84x12157 h84x12157 h84x12157 h 1 kit living 2nd-A 84x12157 h84x12157 h84x12157 h84x12157 h 2 bed 2nd 104x12256 h104x12256 h104x12256 h104x12256 h 2 kit living 2nd 94x12196 h94x12196 h94x12196 h94x12196 h 2bath 2nd 64x1269 h64x1269 h64x1269 h64x1269 h 3 bed 2nd 104x12252 h104x12252 h104x12252 h104x12252 h Storage 1 04x120 c04x120 c04x120 c04x120 c bath main 64x122 c64x122 c64x122 c64x122 c bed 1 2nd 94x12197 h94x12197 h94x12197 h94x12197 h kitchen main 64x1242 c64x1239 c64x1243 c64x1245 c living room main 64x1251 c64x1253 c64x1256 c64x1252 c living room main-A 64x1251 c64x1253 c64x1256 c64x1252 c mech rm 2nd 64x1250 h64x1250 h64x1250 h64x1250 h shower main 64x122 c64x122 c64x122 c64x122 c Supply Trunks st1 14x8147 c14x8148 c14x8159 c14x8153 c st4 14x8102 c14x8106 c14x8112 c14x8104 c st5 14x846 c14x843 c14x847 c14x849 c st2A 14x8252 h14x8252 h14x8252 h14x8252 h st2 20x8822 h20x8822 h20x8822 h20x8822 h st3 14x8578 h14x8578 h14x8578 h14x8578 h st3A 14x8197 h14x8197 h14x8197 h14x8197 h Return Branches rb3 78x24147 c78x24148 c78x24159 c78x24153 c rb1 108x24325 h108x24325 h108x24325 h108x24325 h rb2 108x24314 h108x24314 h108x24314 h108x24314 h rb4 128x24448 h128x24448 h128x24448 h128x24448 h rb5 68x2483 h68x2483 h68x2483 h68x2483 h rb6 88x24231 h88x24231 h88x24231 h88x24231 h Return Trunks rt2A 14x8314 h14x8314 h14x8314 h14x8314 h rt2 22x81086 h22x81086 h22x81086 h22x81086 h rt3 14x8314 h14x8314 h14x8314 h14x8314 h Friction Rates Heating FR 0.0790.0790.0790.079 Cooling FR 0.0790.0790.0790.079 2023-Sep-11 18:04:07 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 3 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Project Information For: Duct Name SmalestLargest Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 1 bath 2nd 64x1233 h64x1233 h 1 bath 2nd-A 64x1233 h64x1233 h 1 kit living 2nd 84x12157 h84x12157 h 1 kit living 2nd-A 84x12157 h84x12157 h 2 bed 2nd 104x12256 h104x12256 h 2 kit living 2nd 94x12196 h94x12196 h 2bath 2nd 64x1269 h64x1269 h 3 bed 2nd 104x12252 h104x12252 h Storage 1 04x120 c04x120 c bath main 64x122 c64x122 c bed 1 2nd 94x12197 h94x12197 h kitchen main 64x1219 c64x1245 c living room main 64x1232 c64x1256 c living room main-A 64x1232 c64x1256 c mech rm 2nd 64x1250 h64x1250 h shower main 64x122 c64x122 c Supply Trunks st1 14x887 c14x8159 c st4 14x864 c14x8112 c st5 14x823 c14x849 c st2A 14x8252 h14x8252 h st2 20x8822 h20x8822 h st3 14x8578 h14x8578 h st3A 14x8197 h14x8197 h Return Branches rb3 68x2487 c78x24159 c rb1 108x24325 h108x24325 h rb2 108x24314 h108x24314 h rb4 128x24448 h128x24448 h rb5 68x2483 h68x2483 h rb6 88x24231 h88x24231 h Return Trunks rt2A 14x8314 h14x8314 h rt2 22x81086 h22x81086 h rt3 14x8314 h14x8314 h Friction Rates Heating FR 0.0790.083 Cooling FR 0.0790.083 2023-Sep-11 18:04:09 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 1 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Static Pressure and Friction Rate Date:Entire House By: Project Information For: Available Static Pressure CoolingHeating (in H2O)(in H2O) 0.500.50External static pressure Pressure losses 0.010.01Coil 00Heat exchanger 0.010.01Supply diffusers 0.200.20Return grilles 00Filter 00Humidifier 00Balancing damper 00Other device 0.280.28Available static pressure Total Effective Length ReturnSupply (ft)(ft) 1820Measured length of run-out 2029Measured length of trunk 160110Equivalent length of fittings 198158Total length 356Total effective length Friction Rate CoolingHeating (in/100ft)(in/100ft) OK0.079OK0.079Supply Ducts OK0.079OK0.079Return Ducts Fitting Equivalent Length Details 4I=10, 2A0=35, 12H1=20, 1C=35, 8B9=10: TotalEL=110Supply 6M=20, 6C3=50, 6CB=25, 6CA=10, 5B=40, 8AF=15: TotalEL=160Return Bold/italic values have been manually overridden 2023-Sep-11 18:04:09 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 1 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Job:Duct System Summary Date:Entire House By: Project Information For: CoolingHeating External static pressure in H2O0.50in H2O0.50 Pressure losses in H2O0.22in H2O0.22 Available static pressure in H2O0.28in H2O0.28 Supply / return available pressure 0.124 / 0.156 in H2O in H2O0.124 / 0.156 Lowest friction rate in/100ft0.079in/100ft0.079 Actual air flow cfm787cfm1400 Total effective length (TEL)ft356 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st3120.06.0VlFx0x06.00.099833991h1 bath 2nd st3110.010.0VlFx0x06.00.104833991h1 bath 2nd-A st390.039.0VlFx0x08.00.096881574658h1 kit living 2nd st3100.029.5VlFx0x08.00.096881574658h1 kit living 2nd-A st290.026.0VlFx0x010.00.1071332567591h2 bed 2nd st2110.032.0VlFx0x09.00.0881421965812h2 kit living 2nd st2100.013.0VlFx0x06.00.11017692041h2bath 2nd st2A110.048.0VlFx0x010.00.0791342527474h3 bed 2nd st5110.014.0VlFx0x000.100000cStorage 1 st5100.027.5VlFx0x06.00.0982037cbath main st3A82.025.5VlFx0x09.00.116741975853hbed 1 2nd st590.045.5VlFx0x06.00.092410872ckitchen main st462.049.0VlFx0x06.00.1125201103cliving room main st4100.047.0VlFx0x06.00.0855201103cliving room main-A st2120.07.0VlFx0x06.00.09812501485hmech rm 2nd st590.034.5VlFx0x06.00.1002048cshower main Bold/italic values have been manually overridden 2023-Sep-11 18:04:09 Rig ht-Su ite® U niv er sal 20 19 19 .0.09 RSU0 5696 Page 2 C:\Users\fred\Shawn galbraith.rup Calc = MJ8 Front Door faces: S Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 0 150 0.085 192 7.0 14x8 ShtMetl st4 Peak AVF 0 104 0.085 134 6.1 14x8 ShtMetl st1 st5 Peak AVF 0 45 0.092 58 4.4 14x8 ShtMetl st1 st2A Peak AVF 252 134 0.079 324 8.6 14x8 ShtMetl st2 st2 Peak AVF 822 437 0.079 740 13.4 20x8 ShtMetl st3 Peak AVF 578 267 0.096 743 11.3 14x8 ShtMetl st3A Peak AVF 197 74 0.116 254 7.3 14x8 ShtMetl st3 Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb3 0x 00 150 125.5 0.124 559 7.0 x0 0 ShMt rb1 0x 3250 150 109.0 0.143 595 10.0 x0 0 ShMt rt2 rb2 0x 3140 177 171.0 0.091 575 10.0 x0 0 ShMt rt2A rb4 0x 4480 275 197.5 0.079 570 12.0 x0 0 ShMt rt2 rb5 0x 830 20 111.0 0.140 425 6.0 x0 0 ShMt rt3 rb6 0x 2310 82 120.0 0.130 661 8.0 x0 0 ShMt rt3 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt2A Peak AVF 314 177 0.091 404 9.1 14x8 ShtMetl rt2 rt2 Peak AVF 1086 602 0.079 889 14.9 22x8 ShtMetl rt3 Peak AVF 314 102 0.130 404 8.5 14x8 ShtMetl Job #: Performed for: Scale: 1 : 154 Page 1 Right-Suite® Univ ers al 2019 19.0.09 RSU05696 2023-Sep-11 18:05:45 C:\Users\fred\Shawn galbraith.rup N 2nd floor bed 1 2nd 1 bath 2nd 1 kit living 2nd mech rm 2nd 2bath 2nd 2 bed 2nd 3 bed 2nd 2 kit living 2nd 33 cfm 69 cfm 256 cfm 252 cfm 50 cfm 197 cfm 157 cfm 33 cfm 196 cfm325 cfm 314 cfm 448 cfm 83 cfm 231 cfm Sup Riser 14 x 8 12 "14 x 8 6 " 8 " 8 " 10 " 6 " 6 " 9 " 10 " 6 " 9 " 10 " 22 x 8 6 " 10 " 14 x 8 Ret Riser 7 " 157 cfm8 " 14 x 8 20 x 8 14 x 8 14 x 8 Job #: Performed for: Scale: 1 : 154 Page 2 Right-Suite® Univ ers al 2019 19.0.09 RSU05696 2023-Sep-11 18:05:45 C:\Users\fred\Shawn galbraith.rup N Main floor Room1 Storage bath main shower main Storage kitchen main Storage 1 living room main 52 cfm 150 cfm 52 cfm 41 cfm2 cfm 2 cfm Sup Riser 14 x 8 6 " 14 x 8 14 x 8 6 " 6 " 6 " 6 " 7 " Ret Riser 7 "14 x 8