As requested, we have reviewed the revised soils report dated Sept 27, 2022 for the above
referenced project. The purpose of the review is to determine if any changes are required to the
structural drawings and foundation plan as a result of that report.
The report states that the allowable soil bearing pressure for the spread footings is 3000 psf. Our
calculations are based on 2000 psf, which is more conservative. No changes are required.
Also the report states that the footings should be at least 36-in. below finished grade. Our design
requires the footings to be 36-in. to the top of the footing, again more conservative. No changes
are required.
The building should be set back from the slope as per the soils report. This will be addressed by
others and is not part of our scope of the project.
In conclusion, based on the revised soils report, no changes are required to the foundation plan as
previously submitted. If there are any questions, please call.