Loading...
HomeMy WebLinkAboutTETON STRUCTURAL ENGINEERS - 22-00611 - EVO Automation - New CommercialTE` ON STRUCTURAL ENGINEERS A Professional Corporation (208) 357-2420 136 So. State (208) 357-2419 Fax (800) 528-6755 Shelley, ID 83274-1245 office@tetoneng.com September 29, 2022 SILVERLINE BUILDERS TROY HASTINGS 1052 WEST 14TH NORTH REXBURG ID 83440 Dear Troy, Project #221327 Re: EVO Securities (Daniel Chiddix) Revised Soils report 2400 S 2000 W (Near) Rexburg, ID As requested, we have reviewed the revised soils report dated Sept 27, 2022 for the above referenced project. The purpose of the review is to determine if any changes are required to the structural drawings and foundation plan as a result of that report. The report states that the allowable soil bearing pressure for the spread footings is 3000 psf. Our calculations are based on 2000 psf, which is more conservative. No changes are required. Also the report states that the footings should be at least 36-in. below finished grade. Our design requires the footings to be 36-in. to the top of the footing, again more conservative. No changes are required. The building should be set back from the slope as per the soils report. This will be addressed by others and is not part of our scope of the project. In conclusion, based on the revised soils report, no changes are required to the foundation plan as previously submitted. If there are any questions, please call. Sincerely, Michael D. Gregory, PE SEP 2 9 2022 Page 1 of 1