HomeMy WebLinkAboutFIRE ALARM REPORT - 22-00269 - Hibbard Elementary School10%%.OAL j,jj1111!!!"`,. fZ T ter'— E
Hire Alarm Inmpection and Beport phone #208.546.0428
Inspection Date:
12/26/2023
Building Occupied As:
Building Address:
Owner/Manager:
Hibbard Elementary
2413 North 3000 West Rexburg, ID 83440
Phone Number:
208-359-3333
Email Address:
Tester Name:
Martin Pelton/Benjamen Vermillion
Monitoring Company: Omni
Account #: Unknown
Notification of Testing?
I Communication Verified?
Yes
Yes
Password:
Unknown
Problems Found: None
Corrections Made: None
Control PaneL-
Control Panel Manufacturer:
Silent Knight
Model:
6820
# of Zones:
1
SLC Loops:
1
NACs-FACP:
8
FCPS:
2
Total # of NACs
8
Battery Lspeetioa
FACP
FCPS 1
FOPS 2
Location:
Main Office
Main Office
Main Office
Voltage:
12v 10a
12v 7a
12v 7a
Amp Hour:
10
10
10
Battery Date (Month -Year):
122023
122023
122023
Is there more FCPS's in addition
If "Yes," see page:
FACP IF.'on
Key to Panel Available?
Yes
Operating Instructions in Panel?
Yes
Circuit Breaker marked Red?
Yes
Panel B #37
Panel Location/Label:
Yes
Trouble Signal with AC Power Off?
Yes
System Operates satisfactory on standby power at maximum load?
Yes
All signals operate on AC power?
Yes
All LED's Illuminate?
All circuits checked for electrical supervision?
Yes
All functions and buttons work properly?
Yes
Does alarm system meet audibillity standards?
Yes
Control panel checks made per manufacturer's instruction?
Yes
All interfaced equipment operates
(Elevators, Fans, and Dampers)?
Yes
E 'sent Tested
Tested
Satisfaetorr
IIniits
FCPS Power Booster:
2 Units
Yes
Annunciator:
1 Unit
Yes
Dialer, Communicator:
1 Unit
Horns, Strobes, Bells, etc:
135
Yes
Smoke Detector:
25
Yes
Heat Detector:
1
Yes
Duct Detector:
3
Yes
Pull Station:
1
Yes
Flow Switch:
3
Yes
Tamper Switch:
4
Yes
Low/High Air Switch:
N/A
Antifreeze Tamper:
N/A
Ansul System:
N/A
Equipment Tested
Tested
Satisisetor•
IInits
Ventilation Controls:
N/A
Elevator Recall Primary:
N/A
Elevator Recall Secondary:
N/A
Elevator Recall Shunt:
N/A
Access Control Door Release:
N/A
Auto Release:
N/A
Door Holders:
11
Notes:
Omni
Notes:
This is to certify that this Fire Alarm has been properly "tested" and "inspected" for liability, to cover the
items listed in this report according to Manufacturer's Recommendations.
Uwner/Mansger Signature- Date:
Certified Tester Signature• Martin Paton Date: 12/26/2023
Dotes 12