Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 23-00726
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
CA-1 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector
CA-1 Free Text Alex Owens : Electrical Open 1 All associated wiring must comply with 2017 NEC.
Fire System Construction Permit
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
ELECTRICAL CABINET
FLOOR VAULT
ELECTRICAL CABINET
ELECTRICAL
CABINET
ELECTRICAL CABINET
FLOOR VAULT
ELECTRICAL CABINET
ELECTRICAL
CABINET
RELEASING
CONTROL PANEL
BATTERY BATTERY
+
+
--
+----
ZONE 1
ZONE 2
ZONE 3
ZONE 4
OUTPUT 1
OUTPUT 2
OUTPUT 3
OUTPUT 4
PROGRAM
MODE
RUN
MODE
AC POWER
POWER TBL
SYSTEM TBL
SUP TBL
GROUND
FAULT
SUP 1/ABORT
SUPERVISORY 2
COMMONALARM
ALARM SILENCE
STEADY: DISCHARGED
FLASHING: PRE-
DISCHARGE
RUN
PROGRAM SET
SELECT
FUNCTION
SCROLL-DOWN
BUZZER SILENCE
SIGNAL SILENCE
SYSTEM RESET
SCROLL-UP
BUZZER SILENCE
VIEWING ANGLE
RED OUTPUT LED STEADY: ABORT
LAMP TEST
ARM-1
RELAY
MATRIX
OPERATIONS
SignalSignal
S+S+S-H+H-S+S+S-H+H-
Strobe Circuit
UL Listed
Control
Panel
Supervised
+
-
Horn Circuit
Supervised
+
-
PIPE MOUNTING DETAIL MOUNTING STRAP DETAIL
Unistrut Nut, Bolt &
Washer
Wall
Container
Mounting Strap
Unistrut Channel
2BBÑSggcU>ShWVÑl>I>bYÑCighÑUcCdBnÑl>hZѽ¤ÁÑ
A4
1
2
3
Janus Fire Systems NovecTM1230 Fluid Hydraulic Flow Calculation Program
Result Printout
Calculation Program Version 2.14.3.14
Calculated by: StateFire
2550 S. West Temple
Salt Lake City, UT 84115
United States
Phone: 801-288-2100
Fax: 801
Designed By: Kyle Arigot
Project Name:1 Stationery Place
Project Number:
Designed For: The Occassions Group
1 Stationery Place
System Constraints
Name of Hazard Electrical Room
Storage Pressure (psig):500 PSI Calculation Report Date:4/5/2023
Initial Cyl. Storage Temperature (F):70.0°Calculation Revision:
Qty of Main Cylinders:1 Mid Discharge Cyl.Pressure:215 PSIG
Qty of Reserve Cylinders:0 Cylinder Fill Density (lbs/cu.ft.):57.71
Total Amount of Agent (lbs):108 Percent of Agent in Pipe:6.46%
Altitude Relative to Sea Level (ft):4000 Average Discharge Time (sec):9.87
Type of Cylinder:Sv 130 Cylinder Cyl. Volume (Cu.ft.):1.87
Page 1 (Continued)
Your gateway to a new kind of service.
Janus Fire Systems NovecTM1230 Fluid Hydraulic Flow Calculation Program
Result Printout
Calculation Program Version 2.14.3.14
Hazard Characteristics
Enclosure Name:Electrical Room Fire Type:Class C Fire
Design Concentration: 5.9 Min Hazard Temp (F):65.0
Max Hazard Temp (F):75.0
Nozzle(s) Used:301 - 360° Nozzle, Brass Dimensions (ft):16.83 X 16.82 X 8.08
Total Volume (Cu.ft.):2288.14
Tot Agent Req'd @ 65.0 (F): 107.82 lbs
Voltage at Discharge:> 480V
Piping Network Input
-- Section --Cyl.------------------------------- Pipe --------------------------------Tee or Cplng/Nozzle
Start End Qty Length Elevation Sched.Size 90's Bends Valve Union Drill
1 2 1 0.0 4.1 SCH 40 1-1/4 0 0 None 0 0.000
2 3 0 4.0 4.0 SCH 40 3/4 1 0 None 0 0.000
3 301 0 15.3 -0.3 SCH 40 3/4 2 0 None 0 0.2570
Piping Network Results
Section Pipe Size Length Elevation EQL Tee or Start Term Flow
Start End (in) sch ft ft ft Valve PSIG (lbs/sec)
1 2 1-1/4 SCH 40 .00 4.08 8.00 None 215 210 11.19
2 3 3/4 SCH 40 4.00 4.00 6.06 None 210 177 11.19
3 301 3/4 SCH 40 15.25 -.25 19.37 None 177 111 11.19
Page 2 (Continued)
Your gateway to a new kind of service.
Janus Fire Systems NovecTM1230 Fluid Hydraulic Flow Calculation Program
Result Printout
Calculation Program Version 2.14.3.14
Nozzle Performance
Nozzle Nozzle Size Stock Nozzle Drill Dia Drill Total Orifice Discharged
ID (inches)Number Type (inches)Size Area (sq.in.)(lbs)
301 3/4"19531-071360° Nozzle, Brass 0.2570 F .415 108.0
Hazard Concentration Summary
Enclosure Agent Agent Concentration
Enclosure Volume Req'd Disch Conc.Achieved @ Pass or
Name (cu.ft)(lbs)(lbs)Req'd Min.Temp / Max.Temp Fail
Electrical Room 2288.14 107.82 108.00 5.90 5.90 / 6.02 Pass
Venting Estimate
Enclosure Leakage Relative Safety Max. Positive Max. NegativePos. ELANeg. ELA
Name Area Known Humidity Factor Pressure - PSFPressure - PSF (sq.in)(sq.in)
Electrical Room No 36%1 5 5 14 102.3
Design / Error Messages
1. - Hydraulic calculation was successful.
2. - Version dated 7/1/2013
3. - Pipe Sizes & Nozzle Diameters are fixed.
4. The designer has determined that additional gas for tees, per NFPA 2001 5.5.3.1.1 is not
required.
5. - * System is designed to meet Factory Mutual & Underwriters Laboratory design criteria.
6. - All agent requirements were calculated based on NFPA 2001, Table A.5.5.1(a).
Page 3 (Continued)
Your gateway to a new kind of service.
Janus Fire Systems NovecTM1230 Fluid Hydraulic Flow Calculation Program
Result Printout
Calculation Program Version 2.14.3.14
Statistics of Piping Used
(Note: Only U.S Standard Values are used by the math module)
Piping information for Pipe Type: -SCH 40
Pipe Metric English Metric English Metric Type of
Size (in)Size (mm)ID (in)ID (mm)lbs/ft kgs/M Joint
1-1/4 32 1.38 35.052 2.27 3.3781 Threaded
3/4 20 0.824 20.9296 1.13 1.6816 Threaded
Note: For Pipe Schedule(s): -SCH 40; these Pipes conform to ANSI A-53/A-106, grade A-ERW or
better
Data File: C:\Users\karigot\Documents\Jobs 2023\FSI Jobs\1 Stationary Place Taylor Corp -
4\Novec Calc.JDN
Page 4 (End of Report)
Your gateway to a new kind of service.
Janus Fire Systems NovecTM1230 Fluid Hydraulic Flow Calculation Program
Agent Calculation Requirements
Calculation Program Version 2.14.3.14
Calculated by: StateFire
2550 S. West Temple
Salt Lake City, UT 84115
United States
Phone: 801-288-2100
Fax: 801
Designed By: Kyle Arigot
Project Name:1 Stationery Place
Project Number:
Hazard Agent Requirements
Enclosure Name:Electrical Room: Electrical Room
Design Concentration:5.9
Fire Type:Class C Fire
Min Hazard Temp (F):65.0
Max Hazard Temp (F):75.0
Total Volume (Cu.ft.):2,288.14
Altitude:4000
Voltage at Discharge:>= 480V
Agent Requirement Formula for NOVEC:
W = (V/s (C/(100 - C))) * Altitude Correction Factor
Where:
W = Weight of agent required
V = Volume (Cu.ft.)
s = 0.9856 + 0.002441(t)
t = Temperature (F)
C = Design Concentration
s = 1.144265
Altitude Correction Factor: 0.86
W = 2,288.14 / 1.144265 (5.9 / (100 - 5.9)) * 0.86
Total quantity of Novec 1230 Fluid required @ Min Temp is: 107.82 lbs
Page 1 (End of Report)
Your gateway to a new kind of service.
30.75"
49.1"
53.0"
11.9"
130 lb
10.0"
Janus Fire Systems NovecTM1230 Fluid Hydraulic Flow Calculation Program
Piping Bill of Material
Calculation Program Version 2.14.3.14
Piping and Nozzle Material:
Hazard Name: Electrical Room
Item Type Style Size (in)Drill Dia Qty
Piping - SCH 40 3/4 N/A 19.25 ft
Elbow Class 300 MI - ANSI B16.3 3/4 N/A 3 (Ea)
Nozzle (S/N: 19531-071)360° Nozzle, Brass 3/4 0.257 1 (Ea)
Statistics of Piping Used
(Note: Only U.S Standard Values are used by the math module)
Piping information for Pipe Type: -SCH 40
Pipe Metric English Metric English Metric Type of
Size (in)Size (mm)ID (in)ID (mm)lbs/ft kgs/M Joint
1-1/4 32 1.38 35.052 2.27 3.3781 Threaded
3/4 20 0.824 20.9296 1.13 1.6816 Threaded
Note: For Pipe Schedule(s): -SCH 40; these Pipes conform to ANSI A-53/A-106, grade A-ERW or
better
Data File: C:\Users\karigot\Documents\Jobs 2023\FSI Jobs\1 Stationary Place Taylor Corp -
4\Novec Calc.JDN
The above list of pipe and fittings was generated based on the information provided to the
calculation program. Any additional equivalent length, inputted as elbows, will appear as elbows
in this list. This list is NOT intended as a buy list, and should be field verified. All piping purchased
should adhere to the requirements set forth in NFPA 2001, Latest Edition. Where Concentric
Reducers are called for, Hex Bushings may be used. These bushings are to be Class 2000
Forged Steel, ANSI B16.11
Page 1 (End of Report)
Your gateway to a new kind of service.
UL LISTED
CONTROL
PANEL
L4L3
L1L2S2
S1
L4L3
L1L2S2
S1
UL LISTED
CONTROL
PANEL
ABORTDISCHARGE
ZONE-3
SUP-1
ZONE-1
&
ZONE-2
FACP Battery Calculation 5/11/2023
PROJECT NAME:
Required Standby Time:24 Hours
Required Alarm Time:5 Minutes
Regulated Load in Standby
Number Current Total Current
Device Type of Devices (Amps)(Amps)
JFS-C1 Main Board 1 X 0.12100 =0.12100
Smoke Detector 2 X 0.00006 =0.00012
Actuator 1 X 0.03000 =0.03000
TOTAL STANDBY LOAD 0.15112
Regulated Load in ALARM
Number Current Total Current
Device Type of Devices (Amps)(Amps)
JFS-C1 Main Board 1 X 0.27400 =0.27400
Smoke Detector 2 X 0.15000 =0.30000
Actuator 1 X 0.50000 =0.50000
OUT #1 (See Voltage Drop Calculations)1 X 0.02800 =0.02800
OUT #2 (See Voltage Drop Calculations)1 X 0.08000 =0.08000
OUT #4 (See Voltage Drop Calculations)1 X 0.17000 =0.17000
TOTAL ALARM LOAD 1.35200
Battery Requirements
Standby Load Required Standby Time in Hours
Current (Amps)0.15112 X 24.00000 =3.62688
Alarm Load Required Alarm Time in Hours
Current (Amps)1.35200 X 0.08333 =0.11267
Total Ampere Hours (before derating factor)3.73955
Derating Factor X 20%
TOTAL AMPERE HOURS REQUIRED =4.48746
BATTERIES (2 - 12v)7 Ah
Taylor Corp. Artco
Point to Point NAC Voltage Drop Calculation 5/11/2023
Project Name Taylor Corp. Artco
Circuit Number OUT-1
Nominal System Voltage 20.4 volts Wire Resistance
Minimum Device Voltage 16.0 volts Gauge Per 1000
Distance from source to 1st device 35 feet 14 3.07
Wire Gauge for balance of circuit 14 3.07
Max Output Current 2.50 amps
Total Circuit Current 0.028 amps
End of Line Voltage 20.39 volts
Distance
Candela Device Previous Voltage at Drop from Percent
Rating Current Device Device source Drop
Device 1 n/a 0.028 20.39 0.006 0.03%
Totals 0.028 35
Notes:
Wire resistance is doubled in the calculations for two wires (Positive and Negative).
The voltage calculated to the last device must not be lower than the manufactures listed
minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)).
Circuit is within limits
Point to Point NAC Voltage Drop Calculation 5/11/2023
Project Name Taylor Corp. Artco
Circuit Number OUT-2
Nominal System Voltage 20.4 volts Wire Resistance
Minimum Device Voltage 16.0 volts Gauge Per 1000
Distance from source to 1st device 35 feet 14 3.07
Wire Gauge for balance of circuit 14 3.07
Max Output Current 2.50 amps
Total Circuit Current 0.080 amps
End of Line Voltage 20.38 volts
Distance
Candela Device previous Voltage at Drop from Percent
Rating Current device Device source Drop
Device 1 75 0.080 20.38 0.017 0.08%
Totals 0.080 35
Notes:
Wire resistance is doubled in the calculations for two wires (Positive and Negative).
The voltage calculated to the last device must not be lower than the manufactures listed
minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)).
Circuit is within limits
Point to Point NAC Voltage Drop Calculation 5/11/2023
Project Name Taylor Corp. Artco
Circuit Number OUT-4
Nominal System Voltage 20.4 volts Wire Resistance
Minimum Device Voltage 16.0 volts Gauge Per 1000
Distance from source to 1st device 38 feet 14 3.07
Wire Gauge for balance of circuit 14 3.07
Max Output Current 2.50 amps
Total Circuit Current 0.170 amps
End of Line Voltage 20.36 volts
Distance
Candela Device previous Voltage at Drop from Percent
Rating Current device Device source Drop
Device 1 75 0.170 20.36 0.040 0.19%
Totals 0.170 38
Notes:
Wire resistance is doubled in the calculations for two wires (Positive and Negative).
The voltage calculated to the last device must not be lower than the manufactures listed
minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)).
Circuit is within limits