HomeMy WebLinkAboutPLANS - 23-00799 - 351 S 3rd E - Solar PanelsPLAN SET LEGEND SHEET INDEX VICINITY MAP APPLICABLE CODES ABBREVIATIONS PROJECT INFORMATION PV-1 COVER PAGE PV-2 SITE PLAN, AERIAL VIEW PV-3 ELECTRICAL LINE DIAGRAM AND NOTES PV-4 ELECTRICAL CALCULATIONS PV-5 REQUIRED SIGNAGE IS S U E D F O R : P E R M I T DA T E 10 / 2 3 / 2 0 2 3 ww w . b i g d o g e n e r g y . c o m SO L A R P H O T O V O L T A I C S Y S T E M LA Y N E D E A R D E N DE S I G N E D B Y CO N T R A C T O R I N F O R M A T I O N PV-1 35 1 S O U T H 3 R D S T R E E T E A S T , RE X B U R G , I D 8 3 4 4 0 BI G D O G R E N E W A B L E E N E R G Y CO N T R A C T O R L I C # : I D A H O # 0 1 7 9 1 6 62 0 P H E A S A N T R I D G E D R CH U B B U C K , I D 8 3 2 0 2 20 8 - 2 4 2 - 3 3 5 2 T 20 8 - 2 3 2 - 5 9 3 5 F X _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ (E)EXISTING (N)NEW EXT EXTERIOR INT INTERIOR EMT ELECTRICAL METALLIC TUBING RMT RIGID METALLIC TUBING FMC FLEXIBLE METALLIC CONDUIT VOC VOLTAGE OPEN CIRCUIT VMP VOLTAGE AT MAX. POWER ISC SHORT CIRCUIT CURRENT IMP CURRENT AT MAX. POWER NTS NOT TO SCALE MSP SUB AC DC SLC M INV JB CB BAT MAIN SERVICE PANEL SUB SERVICE PANEL AC DISCONNECT DC DISCONNECT SOLAR LOAD CENTER MONITORING METER INVERTER JUNCTION BOX COMBINER BOX BATTERY PV PRODUCTION METER RAPID SHUTDOWN DISCONNECT PM RSD LAYNE DEARDEN 351 SOUTH 3RD STREET EAST, REXBURG, ID 83440 16 - Q.PEAK DUO BLK ML-G10+ 405 (405W) PHOTOVOLTAIC MODULES 1 - SOLAREDGE SE6000H-US (6000W) INVERTER(S) SYSTEM SIZE: 6.480 KW DC STC ARRAY AREA: 338.17 SF 1. ALL MODULES WILL BE GROUNDED IN ACCORDANCE WITH THE CODE AND THE MANUFACTURES INSTALLATION INSTRUCTIONS. 2. ALL PLACARDS REQUIRED BY NEC 2017 CODE MACHINE PRINTED LETTERS IN A CONTRASTING COLOR TO THE PLACARD. 3. LIQUID TIGHT FLEXIBLE CONDUIT SHALL BE SUNLIGHT RESISTANT. 4. ELECTRICAL INSTALLATION WILL COMPLY WITH NEC 2017 CODE. 5. ALL SOLAR MODULES EQUIPMENT AND METALLIC COMPONENTS ARE TO BE BONDED. 6. ALL PLUMBING AND MECHANICAL ROOF VENTS TO CLEAR FROM PHOTOVOLTAIC ARRAY, OR EXTEND ABOVE SOLAR PANELS. 7. SOLAR PHOTOVOLTAIC SYSTEM TO BE INSTALLED ON RESIDENTIAL STRUCTURE. 8. DESIGN COMPLYING WITH THE IBC 2018 CODE AND ALL LOCAL ORDINANCES AND POLICIES. 9.THE PROJECT HAS BEEN DESIGNED TO WITHSTAND A MINIMUM 115 MPH WIND LOAD. 10.THE SYSTEM WILL NOT BE INTERCONNECTED UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND A UTILITY IS OBTAINED. 11.IF THE MAIN SERVICE PANEL DOES NOT HAVE VERIFIABLE GROUNDING ELECTRODE, IT IS THE CONTRACTORS RESPONSIBILITY TO INSTALL SUPPLEMENTAL GROUNDING ELECTRODE. 12.EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED ON THE MODULE AND THE MANUFACTURERS INSTALLATION INSTRUCTIONS. 13.A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. 14.PROPER ACCESS AND WORKING CLEARANCE WILL BE PROVIDED "WARNING: PV POWER SOURCE" TO BE PLACED EVERY 10 FT. 15.GFCI PROTECTION IN INVERTER. ALL WORK TO COMPLY WITH THE FOLLOWING CODE: NEC 2017 CODE IBC/IRC/IFC 2018 CODE ADDITIONAL NOTES OCCUPANCY: R-3 CONSTRUCTION TYPE: V-B UNSPRINKLERED ALL CONDUIT TO RUN ON EXTERIOR OF HOUSE UNLESS OTHERWISE NOTED COVER PAGE CO V E R P A G E 10/30/2023 MSPAC IN V MTR SUB AERIAL VIEW SI T E P L A N , A E R I A L V I E W N IS S U E D F O R : P E R M I T DA T E 10 / 2 3 / 2 0 2 3 ww w . b i g d o g e n e r g y . c o m SO L A R P H O T O V O L T A I C S Y S T E M LA Y N E D E A R D E N DE S I G N E D B Y CO N T R A C T O R I N F O R M A T I O N PV-2 35 1 S O U T H 3 R D S T R E E T E A S T , RE X B U R G , I D 8 3 4 4 0 BI G D O G R E N E W A B L E E N E R G Y CO N T R A C T O R L I C # : I D A H O # 0 1 7 9 1 6 62 0 P H E A S A N T R I D G E D R CH U B B U C K , I D 8 3 2 0 2 20 8 - 2 4 2 - 3 3 5 2 T 20 8 - 2 3 2 - 5 9 3 5 F X _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ ROOF DESCRIPTION ROOF ARRAY PITCH AZIMUTH #1 20°180° #2 34°90° SITE PLAN PROPOSED SYSTEM DC SIZE / AC SIZE: 6.480 KW-DC / 6.000 KW-AC TOTAL # OF PANELS: 16 ABBREVIATIONS SCALE: NTS SCALE: NTS SO U T H 3 R D S T R E E T E A S T ROOF TYPE: METAL PANEL PLACEMENT MAY DIFFER FROM APPROVED DESIGN DUE TO UNFORESEEN OBSTRUCTIONS OR PERMITTING SETBACKS TOTAL # OF MODULES TOTAL ARRAY AREA (Sq. Ft.) TOTAL ROOF AREA (Sq. Ft.) ROOF AREA COVERED BY ARRAY (%) 16 338.17 2459.84 13.75 CUSTOMER APPROVED LAYOUT CHANGE x: SOLAR PV MODULE INV INVERTER MSP MAIN SERVICE PANEL AC AC DISCONNECT MTR METER SUB SUB SERVICE PANEL 3FT/18INCH FIRESETBACK AC DISCONNECT WITHIN 3’ FROM UTILITY METER ROOF #2 ROOF #1 10/30/2023 ELECTRICAL NOTES SI N G L E L I N E D I A G R A M RACKING & MODULES ARE GROUNDED VIA A CONTINUOUS #6AWG COPPER CONDUCTOR CONNECTED W/ WEEBS - MODULES ARE FACTORY PROVIDED W/ 2 THREADED HOLES TO FACILITATE LANDING OF THE LUGS ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH ARTICLE 250. ALL CIRCUITS CONNECTED TO MORE THAN ONE SOURCE SHALL HAVE OVERCURRENT DEVICES LOCATED SO AS TO PROVIDE OVERCURRENT PROTECTION FROM ALL SOURCES 690.9 (A) IS S U E D F O R : P E R M I T DA T E 10 / 2 3 / 2 0 2 3 ww w . b i g d o g e n e r g y . c o m SO L A R P H O T O V O L T A I C S Y S T E M LA Y N E D E A R D E N DE S I G N E D B Y CO N T R A C T O R I N F O R M A T I O N PV-3 35 1 SO U T H 3 R D S T R E E T E A S T , RE X B U R G , ID 83 4 4 0 BI G D O G R E N E W A B L E E N E R G Y CO N T R A C T O R L I C # : ID A H O # 0 1 7 9 1 6 62 0 P H E A S A N T R I D G E D R CH U B B U C K , I D 8 3 2 0 2 20 8 - 2 4 2 - 3 3 5 2 T 20 8 - 2 3 2 - 5 9 3 5 F X _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ ALL MODULES WILL BE GROUNDED IN ACCORDANCE WITH CODE AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. MODULE: Q.PEAK DUO BLK ML-G10+ 405 (405W) Voc= 45.34V Isc= 11.17A Vmp= 37.39V Imp= 10.83A PROPOSED SYSTEM DC SIZE / AC SIZE: 6.480 KW-DC / 6.000 KW-AC 1.PV ARRAYS ARE PER SINGLE LINE. 2.PV ARRAY WIRING TO JUNCTION IS #10 AWG USE 2 W/ FIELD INSTALLED MC CONNECTORS TO INTERFACE W/ MODULES. 3.PV ARRAY COMBINER/JUNCTION BOX PROVIDES TRANSITION FROM ARRAY WIRING TO CONDUIT WIRING. 4.USE UFER GROUND ELECTRODE SYSTEM FROM INVERTER TO EXISTING MAIN SERVICE GROUND ELECTRODE PER N.E.C. 250.58. 5.GROUND ELECTRODE CONDUCTOR FROM INVERTER TO GROUND ELECTRODE TO BE MINIMUM PROTECTION OF BARE ARMOR SHEATHED CABLE FOR ALL CONDUCTOR SIZES. 6.ALL GROUND CONNECTED TO MAIN SERVICE GROUND IN MAIN SERVICE PANEL. 7.CONNECTORS SHALL BE POLARIS OR EUROSTRIP IT CONNECTORS. 8.INVERTER SHALL BE PER SINGLE LINE, SEE ATTACHED CUT SHEET. 9.INVERTER IS PER SINGLE LINE. 10.AC DISCONNECT SHALL BE PER SINGLE LINE. 11.EQUIPMENT GROUNDING CONDUCTORS ON AC AND DC SIDE SIZED ACCORDING TO N.E.C. 690. 12.POLE OF PV ARRAY REFERENCED TO GROUND AT THE INVERTER IN SINGLE LINE. 13.ALL CONDUCTORS SHALL BE 600V, 90C STANDARD COPPER. ALL CONDUCTORS IN CONDUIT SHALL BE THWN-2. 14.MAXIMUM DC VOLTAGE DROP SHALL BE 2.5% 15.ALL CONDUCTORS SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED. 16.ALL WORK TO COMPLY WITH NEC 2017 CODE. 17.DC ARRAY CONDUCTORS ARE TO REMAIN OUTSIDE OF BUILDING PRIOR TO FUSIBLE COMBINER BOX OR FUSIBLE DC DISCONNECT MEANS. 18.EXACT CONDUIT RUN LOCATIONS SUBJECT TO CHANGE. 19.3.0 PSF MAX (.5 PSF FROM RACKING, 2.5 PSF FROM MODULES) DEAD LOAD CONTRIBUTED FROM SOLAR ARRAY. 20.ARC FAULT INSTALLED AT INVERTER OR IN COMBINER BOX. 21.DC GROUND FAULT PROTECTION INTEGRATED IN INVERTER. 22.POINT OF CONNECTION BREAKER TO BE LOCATED OPPOSITE END OF BUSBAR FROM MAIN UNLESS OTHERWISE NOTED. 23.ANY UNDERGROUND WIRING METHODS WILL COMPLY WITH NEC 300.5(J), 300.7(B), 352.44, AND OTHER SECTIONS OF CHAPTER 3 AS APPLICABLE. 24.ANY EXPOSED PVC CONDUIT SHALL COMPLY WITH NEC 352.10 25.ALL PV SYSTEM DC CIRCUITS RUN INSIDE A BUILDING SHALL BE CONTAINED IN A METAL RACEWAY IN ACCORDANCE TO NEC 690.31(G) 26.COMPLIES WITH 705.12(B)(2)(3)(B) 27.SUPPLY SIDE CONNECTION WITH LISTED INSULATION PIERCING CONNECTORS IN ACCORDANCE WITH 705.12(A) AND 230.82 28.CONNECTION AT PANEL SECONDARY SERVICE LOCATION 29.COMPLIES WITH 705.12(B)(2)(1)(B) ELECTRICAL SINGLE LINE DIAGRAM ELECTRICAL EQUIPMENT CALLOUTS6,480W TOTAL SOLAR ARRAY 16 Q.PEAK DUO BLK ML-G10+ 405 (405W) PANELS 2 STRING(S) OF 8 MODULES CONNECTED IN SERIES @ INVERTER WIRE AND CONDUIT CALLOUTS SOLADECK MODEL 0783-41 JUNCTION BOX/ROOF PENETRATION, SOLAREDGE SE6000H-US INVERTER UNGROUNDED, NEMA 3R, UL LISTED, (W/ INTEGRATED DC DISCONNECT) WITH INTEGRATED GFP, W/ INTEGRATED AFP (2) #10 AWG THWN-2 (1) #10 AWG THWN-2 GND IN 3/4" EMT/FMC (2) #8 AWG THWN-2 (1) #10 AWG THWN-2 GND IN 3/4" EMT A B C D E F SQUARE D SAFETY SWITCH, #DU222RB 250 VAC, SINGLE PHASE, 60A, NON-FUSED NEMA 3R, UL, CSA, NOM CERTIFIED 1 2 3 (E) MILBANK MAIN SERVICE PANEL (W/ (E) 200A MAIN BREAKER CENTER FED) 200A, SINGLE PHASE, 240V MPPT 1 MPPT 2 3 C _ ~ 8 MODULES IN SERIES 1B A ONE PER PANEL2 STRING 1 1 ELECTRICAL LINE DIAGRAM PV-3 SCALE: NTS (2) #10 AWG PV/RHW-2 IN FREE AIR (1) #6 AWG BARE COPPER GND IN FREE AIR BI-DIRECTIONAL UTILITY METER 200A, SINGLE PHASE, 240V 600V 6.0kW, 240VAC, SINGLE PHASE, 25A, 440W, 1000VDC SOLAREDGE S440 OPTIMIZER ONE PER PANEL EXISTING CONDUCTORS WITH EXISTING CONDUIT4 G 200A, SINGLE PHASE, 240VAC, (E) SUB PANEL (W/ (E) 200A MAIN BREAKER TOP FED) 4 MODULES IN SERIES B A21 ONE PER PANEL STRING 2A ON ROOF 1 4 MODULES IN SERIES B A21 STRING 2B ONE PER PANEL ON ROOF 2 AC DISCONNECT WITHIN 3’ FROM UTILITY METER ON ROOF 2 200A E N G G 4 G N G N 40A BACKFEED 26 F L1 L2 N G D3 L1 L2 N G 200A HOMELINE BREAKER IS S U E D F O R : P E R M I T DA T E 10 / 2 3 / 2 0 2 3 ww w . b i g d o g e n e r g y . c o m SO L A R P H O T O V O L T A I C S Y S T E M LA Y N E D E A R D E N DE S I G N E D B Y CO N T R A C T O R I N F O R M A T I O N PV-4 35 1 SO U T H 3 R D S T R E E T E A S T , RE X B U R G , ID 83 4 4 0 BI G D O G R E N E W A B L E E N E R G Y CO N T R A C T O R L I C # : ID A H O # 0 1 7 9 1 6 62 0 P H E A S A N T R I D G E D R CH U B B U C K , I D 8 3 2 0 2 20 8 - 2 4 2 - 3 3 5 2 T 20 8 - 2 3 2 - 5 9 3 5 F X _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ EL E C T R I C A L C A L C U L A T I O N S ELECTRICAL CALCULATIONS STRINGS 1 - 2 OPERATING VOLTAGE = 37.39V TOTAL OPERATING CURRENT = 6.75A AC CONDUCTOR AMPACITY CALCULATIONS: # OF INVERTERS : 1 EXPECTED WIRE TEMP (°C): 33°C TEMP CORRECTION PER TABLE 310.16 : 0.96 AWG CIRCUIT CONDUCTOR SIZE : #8 # OF CURRENT CARRYING CONDUCTORS : 3 CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a): 1 CIRCUIT CONDUCTOR AMPACITY : 50A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B): 1.25 x MAX INVERTER OUTPUT CURRENT x # OF INVERTERS 1.25 x 25 x 1 = 31.25A DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16: TEMP CORR. PER NEC TABLE 310.16 x CONDUIT FILL CORR. PER NEC 310.15(B)(3)(a) x CIRCUIT CONDUCTOR AMPACITY : 0.96 x 1 x 50 = 48.00A > 31.25A <= 40A OCPD TOTAL ARRAY AC CONDUCTOR AMPACITY CALCULATIONS (FROM ARRAY TO MSP): # OF INVERTERS : 1 CIRCUIT CONDUCTOR SIZE : #8 # OF CURRENT CARRYING CONDUCTORS : 3 CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a): 1 CIRCUIT CONDUCTOR AMPACITY : 50A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B): 1.25 x MAX INVERTER OUTPUT CURRENT x # OF INVERTERS 1.25 x 25 x 1 = 31.25A A MAIN DISCONNECT : 200A NEW SOLAR SYSTEM FUSE/OCPD : 40AMAX PV CONTINUOUS CURRENT PER NEC 690.8(A)(1): 1.25 x SOLAR PANEL Isc: 1.25 x 11.17 = 13.96A MAX PV VOLTAGE & CURRENT CALCULATIONS: RECORD LOW TEMP (°C): -26°C VOLTAGE CORRECTION PER NEC 690.7 : 1.21 MAX PV SYSTEM VOLTAGE PER NEC 690.7: SOLAR PANEL Voc X Vcorrection: 45.34 V x 1.21 = 54.86 V DC CONDUCTOR AMPACITY CALCULATIONS: MAX # OF STRINGS PER SET OF DC CONDUCTORS : 1 EXPECTED WIRE TEMP (°C): +22°C Correction : 55°C TEMP CORRECTION PER TABLE 310.16 : 0.76 # OF CURRENT CARRYING CONDUCTORS : 2 CONDUIT FILL CORRECTION PER NEC 310.15(B)(3)(a): 1 CIRCUIT CONDUCTOR SIZE : #10 AWG CIRCUIT CONDUCTOR AMPACITY : 30 A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B): 1.25 x MAXIMUM OUTPUT CURRENT OF OPTIMIZER 1.25 x 15 = 18.75 A DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16: TEMP CORR. PER NEC TABLE 310.16 x CONDUIT FILL CORR. PER NEC 310.15(B)(3)(a) x CIRCUIT CONDUCTOR AMPACITY: 0.76 x 1 x 30 = 22.80A > 18.75A REQUIRED SIGNAGE IS S U E D F O R : P E R M I T DA T E 10 / 2 3 / 2 0 2 3 ww w . b i g d o g e n e r g y . c o m SO L A R P H O T O V O L T A I C S Y S T E M LA Y N E D E A R D E N DE S I G N E D B Y CO N T R A C T O R I N F O R M A T I O N PV-5 35 1 SO U T H 3 R D S T R E E T E A S T , RE X B U R G , ID 83 4 4 0 BI G D O G R E N E W A B L E E N E R G Y CO N T R A C T O R L I C # : ID A H O # 0 1 7 9 1 6 62 0 P H E A S A N T R I D G E D R CH U B B U C K , I D 8 3 2 0 2 20 8 - 2 4 2 - 3 3 5 2 T 20 8 - 2 3 2 - 5 9 3 5 F X _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ RE Q U I R E D S I G N A G E ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE WEATHER RESISTANT/SUNLIGHT RESISTANT AND CANNOT BE HAND-WRITTEN. NEC 110.21(B) WARNING: PHOTOVOLTAIC POWER SOURCE THE MARKINGS SHALL BE PERMANENTLY AFFIXED AND VISIBLE AFTER INSTALLATION PER NEC 690.31(G)(3-4). 11. AT EVERY ENCLOSURE, EVERY 10’ ALONG CONDUIT OR MC CABLE, AN AT EACH SIDE OF WHERE THE CONDUIT OR CABLE PASSES THROUGH A WALL, FLOOR, OR ANY OTHER PARTITION. DIRECT CURRENT PHOTOVOLTAIC SOURCE SYSTEM AC VOLTAGE: 240V MAX AC CIRCUIT CURRENT: 25A MAX DC CURRENT PER OPTIMIZER: 15A 10. SIGNAGE REQUIRED AT STRING INVERTER PER NEC 690.53: 2. LABEL FOR SOLAR AC DISCONNECT: TOTAL RATED AC AMPS: 40A SYSTEM AC VOLTAGE: 240V 3. THE FOLLOWING SIGNAGE MUST HAVE A MINIMUM OF 3/8" HIGH LETTERING, IN ARIAL FONT (NON-BOLD), WITH CAPITAL LETTERS, WHITE ON RED BACKGROUND AND A REFLECTIVE, WEATHER RESISTANT MATERIAL. 1. PROVIDE A PLACARD WITH THE FOLLOWING WORKING IN 1/4" HIGH LETTERING PER NEC 690-17. AT THE MAIN SERVICE DISCONNECT PROVIDE A SIGN WITH THE FOLLOWING WORDING: THE SIGN SHOULD BE PLACED ON THE OUTSIDE COVER IF THE MAIN SERVICE DISCONNECT IS OPERABLE WITH THE SERVICE PANEL CLOSED. CUSTOMER OWNED ON SITE POWER GENERATION SYSTEM DISCONNECT 8. THE FOLLOWING SIGN MUST BE PROVIDED ON THE OUTSIDE (OR WITHIN 3' OF) THE SERVICE PANELBOARD, AS REQUIRED PER NEC 690.56(C)(1): RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN FIRE DEPARTMENT REQUIRED SIGNAGE 4. LABELS TO BE INSTALLED ON FACE OF THE UTILITY AC DISCONNECT: 5. LABEL INSTALLATION AT INTERCONNECT BREAKER: 9. SIGNAGE REQUIRED AT SERVICE PANELBOARD PER NEC 690.54: 7. AT PV DISCONNECT SWITCH AS REQUIRED PER NEC 690.56(C)(3): 6. REFLECTIVE PLACARD AT SERVICE STATING: SOLAR AC DISCONNECT WARNING: ELECTRICAL SHOCK HAZARD. DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. WARNING: INVERTER CONNECTION. DO NOT RELOCATE THIS OVERCURRENT DEVICE. WARNING DUAL POWER SUPPLY SOURCES: UTILITY GRID AND PV SOLAR ELECTRIC SYSTEM TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN THE PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY SOLAR ELECTRIC PV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN