HomeMy WebLinkAboutFS PRELIM PLANS - 22-00502 - Mountain West Rental and SalesSCOPE OF WORK J IONS FLOW HYD O PRESSURE HYD I SITE PLAN UPRIGHT SPRINKLER DETAIL --� UPRIGHT SPRINKLER WELDED OUTLET BRANCHLINE PIPING INSTALL SPRINKLER 1"-12" BELOW DECK HANGER SPACING - STEEL PIPE SIZE OF PIPE MAX HANGER WEIGHT OF WATER SUPPORTED SPACING FILLED PIPE 1" (Sch 40) 12'-0 2.05 Ibs/ft 1 1/4" (Sch 40) 12'-0 2.93 Ibs/ft 1 1/2" (Sch 10) 15-0 3.04 Ibs/ft 2" (Sch 10) 15-0 4.22 Ibs/ft 2 1/2" (Sch 10) 15'-0 5.89 Ibs/ft 3" (Sch 10) 15-0 7.94 Ibs/ft 4" (Sch 10) 15-0 11.78 Ibs/ft 6" (Sch 10) 15'-0 23.03 Ibs/ft 2011-8 1 r r � i►- y UPRIGHT SPRINKLER DETAIL CEILING z Z� �yCA UPRIGHT SPRINKLER 1" SCH.40 PIPE 1" X 1/2" ELBOW STEEL PIPE DIMENSION TABLE SCHEDULE 10 PIPE SCHEDULE 40 PIPE NOMINAL INSIDE NOMINAL INSIDE PIPE SIZE DIAMETER PIPE SIZE DIAMETER (IN.) (IN.) (IN.) (IN.) 1 " 1.097 1 " 1.049 1'/4• 1.442 1'/4" 1.380 1'/" 1.682 1'/" 1.610 2" 2.157 2" 2.067 2'/" 2.635 2'/" 3" 2.469 3.068 W 3.260 4" 4.260 4" 4.026 6" 6.357 6" 8" 6.065 7.981 V. 8.249 TOP BEAM CLAMP (W/ RETAINER STRAP) RETAINER STRAP _ TOP BEAM CLAMP I-BEA = ALLTHREAD ROD ��zzl • SWIVEL RING PIPE FLEXIBLE DROP TO SPRINKLER NOTE: BRANCHLINE 48" FLEXIBLE DROP LENGTH MAX NUMBER OF BENDS = 6 MIN RADIUS = 2" (UL) / T' (FM) 22'-0 EQUIVALENT LENGTH CE-::u FLEXIBLE DROP MOUNTING BRACKET CEILING SEMI RECESSED SPRINKLER CENTER OF TILE REAOF WORK INVERTED BEAM CLAMP (W/ RETAINER STRAP) I-BEA RETAINER BEAM CLAMP ALLTHREAD ROD SWIVEL RING PIPE WET SYSTEM AIR VENT 1/2" X 0-3 NIPPLE 1/2" 90' ELBOW- 1/2" PLUG 1/2" X 0-3 NIPPLE i 1/2" BALL VALVE BRANCHLINE NOTE: ASINGLE AIR VENT SHALL BE LOCATED NEAR A HIGH POINT IN THE LOWER FIRE PROTECTION PLAN TRAPEZE HANGER DETAIL BEAM / JOIST TOP BEAM CLAMP rc ALLTHREAD ROD PIPE in: I L ALLTHREAD ROD BEAM CLAMP SWIVEL RING - PIPE REFERENCE NFPA 13 2019, SECTION 17.1.1 FOR SIZING 3/8" BEA CLAMP 3/8" RO SWIVEL RIN Gu • TOLCO SWIVEL (FIG 75) 3/8" ROD BRANCHLINE PIPE SPRINKLER DROP DETAIL (RECESSED SPRINKLER) BRANCHLINE 1" SCH.40 DROP V ARMOVER 1" ELBOW aa,4 -2 11OX 1/2" R4C. 8 CEILING ❑ 1 'R LAN SEE PFOR HEIGHT SCALE 1/8" = V-0" SEMI -RECESSED SPRINKLER CENTER OF TILE DROP TO PENDENT SPRINKLER (RECESSED SPRINKLER) VARMOVER " if )❑ 1" ELBOW BRANCHLINE 1" SCH.40 DROP 1" X 1/2" R.C. CEILING SEE PLAN FOR HEIGHT ` SEMI -RECESSED SPRINKLER SAMMY X-PRESS 20 / METAL DECK SAMMY XP20�� I ALLTHREAD RODS SWIVEL RING PIPE STEEL SAMMY SIDEWINDER ZEE PURLING- Fr\ SWIVEL SAMMY SIDEWINDER ALLTHREAD ROD PIPE TO INSTALL AND TESTA NEW FIRE SPRINKLER SYSTEM. UNDERGROUND STUB PIECE FROM 5' OUT IS TO BE PROVIDED. ALL OTHER UNDERGROUND PIPING WILL BE INSTALLED AND FLUSHED BY OTHERS. SYSTEM DESIGN SHALL BE IN ACCORDANCE WITH NFPA 13 2019 EDITION AND LOCALAUTHORITY. DESIGNED BY: JASON BLATTER 208-881-5439 - OFFICE 6312 S. BURGRAFF WAY IDAHO FALLS, ID 83402 AUTHORITY HAVING JURISDICTION: REXBURG FIRE MARSHAL 26 N. CENTER REXBURG, ID 83440 208-359-3010 GENERAL NOTES 1. SYSTEM DESIGN, INSTALLATION AND TESTING SHALL BE IN ACCORDANCE WITH NFPA 13 (2019 EDITION) AND LOCAL FIRE AUTHORITY. 2. ALL MATERIALAND DEVICES TO BE U.L. LISTED AND/OR F.M. APPROVED FOR FIRE SPRINKLER USE. 3. ALL 1" SYSTEM PIPING SHALL BE SCHEDULE 40 BLACK PIPE WITH THREADED Cl FITTINGS. 4. ALL SYSTEM PIPING 1'/4"AND LARGER SHALL BE EDDY FLOW BLACK PIPE WITH GROOVED FITTINGS & GROOVED RIGID COUPLINGS. 5. PIPE SHALL BE MANUFACTURED TO MEETASTM A135 STANDARDS. CRR VALUE = 1.0 OR GREATER 6. ALL HANGERS SHALL BE DESIGNED, SPACEDAND INSTALLEDAS PER NFPA-13, 2019 EDITION, CHAPTER-18. MAX LENGTH OF UNSUPPORTED AR MOVERS SHALL BE 24" (PRESSURE LESS THAN 100 PSI). 7. SPRINKLERS LOCATED IN ACOUSTICAL GRID CEILINGS SHALL BE INSTALLED CENTER OF TILE OR QUARTER POINTS. 8. ALLALARM SYSTEM WIRING AND INSTALLATION IS BY OTHERS. 24 HOUR SUPERVISION TO BE PROVIDED BY OTHERS. 9. PAINTING, WIRING, FIRE EXTINGUISHERS, HYDRANTS, THRUST BLOCKING, CITY WATER CONNECTION, EXCAVATION, BACKFILLING AND SYSTEM MONITORING SHALL BE PROVIDED BY OTHERS. 10. FLUSHING AND TESTING OF UNDERGROUND PIPING SHALL BE COMPLETED BY THE INSTALLING CONTRACTOR BEFORE CONNECTION TO THE FIRE SPRINKLER SYSTEM. 11. ALL PENETRATIONS THROUGH FIRE RATEDASSEMBLIES SHALL BE FIRE STOPPED. FIRE STOPPING MATERIAL SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTION BY OTHERS. 12. HYDRAULIC PLACARD SHALL BE POSTED ON RISER. 13. BUILDING OWNER SHALL BE RESPONSIBLE FOR ADEQUATE HEAT (40°FAND ABOVE) IN ALL WET PIPE AREAS TO PREVENT SPRINKLER SYSTEM FROM FREEZING. DESIGN DETAILS THIS AUTOMATIC SPRINKLER SYSTEM IS SIZED BASED ON HYDRAULIC CALCULATIONS IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 13 2019 EDITION DENSITYAREA METHOD. FIRE SPRINKLER SYSTEM IN AREA OF WORK IS DESIGNED TO, ORDINARY HAZARDS GROUP 2 OCCUPANCIES. PERMISSIBLE DECREASES AND REQUIRED INCREASES FROM NFPA 13 HAVE BEEN APPLIED TO DESIGN AREA. WATER SUPPLY DATA: STATIC PRESSURE: 82 RESIDUAL PRESSURE: 70 FLOW: 1803 DATE: 10/17/2022 SOURCE: 3-D FIRE PROTECTION BUILDING DETAILS - BUILDING STRUCTURE AND CONSTRUCTION CONSISTS OF: -CONCRETE FOUNDATION/FLOOR -STEEL WALLS -SHEETROCK INTERIOR WALLS -STEEL BEAMS -TOTAL SQUARE FOOTAGE: SCOPE OF WORK: 18,400 FTz 99OTE RETAILAREA: 6,133 FTz UPPER AREA: 1,814 FTz SHOP AREA: 11,846 FTz - BUILDING CODE CLASSIFICATION - OCCUPANCY - M, Retail Sales - CONSTRUCTION TYPE - V B (602.5, T 601) SIDE SAMMY W/ SWIVEL ZEE PURLIN, SWIVEL RI SAMMY SIDEWINDER TOLCO FIG 75 SWIVEL ALLTHREAD ROD PIPE ZEE-PURLIN CLAMP W/ SWIVEL PURLIN CLAM ZEE PURLIN ALLTHREAD ROD SWIVEL RING PIPE RISER DETAIL SEE PLAN FOR FIRE DEPARTMENT CONNECTION 1. DI TO FLANGE ADAPTER 2. RELIABLE GROOVE x FLANGE ADAPTER 3. C200 BACKFLOW BUTTERFLY 4. 3" FLEXIBLE COUPLING 5. 3" POTTER FLOW SWITCH 6.1 1/4" INSPECTORS TESTAND DRAIN 7. HYDRAULIC PLACARD 8. GENERAL INFORMATION SIGN 9. 6" x 3" REDUCING COUPLING 10. 3" RISER MANIFOLD LONGITUDINAL BRACE DETAIL LATERAL BRACE DETAIL STEEL BEAM / JOIST STEEL BEAM / JOIST TOLCO FIG 828 TOLCO FIG 828 e e TOLCO FIG 980 BRACE ANGLE 450 - 600 _ F 1" SCH.40 PIPE TOLCO FIG 4L�` 0 SPRINKLER PIPE TOLCO FIG 980 BRACE ANGLE 450 - 600 - i 1" SCH.40 PIPE TOLCO FIG 1 SPRINKLER PIPE "FAST CLAMP" Idaho Falls, ID Tel. 208-881-5421 Idaho Lic: FPSC-008 Jason. Blatter@3Dfire.us OWNERSHIP OF DOCUMENTS ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT OF 3-D FOR THIS PROJECTARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLYAND SHALL REMAIN THE PROPERTY OF 3-D WHETHER THE PROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE, BY THE OWNER OR EXTENSIONS OF THE PROJECT WITHOUT WRITTEN PERMISSION OF 3-D SHALL BE ATTHE OWNER'S RISKAND THE OWNER AGREES TO DEFEND, INDEMNIFY, AND HOLD HARMLESS 3-D FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THE INSTRUMENTS OF SERVICE BYTHE OWNER OR BY OTHERS ACTING THROUGH THE OWNER FREEZING CONDITIONS IN LOCATIONS SUBJECTTO FREEZING CONDITIONS, IT ISTHE OWNERS RESPONSIBILITY TO PROVIDE HEATAND ADEQUATE INSULATION THROUGHOUT WET PIPE SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY PIPE AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES TO SPRINKLER SYSTEMS. I have reviewed these plans and certify that they comply with the adopted N FPA standards. Nicet Name Corey Thompson NICET Level IV 116184 Date of Review 10/21/22 Signature ]AS-BUILTNSUBMITTAL❑ OTHER REVISIONS NO. DATE DESCRIPTION 10/21/22 FOR APPROVAL 1: 2' , �4 .. w O z Wt U_ oL O O N N a� N a 0 IL LL w aJ N � !r t m3 C CL Y Y (A e C3'1 Cy at 'aN N C 0) N CL a' c •°Jv :3 a Y O ui Wi C M .CL LL N LL >' yr N 'e ( V­ r CO o O �LL LL O LL LL LL LL Z Cq N L 4D 4-4)111) 0 a NORTH DRAWN BY Jason Blatter 3-D FIRE PROJECT NUMBER 4C0105 o O 0 � = io 0 O r W Q 1 M SPRINKLER AND HANGING DETAIL NO SCALE PRINT DATE 10/21 /22 FP-0 1 TYPICAL SECTION VIEW 21 0 4 8 SCALE 1/8" = T-0" 1 2 3 4 5 6 7 I I I I I I I I I I I I I I 8 9 10 I I I I I 86 ft2 II (Actual 1590ft2) U U U U U , `:/ U U 10 UPPER FIRE PROTECTION PLAN 21 0 4 8 SCALE 1/8" = 1'-0" Idaho Falls, ID Tel. 208-881-5421 Idaho Lic: FPSC-008 Jason. Blatter@3Dfire.us OWNERSHIP OF DOCUMENTS ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT OF 3-D FORTH IS PROJECTARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF 3-D W NETHER THE PROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE, BY THE OWNER OR EXTENSIONS OF THE PROJECT WITHOUT WRITTEN PERMISSION OF 3-D SHALL BE ATTHE OWNER'S RISKAND THE OWNER AGREES TO DEFEND, INDEMNIFY, AND HOLD HARMLESS 3-D FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEESARISING OUT OF UNAUTHORIZED REUSE OF THE INSTRUMENTS OF SERVICE BYTHE OWNER OR BY OTHERS ACTING THROUGH THE OWNER FREEZING CONDITIONS IN LOCATIONS SUBJECTTO FREEZING CONDITIONS, IT ISTHE OWNERS RESPONSIBILITY TO PROVIDE HEATAND ADEQUATE INSULATION THROUGHOUT WET PIPE SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY PIPE AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES TO SPRINKLER SYSTEMS, I have reviewed these plans and certify that they comply with the adopted N FPA standards. Nicet Name Corey Thompson NICET Level IV 116184 Date of Review 10/21/22 Signature AS-BUILTNsUBMITTALI I OTHER REVISIONS NO. DATE DESCRIPTION 10/21/22 FOR APPROVAL 1 A O r 0 Z r �. LL Eo O O N t N_ y LL m G1 CO) C 0 CL CA t1 �7 CY N C CL LM J 0 C Y .` Q T T C _ c H CO LID 13 W 0 LL LL LID N G I. - NORTH 21 0 4 8 SCALE 1/8" = T-0" DRAWN BY Jason Blatter 3-D FIRE PROJECT NUMBER 4MO105 O O 0 V 00 = io 0 �— a c�a�44 Q M .T f W�/W 1 M PRINT DATE 10/21 /22 FP-02