HomeMy WebLinkAboutAPPROVED ELECTRICAL PLANS - 22-00502 - Mountain West Rental and SalesAuthor Name Author Email Author Phone No.:
Alex Owens Alex.Owens@rexburg.org 208-372-2330
Todd Smith Todd.Smith@rexburg.org 208-372-2181
Description : Mountain West Rental and Sales
Address :
Record Type : New Commercial Building
Document Filename : 22-07-26_Mountain West Equip Rexburg_Electrical_REV#1.pdf
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 22-00502
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
E0.0 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector
E1.0 Stamp Alex Owens : Electrical Open 2 Approved - Electrical Inspector
E2.0 Stamp Alex Owens : Electrical Open 3 Approved - Electrical Inspector
E3.0 Stamp Alex Owens : Electrical Open 4 Approved - Electrical Inspector
New Commercial Building
As per Resolution 2022-07, adopted April 6, 2022, new development is required to follow standards for the installation of fiber conduit and distribution boxes. Location of conduit
and distribution boxes need to be identified and shown on plans.
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
ELECTRICAL SPECIFICATIONS
1. INTENT:
Provide and install complete and operable electrical systems
including but not not limited to; lighting, power, receptacles,
data, fire alarm ande etc.
Provide all required connections to all Mechanical and
Plumbing equipment, as indicated and required, including all
conduits, wiring and controls. Coordinate with mechanical
contractor and drawings.
2. COMPLIANCE WITH CODES:
All work and material shall comply with all applicable codes,
safety orders, laws, ordinances and regulations of governing
authorities and other agencies having jurisdiction including
regulations of the State and Local Fire Marshall, unless
detailed as specified to a more restrictive standard or higher
requirement.
3. INTERPRETATION OF DRAWINGS:
The electrical drawings are essentially diagrammatic in that
all provisions necessary to conform to structural,
architectural, mechanical and plumbing systems can not be
shown. All installations shall be adjusted as necessary to
conform and to avoid obstructions, without additional cost to
the owner.
All work, material and equipment called for by notes,
schedules or otherwise indicated on the drawings shall be
furnished and isntalled as though fully set forth in these
specifications.
4. VISITING THE SITE:
Contractor shall visit the site and become acquainted with
conditions to be encounterd. Extra funds will not be allowed
due to failuer to examine the site and to included existing
conditions in bid price.
5. COORDINATION WITH UTILITIES:
These plans have been prepared without utility company
comments. The contractor shall verify exact requirements for
the electrical, telephone and communication services with the
utility company representatives and provide all work and pay
all costs for a complete and operating systems, as directed by
the governing utilities.
6. MATERIALS AND WORKMANSHIP:
All workmanship shall be performed by skilled electricians
using the best standard practives of the trade. All materials
shall, unless otherwise noted, be new and in perfect
condition and working order. All material for similar uses shall
be of the same type, material and manufacturer for ease of
future maintaenance.
All equipment shall be readily accessible for maintenance and
repairs. All materials, fixtures and equipment shall be
covered or sealed upon installation so as to provide for safety
and to insure that operation and appearance will be
maintained after subsequent construction operations.
7. EXECUTION:
Raceway installation: Seperate underground conduits in a
common trench 4" minimum horizontally, 12" minimum from
other utility lines. Minimum conduit depth shall be 18".
Coordinate conduit installation with pipes, steel, footings and
ducts installed by other trades. Install conduit runs exposed to
view parallel or at right angles to structural members, walls or
building lines. Support conduit with one-hole malleable factory
made pipe straps, fastended with screws.
8. OPERATING AND ADJUSTING:
The owner reserves the right to operate any systems of
equipment prior to final comletion and acceptance of the work.
Such perliminary operation shall not be construed as an
acceptance of any work.
Each piece of equipment and all of the systems shall be
adjusted to insure proper functioning and shall be left in first
class operating condition.
9. CUTTING AND PATCHING:
Do all drilling and cutting as necessary for installation of
equipment or conduit. Cutting or drilling of structure is only
permitted with prior approval of the owner and structural
engineer.
Where cutting and patching of work is necessary, use the
same materials, workmanship and finish to neatly match all
surrounding work.
10. CONDUIT:
All conduit material and installation methods shall be as
allowed by the NEC, local AHJ and as directed by the
owner.
11. CONDUCTORS:
Type THWN or THHN copper wire insulated for 600V.
Smallest wire shall be #14 AWG unless noted otherwise.
All wiring shall be Copper unless indicated otherwise.
Type MC cable shall be permitted provided it is installed in
concealed spaces and installation complies with the Local
AHJ and NEC requirements.
Use "Ideal Yellow" pulling compound for all wire pulls.
Use Scotchlock connectors for all splices in #12 wire and
tape bolted pressure connectors for larger wire.
12. GROUNDING:
All conduit, branch circuits, feeders and etc. shall be
provided with a grounding conductor. All grounding
conductors shall be insulated and green in color, size as
shown.
13. WIRING DEVICES:
Devices shall be Standard type, Specification grade, color
as selected by owner. Decora style devices are prohibited.
Utilize GFCI and Tamper-proof devices in all locations as
defined by the NEC.
Wiring devices shall be as installed as allowed by the
NEC, local AHJ.
14. DEVICE PLATES:
Devices plate type and color shall be as directed by owner
and as required by the NEC.
15. LIGHTING FIXTURES:
As selected by owner and/or indicated in schedules. All light
fixtures shall be installed and connected by the Electrical
Contractor.
16. SERVICE EQUIPMENT & PANELBOARDS:
Service Equipment: Shall be rated as such and shall comply
with local utility co. requirments. .
Panelbards: Shall be provided with typed writtend directories
indicating loads being served.
Maintain all required clearances around equipment as
required by the NEC.
All equpment dimensions to be field verified.
17. CLEAN-UP:
Upon completion of the work, prior to final inspection,
thoroughly clean all exposed fixtures, trim and equipment
and leave the entire installation in a neat, clean and usable
condition. Remove all cement, paint, grease, oil and other
foreign substances.
18. TEST:
Test all conductors for shorts, opens, grounds or other
defects. Correct any defective work and re-test.
Demonstrate continuous satisfactory operation of all
electrical systems and equipment.
Provide training to the owner on electrical systems as
needed for owner operation and maintenance of building.
19. GUARANTEE:
Prior to final acceptacne of the project, deliver to the owner
a written one year guarantee on all workmanship, materials
and equipment and agree to repair or replace all such
defective items promptly that may occure during the
warranty period; including repair or replacement of the
premises that may be damaged due to faulty work and
materials furnished under contract.
ENTRANCE
CONDUIT(S)
4" SQUARE
BOX
RAISED RING
TO SUIT WALL
RECEPTACLE - 20AMP
RATED - SEE SPECIFICATIONS.
NORMAL POWER COLOR - (SEE SPEC'S)
COVER PLATE - STYLE & COLOR
TO BE AS PER SPECIFICATIONS.
CIRCUIT NUMBER TO BE WRITTEN ON
BACK OF COVER W/FELT-TIP MARKER
GREEN INSULATED
GROUND CONDUCTOR
TEE BAR
GRID
POWER SUPPLY CONDUIT FOR
CEILING OR WALL "J" BOX.
SUPPORT WIRE BY ELECTRICAL
CONTRACTOR INDEPENDENT OF CEILING
SYSTEM. (TYPICAL)
ACOUSTIC
CEILING
TILE
SUPPORT
CLIPS
ALL SIDES
CIRCUITING & GENERAL SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
KEYED NOTE REFERENCE1
BRANCH CIRCUIT HOME-RUN TO PANEL INDICATED
A-1,3,5
3/4"C.-6#12,1#12G
QTY & SIZE OF EQUIPMENT GROUND CONDUCTOR
QTY & SIZE OF NEUTRAL AND PHASE CONDUCTOR(S)
SIZE OF CONDUIT
A-1,3,5
3/4"C.-6#12,1#12G
PANEL AND CIRCUIT DESIGNATIONS
EQUIPMENT GROUNDING CONDUCTOR
TICK MARKS
NEUTRAL CONDUCTOR(S)
PHASE AND/OR SWITCH-LEG CONDUCTOR(S)
BRANCH CIRCUIT/FEEDER CONCEALED IN CEILING OR WALL
BRANCH CIRCUIT/FEEDER CONCEALED UNDERGROUND OR FLOOR
NEW EQUIPMENT, DEVICES, ETC.
EXISTING EQUIPMENT, DEVICES, ETC.
DEMOLITION EQUIPMENT, DEVICES, ETC.
DETAIL # / SHEET REFERENCE1 / ES101
*25,000A CALCULATED AVAILABLE FAULT CURRENT AT EQUIPMENT(SEE POWER RISER)
LIGHTING SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
PARKING AREA POLE LIGHT, SINGLE OR DOUBLE HEAD AS INDICATED ON
DRAWINGS. REFER TO LIGHT POLE DETAIL FOR POLE INFORMATION.
2X4 FLUORESCENT OR LED FIXTURE
2X2 FLUORESCENT OR LED FIXTURE
SURFACE MOUNTED FLUORESCENT OR LED FIXTURE
STRIP FLUORESCENT OR LED FIXTURE
WALL MOUNTED FLUORESCENT OR LED FIXTURE
EXTERIOR WALL MOUNTED FIXTURE
ROUND RECESSED FIXTURE
SURFACE OR PENDANT FIXTURE
LIGHT FIXTURE SUBSCRIPTS
NL NIGHT-LIGHT(CONNECT TO UNSWITCHED LEG OF CIRCUIT)
EXIT SIGN, WALL OR CEILING MOUNTING AS REQUIRED (SINGLE OR DOUBLE FACE)
DIRECTIONAL CHEVRONS AS INDICATED; CONNECT TO UNSWITCHED LEG OF LIGHTING
CIRCUIT THAT IS IN THE SAME AREA AS THE EXIT SIGNS.
SHADED FIXTURE INDICATES AN EMERGENCY FIXTURE. PROVIDE WITH EMERG. BATTERY
PACK OR CONNECT TO EMERGENCY POWER SYSTEM (WHERE APPLICABLE). CONNECT
BATTERY PACK TO UNSWITCHED LEG OF LIGHTING CIRCUIT THAT SERVES THE SAME
AREA AS THE EMERGENCY FIXTURE. PROVIDE WITH TEST LIGHT AND SWITCH.
CEILING MOUNTED OCCUPANCY SENSOR, REFER TO OCCUPANCY SENSOR/SWITCH
SCHEDULE FOR SENSOR TYPE AND ADDITIONAL INFORMATION.
SWITCH MOUNTED OCCUPANCY SENSOR, LOW VOLTAGE SWITCHPOD OR DIMMER
SWITCH, REFER TO OCCUPANCY SENSOR/SWITCH SCHEDULE FOR TYPE AND
ADDITIONAL INFORMATION.
SINGLE-POLE SWITCH (SEE SUB-SCRIPTS BELOW FOR ADDITIONAL INFORMATION)
SWITCH SUBSCRIPTS
3 3-WAY SWITCH
4 4-WAY SWITCH
D DIMMER SWITCH (COMPATIBLE W/ LOAD & LTG TYPES)
F 7-DAY PROGRAMMABLE TIMER SWITCH
(INTERMATIC MODEL EI500WC SERIES)
P PILOT LIGHTED SWITCH
F1 LIGHT FIXTURE TYPE DESIGNATION
S
###
WALL OR CEILING MOUNTED EMERGENCY LIGHTING UNIT W/BATTERY PACK
CONNECT TO UNSWITCHED LEG OF LIGHTING CIRCUIT THAT IS IN THE SAME AREA AS
THE EMERGENCY LIGHT.
LV LOW-VOLTAGE SWITCH (PER DWG'S)
T THERMAL-OVERLOAD SWITCH
M SWITCH SUPPLIED WITH EQUIPMENT,
INSTALLED BY E.C.
WP WEATHERPROOF
2P DOUBLE POLE, SINGLE THROW SWITCH
GENERAL LIGHTING NOTES:
A. SYMBOLS SHOWN ABOVE MAY NOT REPRESENT ALL LIGHT FIXTURES USED ON PROJECT, REFER TO
LIGHT FIXTURE SCHEDULE FOR ACTUAL FIXTURE INFORMATION INCLUDING FIXTURE TYPE, LAMPING,
MOUNTING AND ETC.
B. JUNCTION BOXES FOR LIGHTING CIRCUITING ARE NOT SHOWN FOR CLARITY. THE E.C. IS RESPONSIBLE
FOR PROVIDING AND INSTALLING ALL JUNCTION BOXES REQUIRED FOR CIRCUITING OF ALL LIGHT
FIXTURES THAT ARE NOT LISTED FOR "THROUGH-BRANCH CIRCUIT WIRING".
C. IN GENERAL ALL SWITCH-LEG CONDUCTORS MAY NOT BE SHOWN ON DRAWINGS; E.C. SHALL PROVIDE
AND INSTALL CONDUCTORS AS REQUIRED TO ACHIEVE CONTROL SCHEMES INDICATED AND
DESCRIBED ON DRAWINGS. INCLUDING ALL 0 - 10V DIMMING CONTROLS BETWEEN SWITCH AND
FIXTURES.
D. ALL BATTERY EXIT SIGNS AND EMERGENCY LIGHTING TO BE CONNECTED TO THE UNSWITCHED LEG OF
THE LIGHTING CIRCUIT IN THE AREA.
###
F
M
POWER SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
ELECTRICAL SWITCHBOARD EQUIPMENT, (SEE POWER RISER AND PANEL SCHEDULES
FOR ADDITIONAL INFORMATION)
'MSB'
'T##'DRY-TYPE TRANSFORMER, (SEE POWER RISER FOR ADDITIONAL INFORMATION)
'LA'
ELECTRICAL PANELBOARD, (SEE POWER RISER AND PANEL SCHEDULES
FOR ADDITIONAL INFORMATION)
DISCONNECT SWITCH, SIZE/POLES/TYPE AS INDICATED
TYPES: 1=NEMA 1, 3R=NEMA 3R, 4X=NEMA 4X30A/3P/3R
FUSED DISCONNECT SWITCH, SIZE/POLES/TYPE AS INDICATED
TYPES: 1=NEMA 1, 3R=NEMA 3R, 4X=NEMA 4X30A/3P/3R
(30A FUSES)
COMBINATION STARTER & FUSED DISCONNECT SWITCH, SIZE/POLES/TYPE AS INDICATED.
TYPES: 1=NEMA 1, 3R=NEMA 3R, 4X=NEMA 4X
J
JUNCTION BOX
CR = CORD REEL; SEE DRAWINGS FOR INFORMATION
CD = CORD DROP; SEE DRAWINGS FOR INFORMATION
EQUIPMENT CONNECTION; COORDINATE CONNECTION WITH EQUIPMENT
PRIOR TO ROUGH-IN
MOTOR CONNECTION
POWER AND/OR DATA SERVICE POLE
FLOORBOX (SEE FLOORBOX SCHEDULE FOR ADDITIONAL INFORMATION)
PUSHBUTTON STATION
FB#
SPECIAL RECEPTACLE (COORDINATE NEMA TYPE WITH EQUIP.)
(REFER TO PANEL SCHEDULES FOR AMPS)
CEILING MOUNTED DUPLEX RECEPTACLE (COORDINATE PLACEMENT WITH
CEILING EQUIPMENT PRIOR TO ROUGH-IN)
DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED BELOW 5FT
GFCI-TYPE DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED BELOW 5FT
DOUBLE-DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED BELOW 5FT
GFCI-TYPE DOUBLE-DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED
BELOW 5FT.
RECEPTACLE AND EQUIPMENT SUBSCRIPTS
AC ABOVE COUNTER
WP WEATHERPROOF (UL LISTED
WEATHER-RESISTANT)
42"MOUNTING HEIGHT AFF OR AFG
IG ISOLATED GROUND
S SURGE-PROTECTION TYPE
REF REFRIGERATOR
W WASHING MACHINE
D DRYER (30A-240V RATED RECPT.)
M MICROWAVE
HVAC THERMOSTAT OR SENSOR; PROVIDE & INSTALL BACKBOX,3/4" CONDUIT AND
CONDUCTORS TO ASSOCIATED HVAC UNIT. COORDINATE EXACT LOCATION & SIZE AND
NUMBER OF CONDUCTORS WITH M.C.
T SOR
30A/3P/3R
SIZE 1
(30A FUSES)
SMALL EXHAUST FAN CONNECTION
TV 120V RECEPT. FOR TV; VERIFY HEIGHT WITH ARCH.
DRAWINGS & ELEVATIONS
USB 120V RECPT. WITH USB CHARGING PORTS
EWC ELECTRIC WATER COOLER; (SEE DETAIL. RECPT. SHALL
BE ACCESSIBLE, DO NOT MOUNT BEHIND HOUSING.)
DISP GARBAGE DISP. (UNDER SINK)
DW DISHWASHER (COORDINATE W/ MILLWORK, INSTALL PER
NEC 422.16(B)(2)).
M/R MICROWAVE/RANGE HOOD (COORDINATE W/ MILLWORK)
R ELECTRIC RANGE (50A-240V RATED RECPT.)
GENERAL SPECIAL SYSTEM NOTES:
A. ALL DEVICES SHOWN AT OR NEAR MILLWORK/CASEWORK SHALL BE COORDINATED WITH THE
ARCHITECTURAL ELEVATION DRAWINGS AND MILLWORK INSTALLER TO INSURE PROPER MOUNTING
HEIGHTS. CONTRACTOR SHALL ADJUST DEVICES AS NECESSARY IN ORDER TO POSITION DEVICES SUCH
THAT THEY WILL NOT FALL BEHIND MILLWORK, CABINETS OR BE DIRECTLY ABOVE SINKS OR MIDWAY
BETWEEN TILEWORK/WALL OR WAINSCOATING, ETC.
B. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL A GFCI TYPE RECEPTACLE FOR ALL
RECPTACLES SHOWN IN TOILET RMS, BATHROOMS, KITCHENS/SERVING AREAS, ROOFTOP, OUTDOORS
OR WITHIN 6FT OF ANY SINK, BASIN, TUB OR FLOOR SINK AND ALL OTHER AREAS DEFINED BY THE NEC.
SPECIAL SYSTEMS SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
DATA OUTLET; _= # OF DATA CABLES, X=CONDUIT SIZE (SEE NOTES 1,2,3 BELOW)_D-X
TELEPHONE OUTLET; _= # OF TELEPHONE CABLES, X=CONDUIT SIZE
(SEE NOTES 1,2,3 BELOW)
_T-X
TELEPHONE/DATA OUTLET; _= # OF TELEPHONE/DATA CABLES, X=CONDUIT SIZE
(SEE NOTES 1,2,3 BELOW)
_T/_D-X
CEILING MOUNTED DATA OUTLET; _= # OF DATA CABLES, X=CONDUIT SIZE
(SEE NOTES 1,2,3 BELOW)
_D-X
A. COMMUNICATIONS CABLES SHALL HAVE BENDS NO GREATER THAN 90 DEG.
B. CONDUITS FOR COMMUNICATIONS CABLING SHALL HAVE A MAXIMUM BEND RADIUS NOT MORE THAN 10X
THE DIAMETER OF THE CONDUIT.
C. ALL COMMUNICATIONS CONDUITS SHALL BE TERMINATED WITH AN INSULATED NON-METALLIC BUSHING
AT BOTH ENDS.
D. COMMUNICATIONS CONDUITS SHALL HAVE NO MORE THAN (2) 90'S WITHOUT A PULLBOX. PULL BOXES
SHALL BE LOCATED IN ACCESSIBLE LOCATIONS AND SHALL BE SIZED AT LEASED 12X THE LARGEST
CONDUIT DIAMETER IN LENGTH AND MIN, 4" DEEP AND 8" WIDE.
E. IT SHALL BE THE RESPONSIBILITY OF THE E.C. TO INSURE THAT THE PATHWAY FOR THE DATA CABLING
DOES NOT CREATE CABLE LENGTHS TO EXCEEDS THE LENGTH OF 295FT FROM OUTLET TO PATCH
PANEL, THIS INCLUDES SERVICE LOOPS AND PATCH CORDS.
F. WHERE CABLE TRAY IS UTILIZED IN THE PROJECT. COMMUNICATION CONDUITS ENDING AT THE CABLE
TRAY SHALL EXTEND 1" OVER THE SIDE INTO THE TRAY.
GENERAL SPECIAL SYSTEM NOTES:
###_D-X
SPECIAL SYSTEMS NOTES:
1. UTILIZE 4 11/16" DEEP BOX WITH REQUIRED MUDRING AND CONDUIT TO ABOVE NEAREST ACCESSIBLE
CEILING OR DATA RACK, TERMINATE WITH INSULATED THROAT BUSHING. PROVIDE QTY OF CABLES
INDICATED FROM OUTLET TO NEAREST TELE/DATA ROOM. SEE DWGS FOR ADDITIONAL INFORMATION.
UTILIZE J-HOOKS 3FT ON CENTER FOR SUPPORT OF CABLING WHERE CABLE TRAY IS NOT
INSTALLED/SPECIFIED.
2. CONDUIT SIZE ('X' FROM ABOVE); 2=1/2", 3=3/4", 4=1", 5=1-1/4", 6=1-1/2"
3. BLANK (NO LABEL) = 4-11/16" DEEP BOX WITH REQUIRED MUDRING AND 1" CONDUIT TO ABOVE NEAREST
ACCESSIBLE CEILING/CABLE TRAY, TERMINATE WITH INSULATED
THROAT BUSHING, PROVIDE PULL STRING. (UNLESS OTHERWISE NOTED)
WALL/FLOOR ELECTRICAL PATHWAY SLEEVE;
INSTALL THROUGH WALL OR FLOOR AS INDICATED. SLEEVES SHALL BE ABOVE
ACCESSIBLE CEILINGS IN ACCESSIBLE LOCATION, FIELD VERIFY EXACT LOCATION TO
AVOID CONFLICT WITH OTHER TRADES AND UTILITIES. IF WALL/FLOOR IS NOT FIRE RATED
E.C. MAY UTILIZED EMT CONDUIT SLEEVES OF EQUAL SIZE. REFER TO ARCHITECTURAL
DRAWINGS FOR FIRE RATINGS.
(qty) = QUANTITY OF SLEEVES AT LOCATION
EP2 = 2" HILTI SPEED SLEEVE CP-653-BA
EP4 = 4" HILTI SPEED SLEEVE CP-653-BA
###
FB#
_D-X
ELECTRICAL FLOORBOX
REFER TO "ELECTRICAL FLOORBOX SCHEDULE" FOR INFORMATION.
_= # OF DATA CABLES, X=CONDUIT SIZE (SEE NOTES 1,2,3 BELOW)
TV AND/OR AV BOX; WITH POWER, DATA AND/OR AV CONNECTIVITY
### = BOX ID: REFER TO "ELECTRICAL AV/TV BOX SCHEDULE" FOR INFORMATION.
_= # OF DATA CABLES, X=CONDUIT SIZE (SEE NOTE #2 BELOW)
INSTALL CONDUIT (SIZE AS INDICATED) FROM BOX TO NEAREST ACCESSIBLE CEILING
SPACE W/ DATA CABLING/TERMINATIONS AS INDICATED ON DRAWINGS.
WALL
###
FLOOR
(qty)
(qty)
P
1PH
2/C
3/C
3P
3PH
3W
4W
AC
ADA
AFF
AFG
AIC
AL
A or
AMP
ANN
AP
ATS
AV
AWG
BFG
C
CATV
CB
CCTV
CKT
C
CP
CT
CU
DS
EA
E.C.
EM
EMT
ENT
EPO
EQUIP
EX
FA
FACP
FLA
FMC
GND
G.C.
GEN
GFI
GFP
HD
HID
HOA
HP
HPS
HV
HZ
IG
IMC
J-BOX
ABBREVIATIONS
SINGLE POLE
SINGLE-PHASE
TWO-CONDUCTOR
THREE-CONDUCTOR
THREE POLE
THREE-PHASE
THREE-WIRE
FOUR-WIRE
ABOVE COUNTER
AMERICANS WITH DISABILITIES ACT
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMPERE
ANNUNCIATOR
ACCESS POINT
(WIRELESS DATA)
AUTOMATIC TRANSFER SWITCH
AUDIO VISUAL
AMERICAN WIRE GAGE
BELOW FINISHED GRADE
CEILING MOUNTED
CABLE TELEVISION
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CONDUIT
CONTROL PANEL
CURRENT TRANSFORMER
COPPER
DISCONNECT SWITCH
EACH
ELECTRICAL CONTRACTOR
EMERGENCY
ELECTRICAL METALLIC TUBING
ELECTRICAL NONMETALLIC TUBING
EMERGENCY POWER OFF
EQUIPMENT
EXISTING
FIRE ALARM
FIRE ALARM CONTROL PANEL
FULL LOAD AMPS
FLEXIBLE METAL CONDUIT
GROUND
GENERAL CONTRACTOR
GENERATOR
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT PROTECTION
HEAVY DUTY
HIGH INTENSITY DISCHARGE
HAND-OFF-AUTOMATIC
HORSE POWER
HIGH PRESSURE SODIUM
HIGH VOLTAGE
HERTZ
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
JUNCTION BOX
V
KVA
kW
kWh
LED
LFMC
LFNC
LTG
LV
MAX
M.C.
MCA
MCB
MCC
MDP
MH
MIN
MLO
MOCP
NA
NC
NEC
NEMA
NFPA
NIC
NL
NO
NTS
OC
OH DR
OL
PB
P
PNL
PT
PTZ
QTY
RCP
RMC
RNC
SCA
SCBA
SF
SPD
SPEC
SWBD
SWGR
TL
TP
TTB
TV
TYP
UG
UPS
V
VA
V.I.F.
VFD
WAP
W/
W/O
WP
XFMR
KILOVOLT
KILOVOLT AMPERE
KILOWATT
KILOWATT HOUR
LIGHT EMITTING DIODE
LIQUID TIGHT FLEXIBLE METAL CONDUIT
LIQUID TIGHT FLEXIBLE NONMETALLIC
CONDUIT
LIGHTING
LOW VOLTAGE
MAXIMUM
MECH. CONTRACTOR
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION PANEL
MANHOLE
MINIMUM
MAIN LUGS ONLY
MAXIMUM OVERCURRENT PROTECTION
NOT APPLICABLE
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NATIONAL FIRE PROTECTION
ASSOCIATION
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
ON CENTER
OVERHEAD DOOR
OVERLOAD
PUSHBUTTON
PHASE
PANEL
POTENTIAL TRANSFORMER
PAN/TILT/ZOOM
QUANTITY
REFLECTED CEILING PLAN
RIGID METAL CONDUIT
RIGID NONMETALLIC CONDUIT
SHORT CIRCUIT AMPS
STANDARD COLOR BY ARCHITECT
SQUARE FOOT (FEET)
SURGE PROTECTION DEVICE
SPECIFICATION
SWITCHBOARD
SWITCHGEAR
TWIST LOCK
TWISTED PAIR
TELEPHONE TERMINAL BOARD
TELEVISION
TYPICAL
UNDERGROUND
UNINTERRUPTIBLE POWER SUPPLY
VOLTS
VOLT AMPERE
VERIFY IN FIELD
VARIABLE FREQUENCY DRIVE
WIRELESS ACCESS POINT
WITH
WITHOUT
WEATHERPROOF
TRANSFORMER
A. E.C. SHALL REFER TO THE MECHANICAL DRAWINGS FOR EXACT LOCATIONS OF ALL MECHANICAL
EQUIPMENT AND ELECTRICAL CONNECTIONS.
B. E.C. SHALL PROVIDE MINIMUM WORKING CLEARANCE AS PER NEC BEFORE INSTALLING ANY ELECTRICAL
PANELS OR CABINETS. SEE ELECTRICAL EQUIPMENT CLEARANCE DETAIL.
C. INSTALL ALL LIGHT FIXTURES IN MECHANICAL ROOM AFTER THE MECHANICAL EQUIPMENT IS IN PLACE.
ADJUST AS NECESSARY. PROVIDE CHAIN SUSPENSION KITS AS REQUIRED.
D. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN(S) FOR EXACT FIXTURE LOCATIONS, CEILING
TYPES, ETC.
E. E.C. SHALL PROVIDE ALL CONCRETE PADS AS REQUIRED FOR ALL ELECTRICAL EQUIPMENT.
F. CONFIRM EXACT LOCATIONS OF ALL TELEPHONE/DATA OUTLETS WITH OWNER PRIOR TO ROUGH-IN.
G. LOCATE SWITCHES, OUTLETS, ETC., SHOWN AT ROOM ENTRY DOORWAYS, AS CLOSE TO DOOR FRAME AS
POSSIBLE, SO AS NOT RO INTERFERE WITH ROOM CABINETS, ETC.
H. SUPPORT ALL LIGHT FIXTURES INDEPENDENT OF CEILING.
I. ELECTRICAL CONTRACTOR SHALL OBTAIN ALL APPLICABLE PERMITS FOR WORK AND PAY ASSOCIATED
FEES.
J. MAINTAIN 24" MIN. CLEARANCE FROM ALL COMMUNICATIONS CABLING AND ELECTRONIC BALLASTS.
K. UNLESS SPECIFICALLY INDICATED OTHERWISE, E.C. SHALL COORDINATE WITH ANY SPECIAL SYSTEMS
SUPPLIER/SHOP DRAWINGS; DENTAL, MEDICAL, KITCHEN, SPECIALIZED EQUIPMENT, ETC. FOR THE EXACT
ROUGH-IN REQUIREMENTS FOR THEIR EQUIPMENT. ALSO UNLESS INDICATED OTHERWISE, THE E.C. TO
BE RESPONSIBLE FOR FINAL ELECTRICAL CONNECTIONS TO ALL SPECIAL EQUIPMENT.
L. ALL CONDUIT/RACEWAY/CABLES TO BE CONCEALED IN WALLS OR ABOVE CEILINGS. IF ANY SURFACE
WORK IS NECESSARY, IT SHALL BE APPROVED BY THE ARCHITECT/ENGINEER PRIOR TO INSTALLATION.
M. ELECTRICAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND THOROUGHLY INVESTIGATE THE
EXISTING CONDITIONS, AS THEY RELATE TO THE SCOPE OF WORK DESCRIBED. MAKE NECESSARY
PROVISIONS IN THE BASE BID TO ADEQUATELY ACCOMMODATE THESE CONDITIONS.
N. DATA CABLING SYSTEM PRE-INSTALLATION CONFERENCE:
1. E.C. SHALL SCHEDULE A MEETING A MINIMUM OF FIVE CALENDAR DAYS PRIOR TO BEGINNING DATA
CABLING INSTALLATION . ATTENDEES SHOULD INCLUDE OWNER’S REP., ENGINEER, GC, EC AND
CABLING SUB. REFER TO SECTION 26 6210(1.4)(E) FOR ADDITIONAL INFORMATION.
PROJECT GENERAL NOTES:
IDAHO POWER CO. ROCKY MOUNTAIN POWER CO.
WWW.IDAHOPOWER.COM WWW.ROCKYMOUNTAINPOWER.NET
CONTACT: CONTACT:
SHELLEY MARTIN (208) 388-5872 DAN KUHL (503) 308-0233
OR DAN KUHL (503) 308-0233 dan.kuhl@evergreen-efficiency.com
dan.kuhl@evergreen-efficiency.com
UTILITY LIGHTING REBATES & INCENTIVES:
IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PREPARE ALL REQUIRED
APPLICATIONS AND INFORMATION REQUIRED TO PROVIDE THE OWNER WITH THE MAXIMUM AMOUNT OF
REBATE DOLLARS FROM THE LOCAL UTILITY COMPANY. THE ELECTRICAL CONTRACTOR SHALL SUBMIT
VERIFICATION OF THE UTILITY COMPANY PRE-APPLICATION APPROVAL PRIOR TO ORDERING ANY MATERIALS.
VISIT THE FOLLOWING UTILITY CO. WEBSITES FOR INFORMATION:
TYPICAL DEVICE MOUNTING HEIGHTS:
GENERAL COORDINATION NOTE:
GENERAL DETAIL NOTES:
FINISH FLOOR
1' - 6''
THERMOSTAT OR SENSORVERIFY WITH M.C. PRIOR TO
LIGHT SW.
(OR AS NOTED)
* 4' - 0''
* 3' - 6''
(OR AS NOTED)
RECEPTACLE
@ MILLWORK
BACKSPLASH
CA
B
.
D
I
M
E
N
S
I
O
N
S
PE
R
A
R
C
H
.
D
E
T
A
I
L
6"
CABINET
* E.C. SHALL COORDINATE ALL DEVICE
MOUNTING HGTS. AND EXACT LOCATION
WITH ARCHITECTURAL INTERIOR
ELEVATIONS REPORT CONFLICTS TO
ARCHITECT **PRIOR TO ROUGH-IN**
ROUGH-IN.
TYPICAL FOR ALL DEVICES
MOUNTED ABOVE COUNTER
(ie C.O.'S, DATA, PHONE etc.)
A.
B.
C.
D.
ALL MOUNTING HEIGHTS TYPICAL UNLESS
NOTED OTHERWISE.
COORDINATE OUTLET HEIGHTS WITH
ARCHITECTS MILLWORK DWGS. TO INSURE
THAT OUTLETS WILL NOT FALL BEHIND
CABINETS, BACKSPLASHES, OR INTERFERE
WITH WAINSCOTING, ETC.
ALL SWITCHES AND THERMOSTATS TO BE
MOUNTED AS CLOSE TO DOOR JAMS AS
POSSIBLE. COORDINATE ALL DEVICES WITH
ARCHITECTURAL PLANS AND DETAILS.
COORDINATE LIGHT SWITCH & OUTLET
HEIGHTS WITH ARCHITECTURAL
WAINSCOTING AND OR TILE WORK SO AS
NOT TO FALL MIDWAY IN THESE FINISHES.
FIRE
6' - 8''
FIRE ALARM NOTIFICATION
DEVICE
FIRE
MANUAL PULL STATION
HANDLE SHALL BE
BETWEEN 42" & 48" AFF CABINET
RECEPT.
TELE/DATA
OUTLET
TV
OUTLET
ELECTRICAL EQUIP. CLEARANCE
ELECTRICALEQUIPMENT
NO
T
E
#
1
N O T E #4
NOTE#3
NOTE#2
NOTES:
1. THE MINIMUM HEADROOM OF WORKING SPACE SHALL BE 6 1/2FT.
2. THE WIDTH OF THE WORKING SPACE SHALL BE THE WIDTH OF THE EQUIPMENT OR 30", WHICHEVER IS
GREATER. THE PANEL DOOR SHALL OPEN AT LEAST 90 DEGREES.
3. ALL CIRCUIT BREAKERS, WHEN IN THIER HIGHEST POSITION, SHALL NOT BE MORE THAN 6FT 7 IN. ABOVE
THE FINISHED FLOOR.
4. 3FT CLEARANCE IF 0-150V TO GROUND, 3.5FT CLEARANCE IF 151-600V TO GROUND. 4FT IF EXPOSED LIVE
PARTS ON BOTH SIDES OF THE WORKING SPACE.
GENERAL NOTES:
A. ALL WORKING SPACE CLEARANCES ARE FROM THE FACE OF THE EQUIPMENT.
13053
STATEOFIDAHOSHAWNA.M E A D ORREGISTEREDRP
OFESSIONALENGIN
EE
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
BO
O
T
H
Date
Sheet No.
A
r
c
h
i
t
e
c
t
u
r
e
(2
0
8
)
2
3
3
-
4
5
4
8
Ph
o
n
e
Po
c
a
t
e
l
l
o
,
I
d
a
h
o
8
3
2
0
1
34
0
E
a
s
t
C
l
a
r
k
S
t
r
e
e
t
,
S
u
i
t
e
A
(2
0
8
)
2
3
3
-
0
2
6
3
te
d
@
b
o
o
t
h
a
r
c
h
i
t
e
c
t
u
r
e
.
c
o
m
Fa
x
em
a
i
l
P
L
L
C
Ne
w
B
u
i
l
d
i
n
g
f
o
r
:
P.E. #:2265
7/20/22
Re
v
i
s
i
o
n
s
ELECTRICAL
SYMBOLS & DETAILS
Mo
u
n
t
a
i
n
W
e
s
t
07-20-2022
TB
D
Re
x
b
u
r
g
,
I
d
a
h
o
E0.0
SCALE: NONEARECEPTACLE MOUNTING DETAIL
nLIGHT CONTROL SYMBOL SCHEDULE
SYMBOL DESCRIPTION
nLIGHT CEILING MOUNTED SENSOR, SEE nLIGHT SYSTEM
SCHEDULE FOR ADDITIONAL INFORMATION.S n##
n##B nLIGHT BACKBONE DEVICE, SEE nLIGHT SYSTEM SCHEDULE FOR ADDITIONAL
INFORMATION.
n##R nLIGHT RELAY/POWER PACK DEVICE, SEE nLIGHT SYSTEM SCHEDULE FOR ADDITIONAL
INFORMATION.
n##RP nLIGHT RELAY PANEL, SEE nLIGHT SYSTEM SCHEDULE FOR ADDITIONAL INFORMATION.
nLIGHT SWITCH MOUNTED DEVICE, SEE nLIGHT SYSTEM SCHEDULE FOR ADDITIONAL
INFORMATION.
n##
GREEN, CAT-5e PATCH CABLE (LENGTH AS REQUIRED), PLENUM RATED.
• CABLE SHALL BE INSTALLED IN 3/4" CONDUIT WHERE IT CANNOT BE INSTALLED IN AN
ACCESSIBLE CEILING SPACE.
• PROVIDE A MINIMUM OF 2FT SLACK BETWEEN ALL DEVICES AND FIXTURE
CONNECTION POINTS.
0-10V DIMMING WIRING, UTILIZE 1/2" CONDUIT WITH (2) #18 AWG.
VIOLET FOR POSITIVE, GREY FOR NEGATIVE
1. E.C. SHALL BE RESPONSIBLE FOR PROVIDING ALL LIGHTING CONTROL
COMMISSIONING/PROGRAMMING OF ALL nLIGHT COMPONENTS. THE
COMMISSIONING/PROGRAMMING SHALL BE DONE BY A nLIGHT CERTIFIED TECHNICIAN.
2. E.C. SHALL NOTIFY OWNER 1-WEEK PRIOR TO COMMISSIONING/PROGRAMMING OF THE SYSTEM SO
THAT THE OWNER CAN PROVIDE REPRESENTATIVES DURING THE COMMISSIONING/PROGRAMMING
PERIOD.
GENERAL LIGHTING NOTES:
NOTE: ALL SYMBOLS MAY NOT BE USED
SCALE: NONEBRECESSED LIGHT FIXTURE DETAIL
No.
Description
Date
FE
SCPC
WP1 WP1
SCD1
SCD1
SCD1
D1
D2
D2
D2
D2SCD2
S CD2
n4
n4
n4
n4
WD
D
D1
D1
n1
S CD1
D1
SCD7
1 2 3 4 5 6 7 8 9 10
A
B
C
D
(TYP)F4
RR
BREAK
SERVICE
MANAGER
SERVICE
RR
OFFICE
PARTS
LOBBY
GALLERY
SHOP
F5
F5
NLF1E
F1 NLF1E
F1
(TYP)F1
(TYP)F1
F6E
F6E
(TYP)F7
FX1
FX2
FX2
FX1
FX1
FX1
FX1
F6
F6
F7E
F7E
F7E
F6E
F6
F6
(TYP)F7
'LA'
'LCP'F3E
F3E
F3E
F3E
F3E
F3E
F3E
(TYP)F3
F3E
F3E
F3E
F3E
F3E
(TYP)F3
(TYP)F3
TO 'LPC'
LA-1
1
LA-3
#8's
1 LA-5
#8's
1
LA-13
LA-13
LA-13
LA-13
LA-13
LA-13 LA-13
(TYP)F8
(TYP)F8
F8
(TYP)F8
(TYP)F9
LA-13
LA-13
TO 'LPC'
LA-7
1
LA-9
1
F10E
11' -6"
F10E
11' -6"
F10E
11' -6"FX3
FX3
FX3
F11
18' -0"
F11
18' -0"
F11
18' -0"
F11
18' -0"
F11
18' -0"
F11
18' -0"
F11
18' -0"
LA-111
LA-11
LA-11 LA-11 LA-11 LA-11
LA-11
LA-11LA-11LA-11
3 4
A
B
C
D
UPPER
OFFICE
STORAGE
F1F1EF1
(TYP)F2
(TYP)F2
LA-15
LA-15
LA-15
AIRCRAFT CABLE "Y" HANGER
(TYP BOTH ENDS OF FIXTURE"
AIRCRAFT CABLE ANCHORED
SECURELY TO STRUCTURE ABOVE
LEVEL W/ BOTTOM
OF TRUSSES
13053
STATEOFIDAHOSHAWNA.M E A D ORREGISTEREDRP
OFESSIONALENGIN
EE
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
BO
O
T
H
Date
Sheet No.
A
r
c
h
i
t
e
c
t
u
r
e
(2
0
8
)
2
3
3
-
4
5
4
8
Ph
o
n
e
Po
c
a
t
e
l
l
o
,
I
d
a
h
o
8
3
2
0
1
34
0
E
a
s
t
C
l
a
r
k
S
t
r
e
e
t
,
S
u
i
t
e
A
(2
0
8
)
2
3
3
-
0
2
6
3
te
d
@
b
o
o
t
h
a
r
c
h
i
t
e
c
t
u
r
e
.
c
o
m
Fa
x
em
a
i
l
P
L
L
C
Ne
w
B
u
i
l
d
i
n
g
f
o
r
:
P.E. #:2265
7/20/22
Re
v
i
s
i
o
n
s
LIGHTING PLANS
Mo
u
n
t
a
i
n
W
e
s
t
07-20-2022
TB
D
Re
x
b
u
r
g
,
I
d
a
h
o
E1.0
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
KEY NOTES:#
16'8'0"SCALE: 1/8" = 1'-0"1 MAIN FLOOR LIGHTING PLAN
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MOUNTING VOLTAGE LUMENS
COLOR
TEMP.(K) MFGR.CATALOG #
APPROVED
MFGR'S NOTES
F1 2X2 LED FLAT PANEL, 0-10V DIMMING, FIELD SWITCHABLE RECESSED 120-277 MED 4000 LITHONIA CPX 2X2 AL07 M4 COOPER 1
F1E 2X2 LED FLAT PANEL,0-10V DIMMING, FIELD SWITCHABLE, EMERG. BATTERY PACK RECESSED 120-277 MED 4000 LITHONIA CPX 2X2 AL07 M4 IE10WCP COOPER 1
F2 HIGHBAY LED, AIRCRAFT CABLE SUSPENSION SUSPENDED 120-277 15000 4000 LITHONIA IBG-15000LM-SEF-PFL-GND-MVOLT-GZ10-40K-80CRI-SCBA-IBGACVH COOPER 1,3
F3 HIGHBAY LED, AIRCRAFT CABLE SUSPENSION SUSPENDED 30FT AFF 120-277 24000 4000 LITHONIA IBG-24000LM-SEF-PFL-GND-MVOLT-GZ10-40K-80CRI-SCBA-IBGACVH COOPER 1,3
F3E HIGHBAY LED, AIRCRAFT CABLE SUSPENSION, EM. BATTERY PACK SUSPENDED 30FT AFF 120-277 24000 4000 LITHONIA IBG-24000LM-SEF-PFL-GND-MVOLT-GZ10-40K-80CRI-SCBA-E10WCP-IBGACVH COOPER 1,3
F4 6" ROUND RECESSED LED CAN, 0-10V DIMMING RECESSED 120-277 2000 4000 LITHONIA LDN6-40/20-LO6AR-LSS-MVOLT-EZ10 COOPER 1
F5 4FT LED SURFACE WRAPAROUND FIXTURE SURFACE 120-277 4000 4000 LITHONIA FML4W 48 AL06 SEF 840 MVOLT COOPER
F6 8FT LED STRIP, 0-10V DIMMING SURFACE OR SUSPENDED 120-277 8000 4000 LITHONIA CLX-L96-8000LM-SEF-RDL-MVOLT-GZ10-40K-80CRI COOPER
F6E 8FT LED STRIP, 0-10V DIMMING, W/ EM BATTERY PACK SURFACE OR SUSPENDED 120-277 8000 4000 LITHONIA CLX-L96-8000LM-SEF-RDL-MVOLT-GZ10-40K-80CRI-PS1050 COOPER
F7 4FT LED STRIP, 0-10V DIMMING SURFACE/ SUSPENDED 120-277 4000 4000 LITHONIA CLX-L48-4000LM-SEF-RDL-MVOLT-GZ10-40K-80CRI COOPER
F7E 4FT LED STRIP, 0-10V DIMMING SURFACE/ SUSPENDED 120-277 4000 4000 LITHONIA CLX-L48-4000LM-SEF-RDL-MVOLT-GZ10-40K-80CRI-PS1050 COOPER
F8 PENDANT LINEAR LED, AIRCRAFT CABLE SUSPENSION, 0-10V DIMMING SUSPENDED 12FT AFF 120-277 1250LM/FT 4000 FOCAL
POINT LTG
FSM4LS-FL-1250LF-40K-1C-UNV-LD1-C96**-SCBA-(PER DWG'S) COOPER 1,2,3,4
F9 PENDANT LINEAR LED, AIRCRAFT CABLE SUSPENSION, 0-10V DIMMING SUSPENDED 12FT AFF 120-277 375LM/FT 4000 FOCAL
POINT LTG
FSM4LS-FL-375LF-40K-1C-UNV-LD1-C96**-SCBA-(PER DWG'S) COOPER 1,2,3,4
F10E EXTERIOR LED WALL PACK, EMERG. BATTERY PACK WALL 120-277 4500 4000 LITHONIA WDGE2 LED-P4-40K-80CRI-VW-MVOLT-E20WC-SCBA COOPER 3
F11 EXTERIOR LED WALL PACK WALL 120-277 18000 4000 LITHONIA WDGE4 LED-P3-40K-80CRI-R3-MVOLT-SCBA COOPER 3
FX1 EXIT SIGN W/ 90MIN BATTERY,THERMOPLASTIC, GREEN LED, SINGLE/DOUBLE FACE WALL OR CEILING 120-277 N/A N/A LITHONIA LQM-S-W-3-G-20/277-EL N COOPER
FX2 EXIT SIGN/EM LIGHT COMBO W/ 90MIN BATTERY,THERMOPLASTIC, GREEN LED,
SINGLE/DOUBLE FACE
WALL OR CEILING 120-277 N/A N/A LITHONIA LHQM LED-G-SD COOPER
FX3 WALL MOUNTED EXTERIOR EMERGENCY EGRESS LIGHT, W/HEATER WALL ABOVE DOOR 120-277 N/A N/A LITHONIA AFF-OEL-SCBA-UVOLT-LTP-SDRT-WT-CW DUAL-LITE
LIGHTING CONTROL/OCCUPANCY SENSOR SCHEDULE
TYPE DESCRIPTION MFGR. CATALOG # NOTES APPROVED EQUALS
DIMMER SWITCHES - LINE VOLTAGE
D1 LINE VOLTAGE 0-10V DIMMER, ON/OFF/DIMMING PUSH-BUTTONS SENSOR SWITCH sPODMRA-D-** 2,3,4
D2 LINE VOLTAGE 0-10V DIMMER FOR MULTI-WAY OPERATION, ON/OFF/DIMMING PUSH-BUTTONS SENSOR SWITCH sPODMRA MWO-D-** 2,3,4
LIGHTING CONTROL PANELS
'LCP' SURFACE MOUNTED, 8-RELAY DIGITAL RELAY PANEL, W/nLIGHT INTERFACE ACUITY BRANDS ARP INTENC08
NLT/8SPR/MVOLT/SC/SM/DTC
6 COOPER, WATTSTOPPER, LEVITON
nLIGHT DEVICES
n1 nLIGHT ON/OFF PUSHBUTTON SENSOR SWITCH nPODM 3
n4 nLIGHT ON/OFF PUSHBUTTON, 4-CHANNEL SENSOR SWITCH nPODM-4P 3
OCC. SENSORS - CEILING (LINE VOLTAGE)
CD2 DUAL-TECHNOLOGY, LINE VOLTAGE, SMALL MOTION 800W MAX LOAD SENSOR SWITCH CMR PDT 9 COOPER, WATTSOPPER, HUBBELL
OCC. SENSORS - CEILING (LOW VOLTAGE)
CD1 DUAL-TECHNOLOGY, SMALL MOTION 360 DEGREE COVERAGE, LOW VOLTAGE, W/ISOLATED RELAY SENSOR SWITCH CM PDT 9 R 1 COOPER, WATTSTOPPER, HUBBELL
CD7 DUAL-TECHNOLOGY, CORNER MOUNT WIDE VIEW, LOW VOLTAGE, W/ISOLATED RELAY SENSOR SWITCH WV PDT 16 R (KIT) 1 COOPER, WATTSTOPPER, HUBBELL
CPC ON/OFF & AUTOMATIC DIMMING PHOTOCELL SENSOR SWITCH CM PC ADC 1 COOPER, WATTSTOPPER, HUBBELL
OCC. SENSORS - WALL MOUNTED
WDD DUAL-TECHNOLOGY, 0-10V DIMMING SENSOR SWITCH WSX-PDT-D 2,5 COOPER, WATTSTOPPER, HUBBELL
WP1 PASSIVE-INFRARED, 1-POLE, NEUTRAL REQUIRED SENSOR SWITCH WSX-** 2 COOPER, WATTSTOPPER, HUBBELL
SCALE: 1/8" = 1'-0"2 MEZZANINE FLOOR LIGHTING PLAN
16'8'0"
1 ROUTE CIRCUIT THROUGH LIGHTING CONTROL PANEL
(LCP); REFER TO LIGHTING CONTROL/OCCUPANCY
SENSOR SCHEDULE FOR ADDITIONAL INFORMATION.
PROVIDE ADDITIONAL UN-SWITCH LEG AS NEEDED FOR
CONNECTION TO BATTERY PACK OF EMERGENCY
FIXTURE(S) (F#E).
1. PROVIDE ADDITIONAL POWER PACKS; SENSOR SWITCH PP20 AS NEED FOR QTY OF OCCUPANCY SENSORS/SWITCHES.
2. DEVICE COLOR SHALL MATCH WIRING DEVICES; REFER TO SPECIFICATIONS.
3. REFER TO MANUFACTURER DOCUMENTATION FOR QTY AND SIZE OF CONDUCTORS BETWEEN LOW VOLTAGE SWITCH, SENSOR(S) AND POWER/RELAY PACKS.
4. PROVIDE SECONDARY RELAY PACK; SENSOR SWITCH SP20 AS NEEDED TO PROVIDE DUAL-LEVEL SWITCHING OF FIXTURES.
5. PROVIDE 0-10V DIMMING CONDUCTORS (GRAY & VIOLET) BETWEEN SWITCH AND LIGHT FIXTURES FOR DIMMING CONTROL.
6. PROGRAM ON/OFF TIMES OF RELAY'S AS DIRECTED BY OWNER. PROVIDE COMMISSIONING AS INDICATED IN GENERAL NOTES BELOW.
7. CUSTOM WALL STATION ENGRAVINGS IS REQUIRED FOR WALL STATION(S) AND SHALL BE SPECIFIED/COORDINATED WITH OWNER AFTER PROGRAMING OF SYSTEM.
CONTROL & OCCUPANCY SENSOR SCHEDULE NOTES:
• E.C. SHALL BE RESPONSIBLE FOR THE PROGRAMMING/COMMISSIONING OF THE LIGHTING CONTROL SYSTEMS TO FUNCTION AS INDICATED ON THE DRAWINGS AND SHALL INCLUDE ALL REQUIRED COST IN
THE BASE BID. FOR AREAS WITH DAYLIGHTING CONTROL, THE DAYLIGHTING SET-POINTS SHALL BE COORDINATED WITH THE OWNER FOR EACH AREA PRIOR TO FINAL PROGRAMMING OF THE
DAYLIGHTING SENSOR(S). ALL PROGRAMMING/COMMISSIONING SHALL BE DONE BY A FACTORY CERTIFIED OR TRAINED PERSON.
GENERAL LIGHTING CONTROL NOTES:
1. REFER TO DRAWINGS FOR FIXTURES REQUIRED TO HAVE 0-10V OR STEP-LEVEL DIMMING CONTROL. PROVIDE FIXTURE(S) WITH LED DRIVER(S) AND REQUIRED DIMMING/SWITCH-LEG CONDUCTORS
BETWEEN SWITCH(ES) AND FIXTURE(S) TO PROVIDE CONTROL AS INDICATED ON DRAWINGS.
2. FIXTURE LENGTH AS INDICATED ON DRAWINGS.
3. SCBA - STANDARD COLOR BY ARCHITECT/OWNER (COORDINATE COLOR WITH ARCHITECT/OWNER PRIOR TO ORDERING.)
4. FIELD ADJUST PENDANT LENGTH AS REQUIRED, VERIFY LENGTH WITH OWNER.
LIGHT FIXTURE SCHEDULE NOTES:
• LIGHTING FIXTURES INDICATED IN SCHEDULE ARE BASIS OF DESIGN, ALTERNATE MANUFACTURERS SHALL BE PRE-APPROVED BY ADDENDUM. ALTERNATE MANUCATURERS SHALL SUBMIT PER-
APPROVALS TO ENGINEER A MINIMUM OF 10 DAYS PRIOR TO PROJECT BID DATE.
GENERAL LIGHTING SCHEDULE NOTES:
SCALE: NONEALIGHT FIXTURE HIGHBAY MOUNTING DETAIL
No.
Description
Date
FE
MM
T
MM
T
MM
T
MM
T
MM
T
MM
T
MM
T
MM
T
FB2F
FB2F
FF
FP
MM
T
MM
T
MM
T
MM
T
1 2 3 4 5 6 7 8 9 10
A
B
C
D
WP WP WP WP WP WP
WP
WPWPWPWP
WP
1 1 1
1
1111
2
'MDP''LA'
'LB'
'LC'
3
'TTB'
WPWPWP
4
(A/E2.0)
5
5
5
5
5
6 6
5
5
5
7
1"C
1"C
42"
EWC
RR
BREAK
SERVICE
MANAGER
SERVICE
RR
OFFICE
PARTS
LOBBY
GALLERY
SHOP
42"
AC
48"48"48"48"48"48"
48"
48"
48"48"48"48"48"48"
48"
48"
48"
48"
48"
W
W
WP
AIR
COMPRESSOR
60 A/NEMA 3R
8
BRIDGE
CRANE
60 A/NEMA 1
8
99
CU-1 CU-2 CU -3
LB-14 LB-16#10's
LC-14#10's
LC-12
LC-10#10's
LB-12#10'sLB-18#10's
LA-27
LA-17
LA-16
LA-12
LA-12
LA-10
LA-10
LA-10
LA-12
LA-12
LA-14LA-14
LA-12
LA-16 LA-16
LA-18
LA-10
LA-8 LA-8
LA-8
LA-8
LA-28
LA-28
LA-28
LA-12
LA-8
LA-18
LA-18
LA-18
LA-18
LA-20
LA-24
LA-22
LA-6
LA-6
LA-6
LA-20
LA-6 LA-6
LA-20LA-20
LA-22
LA-22
LA-20
LA-24
LA-24
LA-24LA-24
LA-26
LA-22
LA-2LA-2LA-4LA-4LA-6LA-8
LA-10
LA-25
LA-16
LA-24
LA-23
LA-26
LB-2
LB-6 LB-37,39,41#6's
LB-6
LB-6
LB-8
LB-8
LB-8
LB-10
LB-10
LB-10 LC-8
LC-8
LC-8 LC-8
LC-6
LC-40,42#6's
LC-6
LC-36,38#6's
LC-4LC-2
LC-37,39,41#6's
LC-2
LC-2
LC-2LB-4
LB-4
LB-4LB-2
LB-2
10
AHU-1
HVLS-1 HVLS-2
MOTORIZED
DAMPER
LB-8
CONTROL AS
DIRECTED BY MECH.
CONTRACTOR
MOTORIZED
DAMPER
LB-2
CONTROL AS
DIRECTED BY MECH.
CONTRACTOR
PTAC-1
LA-26
CH-1
CH -2
3 4
A
B
C
D
UPPER
OFFICE
STORAGE
WH-1
LA-51,53#10's
LA-19
LA-19
LA-19
LA-19
LA-21LA-21
LA-21
LA-21 LA-21
LA-21
F-1
F-2
F-3
CP-1
LA-19
UH-1
LA-19
PTAC-2
6"
3/4" C., 1#6 B.C. GRND.
CONNECT TO BLDG. GROUND
SYSTEM
FINISH FLOOR
TYPICAL CONDUITS OUT TO VOICE/
DATA OUTLETS. SEE PLAN FOR
SIZE, ETC. (TYPICAL TOP & OR
BOTTOM OF BOARD)
4'X8'X3/4" PLYWOOD
PRIME & PAINT W/TWO
COATS GREY ENAMEL
(INSTALL ON WALLS AS
INDICATED ON PLANS)
ANCHOR SECURELY TO
WALL W/ CONST. ADHESIVE.
DOUBLE-DUPLEX
OUTLET(S) PER PLANS
120V CIRCUIT
PER PLANS
PULL CORD
INCOMING UTILITY
SERVICECONDUIT(S)
WITH INSULATED BUSHING.
SEE SITE PLAN FOR SIZE & QTY
GROUND BAR
(SQ. D #PK27GTA)
COMM. UTILITY CO.
EQUIPMENT
INSTALL INSULATED BUSHING
ON ALL CONDUIT ENDS.
TYP TOP & BOTTOM
UNISTRUT ANCHOR
TYP TOP & BOTTOM
WALL MOUNTED RACK
ORTRONICS# OR-604045451
13053
STATEOFIDAHOSHAWNA.M E A D ORREGISTEREDRP
OFESSIONALENGIN
EE
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
BO
O
T
H
Date
Sheet No.
A
r
c
h
i
t
e
c
t
u
r
e
(2
0
8
)
2
3
3
-
4
5
4
8
Ph
o
n
e
Po
c
a
t
e
l
l
o
,
I
d
a
h
o
8
3
2
0
1
34
0
E
a
s
t
C
l
a
r
k
S
t
r
e
e
t
,
S
u
i
t
e
A
(2
0
8
)
2
3
3
-
0
2
6
3
te
d
@
b
o
o
t
h
a
r
c
h
i
t
e
c
t
u
r
e
.
c
o
m
Fa
x
em
a
i
l
P
L
L
C
Ne
w
B
u
i
l
d
i
n
g
f
o
r
:
P.E. #:2265
7/20/22
Re
v
i
s
i
o
n
s
POWER/DATA PLANS
Mo
u
n
t
a
i
n
W
e
s
t
07-20-2022
TB
D
Re
x
b
u
r
g
,
I
d
a
h
o
E2.0
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
KEY NOTES:#
SCALE: 1/8" = 1'-0"1 MAIN FLOOR POWER/DATA PLAN
16'8'0"
1 CONNECTION TO OVERHEAD DOOR MOTOR, COORDINATE
CONNECTION WITH EQUIPMENT PRIOR TO ROUGH-IN.
PROVIDE CONDUIT AND CONDUCTORS TO PUSH-BUTTON
STATION PER MANUFACTURERS REQUIREMENTS.
2 CT CAN AND METER BASE MOUNTED ON BUILDING. SEE
POWER RISER FOR ADDITIONAL INFORMATION.
3 NEW UNDERGROUND SECONDARY; SEE POWER RISER FOR
ADDITIONAL INFORMATION.
4 (1) 4" CONDUIT FOR TELECOMMUNICATIONS SERVICE TO
BUILDING AND (1) 2" CONDUIT FOR CABLE TV SERVICE TO
BUILDING. STUB CONDUITS TO LOCATIONS AS SPECIFIED BY
LOCAL TELEPHONE AND CABLE TV PROVIDERS, PROVIDE
WITH PULL-STRING. COORDINATE WITH LOCAL UTILITIES AS
INDICATED IN GENERAL NOTES
5 INSTALL RECEPTACLE WITHIN 18" OF THE TOP OF THE
WINDOW IN ACCORANCE WITH NEC 210.62.
6 CONNECTION TO AUTOMATIC DOORS; FIELD VERIFY
CONNECTION LOCATION AND REQUIREMENTS WITH
EQUIPMENT INSTALLERS. PROVIDE ALL REQUIRED
ROUGH-IN AND CONNECTIONS TO PUSH-BUTTONS IF
APPLICABLE.
7 RECEPTACLE(S) AND DATA OUTLET(S) INSTALLED IN
MILLWORK. E.C. SHALL ROUTE POWER AND DATA CONDUIT
UNDERGROUND AND STUB-UP INTO MILLWORK. FIELD
VERIFY EXACT STUP UP LOCATIONS WITH MILLWORK AND
OWNER PRIOR TO ROUGH-IN.
8 FUSE DISCONNECT SWITCH PER EQUIPMENT NAMEPLATE.
9 CONNECT EXHAUST FAN TO ROOM LIGHTING CIRCUIT AND
CONTROL WITH LIGHTING
10 PROVIDE AND INSTALL (2) 2" SPARE CONDUITS STUB OUT
OF BULDING FOR FUTURE WASHBAY BUILDING AND
MONUMENT SIGN. E.C. SHALL FIELD VERIFY STUB OUT
LOCATION WITH OWNER AND G.C. PRIOR TO INSTALLATION.
SCALE: 1/8" = 1'-0"2 MEZZANINE FLOOR POWER/DATA PLAN
16'8'0"SCALE: NONEATELEPHONE TERMINAL BOARD (TTB) DETAIL
ELECTRICAL FLOORBOX SCHEDULE
ID DESCRIPTION MFGR. FLOORBOX p/n COVERPLATE p/n
POWER
DEVICES
DATA
DEVICES NOTES
FB2F 2-GANG, MULTI-SERVICE CONCRETE
FLOORBOX, W/FLUSH STYLE
RECTANGULAR COVER, 3" MIN. POUR
HUBBELL CFB2G30CR 24GTCVRXXX (1) DUPLEX
RECPT.
PER
OWNER
1,2,3
1. PROVIDE REQUIRED SUB-PLATES FOR INSTALLATION OF POWER, DATA AND AV DEVICES.
2. E.C. SHALL FIELD LOCATE EXACT PLACEMENT OF FLOORBOX WITH ARCHITECT/OWNER PRIOR TO INSTALLATION.
3. PROVIDE CONDUIT (SIZE AS INDICATED ON DRAWINGS) TO ACCESSIBLE CEILING SPACE FOR ROUTING OF DATA AND/OR
LOW VOLTAGE CABLING.
FLOORBOX SCHEDULE NOTES:
SHOP SPECIAL NOTES:
• ALL WIRING METHODS AND DEVICES LOCATED IN SHOP AND
AREAS OPEN TO THE SHOP SHALL CONFORM TO NEC
ARTICLE 511, SECTION 501.15 and 210.8(B).
• ALL SURFACE RACEWAY INSTALLED BELOW 6'-0" AFF SHALL
BE RIGID GALVANIZED STEEL CONDUIT.
• PROVIDE AND INSTALL CONDUIT SEAL-OFFS TO COMPLY
WITH NEC SECTION 511, 501.15 AND LOCAL AHJ.
• WHERE PANELS ARE INSTALLED IN SHOP AREA,
INSTALLATION SHALL BE IN COMPLIANCE WITH NEC
ARCTICAL 511, SECTION 501.15, SECTION 240.24(A) AND
LOCAL AHJ REQUIREMENTS.
• ALL UNDERGROUND CONDUITS INSTALLED IN SHOP/LNG
BAY AREAS SHALL BE INSTALLED IN COMPLIANCE WITH NEC
ARTICLE 511 AND SECTION 501.15.
FIRE ALARM SYSTEM SHALL BE DESIGN BUILD BY THE ELECTRICAL CONTRACTOR.
PROVIDE AND INSTALL AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL FIRE CODE
AND LOCAL AHJ REQUIREMENTS. PROVIDE ALL DOCUMENTATION, DRAWINGS, VOLTAGE
DROP AND BATTERY CALCULATIONS AND ECT. TO THE CITY FOR PERMITTING AND
INSTALLATION.
A. NFPA ALLOWS NOTIFICATION APPLIANCES TO BE MOUNTED AT A HEIGHT RANGE
BETWEEN 80" TO 96" ABOVE FINISH FLOOR. THE PREFERRED HEIGHT IS 80". IF THIS
CONFLICTS WITH OTHER TRADES OR ROOM FURNISHINGS, LOCATE AS CLOSE TO 80"
AS POSSIBLE, NOT EXCEEDING 96". ALL NOTIFICATION APPLIANCES IN A COMMON
ROOM OR LINE OF SIGHT SHALL BE LOCATED AT A COMMON HEIGHT.
B. MOUNT PULL STATIONS AT 46-48" A.F.F. TO THE OPERATING HANDLE TO MEET ADA
REQUIREMENTS.
C. IN CORRIDORS, NOTIFICATION APPLIANCES MUST BE LOCATED WITHIN 15' FROM ENDS
OF CORRIDORS AND A MAXIMUM OF 100' SPACING.
D. PROVIDE THE REQUIRED CANDELA RATING OF ALL NOTIFICATION APPLIANCES
ACCORDING TO ROOM SIZE,ETC.
E. NOTIFICATION APPLIANCES TO BE SYNCHRONIZED TO PROVIDE A 3-3-3 TEMPORAL
PATTERN.
F. PROVIDE REQUIRED MONITORING OF FIRE SPRINKLER SYSTEM, COORDINATE WITH
FIRE SPRINKLER CONTRACTOR.
G. ALL HVLS (HIGH VOLUME LOW SPEED) FANS SHALL BE INTERCONNECTED TO FIRE
ALARM SYSTEM AND SHUT-DOWN UPON ACTIVATION OF FIRE ALARM.
FIRE ALARM SYSTEM DESIGN:
MECHANICAL - FURNACE SCHEDULE
EQUIP. ID VOLTS PH. HP FLA CIRCUIT FEEDER NOTES
F-1 120 V 1 3/4 7 A LA-38 #12'S 1,4
F-2 120 V 1 1 9 A LA-40 #12'S 1,4
F-3 120 V 1 1/2 5 A LA-42 #12'S 1,4
MECHANICAL - CONDENSING UNIT SCHEDULE
EQUIP. ID VOLTS PH. MCA MOCP CIRCUIT FEEDER DISCONNECT NOTES
CU-1 208 V 1 32 A 50 A LA-44,46 #8'S 60 A/FUSED/3R 2,4
CU-2 208 V 1 35 A 60 A LA-48,50 #6'S 60 A/FUSED/3R 2,4
CU-3 208 V 1 26 A 40 A LA-52,54 #8'S 60 A/FUSED/3R 2,4
1. E.C. SHALL PROVIDE LOCAL DISCONNECT RATED, THERMAL-OVERLOAD SWITCH FOR EQUIPMENT;
SWITCH RATING SHALL NOT BE LESS THEN CIRCUIT BREAKER SUPPLYING EQUIPMENT.
2. E.C. SHALL PROVIDE LOCAL DISCONNECT SWITCH FOR EQUIPMENT; SIZE AND TYPE AS INDICATED
IN SCHEDULE. IF FUSED DISCONNECT IS SPECIFIED FOR EQUIPMENT, FUSE PER EQUIPMENT
NAMEPLATE RATING.
3. EQUIPMENT IS FACTORY SUPPLYED WITH DISCONNECT AND CONVIENENCE OUTLET; E.C. SHALL
PROVIDE ALL NECESSARY CONNECTIONS.
4. PROVIDE 1/2" CONDUIT AND CONDUCTORS BETWEEN FURNACE AND CORRESPONDING OUTDOOR
CONDENSING UNIT. COORDINATE SIZE AND NUMBER OF CONDUCTORS WITH M.C. PRIOR TO
ROUGH-IN. PROVIDE CONNECTION BETWEEN FURNACE AND ASSOCIATED OUTSIDE AIR MOTORIZED
DAMPER, COORDINATE WITH M.C.
5. E.C. SHALL INTERLOCK FAN WITH FIRE ALARM SYSTEMS, FAN SHALL DE-ENERGIZED UPON
ACTIVATION OF FIRE ALARM SYSTEM, COORDINATE WITH M.C. AND FIRE ALARM INSTALLER.
MECHANICAL SCHEDULE NOTES:
MECHANICAL - AIR HANDLING UNIT SCHEDULE
EQUIP. ID VOLTS PH. HP FLA CIRCUIT FEEDER NOTES
AHU-1 208 V 3 3 12 A LC-31,33,35 #12'S 3
MECHANICAL - CEILING FAN SCHEDULE
EQUIP. ID VOLTS PH. FLA CONTROL CIRCUIT FEEDER NOTES
HVLS-1 208 V 3 6 A WIRELESS CONTROLLER LB-32,34,36 #12'S 5
HVLS-2 208 V 3 6 A WIRELESS CONTROLLER LB-38,40,42 #12'S 5
MECHANICAL - PTAC SCHEDULE
EQUIP. ID VOLTS PH. WATTS FLA CIRCUIT FEEDER NOTES
PTAC-1 208 V 1 3500 W 17 A LA-39,41 #10'S
PTAC-2 208 V 1 3500 W 17 A LA-43,45 #10'S
No.
Description
Date
1
HVAC Changes
7/26/22
1
UTILITY XFMR BY ROCKY MOUNTAIN
POWER (RMP). PAD AND VAULT
PROVIDED AND INSTALLED BY E.C.
PER RMP STANDARDS
UNDERGROUND SECONDARY;
(4) 4" CONDUIT, TRENCHING AND BACKFILL
BY ELEC. CONTRACTOR, CONDUCTORS
BY UTILITY CO.
FAULT CURRENT
CALULATIONS WERE
BASED ON
INFINITE BUS, WITH AN
ESTIMATED 300KVA
TRANSFORMER WITH
A 3.21%Z.
PANEL
'LA'
MAIN FLOOR
UNDERGROUND PRIMARY;
(2) 4"CONDUIT, TRENCHING AND BACKFILL
BY ELEC. CONTRACTOR, CONDUCTORS
BY UTILITY CO.
PANEL
'LB'
PANEL
'LC'
800A
208Y/120V,3P,4W
NEMA 3R
CT CAN
PANEL
'MDP'
GND
BAR
(3) 3"C., EA.
W/4#300
METER BASE & CT CAN
PER RMP CO.
REQUIREMENTS
GROUNDING
ELECTRODE
SYSTEM
M
(2) 2" C. FOR FUTURE
WASHBAY AND MONUMENT
SIGN
*25,972A
*19,817A *13,443A *6,324A
BLDG.
STEEL
WATER
MAIN
GROUND BAR
AT MAIN TTB
GRND
RODS
STAND-OFF GROUND BAR LOCATED
IN ELEC. RM NEXT TO SERVICE EQUIP.
GROUND BAR SHALL BE ERICO #EGBA14412CC
OR EQUAL. PROVIDE AND INSTALL ALL REQ'D
LUGS & TERMINALS. MOUNT VERT. TO
CONSERVE AS MUCH WALL SPACE AS POSSIBLE.
MAIN
SERVICE
EQUIPMENT
G N
NEUTRAL TO GND
BOND AT THIS POINT
ONLY
#3/0 Cu
#6
C
u
CONCRETE ENCASED
ELECTRODE
3/
4
"
C
.
,
1
#
6
C
u
#3
/
0
C
u
#3
/
0
C
u
#4
C
u
BOND
TO FIRE
SPRINKLER
RISER
#3
/
0
C
u
13053
STATEOFIDAHOSHAWNA.M E A D ORREGISTEREDRP
OFESSIONALENGIN
EE
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
BO
O
T
H
Date
Sheet No.
A
r
c
h
i
t
e
c
t
u
r
e
(2
0
8
)
2
3
3
-
4
5
4
8
Ph
o
n
e
Po
c
a
t
e
l
l
o
,
I
d
a
h
o
8
3
2
0
1
34
0
E
a
s
t
C
l
a
r
k
S
t
r
e
e
t
,
S
u
i
t
e
A
(2
0
8
)
2
3
3
-
0
2
6
3
te
d
@
b
o
o
t
h
a
r
c
h
i
t
e
c
t
u
r
e
.
c
o
m
Fa
x
em
a
i
l
P
L
L
C
Ne
w
B
u
i
l
d
i
n
g
f
o
r
:
P.E. #:2265
7/20/22
Re
v
i
s
i
o
n
s
POWER RISER,
SCHEDULES &
DETAILS
Mo
u
n
t
a
i
n
W
e
s
t
07-20-2022
TB
D
Re
x
b
u
r
g
,
I
d
a
h
o
E3.0
SCALE: 12" = 1'-0"1 POWER RISER DIAGRAM
A. THESE PLANS HAVE BEEN PREPARED WITHOUT UTILITY
COMPANY COMMENTS. THE E.C. SHALL VERIFY THE EXACT
REQUIREMENTS FOR THE ELECTRIC AND TELEPHONE
SERVICES WITH THE UTILITY COMPANY REPRESENTATIVES
AND PROVIDE ALL WORK AND PAY ALL COSTS FOR A
COMPLETE AND OPERATING SYSTEM, AS DIRECTED BY THE
GOVERNING UTILITIES.
GENERAL NOTES:
POWER RISER FEEDER SCHEDULE
SOURCE LOAD
# OF CONDUIT
RUNS
CONDUIT
SIZE FEEDER SIZE
CONDUCTOR
TYPE
LOAD
AMPS
FEEDER
BREAKER SIZE
MDP PANEL LA 1 2" 3-#3/0, 1-#3/0, 1-#6 COPPER 152 A 200 A
MDP PANEL LB 1 2" 3-#3/0, 1-#3/0, 1-#6 COPPER 66 A 200 A
MDP PANEL LC 1 2" 3-#3/0, 1-#3/0, 1-#6 COPPER 100 A 200 A
FEEDER SCHEDULE LEGEND & NOTES
QTY & SIZE
OF PHASE
CONDUCTOR(S)
QTY-#PHASE SIZE, QTY-#NEUTRAL SIZE, QTY-#GROUND SIZE
QTY & SIZE
OF NEUTRAL
CONDUCTOR(S)
QTY & SIZE
OF GROUND
CONDUCTOR(S)
1. # OF RUNS INDICATES THE NUMBER OF PARALLEL RUNS FOR THE FEEDER.
2. FEEDER SIZE IN SCHEDULE IS AS INDICATED BELOW:
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
Elec. Heating 12400 VA 100.00% 12400 VA
Welder 16000 VA 87.50% 14000 VA
Receptacle 18060 VA 77.69% 14030 VA TOTAL EST. DEMAND AMPS:310 A
Other 1000 VA 100.00% 1000 VA TOTAL CONN. AMPS.:317 A
Motor 42686 VA 108.23% 46200 VA TOTAL EST. DEMAND:111855 VA
Lighting 9959 VA 100.00% 9959 VA TOTAL CONN. LOAD:114366 VA
HVAC 15425 VA 100.00% 15425 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR EST. DEMAND PANEL TOTALS
PANEL LOAD SUMMARY
TOTAL AMPS:311 A 315 A 328 A
TOTAL LOAD:37.3 kVA 37.7 kVA 39.4 kVA
23 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 24
21 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 22
19 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 20
17 0 -- 1 -- -- PREPARED SPACE 18
15 0 -- 1 -- -- PREPARED SPACE 16
13
SPARE -- 100 A 3
0 -- 1 -- -- PREPARED SPACE 14
11 14467 0 12
9 10107 0 10
7
PANEL LC 200 A 3
11367 0
3 200 A -- SPARE
8
5 17014 7973 6
3 19873 7860 4
1
PANEL LA 200 A 3
18024 7960
3 200 A PANEL LB
2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
SERVICE ENTRANCE RATED
NOTES:
MFG/ MODEL:SQ. D/I-LINE DIMENSIONS:44"W x 11.5"D x *"H FEED:BOTTOM
ENCLOSURE:NEMA 1 BUSSING:SEE SPEC'S MBR AMPS:800 A
MOUNTING:SURFACE WIRES:4 PANEL AMPS:800 A
FED FROM:PHASES:3 PANEL TYPE:MBR Mountain West
LOCATION: VOLTAGE:120/208 Wye A.I.C. RATING:42k PROJECT:
PANEL: MDP
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:149 A
TOTAL AMPS:151 A 167 A 142 A
TOTAL LOAD:18.0 kVA 19.9 kVA 17.0 kVA
53 2250 2138 54
51
Water Heater 30 A 2
2250 2138
2 40 A HVAC CU-3
52
49 SPARE -- 20 A 1 0 2912 50
47 SPARE -- 20 A 1 0 2912
2 60 A HVAC CU-2
48
45 1750 2662 46
43
PTAC 20 A 2
1750 2662
2 50 A HVAC CU-1
44
41 1750 653 1 15 A Furnace 42
39
PTAC 20 A 2
1750 1046 1 15 A Furnace 40
37 SPARE -- 20 A 1 0 806 1 15 A Furnace 38
35 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 36
33 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 34
31 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 32
29 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 30
27 Overhead Door 20 A 1 653 540 1 20 A Receptacle 28
25 Elec. Heating/Recpt. 20 A 1 617 622 1 20 A Receptacle 26
23 Elec. Heating/Recpt. 20 A 1 617 1080 1 20 A Receptacle 24
21 Receptacle 20 A 1 1080 720 1 20 A Receptacle 22
19 Receptacle 20 A 1 1293 900 1 20 A Receptacle 20
17 Receptacle 20 A 1 360 900 1 20 A Receptacle 18
15 Lighting 20 A 1 1065 1140 1 20 A Receptacle 16
13 Lighting 20 A 1 1316 1000 1 20 A Automatic Doors 14
11 Lighting - Exterior LCP 20 A 1 1030 1080 1 20 A Receptacle 12
9 Lighting LCP 20 A 1 740 900 1 20 A Receptacle 10
7 Lighting LCP 20 A 1 1425 1080 1 20 A Receptacle 8
5 Lighting - Shop LCP 20 A 1 1500 1080 1 20 A Receptacle 6
3 Lighting - Shop LCP 20 A 1 1500 360 1 20 A Receptacle 4
1 Lighting - Shop LCP 20 A 1 1500 360 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:BOTTOM
ENCLOSURE:NEMA 1 BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:SURFACE WIRES:4 PANEL AMPS:225 A
FED FROM:MDP PHASES:3 PANEL TYPE:MLO Mountain West
LOCATION: VOLTAGE:120/208 Wye A.I.C. RATING:22k PROJECT:
PANEL: LA
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:76 A
TOTAL AMPS:66 A 65 A 67 A
TOTAL LOAD:8.0 kVA 7.9 kVA 8.0 kVA
41 4667 730 42
39 4667 730 40
37
Bridge Crane 60 A 3
4667 730
3 20 A Shop Fan
38
35 PREPARED SPACE -- -- 1 -- 730 36
33 PREPARED SPACE -- -- 1 -- 730 34
31 PREPARED SPACE -- -- 1 -- 730
3 20 A Shop Fan
32
29 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 30
27 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 28
25 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 26
23 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 24
21 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 22
19 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 20
17 SPARE -- 20 A 1 0 653 1 20 A Overhead Door 18
15 SPARE -- 20 A 1 0 653 1 20 A Overhead Door 16
13 SPARE -- 20 A 1 0 653 1 20 A Overhead Door 14
11 SPARE -- 20 A 1 0 653 1 20 A Overhead Door 12
9 SPARE -- 20 A 1 0 540 1 20 A Receptacle 10
7 SPARE -- 20 A 1 0 590 1 20 A Receptacle 8
5 SPARE -- 20 A 1 0 540 1 20 A Receptacle 6
3 SPARE -- 20 A 1 0 540 1 20 A Receptacle 4
1 SPARE -- 20 A 1 0 590 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:BOTTOM
ENCLOSURE:NEMA 1 BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:SURFACE WIRES:4 PANEL AMPS:225 A
FED FROM:MDP PHASES:3 PANEL TYPE:MLO Mountain West
LOCATION: VOLTAGE:120/208 Wye A.I.C. RATING:22k PROJECT:
PANEL: LB
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:102 A
TOTAL AMPS:96 A 84 A 122 A
TOTAL LOAD:11.4 kVA 10.1 kVA 14.5 kVA
41 3833 4000 42
39 3833 4000
2 50 A G Welder
40
37
Air Compressor 60 A 3
3833 4000 38
35 1441 4000
2 50 A G Welder
36
33 1441 -- 1 -- -- PREPARED SPACE 34
31
Air Handler 20 A 3
1441 -- 1 -- -- PREPARED SPACE 32
29 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 30
27 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 28
25 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 26
23 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 24
21 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 22
19 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 20
17 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 18
15 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 16
13 SPARE -- 20 A 1 0 653 1 20 A Overhead Door 14
11 SPARE -- 20 A 1 0 653 1 20 A Overhead Door 12
9 SPARE -- 20 A 1 0 653 1 20 A Overhead Door 10
7 SPARE -- 20 A 1 0 720 1 20 A Receptacle 8
5 SPARE -- 20 A 1 0 540 1 20 A Receptacle 6
3 SPARE -- 20 A 1 0 180 1 20 A Receptacle 4
1 SPARE -- 20 A 1 0 720 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:BOTTOM
ENCLOSURE:NEMA 1 BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:SURFACE WIRES:4 PANEL AMPS:225 A
FED FROM:MDP PHASES:3 PANEL TYPE:MLO Mountain West
LOCATION: VOLTAGE:120/208 Wye A.I.C. RATING:10k PROJECT:
PANEL: LC
PAYNE ENGINEERING
SCALE: NONEABLDG GROUNDING ELECTRODE SYSTEM DETAIL
No.
Description
Date
1
HVAC Changes
7/26/22
1