Envelope Compliance Certificate
Project Title:
2021 IECC
Project Type:New Construction
Vertical Glazing / Wall Area:19%
Location:Rexburg, Idaho
Climate Zone:6b
Construction Site:
Rexburg, Idaho
Owner/Agent:
Tagg N Go Car Wash
Designer/Contractor:
Project Information
Energy Code:
Tagg N Go Rexburg
Credits: 10.0 Required 11.0 Proposed
Reduced lighting power, 11.0 credit
Additional Efficiency Package(s)
Building Area Floor Area
1-Office : Nonresidential 501
Envelope Assemblies
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
Roof: Insulation Entirely Above Deck, [Bldg. Use 1 - Office]605 ---48.0 0.021 0.032
Floor: Unheated Slab-On-Grade, Vertical 3 ft., [Bldg. Use 1 -
Office] (c)
152 ---10.0 0.510 0.510
NORTH
Ext. Wall: Wood-Framed, 16in. o.c., [Bldg. Use 1 - Office]668 15.0 10.0 0.043 0.051
Window: Metal Frame with Thermal Break: Fixed, Perf. Specs.:
Product ID Kawneer or equivalent, SHGC 0.35, [Bldg. Use 1 -
Office] (b)
216 ------0.350 0.340
Door: Glass (over 50 9.56976e-315lazing): Metal Frame,
Entrance Door, Perf. Specs.: Product ID Kawneer or Equivalent,
SHGC 0.35, [Bldg. Use 1 - Office] (b)
42 ------0.460 0.630
EAST
Ext. Wall: Wood-Framed, 16in. o.c., [Bldg. Use 1 - Office]162 15.0 10.0 0.043 0.051
Ext. Wall: Wood-Framed, 16in. o.c., [Bldg. Use 1 - Office]192 15.0 0.0 0.083 0.051
SOUTH
Ext. Wall: Wood-Framed, 16in. o.c., [Bldg. Use 1 - Office]446 15.0 10.0 0.043 0.051
Ext. Wall: Wood-Framed, 16in. o.c., [Bldg. Use 1 - Office]222 23.0 0.0 0.059 0.051
Window: Metal Frame with Thermal Break: Fixed, Perf. Specs.:
Product ID Kawneer or Equivalent, SHGC 0.35, [Bldg. Use 1 -
Office] (b)
66 ------0.350 0.340
Door: Glass (over 50 9.56976e-315lazing): Metal Frame,
Entrance Door, Perf. Specs.: Product ID Kawneer or Equivalent,
SHGC 0.35, [Bldg. Use 1 - Office] (b)
21 ------0.460 0.630
Door: Insulated Metal, Swinging, [Bldg. Use 1 - Office]21 ------0.200 0.370
WEST
Ext. Wall: Wood-Framed, 16in. o.c., [Bldg. Use 1 - Office]260 15.0 0.0 0.083 0.051
Ext. Wall: Wood-Framed, 16in. o.c., [Bldg. Use 1 - Office]97 23.0 0.0 0.059 0.051
Project Title:
Data filename:
Tagg N Go Rexburg 09/19/23Report date:
161 ofPage
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
46 ------0.350 0.340
(a)
(b)
(c)
-HIIHU\$9LQFHQW3URMHFW$UFKLWHFW
COMcheck Software Version COMcheckWeb
Mechanical Compliance Certificate
Project Title:
2021 IECC
Project Type:New Construction
Location:Rexburg, Idaho
Climate Zone:6b
Construction Site:
Rexburg, Idaho
Owner/Agent:
Tagg N Go Car Wash
Designer/Contractor:
Project Information
Energy Code:
Tagg N Go Rexburg
Credits: 10.0 Required 11.0 Proposed
Reduced lighting power, 11.0 credit
Additional Efficiency Package(s)
Mechanical Systems List
Quantity System Type & Description
Heating: 1 each - Central Furnace, Gas, Capacity = 120 kBtu/h
Proposed Efficiency = 81.00% Et, Required Efficiency: 80.00 % Et or 80% AFUE
Cooling: 1 each - Single Package DX Unit, Capacity = 36 kBtu/h, Air-Cooled Condenser, Unknown Economizer
Proposed Efficiency = 14.00 SEER2, Required Efficiency = 13.40 SEER2
Proposed Part Load Efficiency = 0.00 , Required Part Load Efficiency = 0.00
Fan System: FAN SYSTEM 1 | Office -- Compliance (Motor nameplate HP and fan efficiency method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 1200 CFM, 1.0 motor nameplate hp, 67.00 fan energy index , fan exception: Single
fan <= 5HP
1 HVAC System (Single Zone):
Heating: 1 each - Radiant Heater, Gas, Capacity = 150 kBtu/h
No minimum efficiency requirement applies
1 HVAC System (Single Zone w/ PerimeterSystem):
Heating: 1 each - Radiant Heater, Gas, Capacity = 150 kBtu/h
No minimum efficiency requirement applies
1 HVAC System (Single Zone w/ PerimeterSystem):
Heating: 1 each - Radiant Heater, Gas, Capacity Unknown
No minimum efficiency requirement applies
1 HVAC System (Single Zone w/ PerimeterSystem):
Heating: 1 each - Radiant Heater, Gas, Capacity Unknown
No minimum efficiency requirement applies
1 HVAC System (Single Zone w/ PerimeterSystem):
Heating: 1 each - Radiant Heater, Gas, Capacity = 125 kBtu/h
No minimum efficiency requirement applies
1 HVAC System (Single Zone w/ PerimeterSystem):
Heating: 1 each - Radiant Heater, Gas, Capacity = 125 kBtu/h
No minimum efficiency requirement applies
1 HVAC System (Single Zone w/ PerimeterSystem):
Heating: 1 each - Unit Heater, Gas, Capacity = 200 kBtu/h
Proposed Efficiency = 81.00% Ec, Required Efficiency: 80.00 % Ec
Fan System: FAN SYSTEM 2 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes
Fans:
1 HVAC System (Unknown w/ PerimeterSystem):
Project Title:
Data filename:
Tagg N Go Rexburg 09/19/23Report date:
163 ofPage
Quantity System Type & Description
FAN 2 Supply, Constant Volume, 320 CFM, 0.3 motor nameplate hp, 60.00 fan energy index , fan exception: Single
fan <= 5HP
Heating: 1 each - Other, Electric, Capacity = 18 kBtu/h
No minimum efficiency requirement applies
Cooling: 1 each - Split System, Capacity = 18 kBtu/h, Air-Cooled Condenser, Unknown Economizer
Proposed Efficiency = 0.00 SEER2, Required Efficiency = 13.40 SEER2
Proposed Part Load Efficiency = 0.00 , Required Part Load Efficiency = 0.00
Fan System: FAN SYSTEM 3 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes
Fans:
FAN 3 Supply, Constant Volume, 600 CFM, 0.2 motor nameplate hp, 67.00 fan energy index , fan exception: Single
fan <= 5HP
SYSTEM COMPLIANCE FAILS: PROPOSED EFFICIENCY FAILS TO MEET CODE REQUIREMENTS.
1 HVAC System (Single Zone):
Electric Storage Water Heater, Capacity: 10 gallons w/ Circulation Pump
No minimum efficiency requirement applies
1 Water Heater:
Project Title:
Data filename:
Tagg N Go Rexburg 09/19/23Report date:
164 ofPage
Inspection Checklist
Requirements: 14.0% were addressed directly in the COMcheck software
COMcheck Software Version COMcheckWeb
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2021 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR1]1
Plans and/or specifications provide all
information with which compliance
can be determined for the building
envelope and document where
exceptions to the standard are
claimed.
Complies
Does Not
Not Observable
Not Applicable
C103.2
[PR2]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical and
service water heating systems and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks. Hot water system sized
per manufacturer's sizing guide.
Complies
Does Not
Not Observable
Not Applicable
C402.4.1
[PR10]1
The vertical fenestration area <= 30
percent of the gross above-grade wall
area.
Complies
Does Not
Not Observable
Not Applicable
C402.4.1
[PR11]1
The skylight area <= 3 percent of the
gross roof area.
Complies
Does Not
Not Observable
Not Applicable
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Tagg N Go Rexburg 09/19/23Report date:
165 ofPage
Section
#
& Req.ID
Footing / Foundation Inspection Complies?Comments/Assumptions
C303.2
[FO4]2
Slab edge insulation installed per
manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
C303.2.1
[FO6]1
Exterior insulation protected against
damage, sunlight, moisture, wind,
landscaping and equipment
maintenance activities.
Complies
Does Not
Not Observable
Not Applicable
C105
[FO3]2
Installed slab-on-grade insulation type
and R-value consistent with insulation
specifications reported in plans and
COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.4
[FO7]2
Slab edge insulation depth/length.
Slab insulation extending away from
building is covered by pavement or
>= 10 inches of soil.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C403.13.2
,
C403.13.3
[FO9]3
Snow/ice melting system and freeze
protection systems have sensors and
controls configured to limit service for
pavement temperature above 50F and
outdoor temperature above 40F.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Tagg N Go Rexburg 09/19/23Report date:
166 ofPage
Section
#
& Req.ID
Framing / Rough-In Inspection Complies?Comments/Assumptions
C303.1.3
[FR12]2
Fenestration products rated in
accordance with NFRC certified and as
to performance labels or certificates
provided.
Complies
Does Not
Not Observable
Not Applicable
C402.4.3
[FR10]1
Vertical fenestration SHGC value.Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.4.3,
C402.4.3.
4
[FR8]1
Installed vertical fenestration U-factor
and SHGC consistent with label
specifications and as reported in plans
and COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.4.5
[FR14]2
U-factor of opaque swinging and
nonswinging doors associated with the
building thermal envelope meets
requirements.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.5.1.
3
[FR19]1
The building envelope contains a
continuous air barrier that is sealed in
an approved manner and material
permeability <= 0.004 dfm/ft2. Air
barrier penetrations are sealed in an
approved manner.
Complies
Does Not
Not Observable
Not Applicable
C402.5.4
[FR18]3
Factory-built fenestration and doors
are labeled as meeting air leakage
requirements.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Tagg N Go Rexburg 09/19/23Report date:
167 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.6.1,
C404.6.2
[PL3]1
Automatic time switches installed to
automatically switch off the
recirculating hot-water system or heat
trace.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.1,
C404.6.1.
1
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Tagg N Go Rexburg 09/19/23Report date:
168 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C402.2.6
[ME41]3
Thermally ineffective panel surfaces of
sensible heating panels have
insulation >= R-3.5.
Complies
Does Not
Not Observable
Not Applicable
C403.7.7
[ME58]3
Outdoor air and exhaust systems have
motorized dampers that automatically
shut when not in use and meet
maximum leakage rates. Check
gravity dampers where allowed.
Reference section language for
operational details.
Complies
Does Not
Not Observable
Not Applicable
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.8.3
[ME117]2
Fans have a fan energy index (FEI) >=
1.00. Variable volume fans will have
an FEI >= 0.95.
Complies
Does Not
Not Observable
Not Applicable
C403.8.3
[ME117]2
Fans have a fan energy index (FEI) >=
1.00. Variable volume fans will have
an FEI >= 0.95.
Complies
Does Not
Not Observable
Not Applicable
C403.8.3
[ME117]2
Fans have a fan energy index (FEI) >=
1.00. Variable volume fans will have
an FEI >= 0.95.
Complies
Does Not
Not Observable
Not Applicable
C403.8.3
[ME117]2
Fans have a fan energy index (FEI) >=
1.00. Variable volume fans will have
an FEI >= 0.95.
Complies
Does Not
Not Observable
Not Applicable
C403.8.3
[ME117]2
Fans have a fan energy index (FEI) >=
1.00. Variable volume fans will have
an FEI >= 0.95.
Complies
Does Not
Not Observable
Not Applicable
C403.8.3
[ME117]2
Fans have a fan energy index (FEI) >=
1.00. Variable volume fans will have
an FEI >= 0.95.
Complies
Does Not
Not Observable
Not Applicable
C403.8.4
[ME142]2
Motors for fans that are not less than
1/12 hp and less than 1 hp are
electronically commutated motors or
have a minimum motor efficiency of
70 percent. These motors have the
means to adjust motor speed.
Complies
Does Not
Not Observable
Not Applicable
C403.8.6
[ME143]2
Each DX cooling system > 65 kBtu
and chiller water/evaporative cooling
system with fans > 1/4 hp are
designed to vary the indoor fan airflow
as a function of load and comply with
detailed requirements of this section.
Complies
Does Not
Not Observable
Not Applicable
C403.9
[ME144]2
Large diameter fans where installed
shall be tested and labeled in
accordance with AMCA 230.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Tagg N Go Rexburg 09/19/23Report date:
169 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.3
[ME55]2
HVAC equipment efficiency verified.Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.2.2
[ME59]1
Natural or mechanical ventilation is
provided in accordance with
International Mechanical Code
Chapter 4. Mechanical ventilation has
capability to reduce outdoor air supply
to minimum per IMC Chapter 4.
Complies
Does Not
Not Observable
Not Applicable
C403.7.1
[ME59]1
Demand control ventilation provided
for spaces >500 ft2 and >15
people/1000 ft2 occupant density and
served by systems with air side
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
Complies
Does Not
Not Observable
Not Applicable
C403.7.2
[ME115]3
Enclosed parking garage ventilation
has automatic contaminant detection
and capacity to stage or modulate
fans to 50% or less of design capacity.
Complies
Does Not
Not Observable
Not Applicable
C403.7.6
[ME141]3
HVAC systems serving guestrooms in
Group R-1 buildings with > 50
guestrooms: Each guestroom is
provided with controls that
automatically manage temperature
setpoint and ventilation (see sections
C403.7.6.1 and C403.7.6.2).
Complies
Does Not
Not Observable
Not Applicable
C403.7.4
[ME57]1
Exhaust air energy recovery on
systems meeting Table C403.7.4(1)
and C403.7.4(2).
Complies
Does Not
Not Observable
Not Applicable
C403.7.5
[ME116]3
Kitchen exhaust systems comply with
replacement air and conditioned
supply air limitations, and satisfy hood
rating requirements and maximum
exhaust rate criteria.
Complies
Does Not
Not Observable
Not Applicable
C403.4.1.
4
[ME63]2
Heating for vestibules and air curtains
with integral heating include
automatic controls that shut off the
heating system when outdoor air
temperatures > 45F. Vestibule
heating and cooling systems
controlled by a thermostat in the
vestibule with heating setpoint <=
60F and cooling setpoint >= 80F.
Complies
Does Not
Not Observable
Not Applicable
C403.3.3
[ME35]1
Hot gas bypass limited to: <=240
kBtu/h – 50% >240 kBtu/h – 25%
Complies
Does Not
Not Observable
Not Applicable
C408.2.2.
1
[ME53]3
Air outlets and zone terminal devices
have means for air balancing.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Tagg N Go Rexburg 09/19/23Report date:
1610 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.11.3
,
C403.11.3
.1,
C403.11.3
.2
[ME123]3
Refrigerated display cases, walk-in
coolers or walk-in freezers served by
remote compressors and remote
condensers not located in a
condensing unit, have fan-powered
condensers that comply with Sections
C403.11.3.1 and refrigeration
compressor systems that comply with
C403.11.3.2..
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Tagg N Go Rexburg 09/19/23Report date:
1611 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.7
[EL26]2
Low-voltage dry-type distribution
electric transformers meet the
minimum efficiency requirements of
Table C405.6.
Complies
Does Not
Not Observable
Not Applicable
C405.8
[EL27]2
Electric motors meet the minimum
efficiency requirements of Tables
C405.7(1) through C405.7(4).
Efficiency verified through certification
under an approved certification
program or the equipment efficiency
ratings shall be provided by motor
manufacturer (where certification
programs do not exist).
Complies
Does Not
Not Observable
Not Applicable
C405.9.1,
C405.9.2
[EL28]2
Escalators and moving walks comply
with ASME A17.1/CSA B44 and have
automatic controls configured to
reduce speed to the minimum
permitted speed in accordance with
ASME A17.1/CSA B44 or applicable
local code when not conveying
passengers.
Complies
Does Not
Not Observable
Not Applicable
C405.10
[EL29]2
Total voltage drop across the
combination of feeders and branch
circuits <= 5%.
Complies
Does Not
Not Observable
Not Applicable
C405.1.1
[EL30]2
At least 90% of dwelling unit
permanently installed lighting shall
have lamp efficacy >= 65 lm/W or
luminaires with efficacy >= 45 lm/W
or comply with C405.2.4 or C405.3.
Complies
Does Not
Not Observable
Not Applicable
C405.11,
C405.11.1
[EL31]2
50% of 15/20 amp receptacles
installed in enclosed offices,
conference rooms, copy rooms, break
rooms, classrooms and workstations
and > 25% of branch circuit feeders
for modular furniture will have
automatic receptacle control in
accordance with C405.11.1.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Tagg N Go Rexburg 09/19/23Report date:
1612 ofPage
Section
#
& Req.ID
Insulation Inspection Complies?Comments/Assumptions
C303.1
[IN3]1
Roof insulation installed per
manufacturer’s instructions and is
labeled with R-value or insulation
certificate providing R-value and other
relevant data. Blown or poured loose-
fill insulation is installed only where
the roof slope is <=3 in 12.
Complies
Does Not
Not Observable
Not Applicable
C402.2.1
[IN20]1
Roof assembly meets minimal thermal
resistance installed between roof
framing or in a continuous fashion on
the roof assembly as stipulated in
Table C402.1.3. Requirements for
above deck insulation, minimum
thickness, suspended ceilings,
staggered joints and skylight curbs
will be met.
Complies
Does Not
Not Observable
Not Applicable
C303.2
[IN7]1
Above-grade wall insulation installed
per manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
C105
[IN6]1
Installed above-grade wall insulation
type and R-value consistent with
insulation specifications reported in
plans and COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.3
[IN8]2
Installed floor insulation type and R-
value consistent with insulation
specifications reported in plans and
COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.6
[IN18]3
Radiant panels and associated
components, designed for heat
transfer from the panel surfaces to the
occupants or indoor space are
insulated with a minimum of R-3.5.
Complies
Does Not
Not Observable
Not Applicable
C105
[IN2]1
Installed roof insulation type and R-
value consistent with insulation
specifications reported in plans and
COMcheck reports. For some ceiling
systems, verification may need to
occur during Framing Inspection.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.5.1.
1
[IN1]1
All sources of air leakage in the
building thermal envelope are sealed,
caulked, gasketed, weather stripped
or wrapped with moisture vapor-
permeable wrapping material to
minimize air leakage.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Tagg N Go Rexburg 09/19/23Report date:
1613 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C303.3,
C408.2.5.
3
[FI8]3
Furnished O&M manuals for HVAC
systems within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
C401.3
[FI58]1
A thermal envelope certificate will be
supplied and completed by an
approved third party.
Complies
Does Not
Not Observable
Not Applicable
C402.5.10
[FI26]3
Recessed luminaires in thermal
envelope to limit infiltration and be IC
rated and labeled. Seal between
interior finish and luminaire housing.
Complies
Does Not
Not Observable
Not Applicable
C402.5.11
[FI59]1
Operable openings > 40 ft2 will be
interlocked with heating and cooling
systems to setback setpoint
temperatures within 10 minutes of
opening.
Complies
Does Not
Not Observable
Not Applicable
C402.5.8
[FI37]1
Weatherseals installed on all loading
dock cargo door openings and provide
direct contact along the top and sides
of vehicles parked in the doorway.
Complies
Does Not
Not Observable
Not Applicable
C403.3.1
[FI27]3
HVAC systems and equipment
capacity does not exceed calculated
loads.
Complies
Does Not
Not Observable
Not Applicable
C403.4.1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.4.1.
2
[FI38]3
Thermostatic controls have a 5 °F
deadband.
Complies
Does Not
Not Observable
Not Applicable
C403.4.1.
3
[FI20]3
Temperature controls have setpoint
overlap restrictions.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2
[FI39]3
Each zone equipped with setback
controls using automatic time clock or
programmable control system.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
1,
C403.4.2.
2
[FI40]3
Automatic Controls: Setback to 55°F
(heat) and 85°F (cool); 7-day clock, 2-
hour occupant override, 10-hour
backup
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Tagg N Go Rexburg 09/19/23Report date:
1614 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C404.3
[FI11]3
Heat traps installed on supply and
discharge piping of non-circulating
systems.
Complies
Does Not
Not Observable
Not Applicable
C404.4
[FI25]2
All piping insulated in accordance with
section details and Table C403.12.3.
Complies
Does Not
Not Observable
Not Applicable
C404.6.1
[FI12]3
Controls are installed that limit the
operation of a recirculation pump
installed to maintain temperature of a
storage tank. System return pipe is a
dedicated return pipe or a cold water
supply pipe.
Complies
Does Not
Not Observable
Not Applicable
C406.3
[FI67]1
Reduced lighting power - this credit
specifies that the connected lighting
power is >= 10% more efficient than
2021 IECC requirements.
Complies
Does Not
Not Observable
Not Applicable
C408.1.1
[FI57]1
Building operations and maintenance
documents will be provided to the
owner. Documents will cover
manufacturers' information,
specifications, programming
procedures and means of illustrating
to owner how building, equipment and
systems are intended to be installed,
maintained, and operated.
Complies
Does Not
Not Observable
Not Applicable
C408.2.1
[FI28]1
Commissioning plan developed by
registered design professional or
approved agency.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
1
[FI31]1
HVAC equipment, systems and
system-to-system relationships have
been tested to ensure proper
operation.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
2
[FI10]1
HVAC and service water heating
control systems have been tested to
ensure proper operation, calibration
and adjustment of controls.
Complies
Does Not
Not Observable
Not Applicable
C408.2.4
[FI29]1
Preliminary commissioning report
completed and certified by registered
design professional or approved
agency.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5
[FI7]3
Furnished HVAC as-built drawings
submitted within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
1
[FI43]1
An air and/or hydronic system
balancing report is provided for HVAC
systems.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
2
[FI30]1
Final commissioning report due to
building owner within 90 days of
receipt of certificate of occupancy.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Tagg N Go Rexburg 09/19/23Report date:
1615 ofPage
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Tagg N Go Rexburg 09/19/23Report date:
1616 ofPage