Loading...
HomeMy WebLinkAboutPLANS - 23-00670 - 1493 W 5000 N - Solar panels 76 North Meadowbrook Drive Scott E. Wyssling, PE Alpine, UT 84004 Coleman D. Larsen, SE, PE office (201) 874-3483 Gregory T. Elvestad, PE swyssling@wysslingconsulting.com August 14, 2023 Aveyo 1261 S 820 E American Fork, UT 84003 Re: Engineering Services Einerson Residence 1493 West 5000 North, Rexburg ID 30.000 kW System To Whom It May Concern: Pursuant to your request, we have reviewed the following information regarding ground mount solar panel installation at the above referenced location: 1. Structural drawings prepared by IronRidge identifying specific racking layout and components for the proposed ground mount system. 2. Design drawings of the proposed system including a site plan, and details for the solar panels. This information will be utilized for approval and construction of th e proposed system. Based on our review of the Photovoltaic Array installed at 4 modules high and 5 modules wide. The PV array shall have a pier spacing of 6’9” north/south and 9’4” east/west. Based on a wind speed of 100 mph, Exposure C and ground snow load of 50 psf, it was determined that the minimum required footing depth is 48 inches below grade with a 12” diameter pier footing. The footing size based upon the worst case loading due to horizontal and vertical wind loading. Based on the above evaluation, it is the opinion of this office that with appropriate construction the footing and post assembly will adequately support the proposed solar array. This evaluation is in conformance with the 2015 IBC, current industry and standards, and based on information supplied to us at the time of this report. This certification is specific to the footing design for the solar system and does not include the racking system. Racking system and components designed and specified by the manufacturer (IronRidge). Should you have any questions regarding the above or if you require further information do not hesitate to contact me. Very truly yours, Scott E. Wyssling, PE Idaho License No. 18974 Signed 8/14/2023 1 HOUSE PHOTOPV-1 SCALE: NTS SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-1 14 9 3 W 5 0 0 0 N RE X B U R G , I D 8 3 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : ( 2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : s h o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 SHEET INDEX PV1 COVER PAGE PV2 SITE PLAN PV3 ROOF PLAN & MODULES PV4 STRING LAYOUT & BOM PV5 ATTACHMENT DETAIL PV6-PV6A ELECTRICAL LINE DIAGRAM & CALCS. PV7 SPECIFICATIONS & CALCULATION PV8-PV9 SIGNAGE PV10-PV17 EQUIPMENT SPECIFICATIONS 1 VICINITY MAPPV-1 PROJECT SITE SCALE: NTS PROJECT SITE SYSTEM RATING 9.000 KWDC 30.000 KWAC GOVERNING CODES AHJ NAME: MADISON COUNTY SCOPE OF WORK: TO INSTALL A GROUND MOUNTED SOLAR PHOTOVOLTAIC SYSTEM AT THE RESIDENCE LOCATED AT 1493 W 5000 N, REXBURG, ID 83440, USA THE POWER GENERATED BY THE PV SYSTEM WILL BE INTERCONNECTED WITH THE UTILITY GRID THROUGH THE EXISTING ELECTRICAL SERVICE EQUIPMENT. THE PV SYSTEM DOES INCLUDE STORAGE BATTERIES. PHOTOVOLTAIC SYSTEM FIRE CLASSIFICATION LISTING IN ACCORDANCE WITH UL 1703 STANDARD. COVER PAGE GENERAL NOTES: ·THESE CONSTRUCTION DOCUMENTS HAVE BEEN BASED ON FIELD INSPECTIONS AND OTHER INFORMATION AVAILABLE AT THE TIME. ACTUAL FIELD CONDITIONS MAY REQUIRE MODIFICATIONS IN CONSTRUCTION DETAILS. ·ARCHITECT HAS NOT BEEN RETAINED TO SUPERVISE ANY CONSTRUCTION OR INSTALLATION OF ANY EQUIPMENT AT SITE. ·CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL, EQUIPMENT, TOOLS, OBTAINS ALL PERMITS, LICENSES AND PAY ALL REQUIRED FEES AND COMPLETE INSTALLATION. ·CONTRACTOR HAS THE FULL RESPONSIBILITY TO CHECK AND VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS. ANY DISCREPANCIES SHALL BE REPORTED TO THE ENGINEER BEFORE PROCEEDING WITH THE WORK. ANY WORK STARTED BEFORE CONSULTATION AND ACCEPTANCE BY THE ENGINEER SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE SUBJECT TO CORRECTION BY THEM WITHOUT ADDITIONAL COMPENSATION. ·DAMAGE CAUSED TO THE EXISTING STRUCTURE, PIPES, DUCTS, WINDOWS, WALL, FLOORS, ETC. SHALL BE REPAIRED TO THE ORIGINAL CONDITION OR REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST. ·THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR THE PROPER INSTALLATION AND COMPLETION OF THE WORK WITH APPROVED MATERIALS. ·NO CHANGES ARE TO BE MADE WITHOUT THE CONSULTATION AND APPROVAL OF THE ARCHITECT. ·CONTRACTOR SHALL OBTAIN BUILDING PERMIT. NO WORK TO START UNLESS BUILDING PERMIT IS PROPERLY DISPLAYED. ·ALL WORKMANSHIP AND MATERIALS SHALL BE OF FIRST QUALITY AND IN COMPLIANCE WITH THE REQUIREMENTS OF THE ID BUILDING CODE, THE DEPARTMENT OF ENVIRONMENTAL PROTECTION AND ALL PERTINENT AGENCIES. ·IT IS ESSENTIAL THAT ALL WORK PROCEED WITH THE MAXIMUM COOPERATION OF ALL PARTIES AND WITH MINIMUM INTERFERENCE TO THE OCCUPANTS WITHIN THE BUILDING. THE OWNER'S DIRECTIONS IN THIS REGARD SHALL BE FULLY COMPLIED WITH. ·ALL EXPOSED PLUMBING, HVAC, ELECTRICAL DUCTWORK, PIPING AND CONDUITS ARE TO BE PAINTED BY GENERAL CONTRACTOR. ·THE CONTRACTOR SHALL PERFORM THE WORK IN STRICT CONFORMANCE WITH THE LOCAL LAWS, REGULATIONS AND THE NATIONAL ELECTRIC CODE. ·THE CONTRACTOR SHALL OBTAIN ALL PERMITS, APPROVALS, AFFIDAVITS, CERTIFICATIONS, ETC. AND PAY ALL FEES AS REQUIRED BY THE LOCAL AUTHORITIES. ·CONTRACTORS SHALL OBTAIN FIRE CERTIFY UPON COMPLETION OF WORK. ELECTRICAL NOTES: ·THE EQUIPMENT AND ALL ASSOCIATED WIRING AND INTERCONNECTION SHALL BE INSTALLED ONLY BY QUALIFIED PEOPLE. A QUALIFIED PERSON IS ONE WHO HAS SKILLS AND KNOWLEDGE RELATED TO THE CONSTRUCTION AND OPERATION OF THE ELECTRICAL EQUIPMENT AND INSTALLATIONS AND HAS RECEIVED SAFETY TRAINING TO RECOGNIZE AND AVOID THE HAZARDS INVOLVED. (NEC 690.4(E) AND 705.6) ·LOCAL UTILITY PROVIDER SHALL BE NOTIFIED PRIOR TO USE AND ACTIVATION OF ANY SOLAR PHOTOVOLTAIC INSTALLATION. FOR A LINE SIDE TAP CONNECTION, UTILITY NEEDS TO BE NOTIFIED WELL IN ADVANCE TO COORDINATE BUILDING ELECTRICAL SHUT OFF. ·NEW CONDUIT ROUTING SHOWN IS ESSENTIALLY SCHEMATIC. SUBCONTRACTOR SHALL LAY OUT RUNS TO SUIT FIELD CONDITIONS AND THE COORDINATION REQUIREMENTS OF OTHER TRADES. ·ARRAY WIRING SHOULD NOT BE READILY ACCESSIBLE EXCEPT TO QUALIFIED PERSONNEL. ·ALL EXTERIOR CONDUIT, FITTINGS, AND BOXES SHALL BE WATERTIGHT AND APPROVED FOR USE IN WET LOCATIONS. (NEC 314.15A). ·WIRING METHODS FOR PV SYSTEM CONDUCTORS AREN'T PERMITTED WITHIN 10 IN. OF THE ROOF DECKING OR SHEATHING EXCEPT WHERE LOCATED DIRECTLY BELOW THE ROOF SURFACE THAT'S COVERED BY PV MODULES AND ASSOCIATED EQUIPMENT WIRING ·BACK-FED BREAKER MUST BE AT THE OPPOSITE END OF BUS BAR FROM THE MAIN BREAKER OR MAIN LUG SUPPLYING CURRENT FROM THE UTILITIES. ·ALL CONDUCTORS AND WIRE TIES EXPOSED TO SUNLIGHT ARE LISTED AS UV RESISTANT. ·CONTRACTOR SHALL FOLLOW ALL ELECTRICAL EQUIPMENT LABELING REQUIREMENTS IN NEC 690 AND IFC 2012 ·MEASURE THE LINE-TO-LINE AND LINE-TO-NEUTRAL VOLTAGE OF ALL SERVICE ENTRANCE CONDUCTORS PRIOR TO INSTALLING ANY SOLAR EQUIPMENT. THE VOLTAGES FOR THE 240VAC RATED. WIRING AND CONDUIT NOTES: ·ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE APPLICATIONS ·ALL PV CABLES AND HOMERUN WIRES BE #10AWG *USE-2, PV WIRE, OR PROPRIETARY SOLAR CABLING SPECIFIED BY MFR, OR EQUIVALENT; ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS REQUIRED ·ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO [NEC 690.8 (A)(1) & (B)(1)], [NEC 240] [NEC 690.7] FOR MULTIPLE CONDUCTORS ·ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(C)] BLACK ONLY** ·EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2, 90°C RATED, WET AND UV RESISTANT, AND UL LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP EDGES ·PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90°C RATED, WET AND UV RESISTANT, RATED FOR 600V PER NEC 2008 OR 1000V PER NEC 2011 ·4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS ·ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION ·VOLTAGE DROP LIMITED TO 2% FOR DC CIRCUITS AND 1% FOR AC CIRCUITS ·AC CONDUCTORS >4AWG COLOR CODED OR MARKED: PHASE A OR L1- BLACK, PHASE B OR L2- RED, PHASE C OR L3- BLUE, NEUTRAL- WHITE/GRAY EQUIPMENT SUMMARY 20 CANADIAN SOLAR CS3W-450MS MODULES 2 SOL-ARK-15K-2P-N INVERTERS 6 HOME GRID STACK'D SERIES BATTERY 28.8 kWH 20 TIGO TS4-A-O RAPID SHUTDOWN 2015 INTERNATIONAL FIRE CODE 2015 INTERNATIONAL BUILDING CODE 2015 INTERNATIONAL RESIDENTIAL CODE 2017 NATIONAL ELECTRICAL CODE Signed 8/14/2023 BAT AC IN V UM MS P 13 0 ' - 1 0 " 103'-10" 38'-2" 22 5 ' - 8 " 14 2 ' - 7 " 205'-9" 281'-8" 518'-6" 44 8 ' - 3 " 460'-0" 12 7 6 ' - 4 " 87 4 ' - 5 " 76'-1" IN V SU B GEN BT S LC P GC P GC AC IN V UM MS P IN V SU B BT S LC P GC P GC BATGEN SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-2 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 SCALE: 1/64" = 1'-0" SITE PLAN BACKUP LOADS SOME CIRCUITS WILL BE BACKED UP.LEGEND (E) UTILITY METERUM (E) MAIN SERVICE PANELMSP (N) JUNCTION BOXJB (N) SOL-ARK-15K-2P INVERTERSINV (N) FUSED AC DISCONNECTAC - VENT, ATTIC FAN (ROOF OBSTRUCTION) CANADIAN SOLAR CS3W-450MS (E) SUB PANELBLP (N) HOME GRID BATTERYBAT (E) GENERATORGEN PROPERTY LINE PR O P E R T Y L I N E PROPERTY LINE PR O P E R T Y L I N E W 5000 N (E) DETACH (TYP.) (E) CHIMNEY (E) FENCE (E) DRIVEWAY(TYP.) TREES ARRAY #1 (20) CANADIAN SOLAR CS3W-450MS MODULES (N) GRID COMBINER PANELGC LCP (N) BY PASS TRANSFER SWITCHBTS (N) LOAD COMBINER PANEL (N) GENERATOR COMBINER PANELGCP Signed 8/14/2023 34'-11" 3'-4" 9'-4" 13 ' - 1 0 " 6' - 9 " JB JB BAT AC IN V UM MS P IN V SU B GEN BT S LC P GC P GC SCALE: 3/32" = 1'-0" ROOF PLAN & MODULES SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-3 14 9 3 W 5 0 0 0 N RE X B U R G , I D 8 3 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : ( 2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : s h o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 CANADIAN SOLAR CS3W-450MS MODULES 83 . 0 " 41.3" DESIGN SPECIFICATION RISK CATEGORY:II CONSTRUCTION:SFD ZONING:RESIDENTIAL EXPOSURE CATEGORY:C UNIT WEIGHT OF AREA:2.44 PSF MODULE TYPE, DIMENSIONS & WEIGHT NUMBER OF MODULES:20 MODULES MODULE TYPE:CANADIAN SOLAR CS3W-450MS MODULE WEIGHT:54.9 LBS MODULE DIMENSIONS:83.0" x 41.3" = 23.80 SF UNIT WEIGHT OF AREA:2.30 PSF ARRAY AREA CALC'S ARRAY # OF MODULES ARRAY AREA (Sq. Ft.) #1 20 476.00 ARRAY DESCRIPTION ARRAY ARRAY TILT AZIMUTH #1 25°180° (N) ~286' TRENCH WITH 18" DEPTH MIN. (N) PVC CONDUIT LEGEND (E) UTILITY METERUM (E) MAIN SERVICE PANELMSP (N) JUNCTION BOXJB (N) SOL-ARK-15K-2P INVERTERSINV (N) FUSED AC DISCONNECTAC - VENT, ATTIC FAN (ROOF OBSTRUCTION) - ROOF ATTACHMENT - CONDUIT CANADIAN SOLAR CS3W-450MS MODULES (N) TIGO TS4-A-O RAPID SHUTDOWN TRENCH (E) SUB PANELSUB (N) HOME GRID BATTERYBAT (E) GENERATORGEN GROUND SCREWS PIPE ROOF #1 TILT - 25° AZIM. - 180° (N) TIGO TS4-A-O RAPID SHUTDOWN (08) HELICAL AUGER (10) SMR300 RAIL, 174" (04) DIAGONAL BRACING (N) JUNCTION BOX (TYP.) ARRAY #1 (20) CANADIAN SOLAR CS3W-450MS MODULES (E)FRONT OF RESIDENCE W 5000 N (E)BACK OF RESIDENCE (N) GRID COMBINER PANELGC LCP (N) BY PASS TRANSFER SWITCHBTS (N) LOAD COMBINER PANEL (N) GENERATOR COMBINER PANELGCP WIND SPEED (ASCE 7-10): SNOW LOAD (ASCE 7-10): 100 MPH 50 PSF Signed 8/14/2023 JB JB BAT AC IN V UM MS P IN V SU B GEN BT S LC P GC P GC SCALE: 3/32" = 1'-0" SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-4 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS LinkUs Energy 3900 Atherton Dr Rocklin Ca, 95765 DATE: 06/29/2023 STRING LAYOUT & BOM - MODULE STRINGINGAB BILL OF MATERIALS EQUIPMENT QTY DESCRIPTION SOLAR PV MODULE 20 CANADIAN SOLAR CS3W-450MS MODULES INVERTER 2 SOL-ARK-15K-2P-N INVERTERS AC DISCONNECT 1 200A FUSED AC DISCONNECT, (2) 200A FUSES, 240V, NEMA 3R, UL LISTED BYPASS TRANSFER SWITCH 1 BYPASS TRANSFER SWITCH, 200A RATED, 1-PH, 3-W, 120V/240V GRID COMBINER PANEL 1 GRID COMBINER PANEL, 240V, NEMA 3R LOAD COMBINER PANEL 1 LOAD COMBINER PANEL, 240V, NEMA 3R GENERATOR COMBINER PANEL 1 GENERATOR COMBINER PANEL, 240V, NEMA 3R JUNCTION BOX 2 JUNCTION BOX 600 V, NEMA 3R, UL LISTED OPTIMIZER 20 TIGO TS4-A-O RAPID SHUTDOWN BATTERY 6 HOME GRID STACK'D BATTERY RAILS 10 SUNMODO SMR300 RAIL,174" ATTACHMENT 20 2.5" PIPE U-CLAMP KIT ATTACHMENT 4 HSS 2.375" OD FRONT PIPE ATTACHMENT 4 HSS 2.375" OD REAR PIPE ATTACHMENT 8 2.875" OD E/W PIPE BEAM, 112" ATTACHMENT 2 HSS E/W TUBE BRACE ATTACHMENT 4 HSS N/S TUBE BRACE ATTACHMENT 8 2.5" PIPE T-CAP KIT ATTACHMENT 10 2" PIPE CLAMP KIT ATTACHMENT 2 2.5" PIPE CLAMP KIT ATTACHMENT 6 2.5" PIPE SPLICE KIT GROUND PIER 8 HELICAL AUGER, 79" CLAMP 30 MID CLAMP KIT WITH SHARED RAIL ADAPTOR CLAMP 20 END CLAMP KIT GROUNDING LUG 1 GROUND LUG A-1 A-2 A-3 A-4 A-8 A-7 A-6 A-5 A-9 A-10 B-1 B-2 B-6 B-5 B-4 B-3 B-7 B-8 B-9 B-10 (E)FRONT OF RESIDENCE W 5000 N (E)BACK OF RESIDENCE HSS 2.875" O.D. STEEL PIPE (3" I.D.) NATURAL GRADE (8) 2.5" SPLICE KIT (AS NEEDED) 14'-5" R A I L L E N G T H 40" RA I L E X T E N S I O N FROM F R O N T P O S T 6" MAX. 81" BETWEEN FRONT AND BACK POSTS 12" MIN. PENETRATION 6" MAX. 12 " A P P R O X H E I G H T 22 . 5 " A P P R O X H E I G H T 6" MAX. () 2.5" ALUM. U-CLAMP KITS RAIL TO H-BEAM CONNECTION (10) 2.5" ALUM. T-CLAMP KITS PIER TO H-BEAM CONNECTION 2' - 6 " 62 " A P P R O X H E I G H T 25° NATURAL GRADE HELICAL AUGER 4' - 0 " N-S PIER SPACING 34'-11" 3'-4" 9'-4" 13 ' - 1 0 " 6' - 9 " SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-5 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 ATTACHMENT DETAIL SOIL TYPE: 4 - SANDY, CLAYEY, GRAVEL ANCHORING STRATEGY: HELICAL AUGER PIER DEPTH: 5 FEET NUMBER OF PIERS: 2 CROSS-BRACING: YES EAST\WEST SPAN: MAX: 120" EAST\WEST CANTILEVER: 40" NORTH\SOUTH SPAN: MAX. 85" NORTH\SOUTH CANTILEVER: 40" MODULE COUNT AND TYPE: (20) CANADIAN SOLAR CS3W-450MS ARRAY (1) COLUMNS: 5 ARRAY (1) ROWS: 04 OVERALL ARRAY DIMENSIONS: (L 34'11" X W 13'10") ARRAY TILT: 25° ARRAY AZIMUTH: 180°° SPECIAL CONSTRUCTION NOTES: REVIEW SUNMODO'S INSTALLATION INSTRUCTIONS BEFORE INSTALLATION. RECOMMENDED: USE MINIMUM 5HP TWO-MAN AUGER FOR DRIVING GROUND SCREWS TO FULL DEPTH. A SPECIAL ADAPTER WILL BE NEEDED TO CONNECT AUGER TO GROUND SCREWS. REVIEW DOCUMENTATION FOR ADAPTER BEFORE GOING TO JOB SITE FOR INSTALLATION. SCREWS WILL NOT BE PERFECTLY VERTICAL WHEN DRIVEN TO FULL DEPTH. AN AUGER WITH A GOOD BUBBLE LEVEL IS HIGHLY RECOMMENDED. THE VERTICAL PIPES WILL HAVE ADEQUATE TOLERANCE TO MAKE UP FOR SLIGHT ERRORS IN ALIGNMENT AND POSITION. DO NOT TIGHTEN FASTENERS ON ANCHORS TO PIERS UNTIL HORIZONTAL BEAMS ARE IN POSITION. BRACES SHOULD BE APPLIED AFTER ALL BOLTS ARE TIGHTENED ON ANCHORS TO PIERS. (30) UNIVERSAL MID-CLAMP KIT (10) SMR300 RAIL,212" (2) 2.875" O.D. HORIZONTAL PIPE BEAM Scale: 1/8"=1'-0" 4- UP - PV SYSTEM PLAN DETAILA A EAST-WEST PIER SPACING NO R T H - S O U T H P I E R S P A C I N G CANTILEVER Scale: NTS 4-UP - PV SYSTEM SIDE SECTIONB 1 ATTACHMENT DETAILS PV-5 SCALE: 1/8" = 1'-0" (20) END-CLAMP KIT Signed 8/14/2023 -+ -++ -+ +++--- 2 -+ - 1 3 = = = = = = = = = = (10) CANADIAN SOLAR CS3W-450MS MODULES STRING 1: 10 MODULES 1 3 9 10 (N) JUNCTION BOX-1 600V, NEMA 3R, UL LISTED G G(10) TIGO TS4-A-O OPTIMIZER SOL-ARK BAT DC LOAD GEN GRID (N) (6) HOMEGRID STACK’D SERIES BATTERY(28.8KWH) CAT6 COMM WIRE BASE 4.8kWh 4.8kWh4.8kWh 4.8kWh 4.8kWh 4.8kWh 4.8kWh BMS -+ -++ -+ +++--- 2 -+ - 1 3 = = = = = = = = = = (10) CANADIAN SOLAR CS3W-450MS MODULES STRING 2: 10 MODULES 2 4 9 10 (N) JUNCTION BOX-2 600V, NEMA 3R, UL LISTED G G(10) TIGO TS4-A-O OPTIMIZER SOL-ARK BAT DC LOAD GEN GRID 13 (N) AC DISCONNECT: 200A FUSED, 240V, NEMA 3R, UL LISTED N N G G EXISTING GROUND ELECTRODE CONDUCTOR BI-DIRECTIONAL UTILITY METER # 342 892 458 1-PH, 3-W, 120V/240V (CL-320W) TO UTILITY GRID TO SHOP PANEL (E) MAIN BREAKER TO SHOP, 200A/2P, 240V BACKUP LOADS (N) SOL-ARK-15K-P INVERTER (240V) OUTPUT: 240V, 62.5A 96.5% CEC EFFICIENCY NEMA 1 RATED, UL 1741 LISTED, INTERNAL GFDI WITH INTEGRATED DC DISCONNECT- #1 (N) SOL-ARK-15K-P INVERTER (240V) OUTPUT: 240V, 62.5A 96.5% CEC EFFICIENCY NEMA 1 RATED, UL 1741 LISTED, INTERNAL GFDI WITH INTEGRATED DC DISCONNECT- #2 7 7 6 L2 L1 L2 L1 (2) 200A FUSES (E) METER-MAIN COMBO SERVICE PANEL, 400A RATED 1-PH, 3-W , 240V (E) MAIN BREAKER TO HOUSE, 200A/2P, 240V 5 L1 L2 L1 L2 (N) GRID COMBINER PANEL,240V L1 L2 L1 L2 L1 L2 L1 L2 (N) LOAD COMBINER PANEL,240V L1 L2 L1 L2 (E) HOUSE SUB PANEL, 200A RATED, 1-PH, 3-W, 240V 200A/2P OFF ON ON (N) BYPASS SWITCH 200A, 240V (E) BREAKER TO HOUSE, 200A/2P, 240 V 11 9 10 12 GENERAC TO GENERATOR E L1 L2 L1 L2 (N) GENERATOR COMBINER PANEL,240V L1 L2 L1 L2 8 SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-6 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 ELECTRICAL LINE SCALE: NTS SERVICE INFO. UTILITY PROVIDER: MAIN SERVICE VOLTAGE: MAIN SERVICE PANEL: MAIN BREAKER RATING: MAIN SERVICE LOCATION: SERVICE FEED SOURCE: 240V &CALCS. UNDERGROUND PACIFICORP 400A 200A EAST SYSTEM RATING 9.000 KWDC 30.00KWAC IF ANY EXISTING LOAD CONDUCTORS ARE EXTENDED BY MORE THAN 6’, AFCI PROTECTION WILL BE PROVIDED PER NEC 210.12(B)(2). ALL TERMINAL TEMPERATURES OF EQUIPMENT WILL BE VERIFIED TO BE RATED FOR 75°C, OR THE WIRE WILL NEED TO BE RESIZED USING THE 60°C TERMINAL TEMPERATURE RATINGS FOR 100A OR LESS. A SUPPLEMENTAL GROUND ROD WILL BE DRIVEN IN ACCORDANCE WITH NEC 250.53(A)(3) IF THE EXISTING GROUND ROD HAS A RESISTANCE TO EARTH THAT IS GREATER THAN 25 OHMS. THE ESS CIRCUIT BREAKER SHALL BE SECURED IN PLACE BY AN ADDITIONAL FASTENER PER NEC 408.36(D). LABELS FOR EXISTING PV SYSTEMS WILL BE TRANSFERRED OR REPLACED ON NEW EQUIPMENT. PRODUCER’S STORAGE DEVICE(S) WILL NOT CAUSE THE HOST LOAD TO EXCEED ITS NORMAL PEAK DEMAND. NORMAL PEAK DEMAND IS DEFINED AS THE HIGHEST AMOUNT OF POWER REQUIRED FROM THE DISTRIBUTION SYSTEM BY PRODUCER’S COMPLETE FACILITIES WITHOUT THE INFLUENCE OR USE OF THE ENERGY STORAGE DEVICE(S). SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-6A 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 ELECTRICAL LINE &CALCS. ID TYPICAL INITIAL CONDUCTOR LOCATION FINAL CONDUCTOR LOCATION CONDUCTOR CONDUIT # OF PARALLEL CIRCUITS CURRENT-CARRYING CONDUCTORS IN CONDUIT CONDUIT FILL PERCENT OCPD EGC TEMP. CORR. FACTOR CONDUIT FILL FACTOR CONT. CURRENT (A) MAX. CURRENT (A) BASE AMP. (A) DERATED AMP. (A) TERM. TEMP. RATING LENGTH VOLTAGE DROP 1 1 STRING JUNCTION BOX 1 10 AWG PV WIRE COPPER Open Air 1 2 N/A N/A 6 AWG BARE COPPER 0.71 (55°C)N/A 12.0 15.00 40 N/A 75°C 40FT 0.52% 2 1 STRING JUNCTION BOX 2 10 AWG PV WIRE COPPER Open Air 1 2 N/A N/A 6 AWG BARE COPPER 0.71 (55°C)N/A 12.0 15.00 40 N/A 75°C 40FT 0.52% 3 1 JUNCTION BOX 1 INVERTER 1 6 AWG THWN-2 COPPER MIN 0.75" Dia PVC 1 2 23.79%N/A 8 AWG THWN-2, COPPER 0.96 (33°C)1 12.0 15.00 75 72.00 75°C 300FT 1.47% 4 1 JUNCTION BOX 2 INVERTER 2 6 AWG THWN-2 COPPER MIN 0.75" Dia PVC 1 2 23.79%N/A 8 AWG THWN-2, COPPER 0.96 (33°C)1 12.0 15.00 75 72.00 75°C 300FT 1.47% 5 1 BATTERY INVERTER 1&2 3/0 AWG THWN-2 COPPER MIN 2" Dia EMT 1 3 22.65%N/A N/A N/A 0.96 (33°C)1 160.0 200.00 225 216.00 75°C 30FT 0.31% 6 1 GRID COMBINER PANEL INVERTER 1&2 3/0 AWG THWN-2 COPPER MIN 2" Dia EMT 1 3 22.65%N/A 6 AWG THWN-2, COPPER 0.96 (33°C)1 160.0 200.00 225 216.00 75°C 5FT 0.05% 7 1 INVERTER 1&2 LOAD COMBINER PANEL 3/0 AWG THWN-2 COPPER MIN 2" Dia EMT 1 3 22.65%N/A 6 AWG THWN-2, COPPER 0.96 (33°C)1 160.0 200.00 225 216.00 75°C 5FT 0.05% 8 1 INVERTER 1&2 GENERATOR COMBINER PANEL 3/0 AWG THWN-2 COPPER MIN 2" Dia EMT 1 3 22.65%N/A 6 AWG THWN-2, COPPER 0.96 (33°C)1 160.0 200.00 225 216.00 75°C 5FT 0.05% 9 1 LOAD COMBINER PANEL BY PASS TRANSFER SWITCH 3/0 AWG THWN-2 COPPER MIN 2" Dia EMT 1 2 15.10%N/A N/A N/A 0.96 (33°C)1 160.0 200.00 225 216.00 75°C 5FT 0.05% 10 1 GRID COMBINER PANEL BY PASS TRANSFER SWITCH 3/0 AWG THWN-2 COPPER MIN 2" Dia EMT 1 2 15.10%N/A N/A N/A 0.96 (33°C)1 160.0 200.00 225 216.00 75°C 5FT 0.05% 11 1 BY PASS TRANSFER SWITCH SUBPANEL 3/0 AWG THWN-2 COPPER MIN 2" Dia EMT 1 3 22.65%200A 8 AWG THWN-2, COPPER 0.96 (33°C)1 160.0 200.00 225 216.00 75°C 5FT 0.05% 12 1 GRID COMBINER PANEL FUSED AC DISCONNECT 3/0 AWG THWN-2 COPPER MIN 2" Dia EMT 1 3 22.65%200A 6 AWG THWN-2, COPPER 0.96 (33°C)1 160.0 200.00 225 216.00 75°C 5FT 0.05% 13 1 FUSED AC DISCONNECT MSP 3/0 AWG THWN-2 COPPER MIN 2" Dia EMT 1 3 22.65%200A 6 AWG THWN-2, COPPER 0.96 (33°C)1 160.0 200.00 225 216.00 75°C 5FT 0.05% SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-7 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-7 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 SPECIFICATIONS PERCENT OF VALUES NUMBER OF CURRENT CARRYING CONDUCTORS IN EMT 0.80 4-6 0.70 7-9 0.50 10-20 & INVERTER SPECIFICATIONS MANUFACTURER / MODEL SOL-ARK-15K-2P-N NOMINAL AC POWER 15000 W NOMINAL OUTPUT VOLTAGE 240 V NOMINAL OUTPUT CURRENT 62.5 A CALC. SOLAR MODULE SPECIFICATIONS MANUFACTURER / MODEL CANADIAN SOLAR CS3W-450MS VMP 41.1 V IMP 10.96 A VOC 49.1 V ISC 11.6 A TEMP. COEFF. VOC -0.27%/°K PTC RATING 419.2 W MODULE DIMENSION 83.0" (L) x 41.3" (W) PANEL WATTAGE 400W AMBIENT TEMPERATURE SPECS RECORD LOW TEMP -26°C AMBIENT TEMP (HIGH TEMP 2%)(33°C) CONDUIT HEIGHT 0.5" ROOF TOP TEMP 90°C CONDUCTOR TEMPERATURE RATE 55°C MODULE TEMPERATURE COEFFICIENT OF VOC -0.27%/°K SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-8 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 SIGNAGE WARNING ELECTRIC SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION LABEL LOCATION: POINT OF INTERCONNECTION, MAIN SERVICE DISCONNECT, AC DISCONNECT, INVERTER PER CODE: NEC 690.13(B) ! WARINING PHOTOVOLTAIC POWER SOURCE LABEL LOCATION: INVERTER AT OR WITHIN 3' OF THE DC COMBINER SWITCH PER CODE: NEC 690.56(C)(3) RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM LABEL LOCATION: DC CONDUIT EVERY 10' AND ON CONDUIT BODIES WHEN EXPOSED PER CODE: NEC 690.31(G)(3) 1 2 3 ADHESIVE FASTENED SIGNS: ·ANSI Z535.4-2011 PRODUCT SAFETY SIGNS AND LABELS, PROVIDES GUIDELINES FOR SUITABLE FONT SIZES, WORDS, COLORS, SYMBOLS, AND LOCATION REQUIREMENTS FOR LABELS. NEC 110.21(B)(1) ·THE LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. NEC 110.21(B)(3) ·ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IF PROPERLY ADHERED. VINYL SIGNS SHALL BE WEATHER RESISTANT. 6 SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY SOLAR ELECTRIC PV PANELS LABEL LOCATION: AT THE LOCATION OF C-CODE (MSP, SUBPANEL, TRANSFER SWITCH) 5 WARNING THIS EQUIPEMNT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN SUPPLY OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. LABEL LOCATION: PV BREAKERS 10 PV SOLAR BREAKER DO NOT RELOCATE THIS OVERCURRENT DEVICE 9 BATTERY DISCONNECT DO NOT RELOCATE THIS OVERCURRENT DEVICE LABEL LOCATION: BATTERY BREAKERS CAUTION: STORAGE SYSTEM DISCONNECT LABEL LOCATION: AT THE LOCATION OF THE SERVICE DISCONNECTING. LABEL LOCATION: MAIN SERVICE PANEL IF MSD IS OUTSIDE PLACE IT THERE / IF MSD IS INSIDE PLACE ON THE AC DISCONNECT. 7 4 LABEL LOCATION: SUB PANEL OR BACKUP LOADS PANEL, BATTERY, INVERTER OUTPUT PANEL, MAIN SERVICE PANEL, METER/MAIN, AND PV AC DISCONNECT CAUTION-TRI POWER SOURCE FIRST SOURCE IS UTILITY ELECTRICAL GRID SECOND SOURCE IS AC BATTERY THIRD SOURCE IS PV INVERTER LABEL LOCATION: POINT OF INTERCONNECTION, PHOTOVOLTAIC SYSTEM AC DISCONNECT RATED AC OUTPUT CURRENT 125 AMPS NOMINAL OPERATING AC VOLTAGE 240 VOLTS 8 SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-9 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 PLACARD CAUTION: POWER TO THIS BUILDING IS SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN LABEL LOCATION: EACH SERVICE EQUIPMENT LOCATION AND AT THE LOCATION(S) OF THE SYSTEM DISCONNECT(S) FOR ALL ELECTRIC POWER PRODUCTION SOURCES CAPABLE OF BEING INTERCONNECTED AS PER APPLICABLE NEC BA T AC INVUMMSP INV SUB GE N (N) FUSED AC DISCONNECT (E) MAIN SERVICE PANEL (E) UTILITY METER (N) (6) HOME GRID STACK'D BATTERY (E) SUB PANEL (E) GENERATOR (N) (2) SOL-ARK 15K-P INVERTER W 5 0 0 0 N ARRAY LCPGCPGC (N) GENERATOR COMBINER PANEL (N) LOAD COMBINER PANEL (N) GRID COMBINER PANEL BTS (N) BY PASS TRANSFER SWITCH SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-10 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 ELECTRICAL PHOTO SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-11 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 EQUIPMENT SPECIFICATION SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-12 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 EQUIPMENT SPECIFICATION SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-13 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 EQUIPMENT SPECIFICATION SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-14 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 EQUIPMENT SPECIFICATION SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-15 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 EQUIPMENT SPECIFICATION SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-16 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 EQUIPMENT SPECIFICATION SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-17 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 EQUIPMENT SPECIFICATION SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-18 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 EQUIPMENT SPECIFICATION SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-18A 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 EQUIPMENT SPECIFICATION SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-18B 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 EQUIPMENT SPECIFICATION SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-18C 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 EQUIPMENT SPECIFICATION SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-18D 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 EQUIPMENT SPECIFICATION SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" PROJECT NAME & ADDRESS PV-18E 14 9 3 W 5 0 0 0 N RE X B U R G , ID 83 4 4 0 , U S A TR E V E R E I N E R S O N RE S I D E N C E PH . # : (2 0 8 ) 3 5 1 - 6 2 3 6 Em a i l : sh o v e l b a c k @ g m a i l . c o m REVDATEDESCRIPTION REVISIONS 1261 S 820 E, AMERICAN FORK, UT 84003, USA PH# : (509) 842-7178 DATE:08/09/2023 EQUIPMENT SPECIFICATION