Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
LOAD SHORT FORM - 23-00646 - 2128 W 640 S - New SFR
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-13 08:26:40 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW SF2B21Job:Load Short Form Date:Entire House Vince ByramBy: SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) Semi-tightConstruction quality7570Inside db (°F) 0Fireplaces1476Design TD (°F) H-Daily range 5050Inside humidity (%) -3162Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Lennox Make Lennox Trade LENNOX Trade LENNOX Model ML195UH070XP36B-*Cond 13ACXN030-230-** AHRI ref 4805339 Coil SK6(6,9)30++TD AHRI ref 10317778 Efficiency 95 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh66000 Sensible cooling Btuh19040 Heating output Btuh64000 Latent cooling Btuh8160 Temperature rise °F60 Total cooling Btuh27200 Actual air flow cfm1150 Actual air flow cfm907 Air flow factor cfm/Btuh0.032 Air flow factor cfm/Btuh0.057 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Room1 270 3748 2707 121 153 Room2 108 1005 508 32 29 Room3 54 82 43 3 2 Room4 168 2126 851 68 48 Room5 77 548 102 18 6 Room6 55 469 73 15 4 Room7 154 4428 483 142 27 Room8 156 2976 663 96 38 Room9 384 4237 2831 136 160 Room10 42 0 0 0 0 Room11 143 2468 1184 79 67 Room12 24 0 0 0 0 Room13 60 969 165 31 9 Room14 959 12696 6402 408 362 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-13 08:26:40 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 2 ... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW Entire House d 2654 35752 16012 1150 907 Other equip loads 4972 916 Equip. @ 0.94 RSM 15912 Latent cooling 0 TOTALS 2654 40723 15912 1150 907 2023-Sep-13 08:26:40 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW SF2B21Job:Building Analysis Date:Entire House Vince ByramBy: SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) Semi-tightConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing OtherCeilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 24.6100354.9Walls 24.91015522.8Glazing 1.247911.4Doors 5.723321.5Ceilings 14.257913.83.8Floors 17.169602.8Infiltration 00Ducts 00Piping 00Humidification 12.24972Ventilation0Adjustments 100.040723Total Cooling Walls Glazing Other Ceilings Infiltration Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 5.79640.5Walls 64.61092724.5Glazing 1.32255.4Doors 7.612890.8Ceilings 000Floors 4.16870.3Infiltration 00Ducts 5.4916Ventilation 11.31920Internal gains 00Blower 0Adjustments 100.016928Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 68 Btuh/ft²-°F Data entries checked. 2023-Sep-13 08:26:40 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW SF2B21Job:Component Constructions Date:Entire House Vince ByramBy: SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) Semi-tightConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 2240.4723324.9422.00.065472n 3050.4731714.9422.00.065642e 1970.4720534.9422.00.065416s 2380.4724784.9422.00.065502w 9640.47100354.9422.00.0652031all Partitions (none) Windows 2 glazing, clr outr, air gas, mtl no brk frm mat, clr innr, 1/4" gap, 1/8" thk: 2 glazing, clr outr, air gas, mtl no brk frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32) 79110.3175622.800.30077n 146918.6180122.800.30079s 225434.1150522.800.30066w 451420.3506222.800.300222all 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32) 25710.357022.800.30025n 225718.6276822.800.300121s 262934.1175622.800.30077w 514323.0509322.800.300223all Doors metal: Door, mtl pur core type 2255.3647911.410.50.15042n Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 12890.8423321.5250.00.0201534 Floors 21A-28c: Bg floor, heavy dry or light damp soil, 6.5' depth, carpet flr fnsh 0019841.6700.0221186 22A-cpm: Bg floor, heavy dry or light damp soil, on grade depth, carpet flr fnsh 00380789.701.18042 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-13 08:26:40 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW SF2B21Job:Project Summary Date:Entire House Vince ByramBy: SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F14Daily range H Relative humidity %50Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh35752 Structure Btuh16012 Ducts Btuh0 Ducts Btuh0Central vent (71 cfm)4972 Btuh Central vent (71 cfm)Btuh916 Outside air Outside airHumidificationBtuh0Blower Btuh0 Piping Btuh0Equipment load Btuh40723 Use manufacturer's data n Rate/swing multiplier 0.94InfiltrationEquipment sensible load Btuh15912 Method Latent Cooling Equipment Load SizingSimplified Construction quality Semi-tight0Fireplaces Structure Btuh-155 Ducts Btuh0Central vent (71 cfm)Btuh-1273 CoolingHeating Outside air26542654Area (ft²)Equipment latent load Btuh0 2123521235Volume (ft³)Air changes/hour 0.150.28 Equipment Total Load (Sen+Lat)Btuh15912 Equiv. AVF (cfm)5399 Req. total capacity at 0.70 SHR ton1.9 Heating Equipment Summary Cooling Equipment Summary Make Lennox Make LennoxTradeLENNOXTradeLENNOX Model ML195UH070XP36B-*Cond 13ACXN030-230-**AHRI ref 4805339 Coil SK6(6,9)30++TD AHRI ref 10317778Efficiency95 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh66000 Sensible cooling Btuh19040Heating output Btuh64000 Latent cooling Btuh8160 Temperature rise °F60 Total cooling Btuh27200Actual air flow cfm1150 Actual air flow cfm907 Air flow factor cfm/Btuh0.032 Air flow factor cfm/Btuh0.057Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 2023-Sep-13 08:26:40 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW SF2B21Job:AED Assessment Date:Entire House Vince ByramBy: SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) )H(34-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gl a z i n g l o a d ( B t u h ) Hour of Day 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 41.8%. House does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 1270 Btuh (PFG - 1.3*AFG) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-13 08:26:40Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW SF2B21Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Entire House Room1 2 Exposed wall 314.8 ft 33.0 ft 3 Room height 8.0 dft 8.0 heat/coolft 4 Room dimensions ft18.0x15.0 5 Room area 2654.4 f t²270.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 616 472 2332 224 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 10.2810.28 77 0 1756 791 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 10.2810.28 25 0 570 257 0 0 0 0 .DD metalmetal 0.2900.290 nn 11.4011.40 5.365.36 42 42 479 225 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 642 642 3171 305 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 616 416 2053 197 120 72 356 34 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 18.6018.60 79 0 1801 1469 48 0 1094 893 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 18.6018.60 121 0 2768 2257 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 645 502 2478 238 144 119 588 56 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 34.1434.14 66 0 1505 2254 25 0 570 854 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 34.1434.14 77 0 1756 2629 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 1534 1534 2332 1289 270 270 410 227 FF 21A-28c21A-28c 0.0220.022 --1.671.67 0.000.00 1186 1186 1984 0 0 0 0 0 FF 22A-cpm22A-cpm 1.1801.180 --89.6889.68 0.000.00 352 42 3807 0 0 0 0 0 6 c) AED excursion 1270 111 Envelope loss/gain 28791 13405 3018 2175 12 a)Infiltration 6960 687 730 72 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 4 920 2 460 Appliances/other 1000 0 Subtotal (lines 6 to 13)35752 16012 3748 2707 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 35752 16012 3748 2707 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 35752 16012 3748 2707 Air required (cfm)Air required (cfm)1150 907 121 153 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-13 08:26:40Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 2... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW SF2B21Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room2 Room3 2 Exposed wall 9.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft12.0x9.0 ft6.0x9.0 5 Room area 108.0 f t²54.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 10.2810.28 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 10.2810.28 0 0 0 0 0 0 0 0 .DD metalmetal 0.2900.290 nn 11.4011.40 5.365.36 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 72 56 277 27 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 18.6018.60 16 0 365 298 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 108 108 164 91 54 54 82 45 FF 21A-28c21A-28c 0.0220.022 --1.671.67 0.000.00 0 0 0 0 0 0 0 0 FF 22A-cpm22A-cpm 1.1801.180 --89.6889.68 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 74 -2 Envelope loss/gain 806 488 82 43 12 a)Infiltration 199 20 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1005 508 82 43 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1005 508 82 43 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1005 508 82 43 Air required (cfm)Air required (cfm)32 29 3 2 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-13 08:26:40Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 3... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW SF2B21Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room4 Room5 2 Exposed wall 26.0 ft 7.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft12.0x14.0 ft7.0x11.0 5 Room area 168.0 f t²77.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 10.2810.28 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 10.2810.28 0 0 0 0 0 0 0 0 .DD metalmetal 0.2900.290 nn 11.4011.40 5.365.36 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 96 96 474 46 56 56 277 27 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 112 97 479 46 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 18.6018.60 15 0 342 279 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 168 168 255 141 77 77 117 65 FF 21A-28c21A-28c 0.0220.022 --1.671.67 0.000.00 0 0 0 0 0 0 0 0 FF 22A-cpm22A-cpm 1.1801.180 --89.6889.68 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 53 -4 Envelope loss/gain 1551 564 394 87 12 a)Infiltration 575 57 155 15 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2126 851 548 102 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2126 851 548 102 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2126 851 548 102 Air required (cfm)Air required (cfm)68 48 18 6 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-13 08:26:40Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 4... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW SF2B21Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room6 Room7 2 Exposed wall 5.0 ft 25.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft5.0x11.0 ft14.0x11.0 5 Room area 55.0 f t²154.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 88 65 321 31 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 10.2810.28 0 0 0 0 23 0 524 236 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 10.2810.28 0 0 0 0 0 0 0 0 .DD metalmetal 0.2900.290 nn 11.4011.40 5.365.36 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 40 40 198 19 112 112 553 53 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 55 55 84 46 154 154 234 129 FF 21A-28c21A-28c 0.0220.022 --1.671.67 0.000.00 0 0 0 0 0 0 0 0 FF 22A-cpm22A-cpm 1.1801.180 --89.6889.68 0.000.00 10 1 77 0 154 25 2242 0 6 c) AED excursion -3 -21 Envelope loss/gain 359 62 3875 428 12 a)Infiltration 111 11 553 55 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)469 73 4428 483 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 469 73 4428 483 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 469 73 4428 483 Air required (cfm)Air required (cfm)15 4 142 27 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-13 08:26:40Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 5... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW SF2B21Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room8 Room9 2 Exposed wall 16.0 ft 35.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft13.0x12.0 ft384.0x1.0 5 Room area 156.0 f t²384.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 96 73 361 35 120 89 440 42 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 10.2810.28 23 0 524 236 31 0 707 319 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 10.2810.28 0 0 0 0 0 0 0 0 .DD metalmetal 0.2900.290 nn 11.4011.40 5.365.36 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 16 16 79 8 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 16 16 79 8 160 119 588 56 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 34.1434.14 0 0 0 0 41 0 935 1400 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 156 156 237 131 384 384 584 323 FF 21A-28c21A-28c 0.0220.022 --1.671.67 0.000.00 0 0 0 0 0 0 0 0 FF 22A-cpm22A-cpm 1.1801.180 --89.6889.68 0.000.00 144 15 1325 0 20 2 163 0 6 c) AED excursion -29 590 Envelope loss/gain 2605 389 3416 2730 12 a)Infiltration 354 35 774 76 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2958 653 4190 2806 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 17 9 47 25 14 Subtotal 2976 663 4237 2831 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2976 663 4237 2831 Air required (cfm)Air required (cfm)96 38 136 160 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-13 08:26:40Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 6... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW SF2B21Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room10 Room11 2 Exposed wall 0 ft 24.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.0x7.0 ft13.0x11.0 5 Room area 42.0 f t²143.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 88 63 311 30 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 10.2810.28 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 10.2810.28 0 0 0 0 25 0 570 257 .DD metalmetal 0.2900.290 nn 11.4011.40 5.365.36 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 104 87 430 41 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 34.1434.14 0 0 0 0 17 0 388 580 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 42 42 64 35 0 0 0 0 FF 21A-28c21A-28c 0.0220.022 --1.671.67 0.000.00 0 0 0 0 143 143 239 0 FF 22A-cpm22A-cpm 1.1801.180 --89.6889.68 0.000.00 24 0 0 0 0 0 0 0 6 c) AED excursion -1 223 Envelope loss/gain 64 34 1938 1131 12 a)Infiltration 0 0 531 52 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)64 34 2468 1184 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -64 -34 0 0 14 Subtotal 0 0 2468 1184 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 2468 1184 Air required (cfm)Air required (cfm)0 0 79 67 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-13 08:26:40Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 7... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW SF2B21Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room12 Room13 2 Exposed wall 6.0 ft 10.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft4.0x6.0 ft6.0x10.0 5 Room area 24.0 f t²60.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 48 48 237 23 80 59 291 28 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 10.2810.28 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 10.2810.28 0 0 0 0 0 0 0 0 .DD metalmetal 0.2900.290 nn 11.4011.40 5.365.36 0 0 0 0 21 21 239 113 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 34.1434.14 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 0 0 0 0 FF 21A-28c21A-28c 0.0220.022 --1.671.67 0.000.00 24 24 40 0 60 60 100 0 FF 22A-cpm22A-cpm 1.1801.180 --89.6889.68 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -2 -7 Envelope loss/gain 277 21 631 134 12 a)Infiltration 133 13 221 22 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)410 34 852 156 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -410 -34 117 10 14 Subtotal 0 0 969 165 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 969 165 Air required (cfm)Air required (cfm)0 0 31 9 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-13 08:26:40Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 8... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW SF2B21Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room14 2 Exposed wall 118.8 ft 3 Room height 8.0 heat/coolft 4 Room dimensions ft959.4x1.0 5 Room area 959.4 f t² Ty Construction U-value Or HTM Area (f t²)Load Area Load number (Bt uh/f t²-°F)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Frm wall, vnl ext, 3 0.065 n 4.94 0.47 96 75 370 36 .G 2 glazing, clr outr,0.300 n 22.80 10.28 0 0 0 0 .G 2 glazing, clr outr,0.300 n 22.80 10.28 0 0 0 0 .D metal 0.290 n 11.40 5.36 21 21 239 113 1 1 W Frm wall, vnl ext, 3 0.065 e 4.94 0.47 322 322 1591 153 W Frm wall, vnl ext, 3 0.065 s 4.94 0.47 312 191 942 90 G 2 glazing, clr outr,0.300 s 22.80 18.60 0 0 0 0 G 2 glazing, clr outr,0.300 s 22.80 18.60 121 0 2768 2257 W Frm wall, vnl ext, 3 0.065 w 4.94 0.47 221 161 794 76 G 2 glazing, clr outr,0.300 w 22.80 34.14 0 0 0 0 G 2 glazing, clr outr,0.300 w 22.80 34.14 60 0 1368 2049 C 16B-50ad 0.020 -1.52 0.84 66 66 101 56 F 21A-28c 0.022 -1.67 0.00 959 959 1604 0 F 22A-cpm 1.180 -89.68 0.00 0 0 0 0 6 c) AED excursion 288 Envelope loss/gain 9776 5118 12 a)Infiltration 2627 259 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 1000 Subtotal (lines 6 to 13)12403 6377 Less external load 0 0 Less transfer 0 0 Redistribution 293 25 14 Subtotal 12696 6402 15 Duct loads -0%0%0 0 Total room load 12696 6402 Air required (cfm)408 362 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Sep-13 08:26:41 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW SF2B21Job:Loads for Multiple Orientations Date:Entire House Vince ByramBy: SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) )H(34-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) House North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh)16155 13949 17026 17845 17626 15912 19749 18164 Latent Load (Btuh)0 0 0 0 0 0 0 0 Total Load (Btuh)16155 13949 17026 17845 17626 15912 19749 18164 Heating AVF (cfm)1150 1150 1150 1150 1150 1150 1150 1150 Cooling AVF (cfm)907 907 907 907 907 907 907 907 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction House faces 0 5000 10000 15000 20000 N NE E SE S SW W NW House faces SouthwestCurrent Orientation: House faces WestHighest Cooling Load: Job #: SF2B21 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Kartchner 601 West 1700 South Logan, Utah 84321 Phone: 435-755-7080 Scale: 1 : 70 Page 1 Rig ht-Su i te® Uni v ersa l 20 22 22.0.05 RSU20477 2023-Sep-13 08:27:10 ...soft Program\SF2B21 Savannah.rup N Main Room11 Room12 Room13 Room14 6" Mechanical Damper for Fresh Air 68 cfm 68 cfm 68 cfm 68 cfm 68 cfm 79 cfm 31 cfm 68 cfm 440 cfm 79 cfm 14x3.25 6 " 6 " 2-14x3.25 6 " 2-14x3.25 6 "6 "6 "6 "6 " 6 " 6 " 6 x 8 6 " 6 " 6 "7 " 6 " 6 " 6 " 6 " 16 x 8 2-14x3.25 12 x 8 3-14x3.25 14x3.25 Job #: SF2B21 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Kartchner 601 West 1700 South Logan, Utah 84321 Phone: 435-755-7080 Scale: 1 : 70 Page 2 Ri g ht-S u i te® Uni v ersa l 20 22 22.0.05 RSU20477 2023-Sep-13 08:27:10 ...soft Program\SF2B21 Savannah.rup N 2nd floor Room1 Room2 Room3 Room4 Room5 Room6 Room7 Room8 Room9 Room10 77 cfm 86 cfm 160 cfm 188 cfm 34 cfm 34 cfm 77 cfm 32 cfm 3 cfm 80 cfm 18 cfm 15 cfm 142 cfm 96 cfm 80 cfm 237 cfm 2023-Sep-13 08:26:43 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW SF2B21Job:Duct System Summary Date:Entire House Vince ByramBy: SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0.34in H2O0.34 Available static pressure in H2O0.36in H2O0.36 Supply / return available pressure 0.269 / 0.091 in H2O in H2O0.269 / 0.091 Lowest friction rate in/100ft0.079in/100ft0.079 Actual air flow cfm907cfm1150 Total effective length (TEL)ft453 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st1325.013.0ShMt0x06.00.07977601354cRoom1 st1325.013.0ShMt0x06.00.07977601354cRoom1-A st1325.013.0ShMt0x06.00.07967792468hRoom11 st1325.013.0ShMt0x06.00.079931969hRoom13 st1325.013.0ShMt0x06.00.07960682116hRoom14 st2325.013.0ShMt0x06.00.07960682116hRoom14-A st1325.013.0ShMt0x06.00.07960682116hRoom14-B st1325.013.0ShMt0x06.00.07960682116hRoom14-C 325.013.0ShMt0x06.00.07960682116hRoom14-D st1325.013.0ShMt0x06.00.07960682116hRoom14-E st1325.013.0ShMt0x06.00.07929321005hRoom2 st1325.013.0ShMt0x06.00.0792382hRoom3 325.013.0ShMt0x06.00.07924341063hRoom4-A st1325.013.0ShMt0x06.00.07924341063hRoom4-B st2325.013.0ShMt0x06.00.079618548hRoom5 st2325.013.0ShMt0x06.00.079415469hRoom6 st2325.013.0ShMt0x07.00.079271424428hRoom7 st1325.013.0ShMt0x06.00.07938962976hRoom8 st1325.013.0ShMt0x06.00.07980681416cRoom9 st1325.013.0ShMt6x85.60.07980681416cRoom9-A 2023-Sep-13 08:26:43 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 2 ... Country\Wrightsoft Program\SF2B21 Savannah.rup Calc = MJ8 House faces: SW Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 805 724 0.079 905 13.3 16x8 ShtMetl st2 Peak AVF 243 98 0.079 365 8.5 12x8 ShtMetl Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb5 0x 1600 34 115.0 0.079 253 7.3 2-3.25x14 2-10x18 SJSp rt1 rb6 0x 1880 143 115.0 0.079 298 7.7 2-3.25x14 2-10x18 SJSp rt1 rb4 0x 860 54 115.0 0.079 272 5.8 3.25x14 10x9 SJSp rt1 rb1 0x 1970 237 115.0 0.079 375 8.4 2-3.25x14 2-10x18 SJSp rt1 rb3 0x 790 67 115.0 0.079 251 5.6 3.25x14 10x9 SJSp rt1 rb2 0x 4400 372 115.0 0.079 464 10.6 3-3.25x14 3-10x27 SJSp Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 710 535 0.079 0 8.0 0x14 ShtMetl