HomeMy WebLinkAboutFault_current_calculator_2014 (1) (version 1) (2) by:John Sokolik Ver. 2014 Utility Fault Current amperes kVA = 50 E = 240 I = kVA x 1000 = trans. FLA trans. FLA = 208 Isca = trans. FLA x 100 x PF PF = 100% transformer Z Z = 5.80% Isca = ampere short-circuit current RMS symmetrical. Isca = 3,592 amperes Point to Point Method Length (distance) L = 120 2 x L x I (ASC) Isca = 3,592 N x C x E L-N # conductors per phase N = 1 C = 16,813 E L - L =240 Volt f = 0.214 C = 16,813 Multiplier E L - N =120 Volt f = 0.641 M = 1 1 + f Line to Line M = 0.824 Line to Neutral M = 0.609 Isca x M = fault current at terminals of main disconnect L- L =2,960 amperes Isca x M = fault current at terminals of main disconnect L- N =3,283 amperes Fault Current from L = 40 2 x L x I (ASC) Isca = 2,960 Phase 3,283 Neutral N x C x E L-N # conductors per phase N = 1 C = 16,813 Phase Conductor Volt Line to Line E L - L =240 Volt f = 0.059 C = 16,813 Neutral Conductor Volt Line to Neutral E L - N =120 Volt Multiplier f = 0.130 M = 1 Line to Line M = 0.945 1 + f Line to Neutral M = 0.885 2,796 amperes 2,905 amperes Branch Circuit Fault from L = 115 2 x L x I (ASC) Isca = 2,796 Phase 2,905 Neutral N x C x E L-N # conductors per phase N = 1 C = 0 Phase Conductor Volt Line to Line E L - L =240 Volt f = 0.000 C = 0 Neutral Conductor Volt Line to Neutral E L - N =120 Volt Multiplier f = 0.000 M = 1 Line to Line M = 1.000 1 + f Line to Neutral M = 1.000 2,796 amperes 2,905 amperes Isca x M = fault current at terminal of the panel L- L = Isca x M = fault current at terminal of the panel L- N = TRANFORMER TO MAIN Panel __ Single Phase Feeder 'f ' factor = Phase conductor constant Length (distance) Neutral conductor constant Calculation does not include motor contribution Fault Current at Service Equipment Volt Line to Line Neutral conductor constant Neutral Conductor Volt Line to Neutral 'f ' factor = Phase conductor constant Phase Conductor Calculation does not include motor contribution (example) FROM PANEL TO OUTLET Single Phase Branch 'f ' factor = Phase conductor constant Length (distance) Isca x M = fault current at terminal of the panel L- N = Neutral conductor constant Isca x M = fault current at terminal of the panel L- L = 6 UNIT APT 258 S 3rd WEST CORCORAN 6 UNIT Available Fault Current Calculation E jmp1jds@comcast.net =