HomeMy WebLinkAboutCORCORAN 6 UNIT wLANDSCAPE_ Stamped(2)-Reviewed-ApprovedAuthor Name Author Email Author Phone No.:
Alex Owens Alex.Owens@rexburg.org 208-372-2172
Description : Corcoran 6 Unit - ApartmentsAddress : 358 S 3rd WRecord Type : New Multi-Family ResidenceDocument Filename : CORCORAN 6 UNIT wLANDSCAPE_ Stamped(2).pdf
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report Approved
# 23-00358
Page Reference AnnotationType Author : Department Status Page Review Comments Applicant Response Comments
A-1 Free Text Alex Owens : Electrical Open 1 All electrical work must comply with 2017 NEC. Available faultcurrent calculation submitted L-N is 3283.
A-1 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector
E-1 Callout Alex Owens : Electrical Open 6 Available fault current calculation submitted L-N is 3283. Allelectrical work must comply with 2017 NEC.
E-1 Stamp Alex Owens : Electrical Open 6 Approved - Electrical Inspector
New Multi-Family Residence
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
VICINITY MAP
SCALE: N.T.S.
SUBJECT
PROPERTY
WATERC / W C / W C / W
20'
27'-1"
10'
10'
20'
20'
9'
36'-9"
28'-10"
16'24'-3"
22'1"
5'
9'
8'
S S S S S S
(N) 6 UNIT MULTIFAMILY 4/1
5/2
6/3
11
33
2
6
5
44
5
6
S. 3RD WEST
115.50'
115.50'
82.50'
82.50'
NO
PARKING
STORM
WATER SERVICE
4" SANITARY SEWER
HEATED FIRE RISER &
ALARM PANEL ROOM
TRASH ENCLOSURE
(PERVIOUS PAVERS)
SNOW STORAGE
SNOW STORAGE
(N) SOLID FENCE
CONNECT ROOF
DRAINS TO D.I.
FIRE LANE "NO
PARKING" SIGNAGE
LANDING & SIDEWALK
2% MAX SLOPE AND
CROSS SLOPE
P/L
P/L
P/L
P/L
1
A-1
1
A-16" CURB
(N) STANDARD
HYDRANT
Skyline
Honeylocust
Berberis thunbergii & Viburnum opulus 'Nanum'
60"60"60"
2
NO
PARKING
5%5%2%
2%
2%
2% MAX.
2%2%
MAX. 6" STEP
UP AT CURB
FLUSH
REVISIONS
SHEET:
SCALE:
DATE:
11
8/17/2023
PROJECT DATA:
A.P.N.RPR000P0103610
LOT SIZE .214 ACRES
OCCUPANCY R2
CONSTRUCTION TYPE VB
EXISTING RESIDENCE AREA 969 SF
EXISTING GARAGE AREA 200 SF
(N) 6 UNITS 3,480 SF
UNIT 1 575
UNIT 2 501
UNIT 3 661
UNIT 4 575
UNIT 5 501
UNIT 6 661
SCOPE OF WORK:
REMOVE (E) SINGLE DWELLING,
CONSTRUCT NEW 6 UNIT APARTMENT
BLDG.
SHEET INDEX:
A-1 SITE PLAN
A-2 FLOOR PLANS
A-3 EXTERIOR ELEVATIONS
A-4 BUILDING SECTIONS
S-001 GEN. STRUCTURAL NOTES
S-101 FND PLAN
S-102 2ND FLR FRAMING PLAN
S-103 ROOF FRAMING PLAN
S-501 FND DETAILS
S-510 FLOOR FRAMING DETAILS
S-520 ROOF FRAMING DETAILS
S-601 SCHEDULES
S-602 SCHEDULES
E-1 ELECTRICAL PLANS
SITE PLAN
SCALE: 1" = 10'
JOB NUMBER
CORCORAN 6 UNIT
358 S. 3RD WEST
REXBURG ID
A-1
REFERENCED CODES:
2018 INTERNATIONAL BUILDING CODE
2017 NATIONAL ELECTRICAL CODE
2018 MECHANICAL CODE OF IDAHO
2018 IDAHO COMMERCIAL ENERGY CODE
2018 IECC
2015 IDAHO PLUMBING CODE
2018 INTERNATIONAL FIRE CODE
2009 IDAHO ACCESSIBILITY CODE
DRAWN BY:
DAREN WARDELL
19802 VIA REDONDA RD.
SONORA CA 95370
SNOW STORAGE AREA
PAVED PARKING AREA 4.455 SF
SNOW STORAGE AREA, 493 SF
DEFERRED ITEMS:
1. FIRE SPRINKLERS, NFPA 13R.
SPRINKLERS MUST BE QUICK
RESPONSE
2. ENVELOPE COMM CHECK
1. ACCESSIBLE PATH
SCALE: 1" = 5'
All electrical work must comply with
2017 NEC. Available fault current
calculation submitted L-N is 3283.
SB388
DW
B1233L
B1233L
B18L B18L
SB32 DWB24L
B18RB18R
SB32DW B24R
SB388
DW
B1233L
B1233L
B18L B18L
SB32 DWB24L
B18RB18R
SB32DW B24R
W3024W1842R W1842R
W3042 W2842 W3042
W3024 W1842LW1842L
W3042W2842W3042
W3042BCW3042LBCW2442L
W2742L
W3024
4040LS 4040LS 4040LS 6068
4040LS
4040LS
5040LS306830686040LS
3068
6040LS
4040LS
4040LS
41168
3068
3068 3068
3068
6068
3068
3068
31168
3068
3068
5068
31168
3660
3068
UP
BB
BB
CC
CC
2222
AA
AA
DD
DD
1111
3333
22X24 UNDER
FLOOR ACCESS
DRYER VENT
W/DAMPER
DRYER VENT
W/DAMPER
MINI-SPLIT
WALL UNITMINI-SPLIT
WALL UNIT
MINI-SPLIT
WALL UNIT
MINI-SPLITWALL UNIT MINI-SPLIT
WALL UNIT
MINI-SPLIT
WALL UNIT
MINI-SPLIT
WALL UNIT
MINI-SPLIT
WALL UNIT
3'4'3'-1"4'-2"4'4'-5"
1'-6"
4'
3'-7"
2'-2"
4'
2'-5"
3'-9"6'1'-9"3'11"5"3'7"5'15'-8"12'-6"6'5'-9"
24'-3"6'-2"15'-5"24'-8"
4'-10"
4'
4'-7"
13'-5"
5'-6"
8'-7"
27'-6"
2'-11"
4'
1'-8"
8'-7"
5'-7"
9'-1"
8"
3'
7"
4'-3"
2'-4"4'2'-8"
12'-11"2'-9"9'2'-11"12'-7"6'-1"10'-1"2'-5"11'-9"
70'-6"
40"
40"
36"
CL 24"
60"
48"
60"48"
60"48"
CL
24"33"
2'2'
2'2'
BEDROOM
BATH
LIVING
KITCHEN
BEDROOM BEDROOM
CLOSET
CLOSET
BATH
LIVING
LIVING
BEDROOM
CLOSET
CLOSET
BEDROOM
BATH
KITCHEN
KITCHEN
1
A-4
1
A-4
2
A-4
2
A-4
FIRE RISER
CLOSET
22X24 UNDER
FLOOR ACCESS
22X24 UNDER
FLOOR ACCESS
SPECSEAL LCC150
FIRE STOP COLLAR
AT ABS/PVC DRAIN
PIPE PENETRATION
i/2" GYP. WALL BOARD UNDER MOISTURE
BARRIER AND SIDING AT THIS WALL
SEE A-5 FOR
TYPE B REQ.
SEE A-5 FOR
TYPE B REQ.
DRYER VENT
W/DAMPER
DN
SB39
DW
B9LB24L
B18RB18R
SB32DW B24R
B18L B18L
SB32 DWB24L
SB352132
SB362132
SB302132
B30
B30
B12L
SB39
DW
B9LB24L
B18RB18R
SB32DW B24R
B18L B18L
SB32 DWB24L
SB352132
SB362132
SB302132
B30
B30
B12L
W3024W1842R W1842R
W3042 W2842 W3042
W3024 W1842LW1842L
W3042W2842W3042
W942LBCW2442L
BCW3142
W3642
W3024
4040LS
4040LS
6040LS
6040LS306830686040LS
4040LS
4040LS
4040LS 4040LS 4040LS
2868
2668
2068
3068
2868
6068
28682868
2668
2668
6068
2668
3068
31168
5068
31168
BB
BB
CC
CC
2222
AA
AA
DD
DD
1111
3333
WH
WH
WH
DRYER VENT
W/DAMPER
DRYER VENT
W/DAMPER
MINI-SPLIT
WALL UNIT
MINI-SPLIT
WALL UNIT
MINI-SPLITWALL UNIT MINI-SPLIT
WALL UNIT MINI-SPLITWALL UNIT
MINI-SPLIT
WALL UNIT
MINI-SPLIT
WALL UNIT
MINI-SPLITWALL UNIT
22X30
ATTIC
ACCESS
22X30
ATTIC
ACCESS
22X30
ATTIC
ACCESS
5 1/2 X 12 BEAM
6X6 POST6X6 POST6X6 POST
6X6 POST6X6 POST
2'-2"
4'
2'-5"
2'-9"4'2'-10"4'-2"4'5'-5"
1'-10"
4'
3'-7"
12'-6"6'5'-9"9'-11"6'1'-9"3'11"5"3'21'-3"
24'-3"21'-7"24'-8"
2'-11"
4'
1'-4"
8'-3"
5'-7"
9'-5"
10"
3'
5"
4'-3"
2'-7"4'2'-8"
12'-8"2'-9"9'-3"2'-11"13'-7"5'-7"9'-7"2'-5"11'-9"
70'-6"
4'-10"
4'
4'-4"
13'-2"
5'-9"
8'-7"
27'-6"
CLOSET
CLOSET
KITCHEN
LIVING
BEDROOM
BEDROOM
BEDROOM BEDROOM
BEDROOM
LIVING
LIVING
BATH
BATH
BATH
KITCHEN
KITCHEN
CLOSET FR
DRYER VENT
W/DAMPER
ATTIC DRAFT STOP
(SEE 4/A-2)
i/2" GYP. WALL BOARD UNDER MOISTURE
BARRIER AND SIDING AT THIS WALL
SPECSEAL LCC150
FIRE STOP COLLAR
AT ABS/PVC DRAIN
PIPE PENETRATION
1
A-4
1
A-4
TYP.
BALCONY
BA-PFI-22-30 OR =
1 HR RATED SELF
CLOSING AND
LATCHING ATTIC
ACCESS. TYP.
5/8 TYPE X GYP.
BD. @ CEILING
1/2" GYP. BD. CONTINUOUS FROM
DBL. PLT. OF UNIT SEPARATION
WALLS TO UNDERSIDE OF ROOF
SHEATHING. ATTACH
w/ 1 1/4" TYPE W SCREWS 12" O.C.
VERTICAL 2X MEMBER
BY TRUSS MFG.
ANNULAR SPACES
FILLED WITH APPROVED
FIRE SEALANT
REVISIONS
SHEET:
SCALE:
DATE:
11
8/17/2023
JOB NUMBER
CORCORAN 6 UNIT
358 S. 3RD WEST
REXBURG ID
A-2
1st FLOOR PLAN
SCALE: 1/4" = 1'
2nd FLOOR PLAN
SCALE: 1/4" = 1'
DRAWN BY:
DAREN WARDELL
19802 VIA REDONDA RD.
SONORA CA 95370
1-HR ASSEMBLIES
4. ATTIC DRAFT STOP
2211 33221133
22 1133
25'
17'-7"
22 1133
42" MIN.
34"-38"
4" SPHERE WILL
NOT PASS TROUGH
6" SPHERE WILL
NOT PASS TROUGH
GRASPABLE
RAILING, 1 1//4" - 2"ø
OR 4" MIN. - MAX. 6
PERIMETER DIM.
REVISIONS
SHEET:
SCALE:
DATE:
11
8/17/2023
JOB NUMBER
CORCORAN 6 UNIT
358 S. 3RD WEST
REXBURG ID
A-3
DRAWN BY:
DAREN WARDELL
19802 VIA REDONDA RD.
SONORA CA 95370
EXTERIOR ELEVATIONS
SCALE: 1/4" = 1'
APPROVED CORROSION-RESISTANT FLASHINGS SHALL BE
INSTALLED AT ALL OF THE FOLLOWING LOCATIONS:
1.EXTERIOR DOOR AN WINDOW OPENINGS
2.AT THE INTERSECTION OF CHIMNEY OR OTHER MASONRY
CONSTRUCTION WITH FRAME OR STUCCO WALLS, WITH
PROJECTING LIPS ON BOTH SIDES UNDER STUCCO COPINGS
3.UNDER AND AT THE ENDS OF MASONRY, WOOD OR METAL
COPINGS AND SILLS
4.CONTINUOUSLY ABOVE ALL PROJECTING WOOD TRIMS
5.WHERE EXTERIOR PORCHES,DECKS OR STAIRS ATTACH TO A
WALL OR FLOOR ASSEMBLY OF WOOD-FRAMED CONSTRUCTION
6.AT ALL WALL AND ROOF INTERSECTIONS
VINYL SIDING o/WSP
COMPOSITION ROOF SHINGLES
NORTH
SOUTHEAST
WEST
STAIR NOTES:
1.GUARD RAIL HEIGHT MIN 42"
2.HAND RAIL TO BE CONTINUOUS AND TERMINATE AT WALL, POST OR TURNOUT W/
HEIGHT OF 34" - 38" ABOVE LINE OF STAIRS
3.LESS THAN 4" SPACE BETWEEN RAILING COMPONENTS, 6" ALLOWED BETWEEN
TREAD/RISER INTERSECTION AND BOTTOM OF GUARD RAIL
4.GRASPABLE RAILING 1 1/4" - 2" DIAMETER
5.CLOSED RISER W/ 7" MAX. RISE
6.MIN. 11" TREAD DEPTH W/ MIN.
7.ALL WEATHER LANDING, FULL WIDTH OF STAIR, EXTEND 36" IN DIRECTION OF
TRAVEL
8.HANDRAILS AND GUARDS SHALL BE DESIGNED TO RESIST A LINEAR LOAD OF 50
POUNDS PER LINEAR FOOT (1607.8.1) AND CONCENTRATED LOADS OF 200 POUNDS
(167.8.1.1)
6
12
SELF-ADHERING POLYMER MODIFIED
BITUMEN ICE BARRIER, EXTEND
24"INSIDE THE EXTERIOR WALL (TYP.)
22
22
11
11
33
33
22
22
11
11
33
33
I JOIST
SUBFLOOR
5/8 TYPE X GWB
5/8 TYPE X GWB
2X6 PLT
PSL RIM BD
RESILIENT CHANNEL1/2" GWB
24" MIN.
5/8 TYPE X GYP. BD.
BEHIND INTERSECTING
WALL AT RATED WALLS
LISTED 1 HR WALL
ELEC. BOX
LISTED 1 HR FIRE-
STOP COLLAR
NON METALLIC
DWV PIPING
DOMESTIC
WATER PIPING
COPPER PIPE
FILL ANNULAR SPACE
w/INTUMESCENT FIRE
CAULKING TYP.
1 HR WALL
GA WP 3371 LISTED 1 HR CEILING
ELEC. BOX
6 : 12
6 : 12
WH
WH
WH
DRYER VENTW/DAMPER
DRYER VENT
W/DAMPER
MINI-SPLITWALL UNIT MINI-SPLITWALL UNIT
MINI-SPLIT
WALL UNIT MINI-SPLITWALL UNIT MINI-SPLITWALL UNIT
MINI-SPLITWALL UNIT
MINI-SPLITWALL UNIT
MINI-SPLITWALL UNIT
22X30
ATTIC
ACCESS
22X30
ATTIC
ACCESS
22X30
ATTIC
ACCESS
ATTIC AREA A
670SF
ATTIC AREA B
598SFATTIC AREA C
674SF
V V V V V V V V V
V V V V V V V V V
REVISIONS
SHEET:
SCALE:
DATE:
11
8/17/2023
JOB NUMBER
CORCORAN 6 UNIT
358 S. 3RD WEST
REXBURG ID
A-4
DRAWN BY:
DAREN WARDELL
19802 VIA REDONDA RD.
SONORA CA 95370
SECTION 2
SCALE: 1/4" = 1'
SECTION 1
SCALE: 1/4" = 1'
1. RATED WALL PENETRATION DETAILS
SCALE: 1" = 1'
2. CEILING PENETRATION DETAIL
SCALE: 1" = 1'
3. FLOOR/CEILING DETAIL
SCALE: 1" = 1'
ATTIC VENTILATION
SCALE: 3/16" = 1'
TABULATION
ATTIC AREA A 670 SF
TOTAL VENTILATION 670/150 = 4.47SF
PROVIDE:
(4) 100 SQIN EYEBROW VENTS 2.78SF
(6) 3.5"X22.5" EAVE VENTS 2.24SF
ATTIC AREA B 598 SF
TOTAL VENTILATION 598/150 = 3.99SF
PROVIDE:
(3) 100 SQIN EYEBROW VENTS 2.08SF
(6) 3.5"X22.5" EAVE VENTS 2.24SF
ATTIC AREA C 674 SF
TOTAL VENTILATION 674/150 = 4.49SF
PROVIDE:
(4) 100 SQIN EYEBROW VENTS 2.78SF
(6) 3.5"X22.5" EAVE VENTS 2.24SF
ALL VENTS TO BE COVERED
WITH 1/4" METALLIC SCREENING
REVISIONS
SHEET:
SCALE:
DATE:
11
8/17/2023
JOB NUMBER
CORCORAN 6 UNIT
358 S. 3RD WEST
REXBURG ID
A-5
DRAWN BY:
DAREN WARDELL
19802 VIA REDONDA RD.
SONORA CA 95370
R
CO
SD
DM
VS
120V RECEPTACLE
LIGHT SWITCH
VACANCY SENSOR
DIMMER
RECESSED LED ICAT FIXTURE
SURFACE MOUNTED LIGHT FIXTURE
WALL MOUNTED LIGHT FIXTURE
FAN W/ HUMIDISTAT CONTROL
FAN-LIGHT W/ HUMIDISTAT CONTROL
SMOKE ALARM 110v w/BATTERY BACKUP
C0 ALARM 110v w/BATTERY BACKUP
SURFACE MOUNTED LED "SHOP" LIGHT
CEILING FAN
UP
UNDER
FLOOR
WH
UNDER
FLOOR
WH
UNDER
FLOOR
WH
22X24 UNDER
FLOOR ACCESS
DRYER VENT
W/DAMPER
DRYER VENTW/DAMPER
MINI-SPLITWALL UNITMINI-SPLITWALL UNIT
MINI-SPLITWALL UNIT
MINI-SPLIT
WALL UNIT MINI-SPLITWALL UNIT
MINI-SPLIT
WALL UNIT
MINI-SPLIT
WALL UNIT
MINI-SPLIT
WALL UNIT
R
R
GFCI
GFCI
GFCIGFCIGFCI
GFCI GFCI GFCI
GFCIGFCI
GFCI
GFCI
GFCI GFCI GFCI
GFCIGFCI GFCI
GFCI
SD
SD
SD
SD
SD
SD
SD
SD
3
3
3
3
3
3
EP
EP
EP
BEDROOM
BATH
LIVING
KITCHEN
BEDROOM
BEDROOM
CLOSET
CLOSET
BATH
LIVING
LIVING
BEDROOM
CLOSET
CLOSET
BEDROOM
BATH
KITCHEN
KITCHEN
FIRE RISER
(6) 100
AMP METER
ELEC MAIN
FIRE ALARM
PANEL
HOUSE
PANEL
CLOSET
ELECTRIC
HEATER
100 AMP
SUB-PANEL
100 AMP
SUB-PANEL
100 AMP
SUB-PANEL
DN
WH
WH
WH
WH
WH
WH
DRYER VENT
W/DAMPER
DRYER VENT
W/DAMPER
MINI-SPLITWALL UNIT MINI-SPLITWALL UNIT
MINI-SPLIT
WALL UNIT MINI-SPLITWALL UNIT MINI-SPLIT
WALL UNIT
MINI-SPLIT
WALL UNIT
MINI-SPLITWALL UNIT
MINI-SPLIT
WALL UNIT
22X30
ATTIC
ACCESS
22X30
ATTIC
ACCESS
22X30
ATTIC
ACCESS
3
3
3
3
3
SD
SD
SD
SD
SD
SD
SD
SD
GFCI
GFCIGFCIGFCI
GFCIGFCIGFCI
GFCI
GFCI
GFCIGFCI
GFCIGFCIGFCI
GFCI GFCI GFCI
GFCI
GFCI
R
R
R R R
EP
EP
EP
3
CLOSET
CLOSET
KITCHEN
LIVING
BEDROOM
BEDROOM
BEDROOM BEDROOM
BEDROOM
LIVING
LIVING
BATH
BATH
BATH
KITCHEN
KITCHEN
CLOSET
FR
BALCONY
100 AMP
SUB-PANEL
100 AMP
SUB-PANEL
100 AMP
SUB-PANEL
REVISIONS
SHEET:
SCALE:
DATE:
11
8/17/2023
1ST FLOOR ELECTRICAL PLAN
SCALE: 1/4" = 1'
Electrical notesElectrical notes
a.A grounding electrode shall be provided per [NEC Article 250-50].
b.Provide two or more 20-amp small-appliance circuits to serve all countertop, wall and floor
receptacles in the kitchen, pantry, breakfast room, dining room, or similar areas. Receptacle
outlets shall be installed at each wall, island and peninsular counter space in kitchens and dining
rooms per the requirements found in [NEC Article 210.52 (B) and (C)]. Such circuits shall have
no other outlets.
c.At least one 20-ampere branch circuit shall be dedicated to supply bathroom receptacles. At
least one receptacle is required within 3-ft of each basin. [NEC Articles 210.11(C)(3)] [NEC
210.52(D)]
d.Where the 20-ampere circuit supplies a single bathroom, outlets for other equipment within the
same bathroom shall be permitted to be supplied in accordance with [NEC Article 210.23(A)(1)
and (A)(2)].
e.At least one additional 20-ampere branch circuit shall be dedicated to supply laundry receptacle
outlet(s) required by [NEC Articles 210-11(C)(2) & 210-52(F)]. This circuit shall have no other
outlets.
f.Receptacle outlets shall be installed so that no point along the floor line in any wall space is more
than 6-ft measured horizontally from an outlet in that space. Receptacle outlets are required in
walls 2-ft or greater. Hallways of 10-ft or more in length shall have at least one receptacle
outlet. [NEC Art. 210.52(A) and (H)]
g.Tamper-Resistant Receptacles in Dwelling Units. In all areas specified in 210.52, all 125 volt, 15
and 20 ampere receptacles shall be listed as tamper-resistant receptacles. [NEC 406.12]
h.Light fixtures that weight more than 6lbs or exceed 16-in in any dimension shall not be
supported by the screw shell of a lamp holder. [NEC Art. 410.30(A)]
i.Outlet boxes or outlet box systems used as the sole support of a ceiling-suspended (paddle) fan
shall be listed and marked by the manufacturer as suitable for this purpose. The required
marking shall include the maximum weight to be supported for ceiling fans that weigh more than
35-lbs. [NEC Art. 314.27(D), 422.18]
j.An accessible 125-volt, single phase, 15 or 20 amp rated receptacle outlet shall be installed on
the same level and within 25-ft of heating and air conditioning equipment. This service receptacle
shall not be connected to the load side of the equipment disconnecting means. [NEC Art.
210.63]
k.Receptacles within bathtub or shower space are prohibited, even if enclosed. [NEC Art.
406.9(C)]
l.Cord-connected lighting fixtures, lighting tracks or ceiling-suspended (paddle) fans within 3-ft of
horizontal edge and 8-ft vertical above top of tub/shower dam are prohibited. [NEC Art.
410.10(D)]
JOB NUMBER
CORCORAN 6 UNIT
358 S. 3RD WEST
REXBURG ID
E-1
DRAWN BY:
DAREN WARDELL
19802 VIA REDONDA RD.
SONORA CA 95370
2ND FLOOR ELECTRICAL PLAN
SCALE: 1/4" = 1'Available fault current calculation
submitted L-N is 3283. All electrical
work must comply with 2017 NEC.