Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
C1-Model Free text Alex Owens : Electrical Open 1 No electrical plans submitted. Please submit plans including
the following: wiring method, service size, available fault
current calculation, and grounding method for service.
C1-Model Free text Alex Owens : Electrical Open 1 All work to meet 2017 NEC requirements.
# 22-00502
New Commercial Building
Please digitally re-submit all pages of the plan set in response to requested revisions
for our next review cycle, with noted items resolved.
Report Date: 07.18.2022
Approval of plans does not constitute approval of variance from code
Page 1 of 1
Powered by TCPDF (www.tcpdf.org)
liability.
Gauge:
Gauge:
Gauge:
Gauge:Shadow Gutter:
Shadow Rake:
Corner:
Accessory:
SMP Black
TRIM COLOR
26
26
26
26
Gauge:Downspouts:26
Gauge:Base:26
Gauge:Wainscot Trim:26
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
SMP Black
SMP Black
SMP Black
SMP Black
SMP Black
SMP Old Town Gray
DATE DESCRIPTION
06.09.22 C1 - Cover Sheet
F1 - Anchor Bolt Plan
F2 - Anchor Bolt Reactions
DRAWING INDEX
E1 - Roof Framing Plan
E3 - Elevation Framing
D1 - Standard Details
D2 - Standard Details
P1 - Rigid Frame Elevation
06.09.22
06.09.22
06.11.22
06.11.22
06.11.22
06.11.22
06.11.22
06.11.22
P2 - Rigid Frame Elevation06.11.22
W1 - Portal Frame Elevation06.11.22
P3 - Rigid Frame Elevation06.11.22
P4 - Rigid Frame Elevation06.11.22
F3 - Anchor Bolt Reactions06.09.22
E2 - Roof Sheeting Plan06.11.22
E4 - Elevation Framing06.11.22
E5 - Elevation Framing06.11.22
E6 - Elevation Framing06.11.22
E7 - Wall Liner Panel
06.11.22 E8 - Crane Framing Plan
06.11.22 E9 - Buildings Sections
06/14/2022
Fred
Radfar
Digitally signed
by Fred Radfar
Date: 2022.06.14
12:40:10 -05'00'
No electrical plans submitted.
Please submit plans including
the following: wiring method,
service size, available fault
current calculation, and
grounding method for service.
All work to meet
2017 NEC
requirements.
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
BUILDING "A"BUILDING "B"
DETAIL @ SHEAR WASHERS
SECTION "X"SECTION "Y"
@ONLY FOR BLDG. "A"
TYPICAL AT BASE DETAIL
~
06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
BUILDING "A"
06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
BUILDING "B"
06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
DETAIL @ RIDGE CAPDETAIL @ PANEL END
BUILDING "A"
BUILDING "A"
DETAIL @ FLANGE BRACE ATTACHMENT
DETAIL @ SHEAR WASHERS
@ONLY FOR BLDG. "A"
06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
DETAIL @ RIDGE CAPDETAIL @ PANEL END
BUILDING "A"
DETAIL @ FLANGE BRACE ATTACHMENT
DETAIL @ SHEAR WASHERS
@ONLY FOR BLDG. "A"
06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
DETAIL @ RIDGE CAPDETAIL @ PANEL END
BUILDING "B"
DETAIL @ FLANGE BRACE ATTACHMENT
06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
DETAIL @ RIDGE CAPDETAIL @ PANEL END
DETAIL @ FLANGE BRACE ATTACHMENT
BUILDING "B"
06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
X X
06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
BUILDING "A"BUILDING "B"
06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
BUILDING "A"
BUILDING "B"
BUILDING "A"
BUILDING "B"
Detail at Rake Angle
SECTION "X"
DETAIL AT CORNER TRIM
06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
BUILDING "B"
Detail at Rake Angle
BUILDING "B"
WALL DIAPHRAGM DETAIL
(typical connection at each end)
SECTION "Z"
DETAILS AT FRAMED OPENINGS FOR OVERHEAD DOOR
DETAIL AT CORNER TRIM
06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
DETAILS AT FRAMED OPENINGS FOR OVERHEAD DOOR
BUILDING "A"BUILDING "B"
BUILDING "A"BUILDING "B"
(girt to eave strut connection)
DETAIL AT CORNER TRIM
06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
DETAILS AT FRAMED OPENINGS FOR OVERHEAD DOOR
BUILDING "B"
BUILDING "A"
(girt to eave strut connection)
DETAIL AT CORNER TRIM
06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
Liner Detail
06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
SECTION "AA"
ERECTOR NOTE:
Bolts for crane systems should be installed with the bolt above and the nut below the connected parts.
OWNER/ERECTOR NOTE:
Due to the dynamic nature of a crane system, bolts will tend to loosen over time. As a part of periodic
maintenance all of the bolts for the crane runway system should be checked for tightness.
CRANE DATA
06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
06/14/2022
=EE LAP AT LONG AND S+ORT FLANGES
X
LF
SF
Lap
SF
LF
SECTION "X"
LF
SFSF
LF
LF Long Flange
SF Short Flange
LAP LA<OUT
SF
LF
SF
LF
=ee typ.
Top flange typ.Rotate each ]ee as reTuired
to alternate between the
long and short flanges.
TRAPEZE HANGER ~ 4" MAX. PIPE HANGER ~ 2-1/2" MAX. PIPE
ACCEPTABLE CONNECTION METHODS
Flange C-Clamp is not
an acceptable connection
NOTE:
Whirlwind only provides the
roof purlin. All other material
and hardware is by others.
COLLATERAL LOADS FOR HANGER ATTACHMENT
flange is not acceptable
Connection through the
not an acceptable connection
Caddy clip attached to lip is
ACCEPTABLE CONNECTIONS FOR ALL
CAUTION:
Erector Note!
Failure to tuck facing of insulation
back from panel edge at the base
and eave could result in irreparable
panel damage and will void the
panel warranty.
STANDARD DETAIL @ BLANKET INSULATION
BUILT-UP SECTION LEGEND
W20851
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.06/14/2022
The Engineer whose seal and signature appear on these documents represent Whirlwind SteelBuildings, Inc., and is not the Engineer of Record for the overall project. The Engineer'sresponsibility is limited to material designed and manufactured by Whirlwind Steel Buildings, Inc.,and excludes parts such as doors, windows, foundation design, and erection of the building.
DRAWING STATUS
FOR APPROVAL:
These drawings, being for approval, are by definition not final and are
for conceptual representation only. Their purpose is to confirm the
FOR CONSTRUCTION PERMIT:
These drawings, being for permit, are by definition not final.
Only drawings issued "For Erector Installation" can be considered complete.
FOR ERECTOR INSTALLATION:
Final drawings for construction.
proper interpretation of the project documents. Only drawings issued
"For Erector Installation" can be considered complete.
06/14/2022