HomeMy WebLinkAboutFS - 23-204 FP3 - 22-00795 - Madison Station Apartments(ATTIC DRAFT STOP) —\
NON COMBUSTIBLE
NO SPRINKLER Pf
2 LAYERS 5/8" TYPE Y GYP
Fl\
I" CPVC BRANCH LINE
' it
EXTERIOR WALL BATT
INSULATION. r-21
1RE5IDENAL R3516 4.9k 115°
SEMI RECESS 66F ITYPJ
— — 's IIIII 11II �JI
R5134 5.6k 200° 11
DRY NSW ITYPJ I " CPVC BRANCH LINE(TYP)
a o
FOIL SCRIM KRAFT (FSK) BATT INSULATION ABOVE SU
CY2. CEILING SYSTEMS IN ATTIC SPACE. r-50 /
ABOVE CEILING
'ION REQUIRED
CEILING (1 HOUR RATED)
� • s
RESIDENAL R3516 4.11115*
SEMI RECESS SSP (TYPJ
DRAFT STOP)
NON COMUSTIBLEABOVE
NO SPRINKLER PROTECTION REQUIRED
BID. • I
gal-
.................. ' :: — -09
iRA1664 5bk 200°
_ DH 56 DRY EC NSW
1 " CPVC BRANCH LINE(TYP.)
��� ss rsrrss
WALKWAYS ARE OF NON COMBUSTIBLE ATERI/
AV Ik NO SPRINKLER PROTECTION REQUIRED (TYPJ
�' CPVC BRANCH LINE(TYP.)
C II
CEILINGS A7 9'-O" ABOVE FINISHED
FLOOR FIRE SPRINKLER PIPE AT 9'-6"
ABOVE FINISHED FLOOR
< 7[D Ej]
�Cf I
iRESIDENAL R3516 4.9k 116"
SEMI RECESS 55P (TYP)
iR5134 5bk 200°
DRY NSW (TYP.)
�20'-6ll elev
F.F. 3RD FLOOR
I mr
iRESIDENAL R3516 4.9k 115' EXTERIOR WALL BATT
SEMI RECESS 55P (TYP.) INSULATION. r-21
OIL 10'-3.,
F.F. 2ND FLOOR
I" CPVC BRANCH LINE(TYP.)
o a
F.F. 1ST FLOOR
—4'-0" elev
T.O.FOOTING
INSULATION -TENT OVER PIPE WITH BATT INSULATION TO
AVOID FILLING IN BETWEEN PIPE AND CEILING.
COLD AREA
STRUCTUR
SPRINKLER PIPING TO STAY 64TT INSULATION MIN R38
AS CLOSE TO TRUSS HEATED AREA
BOTTOM CHORDS AS POSSIBLE
TENT INSULATION DETAIL
SCALE: NTS
I
CPVC DOUBLE R45TENER STRAP TYPE HANGER
NOT TO SCALE
HARDENED HEX HEAD SELF THREADING SCREW
IS FURNISHED WITH THE HANGER AND IS THE
MINIMUM FASTENER SIZE ACCEPTABLE
0 0
I
CPVC OFFSET NO BLOCK TYPE HANGER
NOT TO SCALE
LISTED RESTRAINT FOR 3/4" TO 2"
CPVC FOR VERTICAL OR HORIZONTAL
INSTALLATION
0 0
I
CFvG DOUBLE FASTENER STRAP TYPE HANGER
NOT TO SCALE
HARDENED HEX HEAD SELF THREADING SCREW
IS FURNISHED WITH THE HANGER AND IS THE
MINIMUM FASTENER SIZE ACCEPTABLE
** HANGER TICKS AND EARTHQUAKE BRACING SYMBOLS ARE SHOWN
AS GRAPHIC REPRESENTAION ONLY. ACTUAL LOCATIONS MAY VARY
PER FIELD CONDITIONS. ALL HANGERS AND EARTHQUAKE BRACING
IN ACCORDANCE WITH NFPA 13 11.4.2, TABLE 11.4.2.1 FOR HANGERS AND
NFPA 13 18.5 AND HYDRAULIC CALULATIONS FOR EARTHQUAKE BRACING
FULLY -REACTED, FINISHED SPRAY POLYURETHANE FOAM (SPF) IS
COMPATIBLE WITH CPVC AND FIRE-PEX SYSTEMS. CURRENT AND PROPER
INSTALLATION PRACTICES MUST BE ADHERED TO IN ORDER TO ENSURE
THERE IS NO COMPROMISE TO THE CPVC/FIRE-PEX SYSTEM DURING THE
APPLICATION OF SPF.
PHOENIX FIRE WILL NOT BE RESPONSIBLE FOR ANY SYSTEM DAMAGED,
COMPROMISED OR AFFECTED BY IMPROPER INSTALLATION TECHNIQUES,
INSTALLATION EQUIPMENT MALFUNCTIONS, OR SPF CONTRACTOR
NEGLIGENCE.
I-IANGZR SP,4C/NG CHART
TABLE 4-5.2.2.1 MAXIMUM DISTANCE BETWEEN HANGERS (FT -IN.)
NOMINAL PIPE
SIZE (IN)
34
1
11 4
11 2
2
21 2
3
4
6
STEEL PIPE
N/A
12-0
12-0
15-0
15-0
15-0
15-0
15-0
15-0
THREADEAA D
LIGCPVC
N/A
12-0
12-0
12-0
12-0
12-0
12-0
N/A
N/A
5-6
6-0
6-6
7-0
8-0
9-0
10-0
N/A
N/A
PEX
2-8
2-8
4-0
4-0
4-0
N/A
N/A
N/A
N/A
FOR STEEL PIPE, THE MAXIMUM LENGTH FOR UNSUPPORTED
ARMOVER
SHALL BE 2'0"(CPVC 1'0").
WHEN PRESSURE EXCEEDS
100 PSI, UNSUPPORTED LENGTH SHALL BE
1'0"(CPVC 0'9").
FIGURE A-4-5.2.3.3
DISTANCE FROM SPRINKLER TO HANGER
36"
FOR 1"
48"
60"
FOR 11/4" MAX.
FOR 11 /2" OR LARGE
THEN EXTEND
HERE \
GREATER THAN 36" FOR
1"
GREATER THAN 48:: FOR
GREATER THAN 60 FOR
11�2" OR LARGE;!��
TABLE 2-6.4.1 HANGER ROD SIZE
PIPE SIZE
DIAM. OF ROD
PIPE SIZE
DIAM. OF ROD
UP TO AND
3/8"
6 AND 8
1/2"
INCLUDING 4"
NOTE:
TYPICAL HANGER TICK MARKS AS SHOWN ON PIPING PLAN MAY NOT
REFLECT ACTUAL FIELD INSTALLATION. FINAL H,4NGER INSTALLATION
SHALL BE IN ACCORDANCE UJITH THE REQUIREMENTS OF NFP,4 13 11.2.2
TABLE 1-1.4.2.1(a)
AS PER NFPA 13R TABLE 6.2.3.3.3 MINIMUM DISTANCE
FOR SPRINKLERS ARE AS FOLLOWS:
FROM EDGE OF
FROM EDGE OF
SOURCE TO
SOURCE TO
HEAT SOURCE
ORDINARY TEMP.
INTERMEDIATE
SPRINKLER
TEMP. SPRINKLER
* SIDE OF FIREPLACE --------------------
36"
-------------------- 12'1
* FRONT OF FIREPLACE --------------------
6011
-------------------- 3611
, COAL OR WOOD BURNING STOVE---------- 42"
-------------------- 12"
* KITCHEN RANGE, WALL OVEN
HOT AIR FLUES, UNIINSULATED
------------ 18"
-------------------- 911
HEAT DUCTS
* UNINSULATED HOT WATER PIPES --------- 12"
-------------------- loll
, SIDE OF CEILING OR WALL
MOUNTED HOT AIR DIFFUSERS
------------ 2411
--------------------12'1
* FRONT OF WALL MOUNTED
HOT AIR DIFFUSERS -----------------------
36"
--------------------IS"
* HOT WATER HEATER OR FURNACE --------- loll
-------------------- 3"
* LIGHT FIXTURE OW-25OW------------------
loll
-------------------- 311
* LIGHT FIXTURE 250111-499W--------------- 12"
-------------------- loll
* SPRINKLERS ARE NOT REQUIRED IN BATHROOMS
NOT EXCEEDING 55 S.F.
* SPRINKLERS ARE NOT REQUIRED IN CLOTHES
CLOSETS, LINEN CLOSETS, AND PANTRIES WHERE
THE SPACE DOES NOT EXCEED 24 S.F. AND THE
WALLS AND CEILINGS ARE OF NON-COMBUSTIBLE
OR LIMITED COMBUSTIBLE MATERIALS.
* SPRINKLERS ARE NOT REQUIRED IN GARAGES,
OPEN ATTACHED PORCHES, CARPORTS, AND
OTHER SIMILAR STRUCTURES.
* SPRINKLERS ARE NOT REQUIRED IN ATTICS,
CRAWL SPACES, AND OTHER CONCEALED SPACES
THAT ARE NOT INTENDED FOR LIVING PURPOSES
OR STORAGE.
* SPRINKLERS ARE NOT REQUIRED IN ENTRANCE
FOYERS THAT ARE NOT THE ONLY MEANS OF
EGRESS.
4130 AIRPORT ROAD
NAMPA, IDAHO 83687
PHONE: (208)468-9115
FAX: (208) 461-9117
ID. LIC. F.P. S. C. # 108
ID.PUDLIC WORKS LIC. #16630-A-4(13930)
UTAH LIC. ## 6579958-5501 S370
OREGON LIC. ## 181692
WYOMING ID ## 2008-000553828
WASHINGTON LIC. ## PHOENFP911 KL
JOB INFO FR1IATION
23-204 MADISON STATION APT.
BLDG. #1
511 TREJO
REXBURG, ID 03440
RAWN BY - TERI CRUICKSHAI
CHECKED BY : TRENT RICE
NICET # 101524
DATE . JULY, 2023
CODES: NFPA 13R, 2019
IFC 2010
OCCUPANCY CLASS : R-2
CONSTRUCTION TYPE: V B
SQUARE FOOTAGE : 36,019
NUMBER OF FLOORS : 3
PLAN
SCALE : AS NOTED ON PLANS
NOTICE
IT IS THE OWNER'S RESPONSIBILITY
TO PROVIDE HEAT ADEQUATE TO
PREVENT FREEZING THROUGHOUT
AREAS PROTECTED BY WET PIPE FIRE
SPRINKLER SYSTEMS INCLUDING ALL
ENCLOSURES FOR DRY PIPE VALVES,
DELUGE VALVES, AND ALL OTHER
VALVES CONTROLLING WATER
SUPPLIES TO THE FIRE SPRINKLER
SYSTEMS.
CONTRACT WITH:
NORTHERN STATES DEVELOPMENT
PO BOX 142
MENAN, ID 03434
PHONE NUMBER:
P:20a-154-9389 EX:IOI
NATIONAL INSTITUTE FOR CERTIFICATION
IN ENGINEERING TECHNOLOGIES
The records of this organization show that
TRENT 510E
Automatic Sprinkler System Layout
00301 / LEVEL III
is certified in the technical area(s)
Technician Certification No.
101524
Certification(s) Valid Thru 04/01/2024
NATIONAL INSTITUTE FOR CERTIFICATION
IN ENGINEERING TECHNOLOGIES
The records of this organization show that
DON WELAND
Automatic Sprinkler System Layout
LEVEL II
is certified in the technical area(s)
Technician Certification No.
105253
Certification(s) Valid Thru OO/01/2026
NATIONAL INSTITUTE FOR CERTIFICATION
IN ENGINEERING TECHNOLOGIES
The records of this organization show that
505TON ORAHOOD
Automatic Sprinkler System Layout
LEVEL I
is certified in the technical area(s)
Technician Certification No.
156541
Certification(s) Valid ThmO3/01/2025
NATIONAL INSTITUTE FOR CERTIFICATION
IN ENGINEERING TECHNOLOGIES
The records of this organization show that
Automatic Sprinkler System Layout
is certified in the technical area(s)
Technician Certification No.
Certification(s) Valid Thru
9
0
.s
m
o:
Ils
5HEET 3 OF 3