LOAD SHORT FORM - 23-00510 - 2201 W 640 S - New SFR
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jul-24 09:23:55 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW S9B15Job:Load Short Form Date:Entire House Vince ByramBy: SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) Semi-tightConstruction quality7568Inside db (°F) 0Fireplaces1474Design TD (°F) H-Daily range 5050Inside humidity (%) -3157Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Lennox Make Lennox Trade LENNOX Trade LENNOX Model ML195UH070XP36B-*Cond 13ACXN030-230-** AHRI ref 4805339 Coil SK6(6,9)30++TD AHRI ref 10317778 Efficiency 95 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh66000 Sensible cooling Btuh19040 Heating output Btuh64000 Latent cooling Btuh8160 Temperature rise °F60 Total cooling Btuh27200 Actual air flow cfm1150 Actual air flow cfm907 Air flow factor cfm/Btuh0.033 Air flow factor cfm/Btuh0.071 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Room1 270 3649 2126 121 152 Room2 108 978 509 32 36 Room3 54 80 44 3 3 Room4 168 2069 632 69 45 Room5 77 534 102 18 7 Room6 55 457 73 15 5 Room7 154 4311 484 143 35 Room8 156 2897 443 96 32 Room9 384 4125 2192 137 156 Room10 42 0 0 0 0 Room11 143 2403 923 80 66 Room12 24 0 0 0 0 Room13 60 944 166 31 12 Room14 956 12208 5021 405 358 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jul-24 09:23:55 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 2 ... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW Entire House d 2651 34654 12715 1150 907 Other equip loads 4835 915 Equip. @ 0.94 RSM 12812 Latent cooling 0 TOTALS 2651 39489 12812 1150 907 2023-Jul-24 09:23:55 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW S9B15Job:Building Analysis Date:Entire House Vince ByramBy: SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7568Indoor temp era ture (°F)Idaho Falls, ID, US 1474Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-31.557.0Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) Semi-tightConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing OtherCeilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 25.098654.8Walls 25.0988822.2Glazing 0.623311.1Doors 5.722661.5Ceilings 14.356333.73.7Floors 17.167692.7Infiltration 00Ducts 00Piping 00Humidification 12.24835Ventilation0Adjustments 100.039489Total Cooling Walls Glazing Other Ceilings Infiltration Ventilation % of loadBtuhBtuh/ft²Component 7.19730.5Walls 70.9965721.7Glazing 0.81135.4Doors 9.412860.8Ceilings 000Floors 5.06860.3Infiltration 00Ducts 6.7915Ventilation 00Internal gains 00Blower 0Adjustments 100.013630Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 67 Btuh/ft²-°F Data entries checked. 2023-Jul-24 09:23:56 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW S9B15Job:Component Constructions Date:Entire House Vince ByramBy: SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7568Indoor temp era ture (°F)Idaho Falls, ID, US 1474Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.557.0Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) Semi-tightConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 2340.4723714.8122.00.065493n 2380.4724104.8122.00.065501e 1970.4719994.8122.00.065416s 3040.4730854.8122.00.065641w 9730.4798654.8122.00.0652051all Partitions (none) Windows 2 glazing, clr outr, air gas, mtl no brk frm mat, clr innr, 1/4" gap, 1/8" thk: 2 glazing, clr outr, air gas, mtl no brk frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32) 79110.3170922.200.30077n 225434.1146522.200.30066e 146918.6175422.200.30079s 451420.3492822.200.300222all 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.32) 25710.355522.200.30025n 262934.1170922.200.30077e 225718.6269522.200.300121s 514323.0495922.200.300223all Doors metal: Door, mtl pur core type 1135.3623311.110.50.15021n Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 12860.8422661.4850.00.0201531 Floors 21A-28c: Bg floor, heavy dry or light damp soil, 6.5' depth, carpet flr fnsh 0019261.6300.0221183 22A-cpm: Bg floor, heavy dry or light damp soil, on grade depth, carpet flr fnsh 00370787.301.18042 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jul-24 09:23:56 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW S9B15Job:Project Summary Date:Entire House Vince ByramBy: SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89Inside db °F68 Inside db °F75 Design TD °F74 Design TD °F14Daily range H Relative humidity %50Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh34654 Structure Btuh12715 Ducts Btuh0 Ducts Btuh0Central vent (71 cfm)4835 Btuh Central vent (71 cfm)Btuh915 Outside air Outside airHumidificationBtuh0Blower Btuh0 Piping Btuh0Equipment load Btuh39489 Use manufacturer's data n Rate/swing multiplier 0.94InfiltrationEquipment sensible load Btuh12812 Method Latent Cooling Equipment Load SizingSimplified Construction quality Semi-tight0Fireplaces Structure Btuh-954 Ducts Btuh0Central vent (71 cfm)Btuh-1271 CoolingHeating Outside air26512651Area (ft²)Equipment latent load Btuh0 2120921209Volume (ft³)Air changes/hour 0.150.28 Equipment Total Load (Sen+Lat)Btuh12812 Equiv. AVF (cfm)5399 Req. total capacity at 0.70 SHR ton1.5 Heating Equipment Summary Cooling Equipment Summary Make Lennox Make LennoxTradeLENNOXTradeLENNOX Model ML195UH070XP36B-*Cond 13ACXN030-230-**AHRI ref 4805339 Coil SK6(6,9)30++TD AHRI ref 10317778Efficiency95 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh66000 Sensible cooling Btuh19040Heating output Btuh64000 Latent cooling Btuh8160 Temperature rise °F60 Total cooling Btuh27200Actual air flow cfm1150 Actual air flow cfm907 Air flow factor cfm/Btuh0.033 Air flow factor cfm/Btuh0.071Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 2023-Jul-24 09:23:56 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW S9B15Job:AED Assessment Date:Entire House Vince ByramBy: SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7568Indoor temp era ture (°F)Idaho Falls, ID, US 1474Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.557.0Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) )H(34-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gl a z i n g l o a d ( B t u h ) Hour of Day 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 29.3%. House has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 0 Btuh Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jul-24 09:23:56Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW S9B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Entire House Room1 2 Exposed wall 314.7 ft 33.0 ft 3 Room height 8.0 dft 8.0 heat/coolft 4 Room dimensions ft18.0x15.0 5 Room area 2651.2 f t²270.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 616 493 2371 234 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.2022.20 10.2810.28 77 0 1709 791 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.2022.20 10.2810.28 25 0 555 257 0 0 0 0 .DD metalmetal 0.2900.290 nn 11.1011.10 5.365.36 21 21 233 113 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 644 501 2410 238 144 119 572 56 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.2022.20 34.1434.14 66 0 1465 2254 25 0 555 854 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.2022.20 34.1434.14 77 0 1709 2629 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 616 416 1999 197 120 72 346 34 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.2022.20 18.6018.60 79 0 1754 1469 48 0 1066 893 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.2022.20 18.6018.60 121 0 2695 2257 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 641 641 3085 304 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 1531 1531 2266 1286 270 270 400 227 FF 21A-28c21A-28c 0.0220.022 --1.631.63 0.000.00 1183 1183 1926 0 0 0 0 0 FF 22A-cpm22A-cpm 1.1801.180 --87.3287.32 0.000.00 352 42 3707 0 0 0 0 0 6 c) AED excursion 0 -10 Envelope loss/gain 27885 12029 2939 2054 12 a)Infiltration 6769 686 710 72 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)34654 12715 3649 2126 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 34654 12715 3649 2126 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 34654 12715 3649 2126 Air required (cfm)Air required (cfm)1150 907 121 152 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jul-24 09:23:56Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 2... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW S9B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room2 Room3 2 Exposed wall 9.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft12.0x9.0 ft6.0x9.0 5 Room area 108.0 f t²54.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.2022.20 10.2810.28 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.2022.20 10.2810.28 0 0 0 0 0 0 0 0 .DD metalmetal 0.2900.290 nn 11.1011.10 5.365.36 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.2022.20 34.1434.14 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.2022.20 34.1434.14 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 72 56 269 27 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.2022.20 18.6018.60 16 0 355 298 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.2022.20 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 108 108 160 91 54 54 80 45 FF 21A-28c21A-28c 0.0220.022 --1.631.63 0.000.00 0 0 0 0 0 0 0 0 FF 22A-cpm22A-cpm 1.1801.180 --87.3287.32 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 75 -2 Envelope loss/gain 784 490 80 44 12 a)Infiltration 194 20 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)978 509 80 44 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 978 509 80 44 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 978 509 80 44 Air required (cfm)Air required (cfm)32 36 3 3 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jul-24 09:23:56Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 3... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW S9B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room4 Room5 2 Exposed wall 26.0 ft 7.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft12.0x14.0 ft7.0x11.0 5 Room area 168.0 f t²77.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.2022.20 10.2810.28 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.2022.20 10.2810.28 0 0 0 0 0 0 0 0 .DD metalmetal 0.2900.290 nn 11.1011.10 5.365.36 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.2022.20 34.1434.14 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.2022.20 34.1434.14 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 112 97 467 46 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.2022.20 18.6018.60 15 0 333 279 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.2022.20 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 96 96 462 46 56 56 269 27 CC 16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 168 168 249 141 77 77 114 65 FF 21A-28c21A-28c 0.0220.022 --1.631.63 0.000.00 0 0 0 0 0 0 0 0 FF 22A-cpm22A-cpm 1.1801.180 --87.3287.32 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 64 -4 Envelope loss/gain 1510 575 383 87 12 a)Infiltration 559 57 151 15 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2069 632 534 102 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2069 632 534 102 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2069 632 534 102 Air required (cfm)Air required (cfm)69 45 18 7 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jul-24 09:23:56Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 4... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW S9B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room6 Room7 2 Exposed wall 5.0 ft 25.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft5.0x11.0 ft14.0x11.0 5 Room area 55.0 f t²154.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 0 0 0 0 88 65 313 31 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.2022.20 10.2810.28 0 0 0 0 23 0 511 236 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.2022.20 10.2810.28 0 0 0 0 0 0 0 0 .DD metalmetal 0.2900.290 nn 11.1011.10 5.365.36 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.2022.20 34.1434.14 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.2022.20 34.1434.14 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.2022.20 18.6018.60 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.2022.20 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 40 40 192 19 112 112 539 53 CC 16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 55 55 81 46 154 154 228 129 FF 21A-28c21A-28c 0.0220.022 --1.631.63 0.000.00 0 0 0 0 0 0 0 0 FF 22A-cpm22A-cpm 1.1801.180 --87.3287.32 0.000.00 10 1 75 0 154 25 2183 0 6 c) AED excursion -3 -20 Envelope loss/gain 349 62 3773 430 12 a)Infiltration 108 11 538 55 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)457 73 4311 484 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 457 73 4311 484 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 457 73 4311 484 Air required (cfm)Air required (cfm)15 5 143 35 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jul-24 09:23:56Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 5... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW S9B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room8 Room9 2 Exposed wall 16.0 ft 35.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft13.0x12.0 ft384.0x1.0 5 Room area 156.0 f t²384.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 96 73 351 35 120 89 428 42 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.2022.20 10.2810.28 23 0 511 236 31 0 688 319 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.2022.20 10.2810.28 0 0 0 0 0 0 0 0 .DD metalmetal 0.2900.290 nn 11.1011.10 5.365.36 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 16 16 77 8 160 119 572 56 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.2022.20 34.1434.14 0 0 0 0 41 0 910 1400 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.2022.20 34.1434.14 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.2022.20 18.6018.60 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.2022.20 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 16 16 77 8 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 156 156 231 131 384 384 568 323 FF 21A-28c21A-28c 0.0220.022 --1.631.63 0.000.00 0 0 0 0 0 0 0 0 FF 22A-cpm22A-cpm 1.1801.180 --87.3287.32 0.000.00 144 15 1290 0 20 2 159 0 6 c) AED excursion -18 -49 Envelope loss/gain 2536 399 3326 2091 12 a)Infiltration 344 35 753 76 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2880 434 4079 2167 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 17 9 45 25 14 Subtotal 2897 443 4125 2192 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2897 443 4125 2192 Air required (cfm)Air required (cfm)96 32 137 156 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jul-24 09:23:56Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 6... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW S9B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room10 Room11 2 Exposed wall 0 ft 24.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.0x7.0 ft13.0x11.0 5 Room area 42.0 f t²143.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 0 0 0 0 88 63 303 30 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.2022.20 10.2810.28 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.2022.20 10.2810.28 0 0 0 0 25 0 555 257 .DD metalmetal 0.2900.290 nn 11.1011.10 5.365.36 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 0 0 0 0 104 87 418 41 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.2022.20 34.1434.14 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.2022.20 34.1434.14 0 0 0 0 17 0 377 580 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.2022.20 18.6018.60 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.2022.20 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 42 42 62 35 0 0 0 0 FF 21A-28c21A-28c 0.0220.022 --1.631.63 0.000.00 0 0 0 0 143 143 233 0 FF 22A-cpm22A-cpm 1.1801.180 --87.3287.32 0.000.00 24 0 0 0 0 0 0 0 6 c) AED excursion -1 -38 Envelope loss/gain 62 34 1887 870 12 a)Infiltration 0 0 516 52 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)62 34 2403 923 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -62 -34 0 0 14 Subtotal 0 0 2403 923 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 2403 923 Air required (cfm)Air required (cfm)0 0 80 66 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jul-24 09:23:56Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 7... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW S9B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room12 Room13 2 Exposed wall 6.0 ft 10.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft4.0x6.0 ft6.0x10.0 5 Room area 24.0 f t²60.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.814.81 0.470.47 48 48 231 23 80 59 284 28 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.2022.20 10.2810.28 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.2022.20 10.2810.28 0 0 0 0 0 0 0 0 .DD metalmetal 0.2900.290 nn 11.1011.10 5.365.36 0 0 0 0 21 21 233 113 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.2022.20 34.1434.14 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.2022.20 34.1434.14 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.814.81 0.470.47 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.2022.20 18.6018.60 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.2022.20 18.6018.60 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.814.81 0.470.47 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.481.48 0.840.84 0 0 0 0 0 0 0 0 FF 21A-28c21A-28c 0.0220.022 --1.631.63 0.000.00 24 24 39 0 60 60 98 0 FF 22A-cpm22A-cpm 1.1801.180 --87.3287.32 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -1 -6 Envelope loss/gain 270 21 615 134 12 a)Infiltration 129 13 215 22 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)399 34 830 156 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -399 -34 114 10 14 Subtotal 0 0 944 166 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 944 166 Air required (cfm)Air required (cfm)0 0 31 12 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jul-24 09:23:56Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 8... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW S9B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 1 Room name Room14 2 Exposed wall 118.7 ft 3 Room height 8.0 heat/coolft 4 Room dimensions ft956.2x1.0 5 Room area 956.2 f t² Ty Construction U-value Or HTM Area (f t²)Load Area Load number (Bt uh/f t²-°F)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Frm wall, vnl ext, 3 0.065 n 4.81 0.47 96 96 462 46 .G 2 glazing, clr outr,0.300 n 22.20 10.28 0 0 0 0 .G 2 glazing, clr outr,0.300 n 22.20 10.28 0 0 0 0 .D metal 0.290 n 11.10 5.36 0 0 0 0 1 1 W Frm wall, vnl ext, 3 0.065 e 4.81 0.47 220 160 770 76 G 2 glazing, clr outr,0.300 e 22.20 34.14 0 0 0 0 G 2 glazing, clr outr,0.300 e 22.20 34.14 60 0 1332 2049 W Frm wall, vnl ext, 3 0.065 s 4.81 0.47 312 191 917 90 G 2 glazing, clr outr,0.300 s 22.20 18.60 0 0 0 0 G 2 glazing, clr outr,0.300 s 22.20 18.60 121 0 2695 2257 W Frm wall, vnl ext, 3 0.065 w 4.81 0.47 321 321 1546 152 C 16B-50ad 0.020 -1.48 0.84 63 63 93 53 F 21A-28c 0.022 -1.63 0.00 956 956 1557 0 F 22A-cpm 1.180 -87.32 0.00 0 0 0 0 6 c) AED excursion 15 Envelope loss/gain 9370 4738 12 a)Infiltration 2553 259 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)11923 4997 Less external load 0 0 Less transfer 0 0 Redistribution 285 25 14 Subtotal 12208 5021 15 Duct loads -0%0%0 0 Total room load 12208 5021 Air required (cfm)405 358 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jul-24 09:23:57 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW S9B15Job:Loads for Multiple Orientations Date:Entire House Vince ByramBy: SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7568Indoor temp era ture (°F)Idaho Falls, ID, US 1474Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.557.0Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) )H(34-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) House North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh)15719 16578 16976 13499 15193 14821 14848 12812 Latent Load (Btuh)0 0 0 0 0 0 0 0 Total Load (Btuh)15719 16578 16976 13499 15193 14821 14848 12812 Heating AVF (cfm)1150 1150 1150 1150 1150 1150 1150 1150 Cooling AVF (cfm)907 907 907 907 907 907 907 907 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction House faces 0 5000 10000 15000 20000 N NE E SE S SW W NW House faces NorthwestCurrent Orientation: House faces EastHighest Cooling Load: Job #: S9B15 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Kartchner 601 West 1700 South Logan, Utah 84321 Phone: 435-755-7080 Scale: 1 : 70 Page 1 Ri g ht-S u i te® Uni v ersa l 20 22 22.0.05 RSU20477 2023-Jul-24 09:24:24 ...soft Program\SF9B15 Savannah.rup N Main Room11 Room12 Room13 Room14 6" Mechanical Damper for Fresh Air 68 cfm 68 cfm 68 cfm 68 cfm 68 cfm 31 cfm 68 cfm 436 cfm 80 cfm 6 " 2-14x3.25 6 " 14x3.25 6 " 6 " 6 " 6 " 6 " 6 "12 x 814 " 6 "6 "6 " 6 " 6 "6 " 14x3.25 6 "2-14x3.25 3-14x3.25 14x3.25 6 " 80 cfm 6 " 6 " 6 " Job #: S9B15 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Kartchner 601 West 1700 South Logan, Utah 84321 Phone: 435-755-7080 Scale: 1 : 70 Page 2 Ri g ht-Su i te® Uni v ersa l 20 22 22.0.05 RSU20477 2023-Jul-24 09:24:24 ...soft Program\SF9B15 Savannah.rup N 2nd floor Room1 Room2 Room3 Room4 Room5 Room6 Room7 Room8 Room9 Room10 76 cfm 105 cfm 254 cfm 120 cfm 34 cfm34 cfm 76 cfm 3 cfm 78 cfm 18 cfm 15 cfm 143 cfm 96 cfm 188 cfm 36 cfm 78 cfm 2023-Jul-24 09:23:58 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW S9B15Job:Duct System Summary Date:Entire House Vince ByramBy: SAVANNAH CPlan:Kartchner 601 West 1700 South, Logan, Utah 84321 Phone: 435-755-7080 Project Information Cody Puzey, Kartchner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0.34in H2O0.34 Available static pressure in H2O0.36in H2O0.36 Supply / return available pressure 0.269 / 0.091 in H2O in H2O0.269 / 0.091 Lowest friction rate in/100ft0.079in/100ft0.079 Actual air flow cfm907cfm1150 Total effective length (TEL)ft453 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st2325.013.0ShMt0x06.00.07976611063cRoom1 st2325.013.0ShMt0x06.00.07976611063cRoom1-A st2325.013.0ShMt0x06.00.07966802403hRoom11 st2325.013.0ShMt0x06.00.0791231944hRoom13 st2325.013.0ShMt0x06.00.07960682035hRoom14 st1325.013.0ShMt0x06.00.07960682035hRoom14-A st2325.013.0ShMt0x06.00.07960682035hRoom14-B st2325.013.0ShMt0x06.00.07960682035hRoom14-C 325.013.0ShMt0x06.00.07960682035hRoom14-D st2325.013.0ShMt0x06.00.07960682035hRoom14-E st2325.013.0ShMt0x06.00.0793632509cRoom2 st2325.013.0ShMt0x06.00.0793344cRoom3 325.013.0ShMt0x06.00.07923341035hRoom4-A st2325.013.0ShMt0x06.00.07923341035hRoom4-B st1325.013.0ShMt0x06.00.079718534hRoom5 st1325.013.0ShMt0x06.00.079515457hRoom6 st1325.013.0ShMt0x06.00.079351434311hRoom7 st2325.013.0ShMt0x06.00.07932962897hRoom8 st2325.013.0ShMt0x06.00.07978681096cRoom9 st2325.013.0ShMt0x06.00.07978681096cRoom9-A 2023-Jul-24 09:23:58 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 2 ... Country\Wrightsoft Program\SF9B15 Savannah.rup Calc = MJ8 House faces: NW Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st2 Peak AVF 805 718 0.079 753 14.0 0x0 ShtMetl st1 Peak AVF 243 107 0.079 365 8.5 12x8 ShtMetl Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb5 0x 2540 71 115.0 0.079 402 8.6 2-3.25x14 2-10x18 SJSp rt1 rb6 0x 1200 108 115.0 0.079 381 6.5 3.25x14 10x9 SJSp rt1 rb4 0x 1050 104 115.0 0.079 334 6.2 3.25x14 10x9 SJSp rt1 rb1 0x 1540 188 115.0 0.079 297 7.7 2-3.25x14 2-10x18 SJSp rt1 rb3 0x 800 66 115.0 0.079 252 5.6 3.25x14 10x9 SJSp rt1 rb2 0x 4360 370 115.0 0.079 460 10.6 3-3.25x14 3-10x27 SJSp Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 714 537 0.079 0 12.2 0x14 ShtMetl