HomeMy WebLinkAboutAPPROVED PLANS 7/5/2023 - 545 Henderson St - Solar PanelsAuthor Name Author Email Author Phone No.:
Alex Owens Alex.Owens@rexburg.org 208-372-2172
Description : 545 Henderson St - Solar Panels
Address : 545 Henderson St
Record Type : Solar Panels
Document Filename : Kirkpatrick v6 7.5.23.pdf
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 23-00329
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
1 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector
3 Stamp Alex Owens : Electrical Open 3 Approved - Electrical Inspector
Solar Panels
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
N
RevDescriptionDate
REVISIONS
Signature with Seal
ANSI B
11" X 17"
PV 0.0
SHEET INDEX:
PV 0.0:COVER SHEET
PV 1.0:SITE PLAN
S 1.1:
E 1.1:3-LINE DIAGRAM
E 1.2: WIRE CALCULATION
E 1.2:NOTES
E 1.4:WARNING LABELS
E 1.5:PLACARD
DS:EQUIPMENT SPEC SHEET
COVER SHEET
MOUNT DETAILS
2 SATELLITE VIEW
PV 0.0
3 VICINITY MAP
PV 0.0
1 PLOT PLAN
PV 0.0
GENERAL NOTES:
a.INSTALLATION OF SOLAR PHOTOVOLTAIC
SYSTEM SHALL BE IN ACCORDANCE WITH
NEC ARTICLE 690, AND ALL OTHER
APPLICABLE NEC CODES WHERE NOTED
OR EXISTING.
b.PROPER ACCESS AND WORKING
CLEARANCE AROUND EXISTING AND
PROPOSED ELECTRICAL EQUIPMENT WILL
COMPLY WITH NEC ARTICLE 110.
c.ALL CONDUCTORS,INCLUDING THE
GROUNDING ELECTRODE CONDUCTOR
SHALL BE PROTECTED FROM PHYSICAL
DAMAGE IN ACCORDANCE WITH NEC
ARTICLE 250.
d.ALL DC WIRES SHALL BE SIZED
ACCORDING TO [NEC 690.8]
e.DC CONDUCTORS SHALL BE WITHIN
PROTECTED RACEWAYS IN ACCORDANCE
WITH [NEC 690.31]
f.ALL SIGNAGE TO BE PLACED IN
ACCORDANCE WITH LOCAL
JURISDICTIONAL BUILDING CODE.
g.PV MODULES TO BE RATED UL 1703 CLASS
A FIRE RATING OR BETTER.
h.ALL EQUIPMENT TO BE CERTIFIED BY A
NATIONALLY RECOGNIZED TESTING
LABORATORY.
PROTECTION OF EMERGENCY RESPONDERS
ALL SHARP EDGES AND FASTENER TIPS SHALL BE
COVERED OR CRIMPED OVER TO ELIMINATE SHARP
EDGES, TO MINIMIZE RISK OF INJURY TO EMERGENCY
RESPONDERS.
ALL ROOF MOUNTED CONDUITS, BOXES, AND
EQUIPMENT CROSSING PATHWAYS ARE TO BE
CLEARLY IDENTIFIED BY A RED/WHITE REFLECTIVE
TAPE OR OTHER APPROVED MATERIAL.
ROOF ACCESS POINT
ROOF ACCESS POINT SHALL NOT BE LOCATED IN AREAS
THAT REQUIRE THE PLACEMENT OF GROUND LADDERS
OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND
LOCATED AT STRONG POINTS OF BUILDING
CONSTRUCTION IN LOCATIONS WHERE THE ACCESS
POINT DOES NOT CONFLICT WITH OVERHEAD
OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS.
SYSTEM SIZE:
MODULE TYPE & AMOUNT:
MODULE DIMENSIONS:
INVERTER:
INTERCONNECTION METHOD:
PHOTOVOLTAIC SYSTEM SPECIFICATIONS:
PHOTOVOLTAIC ROOF MOUNT SYSTEM
16 MODULES ROOF MOUNTED (LAT. 43.82°, LONG. -111.80°)
GOVERNING CODES
ALL WORK SHALL CONFORM TO THE FOLLOWING CODES
ED
K
I
R
K
P
A
T
R
I
C
K
54
5
H
E
N
D
E
R
S
O
N
S
T
RE
X
B
U
R
G
I
D
,
8
3
4
4
0
AP
N
:
R
P
R
H
N
D
S
0
0
2
0
0
2
0
545 HENDERSON ST REXBURG ID, 834405.60 kW DC 15.00 kW AC
(16) LG350Q1C-A5
(L/W) 67.8"X 44.65"
(1) SOL-ARK 15K-2P
BACKFED
kW AC
kW DC5.60
15.00 85
9
S
.
Y
E
L
L
O
W
S
T
O
N
E
H
W
Y
UN
I
T
3
0
5
RE
X
B
U
R
G
,
I
D
A
H
O
,
8
3
4
4
0
(8
8
8
)
4
6
8
-
7
1
8
0
FR
O
N
T
O
F
H
O
U
S
E
54
5
H
E
N
D
E
R
S
O
N
S
T
2017 NATIONAL ELECTRICAL CODE (NEC)
2018 INTERNATIONAL BUILDING CODE (IBC)
2018 INTERNATIONAL PRESIDENTIAL CODE (IRC)
2018 INTERNATIONAL FIRE CODE (IFC)
2018 INTERNATIONAL MECHANICAL CODE (IMC)
2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
EXISTING INTERIOR MAIN SERVICE PANEL
& POINT OF INTERCONNECTION, TIED TO
EXTERIOR UTILITY METER 85041423
BAT
NEW PV AC DISCONNECT GROUPED WITH
SERVICE EQUIPMENT (VISIBLE,LOCKABLE,
LABELED)
INVERTER SOLARK 15K-2P-K
HOMEGRID STACK'D 14.4KW
BATTERY (3 BATTERY CELLS)
(E)(16) LG350Q1C-A5
(E)(16) P370 SOLAR EDGE OPTIMIZER
SLOPE - 37°
AZIMUTH -180°
ROOF #1
N
Description Date Rev
REVISIONS
Signature with Seal
ANSI B
11" X 17"
PV 1.0
EQUIPMENT
LAYOUT & SITE
PLAN
ROOF SECTION(S)
1 SITE PLAN
PV 1.0
ADDITIONAL NOTES:
FINAL LOCATION OF ALL CONDUIT AND JUNCTION
BOXES TO BE DETERMINED AT TIME OF INSTALLATION.
CONDUIT TO BE PAINTED TO MATCH EXTERIOR OF
RESIDENCE WHERE APPLICABLE AND IS TO BE SUPPORTED
EVERY 10' MAX.
30" WIDE X 36" DEEP WORKING SPACE CLEARANCES
REQUIRED ABOUT ALL ELECTRICAL EQUIPMENT.
STAGGER PENETRATIONS TO EVENLY DISTRIBUTE
LOAD ACROSS ALL TRUSSES UNDER ARRAY.
ALL DIMENSIONS ARE APPROXIMATIONS.
MODULE - (E)16 LG350Q1C-A5
SLOPE - 37°
AZIMUTH - 180°
MATERIAL - ASPHALT SHINGLED
ROOF #01
SYSTEM LEGEND
EXISTING EXTERIOR MAIN SERVICE PANEL & POINT
OF INTERCONNECTION. TIED TO EXTERIOR UTILITY
METER 85041423
NEW PHOTOVOLTAIC UTILITY DISCONNECT SWITCH.
LOCATED WITHIN 10' OF MSP.
NEW DEDICATED PV SYSTEM COMBINER PANEL.
M
CB
16 NEW LG350Q1C-A5 MODULE WITH
NEW 1 SOL-ARK 15K-2P
INVERTERS, MOUNTED ON THE BACK OF EACH
MODULES.
= ATTACHMENT POINTS
= RAFTER
= ROOF OBSTRUCTIONS
= RACKING SYSTEM
= ATTIC RUN
= CONDUIT ATTIC RUN JUNCTION BOX
SYSTEM SIZE:
MODULE TYPE & AMOUNT:
MODULE DIMENSIONS:
INVERTER:
INTERCONNECTION METHOD:
PHOTOVOLTAIC SYSTEM SPECIFICATIONS:
ED
K
I
R
K
P
A
T
R
I
C
K
54
5
H
E
N
D
E
R
S
O
N
S
T
RE
X
B
U
R
G
I
D
,
8
3
4
4
0
AP
N
:
R
P
R
H
N
D
S
0
0
2
0
0
2
0
(16) LG350Q1C-A5
(L/W) 67.8"X 44.65"
(1) SOL-ARK 15K-2P
BACKFED
kW AC
kW DC5.60
15.00
MODULE ARRAY WEIGHT (LOAD
CALC'S)
NUMBER OF MODUELS 16
MODULE WEIGHT 47.39 LBS
TOTAL MODULE (ARRAY) WEIGHT 758.24 LBS
MODULE AREA 20.98 SQFT
TOTAL ARRAY AREA 335.68 SQFT
TOTAL ROOF AREA 1376.36 SQFT
TOTAL PERCENTAGE OF ROOF
COVERED 24%
RAFTER SIZE & SPACING -
2"X4" TRUSSES @24" O.C
85
9
S
.
Y
E
L
L
O
W
S
T
O
N
E
H
W
Y
UN
I
T
3
0
5
RE
X
B
U
R
G
,
I
D
A
H
O
,
8
3
4
4
0
(8
8
8
)
4
6
8
-
7
1
8
0
EXISTING INTERIOR MAIN SERVICE PANEL
& POINT OF INTERCONNECTION, TIED TO
EXTERIOR UTILITY METER 85041423
NEW PV AC DISCONNECT GROUPED WITH
SERVICE EQUIPMENT (VISIBLE,LOCKABLE,
LABELED)
HOMEGRID STACK'D 14.4KW
BATTERY (3 BATTERY CELLS)
ROOF #01
NOTE: -
1.AS PER THE 314.16(A) SOLADECK JUNCTION BOX SIZE SHOULD BE 3" X 2" X 2".
2.300.15(F) FITTING. A FITTING IDENTIFIED FOR THE USE SHALL BE PERMITTED IN LIEU
OF A BOX OR CONDUIT BODY WHERE CONDUCTORS ARE NOT SPLICED OR
TERMINATED WITHIN THE FITTING. THE FITTING SHALL BE ACCESSIBLE AFTER
INSTALLATION, UNLESS LISTED FOR CONCEALED INSTALLATION.
3.FROM FREE AIR WIRING METHODS TRANSITIONING TO A RACEWAY WIRING METHOD
SHALL COMPLY WITH NEC 300.15, 300.17, 314.16 AND 69.43 AS APPLICABLE
NOTE: -
#6 AWG SOLID CU EQUIPMENT GROUND CONDUCTOR CONT. RUN TO GROUND
LUG ON RACKING SYSTEM. ALL ROOFTOP COMPONENTS BONDED TO RACKING
SYSTEM PER NEC 690.43
NOTE: -
1.PV WIRE - GREEN SPEC, UL SUBJECT 4703, UL 44, UL 854, 200V, 90C-RoHS
2.JUNCTION BOX - SOLADECK (0799-5), UL 50, CSA C22.2 NO # 290, NEMA TYPE 3R, UL
1741
NOTES:
1. CONDUCTORS ON ROOF MUST BE SUNLIGHT RESISTANT, 90°C RATED AND SUITABLE FOR WET
LOCATIONS.
2. SEE RACKING SPEC SHEETS FOR RACKING EQUIPMENT GROUNDING METHOD.
3. ALL GROUNDING CONDUCTORS MUST BE PROTECTED FROM DAMAGE IF NOT INSTALLED IN CONDUIT.
4. ALL WIRING MUST BE PROPERLY SUPPORTED BY DEVICES OR MECHANICAL MEANS DESIGNED AND
LISTED FOR SUCH USE. WIRING MUST BE PERMANENTLY AND COMPLETELY HELD OFF OF THE ROOF.
5. ALL DEVICES USED FOR BONDING FRAMES OF MODULES OR OTHER EQUIPMENT TO THE GROUNDING
SYSTEM MUST BE LISTED AND IDENTIFIED FOR THE PURPOSE.
6. OPTIMIZERS ARE TO BE BONDED TO RACKING BY USING EITHER AN OPTIMIZER ATTACHMENT KIT OR
A GROUNDING PLATE.
NOTE:
SOLADECK JUNCTION BOX IS UL50 TYPE 3R AND NEMA TYPE 3R RATED, CONFORMING TO UL 1741.
SOLADECK PRODUCTS ARE LISTED BY ETL TO UL STANDARDS (SEE SPEC SHEETS). NOTE
THAT 8*3/4" = 6" < 8", SO OK TO USE.
Description Date Rev
REVISIONS
Signature with Seal
ANSI B
11" X 17"
E 1.1
3-LINE
DIAGRAM
PV MODULE FRAME
PEGASUS RAIL
UNIVERSAL
FASTENING OBJECT
GROUNDING PIERCES
THROUGH ANODIZED COATINGS
OF MODULE FRAMES AND RAILS
GROUNDING DETAIL PEGASUS INTEGRATED GROUNDING & LAY-IN LUGS ARE UL2703 LISTED
#10-24 X 3/4" SS HCS BOLT SS SET SCREW INCLUDED
#10 SS EXTERNAL TOOTH
LOCK (STAR) WASHER
#10-24 SS LOCK NUT
8 AWG BARE CU WIRE
LAY-IN LUG TERMINAL
AL/CU DUAL RATED
(TIN PLATED CU)
PEGASUS RAIL
RAILS MODULES
SYSTEM SIZE:5.60 kW DC
15.00 kW AC
MODULE:(E)(16) LG350Q1C-A5
INVERTER:(1) SOL-ARK 15K-2PMANUFACTURE'S DOCUMENTATION:-
1.PV WIRE - GREEN SPEC, UL SUBJECT 4703,UL 44,
UL 854,2000V, 90C-RoHS
2.JUNCTION BOX -SOLARDECK (0799-5),UL 50CSA
C22.2 NO#290, NEAM TYPE 3R, UL 1741
SERVICE FEED SOURCE:
PACIFIC POWER
240V
SQUARE-D
SERVICE INFO.
SOUTHWEST
UNDERGROUND
(E) 200A
(E) 200A
120% Rule
(BUS BAR RATING X 120%) - MAIN BREAKER RATING
= MAX PV OCPD
(200A x 120%) - 200 = 40A
ED
K
I
R
K
P
A
T
R
I
C
K
54
5
H
E
N
D
E
R
S
O
N
S
T
RE
X
B
U
R
G
I
D
,
8
3
4
4
0
AP
N
:
R
P
R
H
N
D
S
0
0
2
0
0
2
0
85
9
S
.
Y
E
L
L
O
W
S
T
O
N
E
H
W
Y
UN
I
T
3
0
5
RE
X
B
U
R
G
,
I
D
A
H
O
,
8
3
4
4
0
(8
8
8
)
4
6
8
-
7
1
8
0
02 STRINGS OF 08 MODULES CONNECTED IN SERIES
L
BI-DIRECTIONAL
UTILITY METER
1-PHASE, 3-W,
120V/240V, 60Hz
(3)#4/0 AWG ALUM T
2" EMT OR EQUIVALENT CONDUIT
G
200A
FUSES
(1)#6 AWG ALU THWN
2" EMT OR EQUIVALENT CONDUIT
(N) AC DISCONNECT 200A
FUSED, VISIBLE LOCKABLE
LABELED, 200A FUSES,
240 VAC
(N) MAIN
BREAKER
200A/2P, 240V
(3)#4/0 AWG ALU T
200A
#8 #2 #1
#8 #2 #1
8 MODULES IN STRING #1
8 MODULES IN STRING #2
G
(N)SOL-ARK-15K-P INVERTER
DC
AC
Gen In
AC
In/Out
Load
Out
PV
Input
DC
Input
(2) #10 AWG PV WIRE + RED
(1) #6 BARE CU GND
3/4" EMT CONDUIT
(2) #10 AWG THWN-2 + RED
(2) #10 AWG THWN-2 - BLACK
(1) #8 THWN-2 GND
(N) JUNCTION BOX
600 V, NEMA 3
UL LISTED
3/4 " EMT / LT
(3)#12 AWG COPPER
MASTER
INVERTER
TIGO TS4-A-F RAPID
SHUTDOWN DEVICES
BATTERY
DISCONNECT
RAPID SHUTDOWN BUTTON
WILL BE LOCATED NEXT TO
THE SOL-ARK INVERTER.
TIGO TRANSMITTER
200A BREAKER
EXISTING GROUNDING SYSTEM
#6 AWG COPPER GND
NEW GROUNDING LUG
HOMEGRID STACK'D 14.4
KWH BATTERY (3
BATTERY CELLS)
4.8 KWh
4.8 KWh
4.8 KWh
BMS
BATTERY CABLE
(2) SCE #2/0 AWG COPPER
CABLE CLASS K 600 V
PER NEC 400.4
(N) MAIN SERVICE PANEL,
200A RATED, 120/240V
(3) #3/0 AWG COPPER THWN
(1) #4 AWG COPPER THWN GND
2" EMT OR EQUIVALENT CONDUIT
-
~
(E) SOLAR EDGE SE7600A-US
40A
FUSES
(N) AC DISCONNECT 60A
FUSED, VISIBLE LOCKABLE
LABELED, 40A FUSES,
240 VAC
(2) #8 AWG THWN-2 + RED
(2) #8 AWG THWN-2 - BLACK
(1) #8 THWN-2 GND
Description Date Rev
REVISIONS
Signature with Seal
ANSI B
11" X 17"
E 1.2
NOTES
SITE NOTES:
1.A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA
REGULATIONS.
2.THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A
UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.
3.THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL,
OR BUILDING ROOF VENTS.
4.PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED
ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.
5.ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN
ACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'S
INSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT THE
BUILDING OR STRUCTURE.
EQUIPMENT LOCATIONS:
1.ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.
2.WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED
OPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLES
310.15 (B)(2)(A) AND 310.15 (B)(3)(C).
3.JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES
ACCORDING TO NEC 690.34.
4.ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT
WITHIN SIGHT OF THE AC SERVICING DISCONNECT. 2.2.6 ALL EQUIPMENT SHALL BE
INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NEC
APPLICABLE CODES.
5.ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR
USAGE WHEN APPROPRIATE.
STRUCTURAL NOTES:
1.RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO
CODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED
SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE
BEYOND EITHER EDGE OF THE ARRAY / SUBARRAY, ACCORDING TO RAI
MANUFACTURER’S INSTRUCTIONS.
2.JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IF
ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL
REQUIREMENTS.
3.ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/
APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR.
4.ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE
SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER. 2.3.6 WHEN
POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED
AMONGST THE ROOF FRAMING MEMBERS.
WIRING & CONDUIT NOTES:
1.ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE.
CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE
REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING.
2.CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.
3.VOLTAGE DROP LIMITED TO 1.5%.
4.DC WIRING LIMITED TO MODULE FOOTPRINT. MICRO INVERTER WIRING
SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/ SUITABLE
WIRING CLIPS.
5.AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK
PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3-
BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION NEUTRAL- WHITE OR GREY
IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO
BE MARKED ORANGE [NEC 110.15].
GROUNDING NOTES:
1.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND
GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH
USE.
2.PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM
NEC TABLE 250.122.
3.METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES
CONSIDERED GROUNDED IN ACCORD WITH 250.134 AND 250.136(A).
4.EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC
690.45 AND MICRO INVERTER MANUFACTURERS’ INSTRUCTIONS.
5.EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN
MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE
NOT USED, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED
GROUNDING LUG HOLES PER THE MANUFACTURERS'INSTALLATION
REQUIREMENTS.
6.THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT
THE REMOVAL OFA MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO
ANOTHER MODULE.
7.GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED
GREEN OR MARKED GREEN IF #4 AWG OR LARGER [NEC 250.119]
8.THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50
THROUGH 250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A
GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47
AND AHJ.
9.GROUND-FAULT DETECTION SHALL COMPLY WITH NEC 690.41(B)(1) AND (2) TO
REDUCE FIRE HAZARDS
DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:
1.DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS
OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE
TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS).
2.DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE
LOCKABLE, AND BE A VISIBLE-BREAK SWITCH
3.PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID
SHUTDOWN FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCY
RESPONDERS IN ACCORDANCE WITH 690.12(A) THROUGH (D).
4.ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9, AND
240.
5.MICRO INVERTER BRANCHES CONNECTED TO A SINGLE BREAKER OR GROUPED
FUSES IN ACCORDANCE WITH NEC 110.3(B).
6.IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION
ACCORDING TO NEC 690.11 AND UL1699B.
INTERCONNECTION NOTES:
1.LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC 705.12 (B)]
2.THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS OUTPUT MAY NOT
EXCEED 120% OF BUS BAR RATING [NEC 705.12(D)(2)(3)].
3.THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENT
AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE BUS BAR
SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE BUS BAR, PV
DEDICATED BACKFEED BREAKERS MUST BE LOCATED OPPOSITE END OF THE BUS
FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(2)(3)].
4.AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTAL
RATING OF ALL OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF
BUSBAR. HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BE EXCLUDED
ACCORDING TO NEC 705.12 (B)(2)(3)(C).
5.FEEDER TAP INTERCONNECTION (LOADSIDE) ACCORDING TO NEC 705.12 (B)(2)(1)
6.SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.12 (A) WITH
SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH NEC 230.42
2.7.8BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT
FROM ADDITIONAL FASTENING [NEC 705.12 (B)(5)].
PV MODULE RATING @ STC
MANUFACTURER
MAX. POWER-POINT CURRENT (IMP)
MAX. POWER-POINT VOLTAGE (VMP)
OPEN-CIRCUIT VOLTAGE (VOC)
SHORT-CIRCUIT CURRENT (ISC)
10.74 AMPS
41.00 VOLTS
49.60 VOLTS
11.34 AMPS
NOM. MAX. POWER AT STC (PMAX)
MAX. SYSTEM VOLTAGE
VOC TEMPERATURE COEFFICIENT
440 WATT
1000V
-0.27° %/°C
LG350Q1C-A5
Rooftop conductor ampacities designed in
compliance with art. 690.8, Tables 310.15(B)(2)(a),
310.15(B)(3)(a), 310.15(B)(3)(c), 310.15(B)(16),
Chapter 9 Table 4, 5, & 9. Location specific
temperature obtained from ASHRAE 2017 data tables
AMBIENT TEMP (HIGH TEMP 2%)
RECORD LOW TEMP -16°C
34°C
CONDUIT HEIGHT 0.5"
ROOF TOP TEMP 56°C
CONDUCTOR TEMPERATURE RATE 90°C
INVERTER SPECIFICATIONS
MANUFACTURER
MAX. POWER AT 40 C
58 VOLTS
NOMINAL AC VOLTAGE
349 WATTS
MAX. AC CURRENT
240 VOLTS
MAX. OCPD RATING
MAX. PANELS/CIRCUIT
SHORT CIRCUIT CURRENT
1.45 AMPS
20 AMPS
MAX. DC VOLT RATING
11
15 AMPS
SOL-ARK 15K-2P
ED
K
I
R
K
P
A
T
R
I
C
K
54
5
H
E
N
D
E
R
S
O
N
S
T
RE
X
B
U
R
G
I
D
,
8
3
4
4
0
AP
N
:
R
P
R
H
N
D
S
0
0
2
0
0
2
0
85
9
S
.
Y
E
L
L
O
W
S
T
O
N
E
H
W
Y
UN
I
T
3
0
5
RE
X
B
U
R
G
,
I
D
A
H
O
,
8
3
4
4
0
(8
8
8
)
4
6
8
-
7
1
8
0
Description Date Rev
REVISIONS
Signature with Seal
ANSI B
11" X 17"
E 1.3
WARNING
LABELS
ELECTRICAL NOTES:
1. ALL PV MODULES, ARRAY FRAMING AND RACKING SHALL BE GROUNDED PER MFR'S
SPECIFICATIONS.
2. ALL EQUIPMENT WILL BE UL 1703, UL 1741, OR UL 2703 LISTED AND CERTIFIED.
3. MODULES WILL BE GROUNDED WITH INTEGRADED GROUNDING MODULE CLAMPS. ARRAY
FRAME WILL BE GROUNDED WITH ILSCO GBL-4DBT (OR EQUIVALENT - SUITABLE FOR DIRECT
BURIAL AND CONTACT WITH COPPER OR ALUMINUM) LAY IN TYPE GROUNDING LUG. USE
SPECIFIED MODULE GROUNDING POINTS.
4. ALL WIRE TERMINATIONS, SPLICES AND CONNECTIONS SHALL BE MADE USING A LISTED
DEVICE OR ELECTRICAL BOX SUITED FOR THE PURPOSE. ALL WIRES NOT IN CONDUIT TO BE
PROVIDED WITH STRAIN RELIEF AT ENTRY INTO JUNCTION BOXES.
5. PROVIDE AND INSTALL CONDUIT EXPANSION FITTINGS, PER MANUFACTURER'S
SPECIFICATIONS, IN CONDUIT RUNS WHERE THERMAL EXPANSION IS 0.25" OR MORE, BASED
ON RECORD MAXIMUM AND MINIMUM TEMPERATURES FOR THE SITE (SEE NEC TABLE
310.15(B)(2)(C), AND USING EXPANSION COEFFICIENT OF STEEL.
6. BOTH ENDS OF ALL METALLIC CONDUIT CONTAINING GROUNDING ELECTRODE
CONDUCTORS SHALL BE BONDED PER NEC 250.64(E).
7. PROVIDE AND INSTALL ALL GROUNDING AS REQUIRED BY NEC ARTICLES 250, 690 AND
SYSTEM MANUFACTURER.
8. INSTALLATIONS WHICH USE TRANSFORMER-LESS INVERTERS - PV WIRE TYPE IS REQUIRED
FOR ALL DC WIRE RUNS IN FREE AIR, OR NOT IN CONDUIT.
9. EACH CURRENT CARRYING CONDUCTOR IN ALL PV SOURCE CIRCUITS OR PV OUTPUT
CIRCUITS SHALL BE DISCONNECTED/ FUSED, WHEN NECESSARY.
10. CONTRACTOR SHALL VERIFY EXISTENCE OF UNDERGROUND UTILITIES PRIOR TO ANY
EXCAVATIONS.
11. ELECTRICAL TRENCH RUNS, WHERE USED, SHALL USE SCHEDULE 40 PVC CONDUIT AND
PROVIDE 18" MIN CLEARANCE FROM TOP OF CONDUIT TO GRADE, AND MAGNETIC WARNING
TAPE AT 12" BELOW GRADE. 24" CLEARANCE AND SCHEDULE 80 PVC IS REQUIRED IN AREAS
WHERE SUBJECT TO VEHICLE TRAFFIC.
12. CHECK WITH LOCAL JURISDICTION FOR ANY ADDITIONAL FILL AND COMPACTION
REQUIREMENTS, SPOILS TREATMENT AND/OR EROSION CONTROL MEASURES PRIOR TO
EXCAVATION.
13. INSTALLATIONS IN LIGHTENING-PRONE LOCATIONS ARE RECOMMENDED TO UTILIZE DC
LIGHTENING ARRESTORS IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.
14. SUPPLY SIDE CONNECTIONS SHALL ONLY BE MADE WITH LISTED AND APPROVED TAPS.
15. ALL WIRE RUNS SHALL NOT EXCEED 2% CALCULATED VOLTAGE DROP.
16. VERIFY EXISTING GROUNDING ELECTRODE. IF NONE EXISTS, A NEW GROUND ROD MAY BE
REQUIRED. MIN. SIZE 8' LONG X 5/8" DIA, COPPER CLAD. BOND TO GAS, AND HOT AND COLD
WATER PIPES.
17. USE WATERPROOF FITTINGS FOR ALL EXTERIOR CONDUIT.
18. GROUNDING ELECTRODE CONDUCTOR (AC SIDE OF INVERTER) IS #8 IF IN CONDUIT, OR #6
AWG IF EXPOSED AND SUBJECT TO DAMAGE, AND SHALL BE CONTINUOUS FROM INVERTER TO
GROUND ROD. USE IRREVERSIBLE SPLICES WHERE NECESSARY.
19. EQUIPMENT GROUNDING CONDUCTOR (DC SIDE OF INVERTER) IS #10 IF IN CONDUIT, OR #6
AWG IF EXPOSED AND SUBJECT TO DAMAGE (NEC 690.46).
SIGNAGE NOTES:
1. SIGNAGE SHALL BE PERMANENTLY AFFIXED TO EQUIPMENT WITH POP-RIVETS,
SCREWS OR APPROVED ADHESIVE.
2. OUTDOOR SIGNAGE SHALL BE UV STABLE AND SUITABLE FOR ITS ENVIRONMENT.
CONDUIT STICKERS SHALL BE SHALL BE REFLECTIVE.
3. PLAQUES SHALL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED
LETTERS OR ELECTRO-PHOTO PLATING, SHALL HAVE RED BACKGROUND WITH WHITE
LETTERING. MINIMUM FONT SIZE SHALL BE 3/8" HEIGHT AND ALL CAPITAL LETTERS.
4. DEVICES MARKED WITH "LINE" AND "LOAD" ARE NOT SUITABLE FOR FOR BACKFEED OR
REVERSE CURRENT.
5. SIGNAGE CANNOT BE HAND WRITTEN.
6. NET METER BASE, PRODUCTION METER BASE, AND SOLAR AC DISCONNECT
ENGRAVED LABELS MUST BE MECHANICALLY FASTENED WITH RIVETS, SCREWS, OR BOLTS.
A
SOLAR PV SYSTEM
EQUIPPED WITH RAPID
SHUTDOWN
TURN RAPID
SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUTDOWN PV
SYSTEM AND
REDUCE
SHOCK HAZARD
IN THE ARRAY
SOLAR
ELECTRIC
PV PANELS
LABEL LOCATION: MAIN SERVICE DISCONNECT
PER CODE: NEC 690.56(C)(1)(a)
LABEL LOCATION: EMT, CONDUIT RACEWAY,
CABLE TRAYS
PER CODE: NEC 690.31(G)(3-4)
LABEL LOCATION: POINT OF INTERCONNECTION
PER CODE: NEC 690.54
PHOTOVOLTAIC SYSTEM AC DISCONNECT
RATED AC OPERATING CURRENT 30.45 AMPS
AC NOMINAL OPERATING VOLTAGE 240 VOLTS
ELECTRICAL SHOCK HAZARD
! WARNING
LABEL LOCATION: COMBINER PANEL, AC
DISCONNECT, POINT OF INTERCONNECTION
PER CODE(S): NEC 690.13(B)
DUAL POWER SOURCE
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM
LABEL LOCATION: MAIN SERVICE DISCONNECT
PER CODE: NEC 705.12(B)(3-4), NEC 690.59
LABEL LOCATION: MAIN SERVICE DISCONNECT, UTILITY METER
PER CODE: NEC 690.13(B)
POWER SOURCE OUTPUT
CONNECTION. DO NOT RELOCATE
THIS OVERCURRENT DEVICE.
! WARNING
LABEL LOCATION: MAIN SERVICE DISCONNECT, POINT OF
INTERCONNECTION
PER CODE: 705.12(B)(2)(3)(b)
! WARNING
LABEL LOCATION: COMBINER PANEL(S), MAIN
SERVICE DISCONNECT
PER CODE(S): NEC 110.27(C), OSHA 1910.145(f)(7)
LABEL LOCATION: AC DISCONNECT
PER CODE: NEC 690.13(B)
DO NOT DISCONNECT UNDER
LOAD
LABEL LOCATION: MAIN SERVICE DISCONNECT
PER CODE: NEC 690.15(C) & NEC 690.33(E)(2)
LABEL LOCATION: RSD INITIATION DEVICE, AC DISCONNECT
PER CODE: NEC 690.56(C)(3)
PV SYSTEM
DISCONNECT
THIS EQUIPMENT FED BY MULTIPLE SOURCES,
TOTAL RATING OF ALL OVERCURRENT DEVICES,
EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE,
SHALL NOT EXCEED AMPACITY OF BUSBAR.
! WARNING
LABEL LOCATION: POINT OF INTERCONNECTION, COMBINER PANEL
PER CODE: NEC 705.12(B)(2)(3)(c)
WARNING!
ED
K
I
R
K
P
A
T
R
I
C
K
54
5
H
E
N
D
E
R
S
O
N
S
T
RE
X
B
U
R
G
I
D
,
8
3
4
4
0
AP
N
:
R
P
R
H
N
D
S
0
0
2
0
0
2
0
85
9
S
.
Y
E
L
L
O
W
S
T
O
N
E
H
W
Y
UN
I
T
3
0
5
RE
X
B
U
R
G
,
I
D
A
H
O
,
8
3
4
4
0
(8
8
8
)
4
6
8
-
7
1
8
0
tigoenergy.com
NEC Rapid Shutdown
Compliant
Standard
Warranty
300
MONTHS
Features
• High input current rating
Now rated for 20A Imp/ 25A Isc to better
accommodate bifacial and high current modules
• Simple, Fast Installation
Snap to standard PV module frame or remove
clips for rack mounting
• PLC Signaling
Rapid shutdown signaling over PV conductors
• Automatic Shutdown
PV array enters rapid shutdown in the event of AC
grid loss
• PVRSS Certified
Tested and UL certified with hundreds of top
inverter models
TS4-A-F
Module-level PV Rapid Shutdown
PN: 002-00093-00 | Rev. 3.1 2022.11.3
Quick Specs
TS4-A-F
Dimensions (W x H x D)138.4 x 139.7 x 22.9mm (5.9 x 5.5 x 0.9in)
Weight 490g (1.1lbs)
Max Current (Imp/Isc)*15A 20A/25A
Max Wattage 700W
*Use local codes/requirements to calculate maximum current.
15A 25A
The TS4-A-F (Fire Safety) is the advanced add-on rapid shutdown
solution that brings smart module functionality to standard PV modules
for higher reliability. Ensure safety by upgrading existing PV systems or
by adding safety features to new installations.
The TS4-A-F complies with NEC 2017 & 2020 690.12 Rapid Shutdown
specifications when installed with the Tigo RSS Transmitter or an inverter
with built-in Tigo certified transmitter.
TS4-A-F TS4-A-F
W
H
W
H
DD
tigoenergy.com
PN: 002-00093-00 | Rev. 3.1 2022.11.3
Electrical Data 15A 25A
Maximum input voltage 90V 80V
Operating voltage range¹16 - 90V 16 - 80V
Maximum input current (Isc)N/A 25A
Maximum input current (Imp)15A 20A
Maximum wattage 700W 700W
¹Maximum output voltage of the TS4 is dependent on the PV module voltage. Refer to PV modules nameplate.
Connections
Module Conductor lengths
0.12m, 0.62m, options
available²
0.62m, options
available²
String Conductor lengths 1.2m, options available²
Connectors MC4, EVO2, options available²
²Contact sales for additional connector and conductor length options. MOQ may apply.
General Data
Operating temperature range
UL:-30°C to +75°C
(-22°F to +167°F)
IEC:-40°C to +85°C
(-40°F to +185°F)
UL/IEC:
-40°C to +80°C
(-40°F to +176°F)
Storage temperature range
-40°C to +85°C
(-40°F to +185°F)
-40°C to +85°C
(-40°F to +185°F)
Recommended fuse rating 20A 30A
Outdoor rating IP68, NEMA 3R IP68
Maximum altitude 2000m 3000m
Efficiency 99.6%99.9%
Communication PLC
Rapid Shutdown UL Listed
(NEC 2017 & 2020 690.12)
Yes
Rapid Shutdown Time Limit 30 secs or less³
Conductor AWG Range 10-12 AWG
PVRSE Controlled Conductors ≤30 Vdc, ≤240VA, ≤8A³
³Limits are based on NEC 690.12 rapid shutdown requirements.
Warranty 25 years
Ordering Information UL/IEC IEC
459-00252-32 TS4-A-F, 15A, 700W, 1500V UL / 1000V IEC, 1.2m Cable, MC4 •
459-00252-62 TS4-A-F, 15A, 700W, 1500V UL / 1000V IEC, 0.62/1.2m Cable, MC4 •
459-00261-32 TS4-A-F, 15A, 700W, 1500V UL / IEC, 1.2m Cable, EVO2 •
459-00261-62 TS4-A-F, 15A, 700W, 1500V UL / IEC, 0.62/1.2m Cable, EVO2 •
486-00252-32 TS4-A-F, 25A, 700W, 1500V UL / 1000V IEC, 0.12/1.2m Cable, MC4 •
486-00252-62 TS4-A-F, 25A, 700W, 1500V UL / 1000V IEC, 0.62/1.2m Cable, MC4 •
486-00261-32 TS4-A-F, 25A, 700W, 1500V UL / IEC, 0.12/1.2m Cable, EVO2 •
486-00261-62 TS4-A-F, 25A, 700W, 1500V UL / IEC, 0.62/1.2m Cable, EVO2 •
488-00252-32 TS4-A-F, 25A, 700W, 1000V IEC, 0.12/1.2m Cable, MC4 •
488-00252-62 TS4-A-F, 25A, 700W, 1000V IEC, 0.62/1.2m Cable, MC4 •
488-00261-32 TS4-A-F, 25A, 700W, 1500V IEC, 0.12/1.2m Cable, EVO2 •
488-00261-62 TS4-A-F, 25A, 700W, 1500V IEC, 0.62/1.2m Cable, EVO2 •
Certifications
UL1741, PVRSS, CSA22.2, IEC 62109
PVRSS certified inverters
For a list of all PVRSS certified inverters, please see: www.tigoenergy.com/ul-pvrss
Module mounting requirements
E469960
Photovoltaic Rapid Shutdown System Equipment, QIJW
FRAME THICKNESS RANGE
GLASS
1.2mm - 3mm min. 30mm
min. 22mm
ALUMINUM FRAME
Module frame specifications
for mounting TS4-A
Additional resources
Solar Input Power 19,500W
Max Allowed PV Power 19,500W
Max PV Power Delivered to BaƩery & AC
Outputs
15,000W
Max DC Voltage (Voc) 500V @ 26A
MPPT Voltage Range 125-425V
StarƟng Voltage 125V
Number of MPPT 3
Max Solar Strings Per MPPT 2
Max DC Current per MPPT (Self LimiƟng) 26A
Max AC Coupled Input
(Micro/String Inverters)
19,200W
AC Output Power 15kW On-Grid & Off-Grid
ConnecƟons 120/240/208V Split Phase
ConƟnuous AC Power with PV 15,000W 62.5A-L (240V)
ConƟnuous AC Power from BaƩeries 12,000W 50A-L (240V)
Surge AC Power 10sec
Surge AC Power 100ms
24,000VA L-L (240V)
30,000VA L-L (240V)
Parallel Stacking Yes - Up to 12
Frequency 60/50Hz
ConƟnuous AC Power with Grid or
Generator
48,000W 200A L-L (240V)
24,000W 200A L-N (120V)
CEC Efficiency 96.5% (Peak 97.5%)
Idle ConsumpƟon Typical—No Load 90W
Sell Back Power Modes Limited to Household/Fully
Grid-Tied
Design (DC to AC) Transformerless DC
Response Time (Grid-Tied to Off-Grid) 5ms
Power Factor +/- 0.9 - 1.0
Total Harmonic DistorƟon (THD) ≤ 3%
Fault Current 5sec
Fault Current 100ms
94A w/ PV | 75A w/o PV
120A
BaƩery (opƟonal) Output Power 12,000W
Dimensions (H x W x D) 31.8” x 18.3” x
10.9”
Weight (package) 135 lbs
Enclosure IP65 / NEMA 3R
Ambient Temperature -40~60°C, >45°C
DeraƟng
InstallaƟon Style Wall-Mounted
Wi-Fi & LAN CommunicaƟon Included
Standard Warranty (verified by HALT TesƟng) 10 Years
General
Type Lead-Acid or Li-Ion
Nominal DC Input 48V
Capacity 50 — 9900Ah
Voltage Range 43.0 — 63.0V
ConƟnuous BaƩery Charging Output 275A
Charging Curve 3-Stage w/ EqualizaƟon
Grid to BaƩ Charging Efficiency 96.0%
External Temperature Sensor Included
Current Shunt for Accurate % SOC Integrated
External Gen Start Based on Voltage
or %SOC
Integrated
CommunicaƟon to Lithium BaƩery CanBus & RS485
ProtecƟons & CerƟficaƟons
Electronics CerƟfied Safety by SGS Labs to NEC
& UL Specs - NEC 690.4B & NEC 705.4/6
Yes
Grid Sell Back — UL1741-2010/2018, IEEE1547a
-2003/2014, FCC 15 Class B, UL1741SB, CA Rule
21, HECO Rule 14H
Yes
PV DC Disconnect Switch — NEC 240.15 Integrated
Ground Fault DetecƟon — NEC 690.5 Integrated
PV Rapid Shutdown Control — NEC 690.12 Integrated
PV Arc Fault DetecƟon — NEC 690.11 Integrated
PV Input Lightning ProtecƟon Integrated
PV String Input Reverse Polarity ProtecƟon Integrated
AC Output Breakers - 200A Integrated
200A x 2 BaƩery Breaker / Disconnect Integrated
Surge ProtecƟon DC Type II / AC
Type II
15K-2P-N
UL Model:
“Limitless 15K-LV”
STACK’D SERIES SPECIFICATIONS
High Capacity 38.4kWh
Up to 10 units in parallel
Modular Design
Each module has a capacity of 4.8kWh,
with each Stack supporting 2-8 modules.
High Power 15kW
Whole home backup
Live Communications
Real time display, mobile access,
established closed-loop communications
10 year Warranty
20 year serviceable
Safe for Home &
Environment
Cobalt Free, low voltage
UL 1642, UL 1973, UN 38.3, UL 9540
STACK’D SERIES
Flexible Design that is expandable. Choose from 2, 3, 4, 5, 6, 7, or 8 modules.
# of Modules*Capacity Power Surge(10s)Weight Height
2 Modules 9.6kWh 9.6kW 14.4kW 304lbs 25.25in
3 Modules 14.4kWh 14.4kW 16.8kW 412lbs 30.5in
4 Modules 19.2kWh 15kW 24kW 520lbs 35.75in
5 Modules 24kWh 15kW 24kW 628lbs 41in
6 Modules 28.8kWh 15kW 24kW 736lbs 46.25in
7 Modules 33.6kWh 15kW 24kW 844lbs 51.5in
8 Modules 38.4kWh 15kW 24kW 952lbs 56.75in
*Additional Modules can be added in the future.
Ordering Information
Product Number
BMS/Base HG-MC100-200M2
4.8kWh Module HG-FS48100-15OSJ1
35
.
7
5
i
n
5
.
2
5
i
n
7
i
n
7
.
7
5
i
n
29 in 15.75 in
www.homegridenergy.com Stack’d Series 01
BMS
4.8kWh
4.8kWh
4.8kWh
4.8kWh
BASE
STACK’D SERIES SPECIFICATIONS
Battery Chemistry Technology Lithium Iron Phosphate
Total Energy [kWh]9.6, 14.4, 19.2, 24, 28.8, 33.6, 38.4
Continuous Power Output [kW]9.6, 14.4, 15, 15, 15, 15, 15
Capacity [Ah] 200, 300, 400, 500, 600, 700, 800
Nominal DC Voltage [V]48
DC Voltage Range [V]46-56
Recommended Charge Current [A]200, 300, 312.5, 312.5, 312.5, 312.5, 312.5
Max Discharge Current (Continuous) [A]200, 300, 312.5, 312.5, 312.5, 312.5, 312.5
Max Pulse Current DC (for 10 sec) [A]300, 350, 500, 500, 500, 500, 500
Charge Temperature [F] 32-113
Discharge Temperature [F]14-140
Dimensions [WxDxH, inch]29 x 15.75 x 25.25, 30.5, 35.75, 41, 46.25, 51.5, 56.75
Weight [lbs] 304, 412, 520, 628, 736, 844, 952
Enclosure Rating IP55
Mounting Options Floor Standing
UL 1642, UL 1973, UN 38.3, UL 9540
Warranty 10 Years
Service Plan 20 Years Serviceable
Scalability Units in parallel (384 kWh)
Communication CAN/RS485
>98%
Compatible Inverters Sol-Ark, Schneider, SMA, Growatt, Solis, Sofar, Sermatec,
Victron, Studer, Goodwell, Outback
www.homegridenergy.com Stack’d Series 02
Generac Power Systems, Inc.
S45 W29290 Hwy. 59, Waukesha, WI 53189
www.Generac.com 1-888-GENERAC (1-888-436-3722)
Inverter
Model: X7602, X11402
Solar-plus-storage is simple with the Generac PWRcell Inverter. This bi-directional, REbus™-
powered inverter offers a simple, efficient design for integrating smart batteries with solar. Ideal for
self-supply, backup power, zero-export and energy cost management, the PWRcell inverter is the
industry’s most feature-rich line of inverters, available in single-phase and three-phase models.
ADDITIONAL FEATURES
• Single inverter for grid-tied solar with smart battery integration
• Simplified system design: No autotransformer or battery inverter needed
• User-selectable modes for backup power, self-supply, time-of-use and zero-export
• Free system monitoring included via PWRview Web Portal and Mobile App
FEATURES:
No autotransformer or
battery inverter needed
User-selectable modes
Free system monitoring
AC OUTPUT/ GRID-TIE MODEL X7602 MODEL X11402
RATED AC POWER OUTPUT 7600 W 11400 W
AC OUTPUT VOLTAGE 120/240, 1Ø VAC 120/208, 3Ø VAC
AC FREQUENCY 60 Hz 60 Hz
MAXIMUM CONTINUOUS OUTPUT CURRENT 32 A, RMS 32 A, RMS
GROUND-FAULT ISOLATION DETECTION Included Included
CHARGE BATTERY FROM AC Yes Yes
THD (CURRENT)< 2 %< 2 %
TYPICAL NIGHTTIME POWER
CONSUMPTION < 7 W < 7 W
AC OUTPUT/ BACKUP MODEL X7602 MODEL X11402
RATED AC BACKUP POWER OUTPUT 8000 W 8000 W
MAXIMUM AC BACKUP POWER OUTPUT 12000 W 12000 W
AC BACKUP OUTPUT VOLTAGE 120/240, 1Ø VAC 120/240, 1Ø VAC
AC FREQUENCY 60 HZ 60 HZ
AC CIRCUIT BREAKER 50 A 50 A
THD (VOLTAGE)< 2 %< 2 %
AUTOMATIC SWITCHOVER TIME < 1 Seconds < 1 Seconds
TYPICAL NIGHTTIME POWER
CONSUMPTION 30 W 30 W
DC INPUT MODEL X7602 MODEL X11402
DC INPUT VOLTAGE RANGE 360-420 VDC 360-420 VDC
NOMINAL DC BUS VOLTAGE 380 VDC 380 VDC
MAX INPUT CURRENT 20 A 30 A
REVERSE-POLARITY PROTECTION YES YES
GROUND-FAULT ISOLATION DETECTION YES YES
TRANSFORMERLESS, UNGROUNDED YES YES
DC INPUT/ BATTERY MODEL X7602 MODEL X11402
MAXIMUM CONTINUOUS POWER 8000 W 8000 W
INTERNAL DC DISTRIBUTION BREAKERS 4X 2P30A 4X 2P30A
DC FUSES ON PLUS AND MINUS 40 A 40 A
2-POLE DISCONNECTION YES YES
EFFICIENCY MODEL X7602 MODEL X11402
PEAK EFFCIENCY 97 %98 %
CEC WEIGHTED EFFCIENCY 96.5 %97.5 %
Generac Power Systems, Inc.
S45 W29290 Hwy. 59, Waukesha, WI 53189
www.Generac.com 1-888-GENERAC (1-888-436-3722)
Specifications
Specifications subject to change without notice.
FEATURES AND MODES
ISLANDING3 Yes
GRID SELL Yes
SELF CONSUMPTION Yes
PRIORITIZED CHARGING FROM RENEWABLES Yes
GRID SUPPORT - ZERO EXPORT Yes
ADDITIONAL FEATURES
SUPPORTED COMMUNICATION INTERFACES CANbus, RS4854, Ethernet
SYSTEM MONITORING PWRview Web Portal and Mobile App
CRITICAL LOADS DISCONNECT3 Yes
MANUAL INVERTER BYPASS SWITCH Automatic
WARRANTY 10 Years
STANDARDS COMPLIANCE
SAFETY UL1741 SA, CSA 22.2
GRID CONNECTION STANDARDS IEEE1547, Rule 21, Rule 14H
EMISSIONS FCC part15 class B
DIMENSIONS AND INSTALLATION SPECIFICATIONS
WIRE GAUGE RANGE 10 - 8 AWG
TOTAL AC KNOCKOUTS X SIZE 2“ x 0.75“, 2 x 1“
TOTAL DC KNOCKOUTS X SIZE 5“ x 1“
DIMENSIONS (L,W,H)24.5“ x 19.25“ x 8“
WEIGHT 62.7 lb
COOLING Forced convection
NOISE < 40 dBA
OPERATING TEMPERATURE -20 to 50 °C*
PROTECTION RATING NEMA 3R
INSTALLATION GUIDELINES
BATTERY TYPES SUPPORTED PWRcell battery module
MODULE STRING SIZE PER PV LINK OPTIMIZER 2-9 PV modules
MAXIMUM RECOMMENDED DC POWER FROM PV 10kW (1Ø), 15kW (3Ø)
BATTERIES PER INVERTER Up to 2
3 3Ø inverters offer islanding for 1Ø loads, 4 Modbus,
*Reduced power at extreme temperatures