HomeMy WebLinkAboutAPPROVED STRUCTURAL CALCS - 23-00305 - 366 Oaktrail Dr - Solar PanelsAuthor Name Author Email Author Phone No.:
Larry Beesley Larry.Beesley@rexburg.org 208-372-2176
Description : 366 Oaktrail Dr - Solar Panels
Address : 366 Oaktrail Dr
Record Type : Solar Panels
Document Filename : Alan Christensen - Structural.pdf
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 23-00305
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
1 Stamp Larry Beesley : Building Open 1 Approved - Building Inspector
Solar Panels
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
Freedom Forever LLC
43445 Business Park Dr., STE 110
Temecula, CA, 92590
Attn.: To Whom It May Concern
re: Job 23-06002 : ALAN CHRISTENSEN - 013878
Prepared By:
PZSE, Inc. - Structural Engineers
Roseville, CA
May 19, 2023
If you have any questions on the above, do not hesitate to call.
The following calculations are for the structural engineering design of the photovoltaic panels located at
366 OAKTRAIL DRIVE,, REXBURG, ID 83440. After review, PZSE, Inc. certifies that the roof structure has
sufficient structural capacity for the applied PV loads.
366 OAKTRAIL DRIVE,
REXBURG, ID 83440
1478 Stone Point Drive, Suite 190, Roseville, CA 95661
T 916.961.3960 F 916.961.3965 W www.pzse.com
Experience | Integrity | Empowerment
Paul Zacher
Digitally signed
by Paul Zacher
Date:
2023.05.19
15:02:11-07'00'
Gravity Loading
Project: ALAN CHRISTENSEN -- Job #: 23-06002
Date: 5/19/2023 Engineer: PZSE
50 psf
0.9 ASCE 7-16 Table 7.3-1
1.1 ASCE 7-16 Table 7.3-2
1
35 psf ASCE 7-16 Eq 7.3-1
N/A
N/A
35 psf
ASCE 7-16 Eq 7.4-1
1.000 ARRAY 1
34.7 psf ARRAY 1
18.40 psf ARRAY 1
4.00
1.50
0.48
0.00 Ceiling Not Vaulted
0.02
6.0 psf
6.6 psf
2x4 Top Chords @ 24"o.c.
Roof Snow Load Calculations
pg = Ground Snow Load =
Ce = Exposure Factor =
Ct = Thermal Factor =
I = Importance Factor =
Per ASCE 7-16, minimum values of Pf shall apply to hip and gable roofs with slopes less
than 15◦.
Roof Dead Load ARRAY 1
Roof Plywood
pf = 0.7 Ce Ct I pg
where pg ≤ 20 psf, Pf min = I x pg =
where pg > 20 psf, Pf min = 20 x I =
Therefore, pf = Flat Roof Snow Load =
ps = Cspf
Ps = Sloped Roof Snow Load =
Cs = Slope Factor =
Roof Live Load =
DL Adjusted to 25 Degree Slope
Miscellaneous
Vaulted Ceiling
Total Roof DL ARRAY 1
PV Dead Load = 3 psf (Per Freedom Forever LLC)
Note: Roof live load is removed in area's covered by PV array.
Composition Shingle
2 of 6
Wind Calculations
Project: ALAN CHRISTENSEN -- Job #: 23-06002
Date: 5/19/2023 Engineer: PZSE
115 mph
C
Gable
25 degrees
12 ft
50 ft
6.5 sf
4.8 ft
6.0 ft
8.2 ft
Zone 3
Pressure Equalization Factor,γa 0.8
Eq. 26.10-1
0.85 Table 26.10-1
1 26.8 (Figure 26.8-1)
0.85 Table 26.6-1
0.84 26.9
115 mph Fig. 26.5-1B
II Table 1.5-1
qh = 20.5 psf
12.31
Zone 1 Zone 2 Zone 3 Positive
GCp =-1.50 -2.50 -3.25 0.58
Uplift Pressure =-14.77 psf -24.62 psf -32.04 psf 16.00 psf
Uplift Edge Pressure=-22.15 psf -36.92 psf -48.06 psf 24.00 psf
Attachment Dead Load =3.00 psf 3.00 psf 3.00 psf
Max Rail Span Length =2.00 2.00 2.00
Max Rail Span Length Edge =2.00 0.00 0.00
Longitudinal Length =3.25 3.25 3.25
Attachment Tributary Area =6.50 6.50 6.50
Attachment Tributary Area Edge =6.50 0.00 0.00
Attachment Uplift =-84.00 -148.00 -197.00
Attachment Uplift Edge=-132 0 0
-197 lb
530 lb
Therefore, OK
104 lb
142 lb
Therefore, OK
Fastener =#12 inch
Number of Fasteners =2
Minimum Threaded Embedment Depth =1.5 inch
Withdraw Capacity Per Inch =109 lb NDS Eq 11.2.2
Allowable Withdraw Capacity =522 lb
Therefore, OK
Embedment Depth Reduction Factor 0.694444444
Lateral Force from Gravity Loads=104 lb
Attachment Lateral Capacity =275 lb lb NDS Table 11M
275 lb capacity > 104 lb demand Therefore, OK
Wood Screw Shear Capacity Check
Input Variables
Wind Speed
Exposure Category
Roof Shape
Mean Roof Height
Roof Slope
142 lb capacity > 104 lb demand
522 lb capacity > 197 lb demand
Wood Screw Uplift Capacity Check
Design Wind Pressure Calculations
Ke (Elevation Factor)=
Controlling C&C Wind Zone
Per ASCE 7-16 Components and Cladding
Maximum Design Uplift =
Standoff Uplift Capacity =
530 lb capacity > 197 lb demand
Effective Wind Area
Building Least Width
Roof Zone Edge Distance, a
Standoff Uplift Calculations
Kz (Exposure Coefficient) =
Kzt (topographic factor) =
Kd (Wind Directionality Factor) =
V (Design Wind Speed) =
qh = 0.00256 * Kz * Kzt * Kd *Ke* V^2
Array Edge Factor Length
Panel to Building Edge, d1
Wind Pressure P = qh*(G*Cp)*γe*γa
Standoff Lateral Check - RockIt Smart Slide-Rafters
Maximum Lateral Demand =
Standoff Lateral Capacity =
Risk Category =
0.6 * qh =
Standoff Uplift Check - RockIt Smart Slide-Rafters
3 of 6
Wind Calculations
Project: ALAN CHRISTENSEN -- Job #: 23-06002
Date: 5/19/2023 Engineer: PZSE
4 of 6
Framing Check
Project: ALAN CHRISTENSEN -- Job #: 23-06002
Date: 5/19/2023 Engineer: PZSE
ARRAY 1 PASS
Dead Load 6.6 psf
PV Load 3.0 psf
Snow Load 34.7 psf
Governing Load Comb.DL + SL
Total Load 44.3 psf
Fb (psi) =f'b x Cd x Cf x Cr (NDS Table 4.3.1)
875 x 1.15 x 1.5 x 1.15
Allowed Bending Stress = 1735.7 psi
(wL^2) / 8
=421.158 ft#
=5053.89 in#
Actual Bending Stress = (Maximum Moment) / S
= 1650.3 psi
L/180 (E = 1400000 psi Per NDS)
=0.411 in
Deflection Criteria Based on =
(w*L^4) / (185*E*I)
=
=L/733 <L/180 Therefore OK
Allowed Deflection (Live Load) =L/240
0.308 in
(w*L^4) / (185*E*I)
L/592 <L/240 Therefore OK
Member Area =Fv (psi) =135 psi (NDS Table 4A)
Allowed Shear = Fv * A =Max Shear (V) = w * L / 2 =273 lb
Continuous Span
Actual Deflection (Total Load) =
Allowed > Actual -- 95.1% Stressed -- Therefore, OK
0.101 in
SPF#2
Member Spacing
@ 24" o.c.
Maximum Moment =
(True Dimensions)
5.3 in^2
Actual Deflection (Live Load) =
Allowed > Actual -- 38.6% Stressed -- Therefore, OK
Check Shear
709 lb
w = 89 plf
Member Properties
I (in^4)
5.36
Lumber Sp/Gr
0.125 in
2x4 Top Chords @ 24"o.c.
Check Deflection
Check Bending Stress
Allowed Deflection (Total Load) =
Member Span = 6' - 2"
Note: Attachments may be Unstaggered.
Member Size
2x4
S (in^3)
3.06
5 of 6
Project: ALAN CHRISTENSEN -- Job #: 23-06002
Date: 5/19/2023 Engineer: PZSE
Level Area Weight (psf)Weight (lb)
Roof 2000 sf 6.6 psf 13200 lb
Ceiling 2000 sf 6.0 psf 12000 lb
Vinyl Siding 720 sf 2.0 psf 1440 lb (8' Wall Height)
Int. Walls 360 sf 6.0 psf 2160 lb
28800 lb
3.0 psf
284 sf
852 lb
2880 lb
852 lb
3.0%
Per 2018 IEBC §502.5, the increase in the lateral demand/capacity ratio of the
existing structure due to the installation of the PV system is less than 10%.
Therefore, the existing structure may remain unaltered.
2880 lb > 852 lb, Therefore OK
Lateral Check: 2018 IEBC
Existing Weight of Effected Building
Existing Weight of Effected Building
Proposed Weight of PV System
Weight of PV System (Per Freedom Forever LLC)
Approx. Area of Proposed PV System
Approximate Total Weight of PV System
10% Comparison
10% of Existing Building Weight (Allowed)
Approximate Weight of PV System (Actual)
Percent Increase
6 of 6