HomeMy WebLinkAboutPLANS - 23-00458 - 318 Polo Dr - Solar PanelsUtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
BLAKEMAN RESIDENCE
318 POLO DR
REXBURG, IDAHO 83440
Sheet 1 of 9
PLANT LOCATION
7.6 KW AC PHOTOVOLTAIC SYSTEM Scale
NTS
REVISION 1
PLANT LOCATION:
BLAKEMAN RESIDENCE
318 POLO DR
REXBURG, IDAHO 83440
SOLAR EDGE SE7600H-US INVERTER
25 HANWHA Q.PEAK BLK-G4.1 295
PV PANELS
SOLAR EDGE SE7600HUB-US INVERTER
31 SOLARIA POWERXT-400R-PM PANELS
SOLAR EDGE SE5000H-US INVERTER
17 LG LG335N1C-A5 335 PV PANELS
(2) SOLAR EDGE SE7600H-US INVERTER
47 HANWHA Q.PEAK DUO BLK-G5 310
PV PANELS
SOLAR EDGE SE7600H-US INVERTER
25 JA JAM60S03-310/PR PV PANELS
SOLAR EDGE SE3800H-US INVERTER
14 PANASONIC VBHN320KA03 320
PV PANELS
SOLAR EDGE SE7600H-US INVERTER
24 BLUESUN HEX5 BSM415M10-54HPH
SOLAR EDGE SE7600HUB-US INVERTER
25 JINKO JKM320M-60L PV PANELS
REVISION 1: BP
PLAN BY: BRYCE PETERSON
SOLAR EDGE SE7600HUB-US INVERTER
25 VIKRAM SOMERA VSMHBB.60.365
UPGRADED MODULE TO 415W
(SHEETS 1 - 9)
UtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
INSTALL SITE
Scale
NTSLIMITS OF CONSTRUCTION
APPROX. 40' DC RUN
(IN ATTIC WHERE AVAILABLE)
CONCRETE
DRIVEWAY
SOLADECK
JUNCTION
BOX (S)
SOLAR EDGE SE7600H-US INVERTER
(LOCATED NEXT TO SERVICE) EXISTING 125A SERVICE
ENTRANCE PANELBOARD
Sheet 2 of 9
PHOTOVOLTAIC SYSTEM
COMBINER PANEL 100A, 120/240
VAC LOAD CENTER
DEDICATED PHOTOVOLTAIC SYSTEM AC DISCONNECT
DEDICATED BATTERY SYSTEM AC
DISCONNECT
(LOCATED IN SIGHT OF BATTERY)
DEDICATED PV SYSTEM STOP
DISCONNECT
(LOCATED NEXT TO SERVICE)
SOLAR BOM
NEW SOLADECK JUNCTION BOX (SOLTECTION RJ-1) _2_ QTY
NEW JUNCTION BOX (SOLTECTION RU-2LP) _1_ QTY
RAIL (SNAPNRACK SERIES 100)= _14_ (14 FT LENGTH) QTY
SPLICES (SNAPNRACK SERIES 100)= _6_ QTY
MID CLAMP (SNAPNRACK SERIES 100) = 40 QTY
END CLAMP (SNAPNRACK SERIES 100) = 16 QTY
STANDOFFS FEET AND LAGS (SNAPNRACK SERIES 100) = 48 QTY EACH
Portrait = 4 panels per 14’ rail
Landscape = 2 panels per 14” rail
Portrait = 1 rail to 2 panels (360W/400W = 2 rails to 3 panels)
Landscape = 1 rail to 1 panel
Splices = 2 for every consecutive 4 panels portrait (3 panels for
360W/400W)/ 2 panels landscape
End Clamps = 2 on every end
Mid Clamps = 2 on every joint between panel
7.6 KW AC / 9.9 KW DC PHOTOVOLTAIC
SYSTEM
GENERAL NOTES:
ALL CONSTRUCTION / INSTALLATION SHALL COMPLY WITH:
2017 NATIONAL ELECTRICAL CODE (NEC)
2018 INTERNATIONAL FIRE CODE (IFC)
2018 INTERNATIONAL BUILDING CODE (IBC)
2018 INTERNATIONAL RESIDENTIAL CODE (IRC)
ALL DIMENSIONS SHOWN ARE APPROXIMATE
UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL PV SYSTEM
COMPONENTS LOCATED AT SERVICE ENTRANCE
ALL CONDUITS ON ROOF SHALL BE A MINIMUM OF ½” OFF ROOF
CONSTRUCTION LIMITS: ALL IMPROVEMENTS AND ACCESS
SHALL OCCUR WITHIN PLANT PROPERTY LINES
EXISTING 200A INTERIOR
LOADS PANEL LOCATED IN
BASEMENT
NEW 200A RATED SUB PANEL
(LOCATED NEXT TO SERVICE)
SOLADECK JUNCTION BOX (S)
ONE PER ARRAY APPROX. 40' DC RUN
(IN ATTIC WHERE
AVAILABLE)
SOLADECK JUNCTION
BOX (S)
ONE PER ARRAY
DEDICATED PV METER SOCKET
BLAKEMAN RESIDENCE
318 POLO DR
REXBURG, IDAHO 83440
SOLAR EDGE SE7600H-US INVERTER
24 BLUESUN HEX5 BSM415M10-54HPH
UtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
Scale
NTS
Temperature Correction for Largest String (Per NEC Article 690.7):
Voc = 41.0 Vdc Temperature Coefficient(Voc) = -0.27%/ CVmax = Voc +
[(Tlow** - 25 C) x (-0.27% x Voc)]Vmax = 41.0 Vdc + [(-16 C - 25 C) x
(-0.27% x 41.0 Vdc)]Vmax = 45.5 Vdc (<48 Vdc) Maximum Input DC
Voltage for SolarEdge S440 = 60.0 V dc
**Solarabcs.org extreme low temperature for Ogden
SUBARRAY #1:
Maximum System Voltage (Vmax)
Inverter Maximum Voltage Rating = 500 Vdc
Rated Maximum Power Point Voltage (Vmpp) For 240 Vac grid connection =
350 Vdc
Maximum Circuit Current (Imax) Maximum Input Rating of the Inverter = 15
Adc/string
For 2 string system = 30 Adc
Rated Maximum Circuit Current (Impp)
The Lower Value of the following:
1) System power (STC)/Vmp =9960 W / 379.6 Vdc = 26.24 A
2) Inverter Maximum Output Current = 32 A at 240 Vac ARRAY WIRING
9960 DC WATT PHOTOVOLTAIC ARRAY
REFER TO THREE LINE WIRING DIAGRAM
FOR CONTINUATION
WIRE COLORS DC:
NEGATIVE - BLACK
POSITIVE - RED
WIRE COLORS AC:
HOT - BLACK and RED
NEUTRAL - WHITE
GROUND: - GREEN OR BARE
2 #10 THWN-2 CU PV WIRE PER STRING
1 #6 AWG BARE CU GND (EGC) BONDED TO RAIL WITH
WEEBL 6.7 LUG AND CLIP ASSEMBLIES.
REMAINDER OF ARRAY GROUNDED PER MANUFACTURER'S SPECIFICATIONS. NEC.690.43
SOLAR EDGE POWER OPTIMIZERS TO BE GROUNDED
WITH SST STAR WASHER PER MANUFACTURER'S SPECIFICATIONS
ONE- LINE ARRAY DIAGRAM
Each DC Panel:
JAJAM60S03-310/PR
Source Circuit:
12 Panels:
BLUESUN HEX5 BSM415M10-54HPH
With S440 Power Optimizers
Power=4980 Watts dc
Vmp=379.6 Vdc
Imp= 13.13 Adc
12 Panels:
BLUESUN HEX5 BSM415M10-54HPH
With S440 Power Optimizers
Power=4980 Watts dc
Vmp=379.6 Vdc
Imp= 13.13 Adc
Total Array Specs:
24 panels:
Power =9960 Watts dc
SE3000H-US 12.5
SE3800H-US 16
SE5000H-US 21
SE6000H-US 25
SE7600H-US 32
SE10000H-US 42
SE11400A-US 47.5
Sheet 3A of 9
Each DC Panel:
JINKO JKM375M-6RL3-B
Each DC Panel:
BLUESUN HEX5 BSM415M10-54HPH
7.6 KW AC / 9.9 KW DC PHOTOVOLTAIC
SYSTEM
SOLAR EDGE SE7600H-US INVERTER
24 BLUESUN HEX5 BSM415M10-54HPH
BLAKEMAN RESIDENCE
318 POLO DR
REXBURG, IDAHO 83440
UtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
Scale
NTS Sheet 4 of 9
4 #10 THWN-2 CU PV WIRE1 #10 THWN-2 CU GND3/4" EMT CONDUITSOLADECK JUNCTION BOX TRANSITION BOX
AC ONE LINE
DIAGRAM
A*-EXISTING MAIN SERVICE (SC1624M100S)
B*-EXISTING SUBPANEL (SQUARE D 125A)
C*-SOLAREDGE 7600W HD WAVE INVERTER (SE7600H-US)
D*-60A/2P DISCONNECT (EATON DG222URB)
*WE WILL BE ADDING ONE 125A BREAKER TO THE MAIN SERVICE PANEL TO PROTECT THE EXISTING HOUSE FEEDER WIRES IN COMPLIANCE WITH NEC 705.12(B)(2)(1)(B)PV METERB*- PV METER BOX
A*
100A MAIN
OTHER
LOADS
E*-30A/2P DISCONNECT (EATON DG221URB)
200A/2P
40A/2P
OTHER
LOADS
(2)#6 AWG CU
(1)#6 AWG NEUTRAL CU
(1)#6 AWG EGC CU
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR
(2)#8 AWG CU
(1)#8 AWG NEUTRAL CU
(1)#8 AWG EGC CU
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR
(2)#10 AWG CU
(1)#10 AWG NEUTRAL CU
(1)#10 AWG EGC CU
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR
*WE WILL BE ADDING ONE 125A BREAKER
TO THE MAIN SERVICE PANEL TO PROTECT
THE EXISTING HOUSE FEEDER WIRES IN
COMPLIANCE WITH NEC 705.12(B)(2)(1)(B)
7.6KW SOLAR INVERTER
C*
DC CIRCUITS CONTINUE
ON PAGE 5
ETHERNET LINE TO HOME
NETWORK
40A/2P
B*
OTHER
LOADS
125A SUBPANEL
(2)#8 AWG CU
(1)#8 AWG NEUTRAL CU
(1)#8 AWG EGC CU
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR
(2)#2 AWG CU / #2 AWG AL
(1)#2 AWG NEUTRAL CU / #2 AWG AL
(1)#8 AWG EGC CU / #6 AWG AL
1 ½ ” EMT MIN. W/ THWN-2 OUTDOOR /
SER CABLE INDOOR
(2)3/0 AWG CU / 4/0 AWG AL
(1)3/0 AWG NEUTRAL CU / 4/0 AWG AL
(1)#6 AWG EGC CU / #4 AWG AL
2” EMT MIN. W/ THWN-2 /SER CABLE
(2)1/0 AWG CU / 2/0 AWG AL
(1)1/0 AWG NEUTRAL CU / 2/0 AWG AL
(1)#6 AWG EGC CU / # 4 AWG AL
1 ½ ” EMT MIN. W/ THWN-2 OUTDOOR /
SER CABLE INDOOR
(2)#1 AWG CU / 1/0 AWG AL
(1)#1 AWG NEUTRAL CU / 1/0 AWG AL
(1)#6 AWG EGC CU / #4 AWG AL
1 ½ ” EMT MIN. W/ THWN-2 OUTDOOR /
SER CABLE INDOOR
(2)#2 AWG CU / #2 AWG AL
(1)#2 AWG NEUTRAL CU / #2 AWG AL
(1)#8 AWG EGC CU / #6 AWG AL
1 ½ ” EMT MIN. W/ THWN-2 OUTDOOR /
SER CABLE INDOOR
OGDEN WIRE SIZES NEED TO BE CHANGED TO:
(2)#8 AWG CU
(1)#8 AWG NEUTRAL CU
(1)#10 AWG EGC CU
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM CABLE INDOOR
100A/2P
BLAKEMAN RESIDENCE
318 POLO DR
REXBURG, IDAHO 83440
60A/2P VISIBLY OPEN
DISCONNECT (LOCATED
WITHIN 3 FT OF SERVICE)
D*
EXISTING INTERIOR SUB PANEL
(LOCATED IN INTERIOR)
7.6 KW AC / 9.9 KW DC PHOTOVOLTAIC
SYSTEM
SOLAR EDGE SE7600H-US INVERTER
24 BLUESUN HEX5 BSM415M10-54HPH
NEW JUNCTION BOX
(SOLTECTION RU-2LP)
G
POS
NEG
G
POS
NEG
UtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
Scale
NTS Sheet 5 of 9
13
*5
*5
*5
*5
*5
*5
*5
*5
*4 *3
*1
EXISTING 200A
MAIN SERVICE PANEL
TRANSITION BOX SOLADECK
JUNCTION BOXES
IN ATTIC
(EXTERIOR
*7,*12)
(NEXT TO
SOLAR
BREAKER
*2,*6)
AC INPUT 2
UTILITY AC INPUT 1
A
C
I
N
P
U
T
3
AC OUTPUT
DC INPUT
CRITICAL
LOADS
B
THIS IS NOT A PARALLEL
GENERATION SYSTEM
MAIN SERVICE PANEL 4 #10 THWN-2 CU PV WIRE1 #10 THWN-2 CU GND3/4" EMT CONDUITSOLADECK JUNCTION BOX TRANSITION BOX
1
DC
12
DC
DC
DC DC
DC
1
DC
DC DC
12
9960 DC WATT PHOTOVOLTAIC ARRAY 1
2 #10 AWG 600V PV / USE-2 PER STRING- BLACK and RED
1 #6 AWG BARE CU GND (EGC) BONDED TO RAIL WITH
WEEBL 6.7 LUG AND CLIP ASSEMBLIES.
REMAINDER OF ARRAY GROUNDED PER MANUFACTURER'S SPECIFICATIONS. NEC.690.43
SOLAR EDGE S440 POWER OPTIMIZERS TO BE GROUNDED
WITH SST STAR WASHER PER MANUFACTURER'S SPECIFICATIONS
DC THREE LINE
DIAGRAM
G
POS
NEG
G
POS
NEG
G
POS
NEG
G
POS
NEG
POS
NEG
G
POS
NEG
NEW SOLADECK JUNCTION BOX
(SOLTECTION RJ-1)
2- #10 THWN-2-CU BLACK
2- #10 THWN-2-CU RED
1- #10 THWN-2-CU GREEN
¾”EMT CONDUIT AND/OR ¾” SEALTITE
FLEXIBLE CONDUIT, TO BE GROUNDED AT
EVERY NON METALLIC JUNCTION WITH
GROUND BUSHINGS
1/2" MC CABLE
2 #10 MC CABLE
1 #10 CU GND
IN ATTIC SECURED ACCORDING TO NEC 690.31
(D)(1) AND
TO BE GROUNDED AT EVERY NON METALLIC
JUNCTION WITH GROUND BUSHINGS
1/2" MC CABLE
2 #10 MC CABLE
1 #10 CU GND
IN ATTIC SECURED ACCORDING TO NEC 690.31
(D)(1) AND
TO BE GROUNDED AT EVERY NON METALLIC
JUNCTION WITH GROUND BUSHINGS
CONTINUATION ON PAGE 4
TO INVERTER
*SOLAR EDGE S440 OPTIMIZERS FOR EACH PANEL
BLAKEMAN RESIDENCE
318 POLO DR
REXBURG, IDAHO 83440
7.6 KW AC / 9.9 KW DC PHOTOVOLTAIC
SYSTEM
SOLAR EDGE SE7600H-US INVERTER
24 BLUESUN HEX5 BSM415M10-54HPH
ARRAY SELF WEIGHT
24 BLUESUN 415W PANELS 22 KG = 48.5 LBS/PANEL + SNAP-N-RACK
RACKING MOUNTING HARDWARE:24 X 41.888 = 1006
A = L X W (PANEL): 67.87” X 44.65 = 21.04 SQ FT X 24 = 505
TOTAL SQ FT OF PLANE VIEW ROOF AREA = 2263
PERCENTAGE OF ROOF AREA COVERED IN SOLAR PANELS = 22.32%
(IFC 1204.2.1.2)
ARRAY: 1006 LBS / 505 SQ FT = 2.3 PSF
MAX WEIGHT PER ANCHOR = 44.6 LBS (FOR 4’0” SPANS)
PULL OUT STRENGTH
CONNECTOR 5/16 LAG BOLT 48 STANDOFFS (48 LAGS) 48 X 3”
EMBED X 210 LBS = 30240 LBS
WEATHER LOADING
GROUND SNOW: 50PSF
WIND SPEED: 160MPH
EXPOSURE CATEGORY: B
LIMITS OF CONSTRUCTION
UtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
MOUNTING AND
WEIGHT LOAD
Scale
NTS
MEETS OR EXCEEDS 2018 IBC IRC CONSTRUCTION STANDARDS
CASE 1 Load Calculations 2X4 construction, 24" on center trusses
ROOF LOAD BEARING
______ LBS / ___ STANDOFFS = _____LBS
TOTAL WEIGHT = PANELS + HARDWARE
1412.5 LBS
1412.5 LBS / 460.75 SQ FT=
3.065 PSF
DEDICATED PHOTOVOLTAIC
SYSTEM AC DISCONNECT
Sheet 6 of 9
TIMES
PANELS
BY 630
ALL ROOF
PENETRATIONS MUST
BE PROPERLY
FLASHED. IRC
M2302.2.2.
THIS INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS
SPECIFIED IN SECTION 1204 OF THE 2018 INTERNATIONAL FIRE CODE.
ROOF RACKING SUPPORT SPACING NOT TO EXCEED 4’ SPACING. ALL
SUPPORTS MUST BE STAGGERED FROM ONE ROW OF RACKING TO
THE NEXT SO NOT ALL SUPPORTS ARE BEARING ON THE SAME
TRUSSES
SOLAR PV MODULES CANNOT BE INSTALLED OVER OR BLOCK ANY ATTIC
VENTS, PLUMBING VENTS, FURNACES OR WATER HEATER VENTS, ETC
ALL WIRING MUST BE SUPPORTED BY DEVICES OR MECHANICAL MEANS
DESIGNED AND LISTED FOR SUCH USE AND WIRING MUST BE
PERMANENTLY AND COMPLETELY HELD OFF THE ROOF SURFACE.
36 INCH FIRE
DEPARTMENT
SETBACK
36” PATHWAYS TO RIDGE
WE WILL BE OBSERVING IFC 1204.2 EXCEPTION 1TO BE USED WHEN USING A BARN OR NON INHABITED SPACE FOR ROOF TOP INSTALL
THIS INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS
SPECIFIED IN THE UTAH AMENDED SECTIONS OF THE 2018 IRC THAT PERTAIN
TO ENERGY STORAGE SYSTEMS INCLUDING SHEET ROCK AND AN
INTERCONNECTED FIRE ALARM IN THE ROOM OF THE ENERGY STORAGE
SYSTEM
FOR GRANTSVILLE:
WEATHER LOADING
GROUND SNOW: 30PSF
WIND SPEED: 115MPH
EXPOSURE CATEGORY: C
FOR BINGHAM COUNTY
IDAHO:
WEATHER LOADING
GROUND SNOW: 42PSF
WIND SPEED: 115MPH
EXPOSURE CATEGORY: C
BLAKEMAN RESIDENCE
318 POLO DR
REXBURG, IDAHO 83440
7.6 KW AC / 9.9 KW DC PHOTOVOLTAIC
SYSTEM
SOLAR EDGE SE7600H-US INVERTER
24 BLUESUN HEX5 BSM415M10-54HPH
CAUTION: MULTIPLE SOURCES OF POWER
POWER TO THIS SERVICE IS ALSO SUPPLIED FROM A PV SYSTEM
CONNECTED TO THE AC SERVICE PANEL.
UtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
SIGNAGE
Scale
NTS
1
ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND NOT HAND-WRITTEN. NEC 110.21(B)
SIGN LOCATED AT POINT OF INTERCONNECTION.
NEC 690.56(B) AND 705.10 AND 712.10 AS REQUIRED
2 WARNING:SOLAR POWER SOURCE
OUTPUT CONNECTION,
DO NOT RELOCATE
THIS OVERCURRENT DEVICE
SIGN LOCATED NEXT TO SOLAR BACKFEED BREAKERS AT SERVICE PANEL.
IF BREAKER FEED AND UTILIZING THE 120% RULE NEC 705.12(B)(3)(2)
3 RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
SIGN LOCATED NEXT TO THE SOLAR AC OR DC DISCONNECT THAT
ACTIVATES RAPID SHUTDOWN. NEC 690.56 (C) (2) OR NEXT TO MAIN
SERVICE DISCONNECT OR NEXT TO A RSD RELAY SIGNAL BUTTON
THE MARKINGS SHALL BE REFLECTIVE WHITE ON RED BACKGROUND
5 PHOTOVOLTAIC POWER SOURCE
THIS SIGN IS LOCATED ON THE OUTSIDE OF ANY CONDUITS, ENCLOSURES, OR MC CABLE THAT CONTAINS DC CIRCUITS.
The markings shall be reflective and be provided at every enclosure, every 10’ along conduit or MC cable, and at each side of where the
conduit or cable passes through a wall, floor, or any other partition. NEC 690.31(D)(2) and IFC 605.11.1.2
8
4 PHOTOVOLTAIC ARRAY
DC DISCONNECT SWITCH
MAX SYSTEM VOLTAGE= 480 VDC
MAX CIRCUIT CURRENT= 15 ADC
MAX CURRENT FOR POWER
OPTIMISERS= 15 ADC
THIS SIGN IS LOCATED ON THE OUTSIDE OF EACH DC DISCONNECT.
NEC 690.53 and 690.13(B)
7
PV SYSTEM BACKFEEDING
THROUGH THIS PANEL
AC OUTPUT CURRENT= 32 AAC
AC VOLTAGE=240 VAC
THIS SIGN IS LOCATED AT THE BACKFEED PANEL BOARD
NEC
Sheet 7 of 9
11PHOTOVOLTAIC SYSTEM
DEDICATED KWH METER
THIS SIGN IS LOCATED AT THE DEDICATED
KWH METER
6
NOTICE:
PV SYSTEM COMBINER PANEL
DO NOT ADD LOADS TO THIS PANEL
THIS SIGN IS LOCATED AT THE COMBINER PANEL
PHOTOVOLTAIC SYSTEM
AC DISCONNECT
THIS SIGN IS LOCATED AT THE AC PV SYSTEM DISCONNECT
NEC 690.13 (B)
THIS SIGN IS LOCATED ON OR WITHIN 3’ FEET OF THE
SERVICE METER PANELBOARD AND ON ANY AC DISCONNECT
SWITCH ON THE OUTSIDE OF THE BUILDINGS NEC
690.56(C)(1) / IFC 1204.5.1
9
SE3000H-US 12.5
SE3800H-US 16
SE5000H-US 21
SE6000H-US 25
SE7600H-US 32
SE10000H-US 42
SE11400A-US 47.5
Ansi z535.4 color
specific
9
THIS DIRECTORY LOCATED AT POINTS OF INTERCONNECTION.
NEC 690.56(B) AND 705.10 AND 706.21 AND 710.10 AND 712.10
ALSO PER UTILITY REQUIREMENTS
CAUTION:
MULTIPLE SOURCES OF POWER
BLAKEMAN RESIDENCE
318 POLO DR
REXBURG, IDAHO 83440
7.6 KW AC / 9.9 KW DC PHOTOVOLTAIC
SYSTEM
SOLAR EDGE SE7600H-US INVERTER
24 BLUESUN HEX5 BSM415M10-54HPH
UtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
PLACARDS
Scale
NTS
ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND NOT HAND-WRITTEN. NEC 110.21(B)
Sheet 8 of 9
11
PARALLEL
GENERATION ON
SITE
THIS PLACARD IS LOCATED NEXT TO METER SOCKET. 2”X4”
ENGRAVED METAL OR RED AND WHITE HARD PLASTIC ⅜” OR LARGER
LETTERS AS PER UTILITY REQUIREMENTS
THIS PLACARD IS LOCATED AT THE AC ESS SYSTEM
DISCONNECT. 2”X4” ENGRAVED METAL OR RED AND WHITE
HARD PLASTIC ⅜” OR LARGER LETTERS
12
N
MANUAL
DISCONNECT
FOR PARALLEL
GENERATION
THIS PLACARD IS LOCATED AT THE AC PV SYSTEM
DISCONNECT. 2”X4” ENGRAVED METAL OR RED AND WHITE
HARD PLASTIC ⅜” OR LARGER LETTERS
12
WARNING:
MULTIPLE SOURCES OF POWER. A
PV SYSTEM IS PRESENT.
DISCONNECT ALL POWER SOURCES
BEFORE SERVICING.
FOR ST GEORGE
POWER
MANUAL
DISCONNECT
FOR PARALLEL
GENERATION
WARNING:
ELECTRIC SHOCK HAZARD.
TERMINALS ON BOTH THE LINE
AND LOAD SIDES MAY BE
ENERGIZED IN THE OPEN
POSITION.
BLAKEMAN RESIDENCE
318 POLO DR
REXBURG, IDAHO 83440
7.6 KW AC / 9.9 KW DC PHOTOVOLTAIC
SYSTEM
SOLAR EDGE SE7600H-US INVERTER
24 BLUESUN HEX5 BSM415M10-54HPH
UtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
Scale
NTS
SIGNAGE LOCATION
Sheet 9 of 9
*5
*5
*5
*5
*5
*5
*5EXISTING 125A
MAIN SERVICE PANEL
TRANSITION BOX SOLADECK
JUNCTION BOXES
IN ATTIC
*11,
*1,*8,*13
* NOT REFLECTIVE OF
ACTUAL EQUIPMENT
LOCATION
*1,*9
(EXTERIOR *7)
(NEXT TO
BREAKER
*2,*6)
EXISTING INTERIOR
LOADS PANEL
*2, *6,
*4*3
SOLAREDGE
SE7600H-US
INVERTER
* FOR SIGNAGE AND
PLACARDS SEE PAGES 7 AND
8
*ONLY APPLICABLE STICKER
WILL BE SHOWN ON PAGES 7
AND 8 AND INSTALLED ON
SITE.
BLAKEMAN RESIDENCE
318 POLO DR
REXBURG, IDAHO 83440
DEDICATED
PHOTOVOLTAIC
SYSTEM AC
DISCONNECT
*1,*8,*12
7.6 KW AC / 9.9 KW DC PHOTOVOLTAIC
SYSTEM
SOLAR EDGE SE7600H-US INVERTER
24 BLUESUN HEX5 BSM415M10-54HPH
?? BLUESUN HEX5 BSM415M10 - 54HPH
CHANGES ON
THIS PAGE