HomeMy WebLinkAboutENGINEER LETTER - 23-00458 - 318 Polo Dr - Solar Panels6949 S High Tech Drive Suite 200 Midvale, UT 84047 P (801) 352-0075 F (801) 352-7989 June 5, 2023 Energy Savers 245 E 2150 N Layton, Utah 84041 Re: Jonathan Blakeman Residence: 318 Polo Dr., Rexburg, ID 83440 We have been retained to review the feasibility of adding solar panels to the above referenced site. We have reviewed the solar panel installation site plan and conclude that the panels will not negatively affect the structure at the site mentioned above. The solar panels and their respective design, attachments, and connections shall be per the responsibility of the manufacturer/installer and shall be installed and designed in accordance with the 2018 IBC and ASCE 7-16. The structure is adequate to take on the additional lateral loads due to the solar panels for the following reasons: Any increase in wind loads is negligible due to the mounting pattern of the panels being flush with the existing roof. The solar panels weigh 2.5 psf. Per the IEBC section 503.4, the lateral force resisting system need not be adjusted for less than a 10% change in seismic loads. Since the roof dead load is 15 psf, and the solar panels that weigh 2.5 psf affect less than 50% of the roof structure, the increase in seismic lateral loads is less than 9%. The structure is also adequate to resist the gravity loads due to the solar panels for the following reasons: The live loads will be reduced in the areas where the solar panels are added because no roof live loads will be presen t and snow loads will be reduced. Snow loads will be reduced due to the slippery surface of the solar panels and the heat produced by the black surface. The snow will be more likely to melt and slide off of the panels and be reduced due to these elements as per ASCE 7-16 Figure 7.4-1. With these reductions in the live loads, we can conclude that the additional 2.5 psf increase in dead load will be adequately offset by the reductions in the governing live load. All attachments of the solar panels to the roof structure shall be staggered and spaced on various rafters/truss top chords per the rail system manufacturer in order to have the loads shared by multiple roof structural elements. Focus Engineering & Surveying is not responsible for any problems produced due to improper installation. Focus Engineering & Surveying also assumes the structure is in good condition and was adequately designed by the original design professional and assumes no liability for problems existing due to improper original design. Sincerely, Lynn Gray Focus Engineering & Surveying Reviewed By: Matthew S. Hakes, P.E. Project Engineer Focus Engineering & Surveying 06/05/2023 UtahEnergySavers.com ESSolar.net Layton, UT 801-614-0606 BLAKEMAN RESIDENCE 318 POLO DR REXBURG, IDAHO 83440 Sheet 1 of 9 PLANT LOCATION 7.6 KW AC PHOTOVOLTAIC SYSTEM Scale NTS PLANT LOCATION: BLAKEMAN RESIDENCE 318 POLO DR REXBURG, IDAHO 83440 SOLAR EDGE SE7600H-US INVERTER 25 HANWHA Q.PEAK BLK-G4.1 295 PV PANELS SOLAR EDGE SE7600HUB-US INVERTER 31 SOLARIA POWERXT-400R-PM PANELS SOLAR EDGE SE5000H-US INVERTER 17 LG LG335N1C-A5 335 PV PANELS (2) SOLAR EDGE SE7600H-US INVERTER 47 HANWHA Q.PEAK DUO BLK-G5 310 PV PANELS SOLAR EDGE SE7600H-US INVERTER 25 JA JAM60S03-310/PR PV PANELS SOLAR EDGE SE3800H-US INVERTER 14 PANASONIC VBHN320KA03 320 PV PANELS SOLAR EDGE SE7600H-US INVERTER 26 VIKRAM PREXOS VSMDHT.60.370.05 SOLAR EDGE SE7600HUB-US INVERTER 25 JINKO JKM320M-60L PV PANELS REVISION 1: PLAN BY: BRYCE PETERSON SOLAR EDGE SE7600HUB-US INVERTER 25 VIKRAM SOMERA VSMHBB.60.365 TEXT UtahEnergySavers.com ESSolar.net Layton, UT 801-614-0606 INSTALL SITE Scale NTSLIMITS OF CONSTRUCTION APPROX. 40' DC RUN (IN ATTIC WHERE AVAILABLE) CONCRETE DRIVEWAY SOLADECK JUNCTION BOX (S) SOLAR EDGE SE7600H-US INVERTER (LOCATED NEXT TO SERVICE) EXISTING 125A SERVICE ENTRANCE PANELBOARD Sheet 2 of 9 PHOTOVOLTAIC SYSTEM COMBINER PANEL 100A, 120/240 VAC LOAD CENTER DEDICATED PHOTOVOLTAIC SYSTEM AC DISCONNECT DEDICATED BATTERY SYSTEM AC DISCONNECT (LOCATED IN SIGHT OF BATTERY) DEDICATED PV SYSTEM STOP DISCONNECT (LOCATED NEXT TO SERVICE) SOLAR BOM NEW SOLADECK JUNCTION BOX (SOLTECTION RJ-1) _2_ QTY NEW JUNCTION BOX (SOLTECTION RU-2LP) _1_ QTY RAIL (SNAPNRACK SERIES 100)= _18_ (14 FT LENGTH) QTY SPLICES (SNAPNRACK SERIES 100)= _10_ QTY MID CLAMP (SNAPNRACK SERIES 100) = 44 QTY END CLAMP (SNAPNRACK SERIES 100) = 16 QTY STANDOFFS FEET AND LAGS (SNAPNRACK SERIES 100) = 52 QTY EACH Portrait = 4 panels per 14’ rail Landscape = 2 panels per 14” rail Portrait = 1 rail to 2 panels (360W/400W = 2 rails to 3 panels) Landscape = 1 rail to 1 panel Splices = 2 for every consecutive 4 panels portrait (3 panels for 360W/400W)/ 2 panels landscape End Clamps = 2 on every end Mid Clamps = 2 on every joint between panel 7.6 KW AC / 9.6 KW DC PHOTOVOLTAIC SYSTEM GENERAL NOTES: ALL CONSTRUCTION / INSTALLATION SHALL COMPLY WITH: 2017 NATIONAL ELECTRICAL CODE (NEC) 2018 INTERNATIONAL FIRE CODE (IFC) 2018 INTERNATIONAL BUILDING CODE (IBC) 2018 INTERNATIONAL RESIDENTIAL CODE (IRC) ALL DIMENSIONS SHOWN ARE APPROXIMATE UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL PV SYSTEM COMPONENTS LOCATED AT SERVICE ENTRANCE ALL CONDUITS ON ROOF SHALL BE A MINIMUM OF ½” OFF ROOF CONSTRUCTION LIMITS: ALL IMPROVEMENTS AND ACCESS SHALL OCCUR WITHIN PLANT PROPERTY LINES EXISTING 200A INTERIOR LOADS PANEL LOCATED IN BASEMENT NEW 200A RATED SUB PANEL (LOCATED NEXT TO SERVICE) SOLADECK JUNCTION BOX (S) ONE PER ARRAY APPROX. 40' DC RUN (IN ATTIC WHERE AVAILABLE) SOLADECK JUNCTION BOX (S) ONE PER ARRAY DEDICATED PV METER SOCKET BLAKEMAN RESIDENCE 318 POLO DR REXBURG, IDAHO 83440 SOLAR EDGE SE7600H-US INVERTER 26 VIKRAM PREXOS VSMDHT.60.370.05 UtahEnergySavers.com ESSolar.net Layton, UT 801-614-0606 Scale NTS Temperature Correction for Largest String (Per NEC Article 690.7): Voc = 41.0 Vdc Temperature Coefficient(Voc) = -0.27%/ CVmax = Voc + [(Tlow** - 25 C) x (-0.27% x Voc)]Vmax = 41.0 Vdc + [(-16 C - 25 C) x (-0.27% x 41.0 Vdc)]Vmax = 45.5 Vdc (<48 Vdc) Maximum Input DC Voltage for SolarEdge S440 = 60.0 V dc **Solarabcs.org extreme low temperature for Ogden SUBARRAY #1: Maximum System Voltage (Vmax) Inverter Maximum Voltage Rating = 480 Vdc Rated Maximum Power Point Voltage (Vmpp) For 240 Vac grid connection = 350 Vdc Maximum Circuit Current (Imax) Maximum Input Rating of the Inverter = 20 Adc/string For 2 string system = 30 Adc Rated Maximum Circuit Current (Impp) The Lower Value of the following: 1) System power (STC)/Vmp =9620 W / 452.4 Vdc = 21.26 A 2) Inverter Maximum Output Current = 32A at 240 Vac ARRAY WIRING 9620 DC WATT PHOTOVOLTAIC ARRAY REFER TO THREE LINE WIRING DIAGRAM FOR CONTINUATION WIRE COLORS DC: NEGATIVE - BLACK POSITIVE - RED WIRE COLORS AC: HOT - BLACK and RED NEUTRAL - WHITE GROUND: - GREEN OR BARE 2 #10 THWN-2 CU PV WIRE PER STRING 1 #6 AWG BARE CU GND (EGC) BONDED TO RAIL WITH WEEBL 6.7 LUG AND CLIP ASSEMBLIES. REMAINDER OF ARRAY GROUNDED PER MANUFACTURER'S SPECIFICATIONS. NEC.690.43 SOLAR EDGE POWER OPTIMIZERS TO BE GROUNDED WITH SST STAR WASHER PER MANUFACTURER'S SPECIFICATIONS ONE- LINE ARRAY DIAGRAM Each DC Panel: JAJAM60S03-310/PR Source Circuit: 13 Panels: VIKRAM SOMERA VSMHBB.60.370 With S440 Power Optimizers Power=4810 Watts dc Vmp=452.4 Vdc Imp= 10.53 Adc 13 Panels: VIKRAM SOMERA VSMHBB.60.370 With S440 Power Optimizers Power=4810 Watts dc Vmp=452.4 Vdc Imp= 10.53 Adc Total Array Specs: 26 panels: Power =9620 Watts dc SE3000H-US 12.5 SE3800H-US 16 SE5000H-US 21 SE6000H-US 25 SE7600H-US 32 SE10000H-US 42 SE11400A-US 47.5 Each DC Panel: S ENERGY SN310M-15 Sheet 3 of 9 Each DC Panel: JINKO JKM375M-6RL3-B Each DC Panel: VIKRAM SOMERA VSMHBB.60.370 7.6 KW AC / 9.6 KW DC PHOTOVOLTAIC SYSTEM BLAKEMAN RESIDENCE 318 POLO DR REXBURG, IDAHO 83440 SOLAR EDGE SE7600H-US INVERTER 26 VIKRAM PREXOS VSMDHT.60.370.05 UtahEnergySavers.com
 ESSolar.net
 Layton, UT 801-614-0606
 Scale
 NTS
Sheet 4 of 9
 4 #10 THWN-2 CU PV WIRE1 #10 THWN-2 CU GND3/4" EMT CONDUITSOLADECK JUNCTION BOX TRANSITION BOX AC ONE LINE DIAGRAM
 
 A*-EXISTING MAIN SERVICE (SC1624M100S) B*-EXISTING SUBPANEL (SQUARE D 125A) C*-SOLAREDGE 7600W HD WAVE INVERTER (SE7600H-US) D*-60A/2P DISCONNECT (EATON DG222URB) *WE WILL BE ADDING ONE 125A BREAKER TO THE MAIN SERVICE PANEL TO PROTECT THE EXISTING HOUSE FEEDER WIRES IN COMPLIANCE WITH NEC 705.12(B)(2)(1)(B)PV METERB*- PV METER BOX A* 100A MAIN OTHER LOADS E*-30A/2P DISCONNECT (EATON DG221URB) 200A/2P 40A/2P OTHER LOADS (2)#6 AWG CU (1)#6 AWG NEUTRAL CU (1)#6 AWG EGC CU ¾” EMT MIN. W/ THWN-2 OUTDOOR / NM CABLE INDOOR (2)#8 AWG CU (1)#8 AWG NEUTRAL CU (1)#8 AWG EGC CU ¾” EMT MIN. W/ THWN-2 OUTDOOR / NM CABLE INDOOR (2)#10 AWG CU (1)#10 AWG NEUTRAL CU (1)#10 AWG EGC CU ¾” EMT MIN. W/ THWN-2 OUTDOOR / NM CABLE INDOOR *WE WILL BE ADDING ONE 125A BREAKER TO THE MAIN SERVICE PANEL TO PROTECT THE EXISTING HOUSE FEEDER WIRES IN COMPLIANCE WITH NEC 705.12(B)(2)(1)(B) 7.6KW SOLAR INVERTER C* DC CIRCUITS CONTINUE ON PAGE 5 ETHERNET LINE TO HOME NETWORK 40A/2P B* OTHER LOADS 125A SUBPANEL (2)#8 AWG CU (1)#8 AWG NEUTRAL CU (1)#8 AWG EGC CU ¾” EMT MIN. W/ THWN-2 OUTDOOR / NM CABLE INDOOR (2)#2 AWG CU / #2 AWG AL (1)#2 AWG NEUTRAL CU / #2 AWG AL (1)#8 AWG EGC CU / #6 AWG AL 1 ½ ” EMT MIN. W/ THWN-2 OUTDOOR / SER CABLE INDOOR (2)3/0 AWG CU / 4/0 AWG AL (1)3/0 AWG NEUTRAL CU / 4/0 AWG AL (1)#6 AWG EGC CU / #4 AWG AL 2” EMT MIN. W/ THWN-2 /SER CABLE (2)1/0 AWG CU / 2/0 AWG AL (1)1/0 AWG NEUTRAL CU / 2/0 AWG AL (1)#6 AWG EGC CU / # 4 AWG AL 1 ½ ” EMT MIN. W/ THWN-2 OUTDOOR / SER CABLE INDOOR (2)#1 AWG CU / 1/0 AWG AL (1)#1 AWG NEUTRAL CU / 1/0 AWG AL (1)#6 AWG EGC CU / #4 AWG AL 1 ½ ” EMT MIN. W/ THWN-2 OUTDOOR / SER CABLE INDOOR (2)#2 AWG CU / #2 AWG AL (1)#2 AWG NEUTRAL CU / #2 AWG AL (1)#8 AWG EGC CU / #6 AWG AL 1 ½ ” EMT MIN. W/ THWN-2 OUTDOOR / SER CABLE INDOOR OGDEN WIRE SIZES NEED TO BE CHANGED TO: (2)#8 AWG CU (1)#8 AWG NEUTRAL CU (1)#10 AWG EGC CU ¾” EMT MIN. W/ THWN-2 OUTDOOR / NM CABLE INDOOR 100A/2P 7.6 KW AC / 9.6 KW DC PHOTOVOLTAIC SYSTEM BLAKEMAN RESIDENCE 318 POLO DR REXBURG, IDAHO 83440 SOLAR EDGE SE7600H-US INVERTER 26 VIKRAM PREXOS VSMDHT.60.370.05 60A/2P VISIBLY OPEN DISCONNECT (LOCATED WITHIN 3 FT OF SERVICE) D* EXISTING INTERIOR SUB PANEL (LOCATED IN INTERIOR) NEW JUNCTION BOX (SOLTECTION RU-2LP) G POS NEG G POS NEG UtahEnergySavers.com
 ESSolar.net
 Layton, UT 801-614-0606
 Scale
 NTS
Sheet 5 of 9
 13 *5
 *5
 *5
 *5
 *5
 *5
 *5
 *5
 *4
*3
 *1
 EXISTING 200A
 MAIN SERVICE PANEL
 TRANSITION BOX 
SOLADECK JUNCTION BOXES
 IN ATTIC
 (EXTERIOR *7,*12)
 (NEXT TO SOLAR BREAKER
 *2,*6)
 AC INPUT 2
 UTILITY AC INPUT 1
 A C I N P U T 3 
 AC OUTPUT
 DC INPUT
 CRITICAL LOADS
 B
 THIS IS NOT A PARALLEL GENERATION SYSTEM
 MAIN SERVICE PANEL
4 #10 THWN-2 CU PV WIRE1 #10 THWN-2 CU GND3/4" EMT CONDUITSOLADECK JUNCTION BOX TRANSITION BOX 1 DC 13 DC DC DC DC DC 1 DC DC DC 13 9620 DC WATT PHOTOVOLTAIC ARRAY 1 2 #10 AWG 600V PV / USE-2 PER STRING- BLACK and RED 1 #6 AWG BARE CU GND (EGC) BONDED TO RAIL WITH WEEBL 6.7 LUG AND CLIP ASSEMBLIES. REMAINDER OF ARRAY GROUNDED PER MANUFACTURER'S SPECIFICATIONS. NEC.690.43 SOLAR EDGE S440 POWER OPTIMIZERS TO BE GROUNDED WITH SST STAR WASHER PER MANUFACTURER'S SPECIFICATIONS DC THREE LINE DIAGRAM
 
 G POS NEG G POS NEG G POS NEG G POS NEG POS NEG G POS NEG NEW SOLADECK JUNCTION BOX (SOLTECTION RJ-1) 2- #10 THWN-2-CU BLACK 2- #10 THWN-2-CU RED 1- #10 THWN-2-CU GREEN ¾”EMT CONDUIT AND/OR ¾” SEALTITE FLEXIBLE CONDUIT, TO BE GROUNDED AT EVERY NON METALLIC JUNCTION WITH GROUND BUSHINGS 1/2" MC CABLE 2 #10 MC CABLE 1 #10 CU GND IN ATTIC SECURED ACCORDING TO NEC 690.31 (D)(1) AND TO BE GROUNDED AT EVERY NON METALLIC JUNCTION WITH GROUND BUSHINGS 1/2" MC CABLE 2 #10 MC CABLE 1 #10 CU GND IN ATTIC SECURED ACCORDING TO NEC 690.31 (D)(1) AND TO BE GROUNDED AT EVERY NON METALLIC JUNCTION WITH GROUND BUSHINGS CONTINUATION ON PAGE 4 TO INVERTER *SOLAR EDGE S440 OPTIMIZERS FOR EACH PANEL 7.6 KW AC / 9.6 KW DC PHOTOVOLTAIC SYSTEM BLAKEMAN RESIDENCE 318 POLO DR REXBURG, IDAHO 83440 SOLAR EDGE SE7600H-US INVERTER 26 VIKRAM PREXOS VSMDHT.60.370.05 ARRAY SELF WEIGHT 26 VIKRAM 370W PANELS 18.7 kg = 41.2 LBS/PANEL + SNAP-N-RACK RACKING MOUNTING HARDWARE:26 X 41.888 = 1090 A = L x W (PANEL): 69.53” X 41.34 = 19.96 SQ FT X 26 = 519 TOTAL SQ FT OF PLANE VIEW ROOF AREA = 2263 PERCENTAGE OF ROOF AREA COVERED IN SOLAR PANELS = 22.93% (IFC 1204.2.1.2) ARRAY: 1090 LBS / 519 SQ FT = 2.3 PSF MAX WEIGHT PER ANCHOR = 44.6 LBS (FOR 4’0” SPANS) PULL OUT STRENGTH CONNECTOR 5/16 LAG BOLT 52 STANDOFFS (52 LAGS) 52 x 3” EMBED x 210 LBS = 32760 LBS WEATHER LOADING GROUND SNOW: 50PSF WIND SPEED: 160MPH EXPOSURE CATEGORY: B LIMITS OF CONSTRUCTION UtahEnergySavers.com ESSolar.net Layton, UT 801-614-0606 MOUNTING AND WEIGHT LOAD Scale NTS MEETS OR EXCEEDS 2018 IBC IRC CONSTRUCTION STANDARDS CASE 1 Load Calculations 2X4 construction, 24" on center trusses ROOF LOAD BEARING ______ LBS / ___ STANDOFFS = _____LBS TOTAL WEIGHT = PANELS + HARDWARE 1412.5 LBS 1412.5 LBS / 460.75 SQ FT= 3.065 PSF DEDICATED PHOTOVOLTAIC SYSTEM AC DISCONNECT Sheet 6 of 9 TIMES PANELS BY 630 ALL ROOF PENETRATIONS MUST BE PROPERLY FLASHED. IRC M2302.2.2. THIS INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS SPECIFIED IN SECTION 1204 OF THE 2018 INTERNATIONAL FIRE CODE. ROOF RACKING SUPPORT SPACING NOT TO EXCEED 4’ SPACING. ALL SUPPORTS MUST BE STAGGERED FROM ONE ROW OF RACKING TO THE NEXT SO NOT ALL SUPPORTS ARE BEARING ON THE SAME TRUSSES SOLAR PV MODULES CANNOT BE INSTALLED OVER OR BLOCK ANY ATTIC VENTS, PLUMBING VENTS, FURNACES OR WATER HEATER VENTS, ETC ALL WIRING MUST BE SUPPORTED BY DEVICES OR MECHANICAL MEANS DESIGNED AND LISTED FOR SUCH USE AND WIRING MUST BE PERMANENTLY AND COMPLETELY HELD OFF THE ROOF SURFACE. 36 INCH FIRE DEPARTMENT SETBACK 36” PATHWAYS TO RIDGE WE WILL BE OBSERVING IFC 1204.2 EXCEPTION 1TO BE USED WHEN USING A BARN OR NON INHABITED SPACE FOR ROOF TOP INSTALL THIS INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS SPECIFIED IN THE UTAH AMENDED SECTIONS OF THE 2018 IRC THAT PERTAIN TO ENERGY STORAGE SYSTEMS INCLUDING SHEET ROCK AND AN INTERCONNECTED FIRE ALARM IN THE ROOM OF THE ENERGY STORAGE SYSTEM FOR GRANTSVILLE: WEATHER LOADING GROUND SNOW: 30PSF WIND SPEED: 115MPH EXPOSURE CATEGORY: C FOR BINGHAM COUNTY IDAHO: WEATHER LOADING GROUND SNOW: 42PSF WIND SPEED: 115MPH EXPOSURE CATEGORY: C 7.6 KW AC / 9.6 KW DC PHOTOVOLTAIC SYSTEM BLAKEMAN RESIDENCE 318 POLO DR REXBURG, IDAHO 83440 SOLAR EDGE SE7600H-US INVERTER 26 VIKRAM PREXOS VSMDHT.60.370.05 CAUTION: MULTIPLE SOURCES OF POWER POWER TO THIS SERVICE IS ALSO SUPPLIED FROM A PV SYSTEM CONNECTED TO THE AC SERVICE PANEL. UtahEnergySavers.com ESSolar.net Layton, UT 801-614-0606 SIGNAGE Scale NTS 1 ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND NOT HAND-WRITTEN. NEC 110.21(B) SIGN LOCATED AT POINT OF INTERCONNECTION. NEC 690.56(B) AND 705.10 AND 712.10 AS REQUIRED 2 WARNING:SOLAR POWER SOURCE OUTPUT CONNECTION, DO NOT RELOCATE THIS OVERCURRENT DEVICE SIGN LOCATED NEXT TO SOLAR BACKFEED BREAKERS AT SERVICE PANEL. IF BREAKER FEED AND UTILIZING THE 120% RULE NEC 705.12(B)(3)(2) 3 RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM SIGN LOCATED NEXT TO THE SOLAR AC OR DC DISCONNECT THAT ACTIVATES RAPID SHUTDOWN. NEC 690.56 (C) (2) OR NEXT TO MAIN SERVICE DISCONNECT OR NEXT TO A RSD RELAY SIGNAL BUTTON THE MARKINGS SHALL BE REFLECTIVE WHITE ON RED BACKGROUND 5 PHOTOVOLTAIC POWER SOURCE THIS SIGN IS LOCATED ON THE OUTSIDE OF ANY CONDUITS, ENCLOSURES, OR MC CABLE THAT CONTAINS DC CIRCUITS. The markings shall be reflective and be provided at every enclosure, every 10’ along conduit or MC cable, and at each side of where the conduit or cable passes through a wall, floor, or any other partition. NEC 690.31(D)(2) and IFC 605.11.1.2 8 4 PHOTOVOLTAIC ARRAY DC DISCONNECT SWITCH MAX SYSTEM VOLTAGE= 480 VDC MAX CIRCUIT CURRENT= 15 ADC MAX CURRENT FOR POWER OPTIMISERS= 15 ADC THIS SIGN IS LOCATED ON THE OUTSIDE OF EACH DC DISCONNECT. NEC 690.53 and 690.13(B) 7 PV SYSTEM BACKFEEDING THROUGH THIS PANEL AC OUTPUT CURRENT= 32 AAC AC VOLTAGE=240 VAC THIS SIGN IS LOCATED AT THE BACKFEED PANEL BOARD NEC Sheet 7 of 9 11PHOTOVOLTAIC SYSTEM DEDICATED KWH METER THIS SIGN IS LOCATED AT THE DEDICATED KWH METER 6 NOTICE: PV SYSTEM COMBINER PANEL DO NOT ADD LOADS TO THIS PANEL THIS SIGN IS LOCATED AT THE COMBINER PANEL PHOTOVOLTAIC SYSTEM AC DISCONNECT THIS SIGN IS LOCATED AT THE AC PV SYSTEM DISCONNECT NEC 690.13 (B) THIS SIGN IS LOCATED ON OR WITHIN 3’ FEET OF THE SERVICE METER PANELBOARD AND ON ANY AC DISCONNECT SWITCH ON THE OUTSIDE OF THE BUILDINGS NEC 690.56(C)(1) / IFC 1204.5.1 9 SE3000H-US 12.5 SE3800H-US 16 SE5000H-US 21 SE6000H-US 25 SE7600H-US 32 SE10000H-US 42 SE11400A-US 47.5 Ansi z535.4 color specific 9 THIS DIRECTORY LOCATED AT POINTS OF INTERCONNECTION. NEC 690.56(B) AND 705.10 AND 706.21 AND 710.10 AND 712.10 ALSO PER UTILITY REQUIREMENTS CAUTION: MULTIPLE SOURCES OF POWER 7.6 KW AC / 9.6 KW DC PHOTOVOLTAIC SYSTEM BLAKEMAN RESIDENCE 318 POLO DR REXBURG, IDAHO 83440 SOLAR EDGE SE7600H-US INVERTER 26 VIKRAM PREXOS VSMDHT.60.370.05 UtahEnergySavers.com ESSolar.net Layton, UT 801-614-0606 PLACARDS Scale NTS ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND NOT HAND-WRITTEN. NEC 110.21(B) Sheet 8 of 9 11 PARALLEL GENERATION ON SITE THIS PLACARD IS LOCATED NEXT TO METER SOCKET. 2”X4” ENGRAVED METAL OR RED AND WHITE HARD PLASTIC ⅜” OR LARGER LETTERS AS PER UTILITY REQUIREMENTS THIS PLACARD IS LOCATED AT THE AC ESS SYSTEM DISCONNECT. 2”X4” ENGRAVED METAL OR RED AND WHITE HARD PLASTIC ⅜” OR LARGER LETTERS 12 N MANUAL DISCONNECT FOR PARALLEL GENERATION THIS PLACARD IS LOCATED AT THE AC PV SYSTEM DISCONNECT. 2”X4” ENGRAVED METAL OR RED AND WHITE HARD PLASTIC ⅜” OR LARGER LETTERS 12 WARNING: MULTIPLE SOURCES OF POWER. A PV SYSTEM IS PRESENT. DISCONNECT ALL POWER SOURCES BEFORE SERVICING. FOR ST GEORGE POWER MANUAL DISCONNECT FOR PARALLEL GENERATION WARNING: ELECTRIC SHOCK HAZARD. TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. 7.6 KW AC / 9.6 KW DC PHOTOVOLTAIC SYSTEM BLAKEMAN RESIDENCE 318 POLO DR REXBURG, IDAHO 83440 SOLAR EDGE SE7600H-US INVERTER 26 VIKRAM PREXOS VSMDHT.60.370.05 UtahEnergySavers.com ESSolar.net Layton, UT 801-614-0606 Scale NTS SIGNAGE LOCATION Sheet 9 of 9 *5 *5 *5 *5 *5 *5 *5EXISTING 125A MAIN SERVICE PANEL TRANSITION BOX SOLADECK JUNCTION BOXES IN ATTIC *11, *1,*8,*13 * NOT REFLECTIVE OF ACTUAL EQUIPMENT LOCATION *1,*9 (EXTERIOR *7) (NEXT TO BREAKER *2,*6) EXISTING INTERIOR LOADS PANEL *2, *6, *4*3 SOLAREDGE SE7600H-US INVERTER * FOR SIGNAGE AND PLACARDS SEE PAGES 7 AND 8 *ONLY APPLICABLE STICKER WILL BE SHOWN ON PAGES 7 AND 8 AND INSTALLED ON SITE. 7.6 KW AC / 9.6 KW DC PHOTOVOLTAIC SYSTEM BLAKEMAN RESIDENCE 318 POLO DR REXBURG, IDAHO 83440 SOLAR EDGE SE7600H-US INVERTER 26 VIKRAM PREXOS VSMDHT.60.370.05 DEDICATED PHOTOVOLTAIC SYSTEM AC DISCONNECT *1,*8,*12