HomeMy WebLinkAboutFS APPROVAL - 22-00800 - Madison Station Apartments - Bldg 6 Madison Station Apt. Bldg 6 UG – Rexburg 1 of 2
STATE FIRE MARSHAL
IDAHO DEPARTMENT OF INSURANCE
700 W. State Street, 3rd Floor
P.O. Box 83720
Boise, ID 83720-0043
(208) 334-4370 | www.doi.idaho.gov/sfm
PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS
PLANS RECEIVED: May 31, 2023 APPROVED: June 22, 2023
REVIEWED BY: Rory Winch, Fire Plans Examiner
PROJECT: Madison Station Apt. Bldg 6 UG
STREET ADDRESS: Westates Subdivision #1 lot 4 Blk 2 CITY: Rexburg
AHJ: Madison Fire Department
SPRINKLER CONTRACTOR: Phoenix Fire Protection
4130 Airport Road
Nampa, ID 83687
IDAHO LICENSE: FPSC-108
CONTACT NAME: Josie Brannon
design@phoenixfp.com
PHONE NO: (208) 468-9115
SYSTEM DESIGNED BY: Teri Cruickshank
teri@phoenixfp.com
PHONE NO: (208) 468-9115
TYPE OF SYSTEM: NFPA 13R HEAD COUNT: 0
TOTAL SYSTEMS: 1 OCCUPANCY CLASSIFICATION: Residential
CONSTRUCTION TYPE: V B AREA SQUARE FOOTAGE: 37,000
SCOPE OF WORK: New 6" underground approx 71 LF C-900 and 6" Gate Valve installed by
others.
PLAN REVIEW COMMENTS: Approved with comments
1. Underground Plans should include the following information in addition to the
information provided:
a. Underground Flushing: Underground flushing must be witnessed by the local
authority having jurisdiction. (NFPA 13, 10.10.2.1)
b. Underground Hydrostatic Test: Underground hydrostatic test, 200 lbs./2
hours, must be witnessed by the local authority having jurisdiction. (NFPA
13, 24.2.1.5)
c. Testing and Inspection Requirements: Include details about the testing and
inspection requirements for the system, type and frequency of testing, and
qualifications of testing and inspection personnel. (NFPA 13, 25.2)
d. Backflow Prevention: Include details about backflow prevention devices
including type, location, and installation requirements. (NFPA 13, 6.5.4)
Madison Station Apt. Bldg 6 UG – Rexburg 2 of 2
e. The 2018 International Fire Code and International Building Code, and the
2019 editions of NFPA 13 have been adopted by the State of Idaho. (IDAPA
18.08.01.004.01)
Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or
Rules, International Fire Code, NFPA Standards or any other applicable criteria.
It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s
Office and its personnel does not take any responsibility for the back flow device.