HomeMy WebLinkAbout22211 Palisades Apt. ComCheck 5.30.23U
COMcheck Software Version COMcheckWeb
Mechanical Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Construction Site:
Rexburg, Idaho
2018 IECC
22211 Palisades Apt
Pocatello, Idaho
6b
New Construction
Owner/Agent:
Additional Efficiency Package(s)
Credits: 1.0 Required 0.0 Proposed
Mechanical Systems List
Quantity System Type & Description
Designer/Contractor:
Scott Roberts
Engineered Systems Associates
1355 East Center St.
Pocatello, Idaho 83201
208-233-0501
scott@engsystems.com
F2 (Single Zone):
Heating: 1 each - Duct Furnace, Gas, Capacity = 36 kBtu/h
Proposed Efficiency = 80.00% Ec, Required Efficiency: 80.00 % Ec
Cooling: 1 each - Single Package DX Unit, Capacity = 18 kBtu/h, Air -Cooled Condenser, Unknown Economizer
Proposed Efficiency = 14.00 SEER, Required Efficiency = 14.00 SEER
Proposed Part Load Efficiency = 0.00 , Required Part Load Efficiency = 0.00
Fan System: F2 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 600 CFM, 0.3 motor nameplate hp, 70.0 fan efficiency grade, 0.0 total fan
efficiency, 0.0 design fan efficiency
F3 (Single Zone):
Heating: 1 each - Duct Furnace, Gas, Capacity = 40 kBtu/h
Proposed Efficiency = 80.00% Ec, Required Efficiency: 80.00 % Ec
Cooling: 1 each - Single Package DX Unit, Capacity = 18 kBtu/h, Air -Cooled Condenser, Unknown Economizer
Proposed Efficiency = 14.00 SEER, Required Efficiency = 14.00 SEER
Proposed Part Load Efficiency = 0.00 , Required Part Load Efficiency = 0.00
Fan System: F2 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 600 CFM, 0.3 motor nameplate hp, 70.0 fan efficiency grade, 0.0 total fan
efficiency, 0.0 design fan efficiency
F1 (Single Zone):
Heating: 1 each - Duct Furnace, Gas, Capacity = 44 kBtu/h
Proposed Efficiency = 95.00% Ec, Required Efficiency: 80.00 % Ec
Fan System: F1 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes
Fans:
FAN 2 Supply, Constant Volume, 600 CFM, 0.3 motor nameplate hp, 70.0 fan efficiency grade, 0.0 total fan
efficiency, 0.0 design fan efficiency
Water Heater:
Gas Storage Water Heater, Capacity: 100 gallons, Input Rating: 250 kBtu/h w/ Circulation Pump
Proposed Efficiency: 80.00 % Et, Required Efficiency: 80.00 % Et
Project Title: 22211 Palisades Apt
Data filename:
Report date: 05/16/23
Page 1 of 10
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2018 IECC requirements in COMcheck Version COMcheckWeb and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
David Hansen, Engineer5/16/2023
Name - Title Signature Date
Project Title: 22211 Palisades Apt
Data filename:
Report date: 05/16/23
Page 2 of 10
COMcheck Software Version COMcheckWeb
Inspection Checklist
Energy Code: 2018 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
Plan Review
Complies?
Comments/Assumptions
& Req.ID
C103.2
Plans, specifications, and/or
❑Complies
[PR2]1
calculations provide all information
❑Does Not
with which compliance can be
❑Not Observable
determined for the mechanical
❑Not Applicable
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
C103.2
Plans, specifications, and/or
❑Complies
[PR3]1
calculations provide all information
❑Does Not
with which compliance can be
❑Not Observable
determined for the service water
❑Not Applicable
heating systems and equipment and
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
C406
Plans, specifications, and/or
❑Complies
[PR9]1
calculations provide all information
❑Does Not
with which compliance can be
❑Not Observable
determined for the additional energy
❑Not Applicable
efficiency package options.
Additional Comments/Assumptions:
111 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: 22211 Palisades Apt
Data filename:
Report date: 05/16/23
Page 3 of 10
Section
#
& Req.ID
Footing / Foundation Inspection
Complies?
Comments/Assumptions
C403.12.2 ' Snow/ice melting system and freeze
❑Complies
protection systems have sensors and
'❑Does Not
C403.12.3 controls configured to limit service for
❑Not Observable
[F09]3 pavement temperature and outdoor
❑Not Applicable
temperature. future connection to
j controls.
Additional Comments/Assumptions:
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: 22211 Palisades Apt
Data filename:
Report date: 05/16/23
Page 4 of 10
Section
#
Plumbing Rough -In Inspection
Complies?
Comments/Assumptions
& Req.ID
C404.5,
Heated water supply piping conforms
❑Complies
C404.5.1,
to pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details.
❑Not Observable
[PL6]3
❑Not Applicable
C404.6.1,
Automatic time switches installed to
❑Complies
C404.6.2
automatically switch off the
❑Does Not
[PL3]1
recirculating hot-water system or heat
❑ Not Observable
trace.
❑Not Applicable
C404.6.3
Pumps that circulate water between a
❑Complies
[PL7]3
heater and storage tank have controls
❑Does Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
❑Not Applicable
cycle.
C404.7
Demand recirculation water systems
❑Complies
[PL8]3
have controls that start the pump
❑Does Not
upon receiving a signal from the
❑Not Observable
action of a user of a fixture or
❑Not Applicable
appliance and limits the temperature
of the water entering the cold -water
piping to 104°F.
Additional Comments/Assumptions:
111 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: 22211 Palisades Apt Report date: 05/16/23
Data filename: Page 5 of 10
Section
#
Mechanical Rough -In Inspection
Complies?
Comments/Assumptions
& Req.ID
C402.2.6
Thermally ineffective panel surfaces ofl❑Complies
[ME41]3
sensible heating panels have
❑Does Not
insulation >= R-3.5.
,❑Not Observable
❑Not Applicable
C403.8.4
Motors for fans that are not less than❑Complies
[ME142]2
1/12 hp and less than 1 hp are
PDoes Not
;electronically commutated motors or
I❑Not Observable;
',
have a minimum motor efficiency of
❑Not Applicable j
70 percent. These motors have the
means to adjust motor speed.
C403.8.5
Each DX cooling system > 65 kBtu
❑Complies
[ME143]2
and chiller water/evaporative cooling
❑Does Not
j system with fans > 1/4 hp are
:designed to vary the indoor fan airflow
❑Not Observable
as a function of load and comply with
❑Not Applicable
:detailed requirements of this section.
C403.12.1:
Systems that heat outside the building
❑Complies
[ME71]2
envelope are radiant heat systems
❑Does Not
;controlled by an occupancy sensing
I❑Not Observable
device or timer switch.
❑Not Applicable
C403.2.2
:Natural or mechanical ventilation is
❑Complies
[ME59]1
provided in accordance with
❑Does Not
; International Mechanical Code
❑Not Observable
Chapter 4. Mechanical ventilation has
capability to reduce outdoor air supply,❑Not
Applicable
to minimum per IMC Chapter 4.
C403.7.1
Demand control ventilation provided
❑Complies
[ME59]1
for spaces >500 ft2 and >25
❑Does Not
people/1000 ft2 occupant density and
❑Not Observable
I served by systems with air side
economizer, auto modulating outside
❑Not Applicable
air damper control, or design airflow
>3,000 cfm.
C403.7.2
:Enclosed parking garage ventilation
❑Complies
[ME115]3
; has automatic contaminant detection
❑Does Not
and capacity to stage or modulate
❑Not Observable
;fans to 50% or less of design capacity.
❑Not Applicable
C403.7.6
'HVAC systems serving guestrooms in
❑Complies
[ME141]3
Group R-1 buildings with > 50
❑Does Not
guestrooms: Each guestroom is
❑Not Observable
provided with controls that
automatically manage temperature
❑Not Applicable
setpoint and ventilation (see sections
!,
IC403.7.6.1 and C403.7.6.2).
C403.7.4
Exhaust air energy recovery on
❑Complies
[ME57]1
:systems meeting Table C403.7.4(1)
❑Does Not
;and C403.7.4(2).
❑Not Observable
❑Not Applicable
C403.7.5
Kitchen exhaust systems comply with
❑Complies
[ME116]3
:replacement air and conditioned
I❑Does Not
supply air limitations, and satisfy hood
rating requirements and maximum
❑Not Observable
Applicable
exhaust rate criteria.
I❑Not
C403.11.1 ' HVAC ducts and plenums insulated in
❑Complies
accordance with C403.11.1 and
❑Does Not
C403.11.2
constructed in accordance with
❑Not Observable
[ME60]2
C403.11.2, verification may need to
❑Not Applicable
occur during Foundation Inspection.
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: 22211 Palisades Apt Report date: 05/16/23
Data filename: Page 6 of 10
Section
#
Mechanical Rough -In Inspection
Complies?
Comments/Assumptions
& Req.ID
C403.4.1.
Heating for vestibules and air curtains❑Complies
4
with integral heating include
❑Does Not
[ME63]2
automatic controls that shut off the
❑Not Observable
I heating system when outdoor air
I
❑Not Applicable
temperatures > 45F. Vestibule
,heating and cooling systems
;controlled by a thermostat in the
vestibule with heating setpoint <_
60F and cooling setpoint >= 80F.
C403.3.3
Hot gas bypass limited to: <=240
❑Complies
[ME35]1
kBtu/h - 50% >240 kBtu/h - 25%
❑Does Not
❑Not Observable
❑Not Applicable
C404.2.1
;,Gas-fired water -heating equipment
❑Complies
[ME111]2
!installed in new buildings: where a
❑Does Not
;singular piece of water -heating
❑Not Observable
;equipment >= 1,000 kBtu/h serves
the entire building, thermal efficiency
❑Not Applicable
>= 90 Et. Where multiple pieces of
;water -heating equipment serve the
building with combined rating >_
1,000 kBtu/h, the combined input -
capacity -weighted -average thermal
efficiency >= 90 Et. Exclude input
rating of equipment in individual
dwelling units and equipment <= 100
kBtu/h.
C408.2.2.
Air outlets and zone terminal devices❑Complies
1
have means for air balancing.
❑Does Not
[ME53]3
❑Not Observable
❑Not Applicable
C403.5,
Refrigerated display cases, walk-in
❑Complies
C403.5.1,
coolers or walk-in freezers served by
❑Does Not
C403.5.2
remote compressors and remote
❑Not Observable
[ME123]3
condensers not located in a
❑Not Applicable
condensing unit, have fan -powered
condensers that comply with Sections
IC403.5.1 and refrigeration compressor!
systems that comply with C403.5.2..
Additional Comments/Assumptions:
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: 22211 Palisades Apt Report date: 05/16/23
Data filename: Page 7 of 10
Section
#
& Req.ID
Rough -In Electrical Inspection
Complies?
C405.6
Low -voltage dry -type distribution
❑Complies
[EL26]2
electric transformers meet the
❑Does Not
:minimum efficiency requirements of
❑Not Observable:
I local code when not conveying
;Table C405.6.
❑Not Applicable j
C405.7
I Electric motors meet the minimum
❑Complies
[EL27]2
efficiency requirements of Tables
I❑Does Not
jC405.7(1) through C405.7(4).
Efficiency verified through certification',
i❑Not Observable;
I under an approved certification
❑Not Applicable j
program or the equipment efficiency
ratings shall be provided by motor
:manufacturer (where certification
I programs do not exist).
C405.8.2, !Escalators and moving walks comply
C405.8.2.
with ASME A17.1/CSA B44 and have
1
automatic controls configured to
[EL28]2
reduce speed to the minimum
permitted speed in accordance with
:ASME A17.1/CSA B44 or applicable
I local code when not conveying
passengers.
C405.9
;Total voltage drop across the
[EL29]2
:combination of feeders and branch
:circuits <= 5%.
Additional Comments/Assumptions:
LIComplies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
;
❑Does Not
❑Not Observable
❑Not Applicable
Comments/Assumptions
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: 22211 Palisades Apt
Data filename:
Report date: 05/16/23
Page 8 of 10
Section
#
Final Inspection
Complies?
Comments/Assumptions
& Reci.ID
C303.3, :Furnished O&M manuals for HVAC ❑Complies
C408.2.5. systems within 90 days of system ❑Does Not
3 ;acceptance.
[F18]3 ❑Not Observable:
❑Not Applicable j
C403.2.2 HVAC systems and equipment ❑Complies
[F127]3 capacity does not exceed calculated ❑Does Not
loads. '❑Not Observable
1❑Not Applicable j
C403.2.4. Heating and cooling to each zone is ❑Complies
1 controlled by a thermostat control. ❑Does Not
[F147]3 :Minimum one humidity control device
❑Not Observable
;per installed
.humidification/dehumidification ❑Not Applicable
j system.
C403.4.1. Thermostatic controls have a 5 °F ❑Complies
2 deadband. ❑Does Not
[F138]3 ❑Not Observable
❑Not Applicable
C403.2.4. Temperature controls have setpoint ❑Complies
1.3 overlap restrictions. ❑Does Not
[F120]3 1117Not Observable:
❑Not Applicable j
C403.2.4. :Each zone equipped with setback
i❑Complies
2 :controls using automatic time clock or
❑Does Not
[F139]3 programmable control system.
❑Not Observable
❑Not Applicable
C403.2.4. (Automatic Controls: Setback to 55°F
I❑Complies
2.1, (heat) and 85°F (cool); 7 -day clock, 2-
❑Does Not j
C403.2.4. :hour occupant override, 10 -hour
:backup
17Not Observable:,
2.2
[F140]3❑Not
I
Applicable
;
C403.2.4.
;Systems include optimum start
❑Complies
2.3
controls.
❑Does Not
[F141]3
❑Not Observable:
❑Not Applicable j
C404.3 Heat traps installed on supply and
'❑Complies
[FI11]3 discharge piping of non -circulating
❑Does Not
systems.
Observable
�❑Not
E]Not Applicable
C404.4 All piping insulated in accordance with
❑Complies
[F125]2 section details and Table C403.11.3.
❑Does Not
❑Not Observable
❑Not Applicable
C404.6.1 ;Controls are installed that limit the ❑Complies
[F112]3 ,operation of a recirculation pump ❑Does Not
; installed to maintain temperature of a
❑Not Observable
;storage tank. System return pipe is a
❑Not Applicable
dedicated return pipe or a cold water
:supply pipe.
1 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: 22211 Palisades Apt Report date: 05/16/23
Data filename: Page 9 of 10
Section
#
Final Inspection
Complies?
Comments/Assumptions
& Req.ID
C408.1.1
Building operations and maintenance
❑Complies
[F[57]1
documents will be provided to the
❑Does Not
owner. Documents will cover
❑Not Observable
manufacturers' information,
❑Not Applicable
;specifications, programming
procedures and means of illustrating
;to owner how building, equipment and
systems are intended to be installed,
:maintained, and operated.
C408.2.1
;Commissioning plan developed by
❑Complies
[F128]1
'registered design professional or
❑Does Not
approved agency.
❑Not Observable
❑Not Applicable
C408.2.3.
HVAC equipment has been tested to
❑Complies
1
;ensure proper operation.
❑Does Not
[F131]1
❑Not Observable
❑Not Applicable
C408.2.3.
I HVAC control systems have been
❑Complies
2
:tested to ensure proper operation,
❑Does Not
[FI10]1
;calibration and adjustment of controls.
❑Not Observable
❑Not Applicable
C408.2.4
:Preliminary commissioning report
❑Complies
[F129]1
:completed and certified by registered
❑Does Not
design professional or approved
:agency.
❑Not Observable
❑Not Applicable
C408.2.5.
:Furnished HVAC as -built drawings
E❑complies
1
submitted within 90 days of system
lElDoes Not
[F17]3
acceptance.
❑Not Observable
❑Not Applicable
C408.2.5.
:An air and/or hydronic system
❑Complies
3
'balancing report is provided for HVAC
❑Does Not
[F143]1 ;systems.
❑Not Observable
❑Not Applicable
C408.2.5.
Final commissioning report due to
❑Complies
4
buildin owner within 90 da s of
❑
g Y
[F130]1 ! receipt of certificate of occupancy
Additional Comments/Assumptions:
Does Not
❑Not Observable
❑Not Applicable
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: 22211 Palisades Apt
Data filename:
Report date: 05/16/23
Page 10 of 10