HomeMy WebLinkAboutPLANS - 23-00351 - City Hall Server Room - Fire Alarm1
2
3
OUTPUTS DISABLED
GROUND FAULT
PREDISCHARGE
SUPERVISORY
PANEL SILENCED
12VDC
BATT #1
AC NEUTRAL
ALARM
DISABLE
SILENCE
RESET
AC NORMAL
RELEASE
TROUBLE
ABORT
AC LINE
ENABLE
-+-+
INPUT #5DETECT #2
4 -
H1
SW4 CONFIG SWITCHES
DIAGNOSTICS
BATT 10AAC 10A
AC SECONDARY
-
+
+
-
R
E
S
+
P
5
INPUT #4INPUT #3DETECT #1
3 +
NC
NO
NC
C
P
4
5
129
+
-
43
63
BATTERY
P1
120V
P2
1010
NC
NO
C
NO
C
A
U
X
O
U
T
P
U
T
S
A
U
D
I
B
L
E
#
1
A
U
D
I
B
L
E
#
2
S
O
L
E
N
O
I
D
TR
O
U
B
L
E
R
E
L
A
Y
SU
P
E
R
V
I
S
O
R
Y
R
E
L
A
Y
A
U
D
I
B
L
E
#
3
7
5
6
A
G
E
N
T
R
E
L
E
A
S
E
ON
21
X2
24V
H2
X1
AL
A
R
M
R
E
L
A
Y
3
2
4
1
2
3
4
1
2
3
4
8
9
1
0
1
1
1
2
1
3
131211109876
1110875421
P3 21
F2
9
8
7
6
5
1
F1
4A
F4
4A
F3
4 4
12VDC
BATT #2
-
-
+
-
-
+
-
-
+
-
-
+
-
-
+
-
+
-
+
-
+
-
RE
L
A
Y
1
C
NC
NO
CR
M
-
4
R
E
L
A
Y
M
O
D
U
L
E
C
NC
NC
NO
C
NO
RE
L
A
Y
2
RE
L
A
Y
3
NO
NC
C RE
L
A
Y
4
MATRIX
OPERATIONS
PIPE MOUNTING DETAIL
MOUNTING STRAP DETAIL
Unistrut Nut, Bolt &
Washer
Wall
Container
Mounting Strap
Unistrut Channel
27.0"
10.75"
N N
Company Information
Name:Fire Services of Idaho
Address:610 Mallard St.
City:Chubbuck
State/Province:ID
Postal Code:83202
Country:US
Web Site:
Contact Information
Name:Patrick Jackson
Email:patrick.jackson@rexburg.org
Site Information
Name:Rexburg City Hall
Address:35 N. 1st E.
City:Rexburg
State/Province:ID
Postal Code:83340
Country:US
Project Setup
Selected Agent Type:FK-5-1-12
Selected Hardware Group:Fike US
Ambient Room Temperature:68 °F
Discharge Time:10 s
Project Information
Description:Server Room Fire Suppression
Designer:Kyle Arigot
C:\Users\karigot\Documents\Jobs 2023\FSI Jobs\Rexburg City Hall Server Rm -4\Rexburg City Hall.ffc Page 2
Hazard Information
Description:Server Room
Protecting Agent:FK-5-1-12
Length:15.75 ft
Width:7.67 ft
Height:8.06 ft
Added Volume:0.00 ft^3
Removed Volume:0.00 ft^3
Protected Volume:972.56 ft^3
Minimum Temperature:65 °F
Maximum Temperature:72 °F
Relative Humidity:38.00 %
Altitude:4865 ft
Minimum Agent Concentration:4.5 %
Agent Design Concentration:4.5 %
Maximum Agent Concentration:4.7 %
Agent Required:34.0 lb
Total Agent Required
Agent Required for all Hazards:34.0 lb
C:\Users\karigot\Documents\Jobs 2023\FSI Jobs\Rexburg City Hall Server Rm -4\Rexburg City Hall.ffc Page 4
Pipe Network Layout
Cylinder Information
Description Agent Qty Pressure Volume Diameter Height
70-361-X-X 60 lb Upright 34.0 lb 500 psi 0.9740 ft^3 0.8960 ft 2.3440 ft
Nozzle Information
Description Requested Agent Orifice Thread Dispersion Angle
80-122-075-X 3/4 in (20
mm)
34.0 lb 0.3230 in NPT 180
C:\Users\karigot\Documents\Jobs 2023\FSI Jobs\Rexburg City Hall Server Rm -4\Rexburg City Hall.ffc Page 5
Table Input Data
Start End Length Elevation
Change
Diameter Schedule Cylinder 90° Elbows 45° Elbows Thru Branch Side Branch Union Equiv
Length
Agent
Quantity
Nozz
Type
Nozz Orifice
1 2 2.3440 ft 2.3440 ft 1 in Schedule 40T 1 0 0 0 0 0 3.6860 ft
2 3 0.5000 ft 0.5000 ft 3/4 in Schedule 40T 0 0 0 0 0 0
3 101 12.2490 ft 4.5000 ft 3/4 in Schedule 40T 0 5 0 0 0 0 34.0000 lb 180 0.3230 in
Table Results Data
Start End Pipe Type Equivalent
Length
Start Pressure End Pressure Agent Flow Rate Nozzle Agent Nozzle Orifice Size Initial Vapor Time Liquid Discharge
Time
End of Liquid Time
1 2 1 -SCH 40 6.0300 ft 360.0000 psi 357.0000 psi 4.2102 lb / s
2 3 3/4 -SCH 40 0.5000 ft 357.0000 psi 356.0000 psi 4.2102 lb / s
3 101 3/4 -SCH 40 22.5490 ft 356.0000 psi 343.0000 psi 4.2102 lb / s 34.0000 lb 0.3230 in 0.1505 s 7.1552 s 7.3058 s
Table Results Messages
FK-5-1-12 Flow Calculation Engine Version 1.00.0000
Final calculation with selected nozzle drill sizes. Convergance of the iteration of nozzle flow rate and pressure is 0.05
System calculated within limits of Fikes UL listing and FM approval
Calculation performed on 5/9/2023 8:22 AM
Discharge time is 7.305769 seconds, which is within the 5.95 to 10 second limits.
C:\Users\karigot\Documents\Jobs 2023\FSI Jobs\Rexburg City Hall Server Rm -4\Rexburg City Hall.ffc Page 6
Bill of Materials
Pipes
Quantity Description
1 3/4 in x 0.2500 ft (Schedule 40T)
1 3/4 in x 0.3330 ft (Schedule 40T)
1 3/4 in x 0.4160 ft (Schedule 40T)
1 3/4 in x 0.5000 ft (Schedule 40T)
1 3/4 in x 4.7500 ft (Schedule 40T)
1 3/4 in x 6.5000 ft (Schedule 40T)
Nozzles
Quantity Description
1 3/4 in (20 mm) (Part Number '80-122-075-3230')
Cylinders
Quantity Description
1 60 lb Upright (34.0000 lb) (Part Number '70-361-X-X')
Elbows
Quantity Description
5 3/4 in x 3/4 in
C:\Users\karigot\Documents\Jobs 2023\FSI Jobs\Rexburg City Hall Server Rm -4\Rexburg City Hall.ffc Page 7
System Acceptance Report
Nozzle Performance
Nozzle Number Orifice Diameter Agent Requested Agent Predicted Nozzle Pressure
101 0.3230 in 34.0000 lb 34.0000 lb 343.0000 psi
Agent Concentration Per Hazard
Hazard Minimum Concentration Design Concentration Min Predicted
Concentration
Max Predicted
Concentration
Discharge Time
Server Room 4.5 %4.5 %4.6253 %4.6912 %7.3058 s
Hazard Venting Requirements
Hazard Positive (Flow Out) ELA Negative (Flow In) ELA
Server Room 2.8045 in^2 42.1689 in^2
C:\Users\karigot\Documents\Jobs 2023\FSI Jobs\Rexburg City Hall Server Rm -4\Rexburg City Hall.ffc Page 8
FACP Battery Calculation 5/15/2023
PROJECT NAME:
Required Standby Time:24 Hours
Required Alarm Time:5 Minutes
Regulated Load in Standby
Number Current Total Current
Device Type of Devices (Amps)(Amps)
SHP Pro Main Board 1 X 0.13500 =0.13500
CRM-4 Relay 1 X 0.00000 =0.00000
Smoke Detector 2 X 0.00005 =0.00010
Impulse Release Module 1 X 0.00300 =0.00300
TOTAL STANDBY LOAD 0.13810
Regulated Load in ALARM
Number Current Total Current
Device Type of Devices (Amps)(Amps)
SHP Pro Main Board 1 X 1.23500 =1.23500
CRM-4 Relay 1 X 0.01000 =0.01000
Smoke Detector 2 X 0.13000 =0.26000
Impulse Release Module 1 X 0.03700 =0.03700
AUD #1 (See Voltage Drop Calculations)1 X 0.04400 =0.04400
AUD #2 (See Voltage Drop Calculations)1 X 0.04300 =0.04300
AUD #3 (See Voltage Drop Calculations)1 X 0.04300 =0.04300
TOTAL ALARM LOAD 1.67200
Battery Requirements
Standby Load Required Standby Time in Hours
Current (Amps)0.13810 X 24.00000 =3.31440
Alarm Load Required Alarm Time in Hours
Current (Amps)1.67200 X 0.08333 =0.13933
Total Ampere Hours (before derating factor)3.45373
Derating Factor X 20%
TOTAL AMPERE HOURS REQUIRED =4.14448
BATTERIES (2 - 12v)7 Ah
Rexburg City Hall - Server Room
Point to Point NAC Voltage Drop Calculation 5/15/2023
Project Name Rexburg City Hall - Server Room
Circuit Number AUD-1
Nominal System Voltage 20.4 volts Wire Resistance
Minimum Device Voltage 16.0 volts Gauge Per 1000
Distance from source to 1st device 15 feet 14 3.07
Wire Gauge for balance of circuit 14 3.07
Max Output Current 2.50 amps
Total Circuit Current 0.044 amps
End of Line Voltage 20.40 volts
Distance
Candela Device previous Voltage at Drop from Percent
Rating Current device Device source Drop
Device 1 n/a 0.044 20.40 0.004 0.02%
Totals 0.044 15
Notes:
Wire resistance is doubled in the calculations for two wires (Positive and Negative).
The voltage calculated to the last device must not be lower than the manufactures listed
minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)).
Circuit is within limits
Point to Point NAC Voltage Drop Calculation 5/15/2023
Project Name Rexburg City Hall - Server Room
Circuit Number AUD-2
Nominal System Voltage 20.4 volts Wire Resistance
Minimum Device Voltage 16.0 volts Gauge Per 1000
Distance from source to 1st device 15 feet 14 3.07
Wire Gauge for balance of circuit 14 3.07
Max Output Current 2.50 amps
Total Circuit Current 0.043 amps
End of Line Voltage 20.40 volts
Distance
Candela Device previous Voltage at Drop from Percent
Rating Current device Device source Drop
Device 1 15 0.043 20.40 0.004 0.02%
Totals 0.043 15
Notes:
Wire resistance is doubled in the calculations for two wires (Positive and Negative).
The voltage calculated to the last device must not be lower than the manufactures listed
minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)).
Circuit is within limits
Point to Point NAC Voltage Drop Calculation 5/15/2023
Project Name Rexburg City Hall - Server Room
Circuit Number AUD-3
Nominal System Voltage 20.4 volts Wire Resistance
Minimum Device Voltage 16.0 volts Gauge Per 1000
Distance from source to 1st device 15 feet 14 3.07
Wire Gauge for balance of circuit 14 3.07
Max Output Current 2.50 amps
Total Circuit Current 0.043 amps
End of Line Voltage 20.40 volts
Distance
Candela Device previous Voltage at Drop from Percent
Rating Current device Device source Drop
Device 1 15 0.043 20.40 0.004 0.02%
Totals 0.043 15
Notes:
Wire resistance is doubled in the calculations for two wires (Positive and Negative).
The voltage calculated to the last device must not be lower than the manufactures listed
minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)).
Circuit is within limits