HomeMy WebLinkAboutCONCRETE FIELD TEST10 - 22-00269 - Hibbard Elementary SchoolFile name:
22229FB06012023JPC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
3A39F358-8A85-4D8D-98C7-23B2CF4B7F34 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
Compressive Strength of Concrete Test Specimens
Project Number:
22-229
Cumulative Test Load Amount:
4.5
Project Name:
Hibbard Elementary
Test Location:
Top lift of gym wall. See photo referencing Structural
Plans, page S2.0
Client:
Madison School District
Admixtures:
P-200N
Ticket Number:
79116554
Contractor:
ML Masonry
Supplier:
IMC
Mix Number:
3336531
Date:
5/25/2023
Cylinder Log #:
213
Field Test Results:
Set #:
1
Entrained Air
(%):
0.0
Concrete
Temperature
(°F):
69
Ambient
Temperature
(°F):
68
Unit Weight
(PCF):
0
Tested By:
E. Vail
Date:
5/25/2023
Picked Up By:
Jense Christensen
Date:
5/26/2023
Time:
7:45 AM
Max, Min Temperature
80, 60
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 6/1/2023 3.400 9.07 39,535.0 4359 4,000.0 Type 6
Date:
06/01/2023
Reviewed By:
Luke Hammar
Signature: