I have been provided and reviewed several construction photos and
information regarding the concrete supplier's anticipated concrete
strength. I have reviewed the structures foundation loads. Building
loads applied to the the concrete are relatively light, maximum
distributed wall load is ~2,400 lbs per foot and maximum spot
footing load is ~2,500 lbs. Based on my review of the provided
information and the foundation loads, it is my opinion that additional
concrete testing is not required.