HomeMy WebLinkAboutAPPROVED PLANS - 22-00854 - BYUI Kimball Bldg 170, 244, 250 - Fire AlarmAuthor Name Author Email Author Phone No.: Bret Stoddard brets@rexburg.org 208-372-2171 Description : BYUI Kimball Bldg 170, 244, 250 - Fire Alarm Address : 538 S 2nd E Record Type : Fire System Construction Permit Document Filename : BYU-I Kimball I.T FA Submittal.pdf Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Approved # 22-00854 Page Reference Annotation Type Author : Department Status Page Review Comments Applicant Response Comments 1 Stamp Bret Stoddard : Electrical Open 1 Approved - Fire Inspector 2 Stamp Bret Stoddard : Electrical Open 2 Approved - Fire Inspector 3 Stamp Bret Stoddard : Electrical Open 3 Approved - Fire Inspector 4 Stamp Bret Stoddard : Electrical Open 4 Approved - Fire Inspector 5 Stamp Bret Stoddard : Electrical Open 5 Approved - Fire Inspector 6 Stamp Bret Stoddard : Electrical Open 6 Approved - Fire Inspector 7 Stamp Bret Stoddard : Electrical Open 7 Approved - Fire Inspector 8 Stamp Bret Stoddard : Electrical Open 8 Approved - Fire Inspector Fire System Construction Permit Approval of plans does not constitute approval of variance from code Page Reference Annotation Type Author : Department Status Page Review Comments Applicant Response Comments 9 Stamp Bret Stoddard : Electrical Open 9 Approved - Fire Inspector 10 Stamp Bret Stoddard : Electrical Open 10 Approved - Fire Inspector 11 Stamp Bret Stoddard : Electrical Open 11 Approved - Fire Inspector 12 Stamp Bret Stoddard : Electrical Open 12 Approved - Fire Inspector 13 Stamp Bret Stoddard : Electrical Open 13 Approved - Fire Inspector 14 Stamp Bret Stoddard : Electrical Open 14 Approved - Fire Inspector 15 Stamp Bret Stoddard : Electrical Open 15 Approved - Fire Inspector 16 Stamp Bret Stoddard : Electrical Open 16 Approved - Fire Inspector 17 Stamp Bret Stoddard : Electrical Open 17 Approved - Fire Inspector 18 Stamp Bret Stoddard : Electrical Open 18 Approved - Fire Inspector 19 Stamp Bret Stoddard : Electrical Open 19 Approved - Fire Inspector 20 Stamp Bret Stoddard : Electrical Open 20 Approved - Fire Inspector 21 Stamp Bret Stoddard : Electrical Open 21 Approved - Fire Inspector 22 Stamp Bret Stoddard : Electrical Open 22 Approved - Fire Inspector 23 Stamp Bret Stoddard : Electrical Open 23 Approved - Fire Inspector 24 Stamp Bret Stoddard : Electrical Open 24 Approved - Fire Inspector 25 Stamp Bret Stoddard : Electrical Open 25 Approved - Fire Inspector 26 Stamp Bret Stoddard : Electrical Open 26 Approved - Fire Inspector 27 Stamp Bret Stoddard : Electrical Open 27 Approved - Fire Inspector Approval of plans does not constitute approval of variance from code Page Reference Annotation Type Author : Department Status Page Review Comments Applicant Response Comments 28 Stamp Bret Stoddard : Electrical Open 28 Approved - Fire Inspector 29 Stamp Bret Stoddard : Electrical Open 29 Approved - Fire Inspector Approval of plans does not constitute approval of variance from code Powered by TCPDF (www.tcpdf.org) FIRE CONTROL INSTRUMENTS-GAMEWELL-BOSCH 1481 SOUTH MAJOR STREET S.L.C., UT 84115 P. 801-468-8300 F. 801-468-8305 Kimball Building Information Technologies Office Remodel – BYU-I 525 S Center Street Rexburg, ID 83460 Kimball Building Information Technologies Office Remodel BYU-I Fire Alarm System Submittal & Drawings PROJECT Equipment Manufacturer: Gamewell-FCI Kimball Building Information Technologies Authorized Distributor: Nelson Fire Systems Office Remodel 1481 S Major St BYU-I SLC, UT 84115 Fire Alarm System 801-468-8300... Kimball Building Information Technologies Office Remodel – BYU-I 525 S Center Street Rexburg, ID 83460 TABLE OF CONTENTS Data Sheet Part No. Description FACU: (Existing) Gamewell-FCI E3 Series Emergency Evacuation System NAC POWER SUPPLY: (Existing) Gamewell-FCI HPFF8 NAC Power Supply w/Internal Sync Module DEVICES: Gamewell-FCI SPSCWL Speaker/Strobe White – Ceiling Mount Gamewell-FCI SPCWL Speaker only White – Ceiling Mount Battery Calculations E3 System Battery Calc HPFF8 Battery Calc CKT Voltage Drops Drawings Sheet No. Description Cover Page FA-C-01 Fire Alarm Cover Riser Diagram FA-R-01 Fire Alarm Riser and Matrix Level 1 and 2 FA-1-01 Notification Circuits Fire Alarm Control Unit (Existing) E3 SERIES® BROADBAND SYSTEM Intelligent, Networked, Multi-Channel Fire Alarm Control E3 Series Broadband System GENERAL The Gamewell-FCI, E3 Series® Broadband System is a modular design and offers a wide range of configurations from two basic sub- assemblies. These sub-assemblies form an integrated, distributed fire alarm system that includes audio evacuation and fire command capability. The network communication transmits all fire alarm, audio evacuation, voice paging, and fire fighter communications. This System can be used as a component of the following E3 Series Systems: • E3 Series Broadband Voice Evacuation System • E3 Series Combined Fire and Mass Notification System The E3 Series Broadband System is a revolutionary advance in fire detection and emergency voice evacuation system design. E3 Series Broadband employs proven technology and expands it to accomplish emergency multi-channel voice evacuation, two-way fire fighter communications, and building control applications, while simultaneously sent over a single pair of wires or fiber-optic cable. It is a true peer-to-peer, token ring passing, networked system capable of supporting up to 64 individual nodes. In addition, the Addressable Node Expander (ANX) board expands the network to 122 nodes. All system status, control-by-event sequences, audio voice paging, and fire fighter telephone signals are sent between nodes over a single pair of wires or fiber-optic cable. Each E3 Series Broadband node can be spaced along the network a maximum distance of 3,000 feet (914.4 m) over an unshielded, twisted-pair of wires or fiber-optic cable with signal loss up to 8dB loss. Built-in isolation at each node permits Class B, Class A and Class X network configurations. The E3 Series Broadband is simple to configure for any project requirement. A complete E3 Series Broadband application can be assembled from the following types of nodes: • ILI-E3/ILI95-E3 Series • ANX • INCC Command Center •INX Transponder FEATURES AND BENEFITS • IBC Seismic Certified • Listed under UL® Standard 864, 10th Edition • Listed under UL Standard UL2572, 2nd Edition for Mass Notification • UL Listed for smoke control (dedicated and non-dedicated) when properly configured. • FM/UL Listed for Pre-action/Deluge use • All communication signals and control-by- event sequences over a single pair of twisted, unshielded wires or fiber-optic cable • Distributed architecture, including Class X wiring configurations, allow system components to continue normal operation with no loss of function during single line fault conditions • Integrates INX transponders and INCC command centers to create a complete audio evacuation system with up to 122 nodes • Redundant command centers with microphone and fire fighter’s handset are easily configured by adding INCCs • Uses state-of-the-art digital signal processor (DSP) technology for efficient audio compression and filtering • Provides up to 150 watts of audio power from 3 AM-50 Series amplifiers with an additional 50 watts of standby power in each Intelligent Network Transponder (INX) The E3 Series® Broadband System offers audio evacuation and fire command configurations. Page 2 of 6 — 9020-0613:O General The E3 Series Broadband System is capable of the most sophisticated sequences of operations. The Field Configuration Program (FCP) is based on Boolean logic statements providing AND, OR, NOT, and XOR logic operators. These operators can be combined to produce additional Boolean operators such as NAND, NOR, XNOR. The E3 Series Broadband is software-programmable for multi-channel digital audio applications. It is ideal for use with a wide range of complex system applications including high-rise or campus installations. An array of cabinets allows for neat, compact, installations. A comprehensive set of timing functions can be attached to any input/ output logic statement for the staggered reset of fan control relays, time-delayed alarm activation, automatic. The E3 Series control panel is a microprocessor-based fire alarm control panel that uses the following: • ILI-E3/ILI95-E3 Series, Intelligent Loop Module or • ANX with two signaling line circuits • Two notification appliance circuits When the E3 Series control panel transmits to remote locations, the optional RPT-E3 provides the ILI-E3/ILI95-E3 Series or the ANX with signal boosting and transient protection, as well as connectivity for both wire and fiber-optic cables. Other options also include an integral Digital Alarm Communicator Transmitter (DACT) that supports most popular reporting formats. INCC (Intelligent Network Command Center) The Intelligent Network Command Center (INCC) serves as the central point of interface between an operator and the system’s audio evacuation, fire fighter intercom, and building network. The INCC occupies a single address on the E3 Series Broadband network. A typical INCC assembly consists of the following: • Intelligent Network Interface-Voice Gateway (INI-VGC-Third Generation) or (INI-VGC-UTP-fiber-optic or unshielded twisted-pair) modules • One or more Addressable Switch Modules (ASM-16) • Optional Network Graphic Annunciator (NGA) • Remote 48 LED driver module (ANU-48) Other component options include a paging microphone and a fire fighter’s handset that connects to the INI-VGC (Third Generation) or INI-VGC-UTP module. Each INI-VGC (Third Generation) or INI-VGC- UTP module can support up to 16 ASM-16 modules. Each ASM-16 has 16 push-button switches for a maximum capac- ity of 256 switches per INI-VGC command center. Each switch has three associated LEDs, colored green, yellow, and red. These switches and their LEDs that are fully programmable to serve any system function desired. These switches and LEDs can control the following: • audio speaker circuits • addressable relay outputs • notification appliance circuits • fire fighter phone control circuits • any other special application that might be required Multiple INCCs can be configured into the E3 Series Broadband network to serve as a completely independent command center to operate either for the local area or to operate as remote command centers mimicking, in part or in whole, the function of a main com- mand center. INX (Intelligent Network Transponder) The Intelligent Network Transponder (INX) acts as a network audio transponder for the E3 Series Broadband Network. The INX transponder serves as the point of distribution for the sys- tem’s audio and fire fighter telephone circuits and occupies a single node on the E3 Series Broadband network. A typical INX assembly consists of the following components: The INX transponder occupies a single address on the network and provides termination points for the network connection using either a pair of unshielded twisted-pair wire or fiber-optic cable. The INX transponder receives its power from a PM-9/PM-9G, 9 ampere, filtered, switching power supply providing 24 VDC nominal operating voltage. The PM-9/PM-9G has an integral standby battery charger capable of recharging up to 55 A/H batteries. The E3BB-BB-BC/INX cabinet can house up to 18 A/H sized batteries. INI-VGX (Intelligent Network Interface-Voice Gateway) The INI-VGX uses advanced Digital Signal Processing (DSP) technology for audio compression and filtering allowing the E3 Series Broadband to produce a superior audio tone while conserving network bandwidth to broadcast an instantaneous response. Background noise is automatically filtered during voice paging and fire fighter communications increasing audibility and eliminating the need for push-to-talk devices. The INI-VGX can accommodate up to 16 different messages with a total combined duration of three minutes. Each message can be field installed via a laptop computer and setup to broadcast a voice message or an evacuation tone. The INI-VGX also provides a fire fighter phone riser and an addressable signaling line circuit that can connect to multiple phone jacks or warden stations through as many as 16 AOM-TELF modules. In addition, the INI-VGX SLC can support up to 32 speaker circuits using the AOM-2SF for single channel applications. AM-50 Series Amplifiers The INX or INX CAB-B cabinet can contain up to four AM-50 Series amplifiers that produce 50 watts of power @ either 25 VRMS or 70.7 VRMS audio output. Each amplifier includes two separate speaker circuits that can be wired Class B or Class A. In addition, each amplifier can produce its own tone or message independently of other system amplifiers. Thus, an INX transponder can produce three audio channels simultaneously. Each INX transponder can support up to four AM-50 Series amplifiers operating as main amplifiers with one AM-50 Series amplifier used as a fail-safe backup amplifier. • ANX • ILI-MB-E3/ILI95-MB-E3 • INI-VGX Module • ILI-S-E3/ILI95-S-E3 • PM-9/PM-9G power supply • Up to four AM-50 Series amplifiers 9020-0613:O Page 3 of 6 Figure 1 illustrates the INCC Command Center and the INX Cabinet. Figure 1 INCC Command Center and INX FIRE FIRE IN X E3 Series with 2 notification appliance circuits, each rated 2.0 amps. @ 24 VDC (Class 2 Power-Limited). Two analog addressable signaling line circuits (Class 2 Power-Limited) (Class “A”) INCC-C Command Center with optional Microphone and Firefighter’s Handset ASM-16 Addressable Switch Modules with 16 programmable, addressable switches, each with 3 programmable indicating LEDs: (red, green yellow) INX Transponder with 6 independently programmable speaker circuits, each rated 50 watts (Class 2 Power-Limited) Three simultaneous Audio channels up to 16 programmable voice messages Optional Digital Alarm Communicator Transmitter (DACT-E3) for local or network- wide event reporting One signaling line circuit with 16-AOM-TELF and 32 AOM-2SF addressable devices (AOM-TELFs shown) (Class “B”) standard (Class 2 Power-Limited) Firefighter phone riser (Class 2 Power-Limited) FIRE FIRE Note: The maximum loss between nodes is 8dB using fiber-optic cable. For Class A only, twisted-pair or fiber- optic cable, the maximum distance between nodes is 4,500 ft. (1372m). Class 2 Power-Limited Page 4 of 6 — 9020-0613:O Figure 2 E3 Series Broadband System Initiating / Control Devices NAC NAC FIRE FIRE One phone riser One SLC (16 AOM-TELFs & 32 AOM-2SFs) 6 Speaker appliance circuits 150 watts max. @ w/ 50 watts standby One phone riser NAC NAC FIRE FIRE Local Annunciators, LCD-E3 (max. 6) and LCD-7100, (max. 5) Global display for all network events if set to Region “0” Initiating / Control Devices One SLC (16 AOM-TELFs & 32 AOM-2SFs) One phone riser One SLC (16 AOM-TELFs & 32 AOM-2SFs) Optional Integral DACT Initiating / Control Devices Local annunciators, LCD-7100, (max. 5) Global display for all network Events add LCD-E3 (m ax. 6) FIRE Connect if wired Class A or Class X IN X IN X IN X 6 Speaker appliance circuits 150 watts max. @ w/ 50 watts standby 6 Speaker appliance circuits 150 watts max. @ w/ 50 watts standby E3 Series E3 Series E3 Series Note: The maximum loss between nodes is 8dB using fiber-optic cable. For Class A only (twisted-pair or fiber-optic cable), the maximum distance between nodes is 4,500 ft. (1372m). 9020-0613:O Page 5 of 6 Ordering Information Part Number Description E3 Series Control ILI95-MB-E3 Intelligent Loop Interface95-Main Board ILI-MB-E3 Intelligent Loop Interface-Main Board ILI-S-E3 Intelligent Loop Interface-Expansion ILI95-S-E3 Intelligent Loop Interface95-Expansion ANX-SR Addressable Node Expander-Single Ring ANX-MR-FO Addressable Node Expander-Multi-Ring Twisted-Pair ANX-MR-UTP Addressable Node Expander-Multi-Ring Fiber-Optic LCD-E3 LCD Keypad Display PM-9/PM-9G Power Supply RPT-E3-UTP Network Repeater DACT-E3 Digital Alarm Communicator Transmitter LCD-7100 (Optional) Remote Serial LCD Display INCC Intelligent Network Command Center 1100-0455 ASM-16 Programmable Switch Module (occupies single slot of the inner door) ANU-48 Remote LED Driver INCC-ID Inner door w/6 single slots INCC-CABR INCC backbox (black) with red outer door, Dimensions: 19” W x 19” H x 4” D (48 W x 48 H x 10 cm) 1100-0505 NGA Network Graphic Annunciator INI-VG Series (Third Generation-Voice Gateway Models): INI-VGC Command Center Voice Gateway with unshielded twisted-pair wire networking, optional fiber-optic module connection FML-E3 Fiber-Optic module, multi-mode fiber connec- tor, single channel FSL-E3 Fiber-optic module, single-mode fiber con- nector, single channel INI-VG Series (Legacy Modules): 1100-1321 INI-VGC-FO: Command Center Voice Gateway for fiber-optic only 1100-1322 INI-VGC-UTP: Command Center Voice Gate- way for unshielded twisted-pair wire only Ordering Information Part Number Description Optional Accessories 1100-0503 ANU-48, Remote LED Driver 1100-0451 INICC-TEL, Fire Fighter Telephone Handset 1100-0452 INCC-MIC, Paging Microphone Module (occupies one single slot of Inner Door) 1100-0450 Command Center Blank Plate, 3-Pack INX Intelligent Network Transponder INI-VG Series (Third Generation-Voice Gateway Models): INI-VGX Voice Transponder Gateway with unshielded twisted-pair wire networking, optional fiber-optic module connection FML-E3 Fiber-Optic module, multi-mode fiber connector, single channel FSL-E3 Fiber-optic module, single-mode fiber connector, single channel INI-VG Series (Legacy Modules): 1100-1323 INI-VGX-FO, Transponder Voice Gateway, fiber-optic only 1100-1324 INI-VGX-UTP, Transponder Voice Gateway, unshielded twisted-pair wire only Power Supply: PM-9/PM-9G INX 9 ampere Power Supply AM-50 Series Amplifiers: 1100-0456 AM-50-25, INX 50 Watt Amplifiers 25 VRMS only AM-50-70 INX 50 Watt amplifier 70.7 VRMS output Cabinets: INX-CAB INX Backbox with Black Door Dimensions: 19” W x 19” H x 4” D (48 x 48 x 10 cm) INX-CABR INX Backbox with Red Door Dimensions: 19” W x 19” H x 4” D (48 x 48 x 10 cm) INX CAB-B Enclosure louvered door and INX-CAB-B mounting plate Dimensions: 19 3/8” W x 19 3/8” H x 4.5” D (49 W x 39 H x 11 D cm) For additional information on the cabinets, refer to the E3 Series Cabinets Data Sheet (Part Number: 9020-0649). Seismic Battery Bracket Kits For information on the types of Seismic Battery Bracket Kits available and the Seismic Battery Bracket Kit Part Numbers, refer to the following documents: Seismic Battery Bracket Installation Guide, P/N: 53839 E3 Series Cabinets Data Sheet P/N: 9020-0649 E3 SERIES® BROADBAND SYSTEM TECHNICAL SPECIFICATIONS 9020-0613 | O | 06/20 ©2020 Honeywell International Inc. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.gamewell-fci.com E3 Series® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Country of origin: U.S.A. SYSTEM Detailed product specifications may be found in the following documents: 9020-0542: INCC Intelligent Network Command Center Data Sheet 9020-0637: E3 Series Control Panel Data Sheet 9020-0541: INX Intelligent Network Transponder Data Sheet 9021-60758: E3 Series Combined Fire and Mass Notification Data Sheet TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (non- condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The E3 Series Broadband System is designed to comply with the following standards: UL Standards: UL 864, 10th Edition UL 2572, 2nd Edition for Mass Notification AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult the factory for the latest listing status. UL Listed: S1869, UL 864, 10th Edition UL 2572, 2nd Edition for Mass Notification FM Approved: 3025415 MEA FDNY: 6175 231-06-2E CSFM: 7165-1703:125 City of Chicago Approved: 7165-1703:125 City of Denver Approved ISO 9001 Certification NAC Power Supply (Existing) GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. ©2010 by Honeywell International Inc. All rights reserved.www.gamewell-fci.com 9021-60521 Rev. B page 1 of 2 HPFF8 NAC Expander/Power SupplyDescription The Gamewell-FCI, HPFF8 is a Notification Appliance Cir- cuit (NAC) expansion panel designed to extend the power capabilities of existing NACs and provide power for the auxiliary devices. The HPFF8 connects to any 12 or 24V Fire Alarm Control Panel (FACP) or stand alone. The HPFF8 is available in 8.0 amps. It provides regulated and filtered 24VDC power to each of the four NACs and an auxiliary output. The NAC outputs are rated at 3.0 amps each (the total output cannot exceed 8.0 amps). The auxil- iary output is rated at 2.0 amps. This output is continuously supplied, even in alarm, and therefore must be taken into account for power supply loading and battery size calcula- tions. The NAC outputs may be configured as any of the follow- ing: • Four Class B (Style Y) • Two Class A (Style Z) • Two Class B and one Class A • Four Class A with the optional HPP31076 Class A adapter installed These power supplies contain an internal Battery charger capable of charging up to 26.0 amp-hour (AH) batteries. The HPFF8 is mounted in lockable wall cabinet units that can accommodate up to two (2), 18AH batteries. A multi- pack option allows for up to four chassis mount units installed in a single lockable SBB-D4 enclosure. These chassis mount units have a "CM" suffix, HPFF8CM and can accommodate two 12AH batteries. Power supplies are available in either 120VAC/60 Hz or 240VAC/50 Hz. One of the most challenging aspects of a retrofit applica- tion is locating the existing End-of-Line (EOL) resistor. In these applications that have EOL values, other than the 3.9k normally used with the HPFF8, a single resistor matching the existing EOL can be used as a reference for all the outputs. This feature speeds the installation and the system checkout, because the actual EOL does not need to be located and changed in the circuit. The reference resistor must be within the range of 1.9k to 25k. Features • Four (4) supervised notification application circuits (NACs) capable of supplying +24VDC at 3.0 amp maximum each • NAC output circuits may be configured as any of the following: - Four Class B (Style Y) - Two Class B & one Class A - Two Class A (Style Z) - Four Class A with the optional HPP31076 Class A adapter installed • Four field-programmable operational modes • 2.0 amp auxiliary continuously supplied output • Two (2) fully supervised input/output control circuits • Temporal coding and sync protocols compatible with the following notification appliance brands: - System Sensor - Faraday - Gamewell - Amseco - Cooper-Wheelock - Gentex • Supervised AC input, battery voltage, auxiliary output, charger, and earth ground faults • Trouble indication for supervision of the following: - NAC circuits - Auxiliary output - AC input - Charger - Battery voltage - Open contacts in the initiat- ing device signal inputs (for FACP trouble notification) - Earth ground faults by individual status LED's • Separate Trouble and AC Fail Form-C relay Contacts HPFF8 An ISO 9001-2000 Company 7315-1637:0102 SIGNALING S24562 FM APPROVED GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9021-60521 Rev. B page 2 of 2 www.gamewell-fci.com Features (Continued) • The Trouble Form-C relay contacts selectable for imme- diate or a 2 hour delay with AC failure • 26 AH battery charger capability; the wall cabinet supports two 12V 18AH batteries, while the multi-pack equipment cabinets supports two 12V 12AH batteries. • NAC Overload protection and indication • Up to four chassis mount units (HPFF8CM) can be installed in the SBB-D4 backbox • Wall mount units can be configured to internally house the following: - one AOM-2SF single control module - one AOM-2R single relay module Specifications Primary Input Power:120VAC/60Hz, 3.6A or 220VAC/50Hz, 1.5A Secondary Power:24 volt operation: two (2), 7-24 AH batteries Battery Charging Capacity:Up to 26 AH batteries mounted Battery Space: HPFF8 Cabinet:Up to two 18AH batteries SBB-D4 Cabinet:Up to two 12AH batteries per supply Total Output Power:8.0A max Standby Current: 0.030 A Auxiliary Power Output:0.15A under all conditions 2.0A if load is removed dur- ing operation (external relay or AC Fail Relay is required) Specifications (Continued) NAC Output Ratings:24VDC fully regulated, 3.0A max per circuit (8.0A total) End-of-Line Resistor Range: 2K to 25k ohm, ½ watt Common Trouble Relay/AC Fail Relay:2.0A at 28VDC or 120VAC Input Control Circuit:16-30VDC @ 5mA min. Temperature Rating:32°F to 120°F (0°C to 49°C Relative Humidity:10% to 93% non-condensing Cabinet Dimensions: HPFF8 Cabinet:16.65” W x 19.0” H x 5.2” D (42.29 W x 48.26 H 13.23 D cm) SBB-D4 Cabinet:24” W x 45.9” H x 5.15” D (60.96 W x 116.52 H x 13.1D cm) Ordering Information Part Number Description HPFF8 8A fire rated power supply operating at 120VAC/60 Hz. Unit includes red enclosure with HPP lock and key HPFF8CM 8A fire rated power supply - chassis mounted operating at 120VAC/60 Hz. Unit includes mounting hardware for installation in the SBB-D4 enclosure HPFF8E 8A fire rated power supply operating at 240VAC/50 Hz HPFF8CME 8A fire rated power supply chassis mounted operating at 240VAC/50 Hz HPP31076 Class A (Style Z) NAC module FCI-VDR-D4 Vented door, PK-625 lock and key for SBB-D4 backbox, black SBB-D4 Backbox, accepts up to 4 chassis, black Devices Ceiling Speaker Strobes L Series, Indoor Ceiling Strobes and Dual Speakers Indoor Output Speaker Strobes and Dual Speakers for Ceiling Applications Notification Appliances General The L-Series indoor selectable-output speaker strobes and dual-voltage evacuation speakers offer a modern, aesthetic plug-in design that reduce costly ground faults. The universal mounting plate can be used in ceiling applications and its flexible design enables the Installer to easily perform the following: • Pre-wire mounting plates •Dress the wires Confirm wiring continuity before the Installer plugs-in the speakers. In addition, this product includes a protective plastic cover which shields exposed speaker components and prevents nicked wires. These devices enable faster installations by providing instant feedback to the Installer to ensure the following: • The wiring is properly connected. • The rotary switches are set to the selected voltage and power settings. • The 7 field-selectable candela settings are configured for wall speaker strobes. • The low total harmonic distortion of the SP speaker offers both high-fidelity and high-volume sound output so that it can be used in high ambient noise applications. L-Series makes installation easy to install the L-Series speakers or speaker strobe, do the following: 1. Attach a universal mounting plate to a 4 x 4 x 2 1/8 inch backbox. Flush- mount applications do not require an extension ring. 2. Connect the notification appliance circuit or speaker wiring to the terminals on the mounting plate. 3. To attach the speaker or speaker strobe to the mounting plate, insert the product tabs into the mounting plate grooves. 4. Hinge the device into position to lock the product pins into the mounting plate terminals. 5. A catch temporarily holds the device in place until you secure the device with a captured mounting screw. FEATURES & BENEFITS • Includes a plug-in feature and protective cover to reduce ground faults • Contains a universal mounting plate with an on-board shorting spring that is used to test the wiring continuity before an installation • No extension ring required • Field-selectable candela settings on ceiling units: - 15 - 30 - 75 - 95 - 115 - 150 - 177 • Uses an automatic selection of 12- or 24- volt operation at 15 and 30 candela • Provides a rotary switch that simplifies the field selection of speaker voltage (25) and 70.7 VRMS) and the following power settings: - 1/4 watt - 1/2 watt - 1 watt - 2 watts • Offers speakers with both high-fidelity and high-volume sound output • Compatible with the System Sensor synchronization protocol • Supports electrical compatibility with the existing SpectrAlert and the SpectrAlert Advance products •Designed with a tamper-resistant construction • Built with an updated modern design 2 L-Series Speaker and Speaker Strobe Specifications Architectural/Engineering Specifications General The L-Series speaker and speaker strobes shall mount to a 4 x 4 x 2 1/8-inch backbox. A universal mounting plate shall be used for the mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also, the L-Series speaker strobes, when used with the Sync•Circuit. Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When these devices are used with the Sync•Circuit Module, either of the following may occur. • 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts. • 24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. The Indoor L-Series products shall operate between 32° F and 120°F from a regulated DC, or full-wave rectified, unfiltered power supply. Speaker strobes shall have the following field-selectable candela settings: Speaker The speaker shall be an L-Series model _______ dual- voltage transformer speaker capable of operating at 25.0 or 70.7 nominal VRMS. It should be listed to UL Standard 1480 and shall be approved for fire protective service. The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F. The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe Combination The speaker strobe shall be an L-Series model __________ listed to UL Standard 1480 and UL Standard 1971 and be approved for fire protective signaling systems. The speaker shall be capable of operating at 25.0 or 70.7 nominal VRMS selected via rotary switch, and shall have a frequency range of 400 to 4,000 Hz. The speaker shall have power taps that are selected by rotary switch. The strobe shall comply with the NFPA 72 requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a Sync•Circuit model MDL3 listed to UL Standard 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz. The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box. The module shall also control two Style Y (Class B) circuits or one Style Z (Class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. UL Current Draw Data Table 1 lists the UL maximum strobe current draw. Table 2 lists the ceiling mount speaker sound outputs. Table 3 lists the ceiling-mount speaker strobe sound outputs. •15 •30 •75 •95 •115 •150 •177 8-17.5 Volts 16-33 Volts Candela DC DC FWR 15 87 41 60 30 153 63 86 75 NA 111 142 95 NA 134 164 115 NA 158 191 150 NA 189 228 177 NA 226 264 Table 1 UL Max. Strobe Current Draw (mA RMS) Setting UL Reverberant (dBA @10 ft) UL Anechoic (dBA @10 ft) 1/4 W 79 79 1/2 W 82 82 1 W 85 85 2 W 88 88 Table 2 Ceiling Speaker Sound Outputs Setting UL Reverberant (dBA @10 ft) UL Anechoic (dBA @10 ft) 1/4 W 77 77 1/2 W 80 80 1 W 83 83 2 W 86 86 Table 3 Ceiling-Mount Speaker Strobe Sound Output 3 Dimensions Figure 1 shows the speaker dimensions. Figure 2 shows the speaker dimensions. Surface Mounting Figure 3 illustrates the ceiling-mount speaker and speaker strobes with the SBBCR/SBBCWL surface mount backbox. L-Series Ordering Information SpectrAlert Speakers and Strobes: Ceiling Mount: SPCWL: White Speaker only SPCRL: Red Speaker only SPSCWL: White Speaker Strobe SPSCRL: Red Speaker Strobe SPSCWL-P: Plain, Speaker Strobe SPSCWL-SP: Fuego, Speaker Strobe SPSCWL-CLR-ALERT : Alert, Speaker Strobe,Clear Lens Accessories: SBBCWL: White, Universal Ceiling Surface Mount Back Box SBBCRL: Red, Universal Ceiling Surface Mount Back Box TRC-2W: White, Universal Ceiling Trim Ring TRC-2: Red, Universal Ceiling Trim Ring Figure 1 Speaker Dimensions Figure 2 Speaker Dimensions Figure 3 Ceiling-Mount Speaker and Speaker Strobe with SBBCRL/SBBCWL Surface Mount Backbox L Series, Indoor Ceiling Strobes and Dual Speakers Technical Specifications 9021-60930 | C | 03/18 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s L Series, Indoor Ceiling Strobes and Dual Speakers and other products available by visiting www.Gamewell-FCI.com SYSTEM Electrical/Operating Specifications: Nominal Voltage (speakers): 25 Volts or 70.7 Volts (nominal) Maximum Supervisory Voltage (speakers): 50 VDC Strobe Flash Rate: 1 flash per second Nominal Voltage (strobes): Regulated 12 VDC or Regulated 24 VDC/FWR Operating Voltage Range (includes fire alarm panels with built-in sync): 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage with MDL3 Sync Module: 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Frequency Range: Frequency Range: 400 to 4,000 Hz Power: ¼, ½, 1, 2 watts STANDARDS The L-Series, Indoor Ceiling Strobes and Horn Strobes are designed to comply with the following standard: UL Standard: UL 1971 and UL 464 AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S5512, S4011 CSFM: 7320-1653:0505 ISO 9001 Certification Physical Specifications: Operating Temperature:32°F to 120°F (0°C to 49°C) Humidity Range:10 to 93% non-condensing Dimensions,Ceiling-Mount:Diameter Depth SPC Speaker 6.8 in, 173 mm 1.0 in, 25 mm With Surface Mount BacKbox 6.9 in, 176 mm 3.5 in, 89 mm SPSC Speaker Strobe 6.8 in, 173 mm 2.8 in, 73 mm With Surface Mount Backbox 6.9 in, 176 mm 5.37 in,136 mm Calculations Protected Premises:Date:10/4/2022 Address: City:State:ID Zip:83460 Prepared B Phone:801-468-8300 Address:Email: City:State:Utah Zip:84115 Secondary Load Requirements 15.24 Amp Hours Total (AH) 11.83 0.86 12.70 x 1.20 15.24 AH 18.00 Amp Hours Battery Distribution Chart Spare Battery Capacity 2.76 Amp Hours Secondary Standby Load 14.20 Amp Hours Secondary Alarm Load 1.04 Amp Hours 10.297 A x x Select batteries from the list bl Total Secondary Load System Power Requirements E3 Fire Alarm Control Panel with Broadband Battery Selection Secondary Standby Load 0.493 A Secondary Alarm Load 1481 S Major Street office@nelsonfire.com Salt Lake City 24 hours Required Standby Time BYU-I Kimball Information Technologies Office- Remodel 525 S Center Street Rexburg Nelson Fire Systems Current Draw Time (hours) Total Secondary Load from the calculation table below. Shows amp-hour distribution of your selections. Derating factor Secondary Load Requirements 18 AH Battery (12 Volt Required Alarm Time (hours) 0.084 hours Spare Battery Capacity 15% Secondary Standby Load 79% Secondary Alarm Load 6% Spare Battery Capacity Secondary Standby Load Secondary Alarm Load 0.493 A 10.297 A Qty Draw Standby Qty Draw Alarm 0 x 0.08100 1 x 0.15000 0.15000 0 x 0.08100 0 x 0.15000 Intel. Loop Interface Main Board - Apollo (ILI95-MB-E3)0 x 0.05000 0 x 0.09100 Intel. Loop Interface Supplement Board - Apollo (ILI95-S-E3)0 x 0.05000 0 x 0.09100 E3 Panel, 1 SLC 0 x 0.05600 0 x 0.07600 E3 Panel, 1 SLC with DACT 0 x 0.07500 0 x 0.09500 0 x 0.06500 0 x 0.08500 0 x 0.08500 0 x 0.10500 120V Power Supply Sub-Assembly (PM-9)0 x 0.05000 0 x 0.05000 240V Power Supply Sub-Assembly (PM-9G)0 x 0.02700 0 x 0.05000 1 x 0.02400 0.02400 1 x 0.02800 0.02800 0 x 0.01300 0 x 0.01300 0 x 0.01800 0 x 0.01800 0 x 0.05000 0 x 0.07500 0 x 0.20000 0 x 0.20000 1 x 0.01100 0.01100 1 x 0.01100 0.01100 0 x 0.01100 0 x 0.01100 0 x 0.06500 0 x 0.06500 Intelligent Network Inferface Module (INI-7100)0 x 0.04000 0 x 0.04000 0 x 0.02000 0 x 0.02000 0 x 0.03500 0 x 0.20000 0 x 0.00100 0 x 0.00100 0 x 0.00100 0 x 0.00100 0 x 0.15000 0 x 0.15000 0 x 0.01100 0 x 0.01100 0 x 0.00100 0 x 0.00100 0 x 0.02000 0 x 0.020000x0.00200 0 x 0.00650 1 x 0.15000 0.15000 1 x 0.15000 0.15000 1 x 0.05000 0.05000 1 x 0.05000 0.05000 240V Power Supply Sub-Assembly (PM-9G)0 x 0.02700 0 x 0.05000 3 x 0.08600 0.25800 3 x 2.20600 6.61800 Amplifier Sub-assembly, 50 watt 70V (AM-50-70)0 x 0.04900 0 x 2.30000 0 x 0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 0 x 0.15000 0 x 0.15000 0 x 0.01100 0 x 0.01100 0 x 0.00100 0 x 0.00100 0 x 0.02000 0 x 0.02000 0 x 0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 0 x 0.00020 0 x 0.00200 0 x 0.00020 0 x 0.00200 0 x 0.00020 0 x 0.00200 0 x 0.00038 0 x 0.00500 0 x 0.00038 0 x 0.00650 0 x 0.00030 0 x 0.00700 0 x 0.00000 0 x 0.00000 10 x 0.00000 0.00000 10 x 0.04100 0.41000 1 x 0.00000 0.00000 1 x 0.06300 0.06300 1 x 0.00000 0.00000 1 x 0.11100 0.11100 33 x 0.00000 0.00000 33 x 0.08200 2.70600 1 1 SPSCWL75 SPCWL Device AMM-4F/AMM-2F AOM-2RF/AOM-2SF MS-7AF SPSCWL30 8. Notification Appliances SPSCWL15 Addressable Output Module-Telephone (AOM-TEL) Addressable Output Module-Audio (AOM-MUX) ASD-PL3 7. Smoke Detectors/Modules ATD-RL3 DNR Firefighter's Telephone (Handset) Addressable Output Module-Signal (AOM-2SF) Intel. Network Voice Gateway (INI-VGX) 120V Power Supply Sub-Assembly (PM-9) Class A Option Module (CAOM) Municipal Circuit Option Module (MCOM) Addressable Output Module-Telephone (AOM-TEL) Addressable Output Module-Audio (AOM-MUX) Voice Paging Microphone (Microphone) Firefighter's Telephone (Handset) 3. 7100 Optional Modules Intel. Network Command Voice Gateway (INI-VGE) Addressable Switch Sub-assembly (ASM-16) Voice Paging Microphone (Microphone) Network LCD Annunicator (NGA) Auxiliary Switch Sub-Assembly (ASM-16) 4. INI-VGC Command Center Intel. Network Command Center (INI-VGC) 6. INI-VGE Command Center Voice Gateway Addressable Switch Sub-assembly (ASM-16) Addressable Output Module-Telephone (AOM-TEL) Addressable Output Module-Signal (AOM-2SF) 1. System Device E3 Panel, 2 SLC Amplifier Sub-assembly, 50 watt 25V (AM-50) 5. INI-VGX Voice Gateway LCD Display & Switch Control (LCD-E3) ARCNET Repeater (RPT-E3) Printer Transient Module (PTRM) Remote LED Driver Module (LDM-7100) Optional Remote Serial Annunicator (LCD-7100) Alarm CurrentStandby Current System Current Draw - FACP E3 Series Control Panel with Broadband Total AlarmTotal Standby Intel. Loop Interface, Main Board (ILI-MB-E3) Intel. Loop Interface Supplement Board (ILI-S-E3) Total Standby Load:0.493 A 10.297 ATotal Alarm Load: E3 Panel, 2 SLC with DACT 2. E3 Optional Modules Remote LED Driver Module (ANU-48) Addressable Node Expander (ANX) Digital Communicator (DACT-E3) Protected Premises:Date:10/4/2022 Address: City:State:ID Zip:83460 Prepared By:Phone:801.468.8300 Address:Email: City:State:UT Zip:84115 Secondary Load Requirements 2.45 Amp Hours Total (AH) 1.80 0.24 2.04 x 1.2 2.45 AH 8 Amp Hours TRUE 1481 S Major Street Office@nelsonfire.com Salt Lake City Secondary Power Requirements BYU-I Kimball Information Technologies Office - Remode 525 S Center Street Rexburg Nelson Fire Systems HPFF8 Power Supply Time (hours) Required Standby Time 24 hoursx Total Secondary Load from the calculation table below. 0.075 A Secondary Load Requirements Total Secondary Load Secondary Alarm Load x0.954 A Required Alarm Time (hours) 0.250 hours Current Draw Secondary Standby Load Select batteries from the list below. Battery Selection 8.0 AH BAT-1270 Battery (12 volt) Derating factor Page 1 of 2 Battery Distribution Chart Comments 5.55 2.16 0.29 Secondary Alarm Load (AH) * Derating FactorSecondary Alarm Load Shows amp-hour distribution of your selections. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Spare Battery Capacity Secondary Standby Load 2. Selected battery size meets secondary load requirements. Battery Selection (AH) - Secondary Load Requirements (AH) Secondary Standby Load (AH) * Derating Factor 1. Batteries will fit in the FACP cabinet. Spare Battery Capacity 69% Secondary Standby Load 27% Secondary Alarm Load 4% Spare Battery Capacity Secondary Standby Load Secondary Alarm Load Page 2 of 2 Standby 0.075 A Alarm 0.954 A Qty Draw Non-Alarm Qty Draw Alarm 1 x 0.07500 0.07500 1 x 0.20600 0.20600 7 x 0.00000 0.00000 7 x 0.05400 0.37800 1 x 0.00000 0.00000 1 x 0.07100 0.07100 0 x 0.00000 0 x 0.13700 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.00000 0.44900 3 x 0.00000 0.00000 3 x 0.05400 0.16200 0 x 0.00000 0 x 0.07100 1 x 0.00000 0.00000 1 x 0.13700 0.13700 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.00000 0.29900 0 x 0.00000 0 x 0.05400 0 x 0.00000 0 x 0.07100 0 x 0.00000 0 x 0.13700 0 x 0.00000 0 x 0.18500 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.00000 0.00000 0 x 0.00000 0 x 0.05400 0 x 0.00000 0 x 0.07100 0 x 0.00000 0 x 0.13700 0 x 0.00000 0 x 0.18500 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.00000 0.00000 0 x 0.00000 0 x 0.03000 0 x 0.03700 0 x 0.00850 0 x 0.02000 0 x 0.04000 0 x 0.05000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0.00000 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #3 Totals (Max 3 Amps): SPSCWL115 4. L4 SPSCWL15 SPSCWL30 SPSCWL75 SPSCWL30 SPSCWL75 NAC #2 Totals (Max 3 Amps): Device SPSCWL15 SPSCWL75 0.954 System Current Draw - HPFF8 Total Current SPSCWL30 Secondary Alarm CurrentSecondary Non-Alarm Current 1. System Modules 1. L1 HPFF8 Main Circuit Board Other compatible devices Other compatible devices Total Non-Alarm Load: 2. L2 NAC #1 Totals (Max 3 Amps): SPSCWL30 SPSCWL75 NAC #4 Totals (Max 3 Amps): 3. L3 SPSCWL15 TB4 Totals (Max 2 Amps): SPSCWL115 SPSCWL15 Other compatible devices 7. Compatible Devices not listed 0.075 6. Auxiliary Power PR-3 FIRERAY5000 CO1224TR E3SMRCO/E3SA Auxiliary Device Total Alarm Load: Drawings KIMBALL BUILDING 170, 244, AND 250 INFORMATION TECHNOLOGY OFFICE REMODEL BRIGHAM YOUNG UNIVERSITY- IDAHO FIRE ALARM SYSTEM JPK PAYNE ENG TDT (ANSI B) 1/16" = 1' XXXX XXXX KI M B A L L B U I L D I N G 1 7 0 , 2 4 4 , A N D 2 5 0 IN F O R M A T I O N T E C H N O L O G Y O F F I C E R E M O D E L BR I G H A M Y O U N G U N I V E R S I T Y - I D A H O 52 5 S C E N T E R S T R E E T RE X B U R G , I D A H O 8 3 4 6 0 FI R E A L A R M S Y S T E M PROJECT COVER SHEET FA-C-01 NELSON FIRE SYSTEMS DRAWN BY: DESIGNED BY: APPROVED BY: DATE: SCALE: PROJECT NO: REVISION NO: DRAWING NAME: NO T E : NF S D R A W I N G S A R E B A S E D O N T H E P R O J E C T AR C H I T E C T U R E / E N G I N E E R ( A / E ) P L A N S A N D SP E C I F I C A T I O N S F U R N I S H E D T O N F S . A / E I S S O L E L Y RE S P O N S I B L E ( N O T N F S ) F O R T H E T Y P E , S I Z E , LO C A T I O N , A N D S U I T A B I L I T Y O F A L L F I R E A L A R M S , CO N T R O L P A N E L S , A N D O T H E R D E V I C E S S H O W N O N TH E A / E P L A N S . N F S D R A W I N G S A R E T O S H O W O N L Y TH E W I R I N G D I A G R A M S B E T W E E N F I R E A L A R M DE V I C E S A N D C O N T R O L P A N E L S . N F S I S N O T RE S P O N S I B L E F O R T H E I N F O R M A T I O N S H O W N O N T H E A/ E P L A N S . NELSON FIRE SYSTEMS PAGE: BYUI KIMBALL REM 2022 C.DWG 9/16/2022 9:39:24 AMINDEX OF DRAWINGS PAGE 1 2 3 FA-C-01 FA-R-01 FA-1-01 SHEET #LEVEL PROJECT COVER SHEET / INDEX OF DRAWINGS FIRE ALARM BUILDING RISER DIAGRAM / MATRIX LEVEL 1 & 2 SHEET CONTENTS NOTIFICATION CIRCUITS BUILDING CONSTRUCTION TYPE: IIB BUILDING SQUARE FOOTAGE: 7,987 FT 2 DEVICE SCHEDULE COUNTS SPEAKER/STROBE- CEILING SPSCWL DESCRIPTION FIRE ALARM CONTROL UNIT EXISTING TRANSPONDER PANEL EXISTING SS FACU TRAN C 4 SQ. 2-1/8" DEEP BOX MINIMUM w/1-1/2" EXT. RING EXISTING TO REMAIN EXISTING TO REMAIN PART NUMBER MOUNTING REQUIREMENTSYMBOL 12 33 SPEAKER ONLY- CEILING SPCWLSC 4 SQ. 2-1/8" DEEP BOX MINIMUM w/1-1/2" EXT. RING LEVEL 1 DO NOT USE SHIELDED WIRE ON ADDRESSABLE CIRCUIT JPK PAYNE ENG TDT (ANSI B) 1/16" = 1' XXXX XXXX KI M B A L L B U I L D I N G 1 7 0 , 2 4 4 , A N D 2 5 0 IN F O R M A T I O N T E C H N O L O G Y O F F I C E R E M O D E L BR I G H A M Y O U N G U N I V E R S I T Y FI R E A L A R M R I S E R D I A G R A M / M A T R I X 52 5 S C E N T E R S T R E E T RE X B U R G , I D A H O 8 3 4 6 0 FI R E A L A R M S Y S T E M FIRE RISER DIAGRAM / MATRIX FA-R-01 NELSON FIRE SYSTEMS DRAWN BY: DESIGNED BY: APPROVED BY: DATE: SCALE: PROJECT NO: REVISION NO: DRAWING NAME: NO T E : NF S D R A W I N G S A R E B A S E D O N T H E P R O J E C T AR C H I T E C T U R E / E N G I N E E R ( A / E ) P L A N S A N D SP E C I F I C A T I O N S F U R N I S H E D T O N F S . A / E I S S O L E L Y RE S P O N S I B L E ( N O T N F S ) F O R T H E T Y P E , S I Z E , LO C A T I O N , A N D S U I T A B I L I T Y O F A L L F I R E A L A R M S , CO N T R O L P A N E L S , A N D O T H E R D E V I C E S S H O W N O N TH E A / E P L A N S . N F S D R A W I N G S A R E T O S H O W O N L Y TH E W I R I N G D I A G R A M S B E T W E E N F I R E A L A R M DE V I C E S A N D C O N T R O L P A N E L S . N F S I S N O T RE S P O N S I B L E F O R T H E I N F O R M A T I O N S H O W N O N T H E A/ E P L A N S . NELSON FIRE SYSTEMS PAGE: BYUI KIMBALL REM 2022 R.DWG 9/16/2022 2:20:00 PM LEVEL 2 FACU EXISTING TRANSPONDER EXISTING SS C SS CSSCSSCSSC SS CSSCSCSCSCSCSCSC S CSCSCSCSCSC S C S C S C S C S C S C S C S C S C S C 1/4W 1/2W SP1-1 1/4W 1/4W SP1-2 1/4W SP1-3 1/4W SP1-4 1/4W1/4W SP1-5 SP1-7SP1-6 1/2W SP1-8 1/4W 1/4W SP1-9 1/4W SP1-10 SP1-11 SP1-12 L1-1 15cd L1-2 15cd 1/4W SP1-28 1/4W SP1-27 1/2W SP1-26 1/4W SP1-18SP1-25 1/4W SP1-24 1/4W SP1-23 1/4W SP1-22 1/4W SP1-21 1/4W SP1-20 1/2W SP1-19 1/4W 1/4W SP1-17 L1-6 15cd L1-5 15cd SS (E) 1/4W SP1-13 1/4W SP1-14 1/2W SP1-16 L1-4 30cd 1/2W SP1-15 L1-3 15cd 1/2W SP1-29 L1-7 15cd SS (E) 1/2W 1/2W 1/2W SP2-6 1/2W SP2-1 SP2-2 1/2W SP2-3 1/2W SP2-4 1/2W SP2-5 SP2-7 SP2-8 1/2W 1 PAIR #14'S TWISTED SHIELDED NEW SPEAKER CIRCUITL2-1 15cd L2-2 15cd L2-3 75cd 1/2W SP2-15 1/2W SP2-14 1/2W SP2-13 1/2W SP2-12 1/2W SP2-11 1/2W SP2-10 1/2W SP2-9 L2-4 15cd 2 #14'S NEW STROBE CIRCUIT 1 PAIR #14'S TWISTED SHIELDED NEW SPEAKER CIRCUIT 2 #14'S NEW STROBE CIRCUIT SS C SS CSSCSSC S CSCSCSCSC S C S C S C S CSCSC SS C 1/4W SP1-30 L1-8 15cd [SPCWL] CEILING SPEAKER ONLY TO NEXT DEVICESPEAKER CKT OUTIN [SPSWL] WALL SPEAKER STROBE TO NEXT DEVICESPEAKER CKT OUTIN TO NEXT DEVICE(+) (-)STROBE CIRCUIT IN OUT(+) (-) [SPSCWL] CEILING SPEAKER STROBE TO NEXT DEVICESPEAKER CKT OUTIN TO NEXT DEVICE(+) (-)STROBE CIRCUIT IN OUT(+) (-) BUILDING- SMOKE DETECTORS BUILDING- DUCT DETECTORS BUILDING- PULL STATIONS BUILDING- TAMPER SWITCH BUILDING- WATERFLOW SWITCH LOSS OF POWER ANY PANEL OR NAC LOW BATTERY CONDITIONS OPEN CIRCUIT CONDITIONS GROUND FAULTS AL A R M S I G N A L T O F I R E A L A R M D I S P L A Y SU P E R V I S O R Y S I G N A L T O F I R E A L A R M D I S P L A Y TR O U B L E S I G N A L T O F I R E A L A R M D I S P L A Y BU I L D I N G S P E A K E R / S T R O B E S HV A C S H U T - D O W N FI R E / S M O K E D A M P E R S RE L E A S E M A G N E T I C D O O R H O L D E R S AL A R M S I G N A L T O M O N I T O R I N G C O M P A N Y SU P E R V I S O R Y S I G N A L T O M O N I T O R I N G C O M P A N Y TR O U B L E S I G N A L T O M O N I T O R I N G C O M P A N Y FACP ANNUNCIATIONNOTIFICATION FIRE SAFETY CONTROL REPORTING SYSTEM INPUTS SYSTEM OUTPUTSFIRE ALARM INPUT/OUTPUT MATRIX SS SPEAKER/STROBE- WALL SS SPEAKER/STROBE- CEILING12C S SPEAKER ONLY- CEILING33C DEVICE LEGEND DESCRIPTIONCOUNTSSYMBOL EXISTING DEVICE(E) SS (E)SS (E)SS (E)SS (E) 3.9K E.O.L. 4.7K E.O.L. EXISTING SPEAKER/STROBE CIRCUIT SS (E)SS (E)SS (E)SS (E) 3.9K E.O.L. 4.7K E.O.L. EXISTING SPEAKER/STROBE CIRCUIT 3.9K E.O.L. 4.7K E.O.L. 3.9K E.O.L. 4.7K E.O.L. JPK PAYNE ENG TDT (ANSI B) 1/16" = 1' XXXX XXXX KI M B A L L B U I L D I N G 1 7 0 , 2 4 4 , A N D 2 5 0 IN F O R M A T I O N T E C H N O L O G Y O F F I C E R E M O D E L BR I G H A M Y O U N G U N I V E R S I T Y - I D A H O 52 5 S C E N T E R S T R E E T RE X B U R G , I D A H O 8 3 4 6 0 FI R E A L A R M S Y S T E M LEVEL 1 & LEVEL 2 NOTIFICATION FA-1-02 NELSON FIRE SYSTEMS 801-468-8300 DRAWN BY: DESIGNED BY: APPROVED BY: DATE: SCALE: PROJECT NO: REVISION NO: DRAWING NAME: NO T E : NF S D R A W I N G S A R E B A S E D O N T H E P R O J E C T AR C H I T E C T U R E / E N G I N E E R ( A / E ) P L A N S A N D SP E C I F I C A T I O N S F U R N I S H E D T O N F S . A / E I S S O L E L Y RE S P O N S I B L E ( N O T N F S ) F O R T H E T Y P E , S I Z E , LO C A T I O N , A N D S U I T A B I L I T Y O F A L L F I R E A L A R M S , CO N T R O L P A N E L S , A N D O T H E R D E V I C E S S H O W N O N TH E A / E P L A N S . N F S D R A W I N G S A R E T O S H O W O N L Y TH E W I R I N G D I A G R A M S B E T W E E N F I R E A L A R M DE V I C E S A N D C O N T R O L P A N E L S . N F S I S N O T RE S P O N S I B L E F O R T H E I N F O R M A T I O N S H O W N O N T H E A/ E P L A N S . NELSON FIRE SYSTEMS PAGE: 25'10'50' W E SN 1.INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND OTHER APPLICABLE CODES AS REQUIRED BY THE LOCAL AHJ. CLASS "B" WIRING IS REQUIRED. 2.WIRING DEPICTED ON THESE PLAN IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY DIFFER FROM THESE PLANS. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING CONSTRUCTION CONDITION ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS LONG AS NO 110V OR HIGHER CABLES ARE IN THE RACEWAY. 3.POWER-LIMITED (PL) AND NONPOWER-LIMITED (NPL) CKT WIRING MUST REMAIN SEPARATED IN CABINET. ALL PL CKT WIRING MUST REMAIN AT LEAST 0.25" AWAY FROM ANY NPL CKT. FURTHERMORE, ALL PL AND NPL CKT WIRING MUST ENTER AND EXIT THE CABINET THROUGH A DIFFERENT KNOCKOUT AND/OR SEPARATE CONDUIT. 4.ONLY FIRE ALARM WIRING IS PERMITTED IN FIRE ALARM CONDUIT. DO NOT USE 110V OR HIGHER IN FIRE ALARM CONDUIT. 5.SMOKE DETECTORS SHALL BE INSTALLED AND COVERED UNTIL TESTING AND FINAL INSPECTION ARE COMPLETED. DO NOT INSTALL SMOKE DETECTORS UNTIL BUILDING IS CLEAN. 6.LOCATE SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM MECHANICAL DIFFUSERS. 7.DO NOT USE SHIELDED WIRE ON ADDRESSABLE CKTS. 8.A SMOKE DETECTOR MUST BE IN EVERY ROOM WITH A FIRE ALARM CONTROL UNIT OR POWER SUPPLY. 9.FIRE ALARM CKTS NEED TO BE FREE OF GROUNDS, FAULTS, AND SHORTS PRIOR TO CONNECTION TO FIRE ALARM EQUIPMENT. 10.DEDICATED 120 VAC CKTS SHALL BE MARKED AS "FIRE ALARM CKT" AND BE ACCESSIBLE ONLY TO PERSONNEL. DISCONNECTS FOR THESE CKTS WILL BE RED IN COLOR AND THEIR LOCATION WILL BE NOTED AT EACH CONTROL UNIT. GENERAL NOTES: 9/16/2022 9:39:17 AM BYUI KIMBALL REM 2022.DWG WIRE SCHEDULE NOTE DESCRIPTION WIRES S L SPEAKER CIRCUIT 1 PAIR #14'S TWISTED/SHIELDED STROBE CIRCUIT 2 #14'S WIRING NOTE DESCRIPTION A =2 TOTAL CONDUCTORS (2)A =4 TOTAL CONDUCTORS A,(2)B =6 TOTAL CONDUCTORS SS SPEAKER/STROBE- WALL SS SPEAKER/STROBE- CEILING12C S SPEAKER ONLY- CEILING33C DEVICE LEGEND DESCRIPTIONCOUNTSSYMBOL SYSTEM NOTES: 1 EXISTING DEVICE TO BE DEMOED. MAINTAIN CIRCUIT INTEGRITY AND CONNECT NEW SPEAKER/STROBE CIRCUIT. SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C S C S C S C S C S C S C S C S C S C S C S C S C S C S C S C S C S C S CSCSCSC S CSC S C S C S C S C S C S C S C S C S C S C SS (E) SP1-1 1/4W SP1-2 1/4W SP1-3 1/4W SP1-4 1/4W SP1-5 1/4W SP1-6 1/4W SP1-9 1/4W SP1-10 1/4W SP1-11 1/4W SP1-12 1/4W SP1-13 1/4W SP1-14 1/4W SP1-17 1/4WSP1-18 1/4W SP1-20 1/4WSP1-21 1/4W SP1-22 1/4W SP1-23 1/4W SP1-24 1/4WSP1-25 1/4W SP1-27 1/4WSP1-28 1/4W SP1-8 1/2W L1-2 15cd SP1-7 1/2W L1-1 15cd SP1-19 1/2W L1-5 15cd SP1-26 1/2W L1-6 15cd SP1-15 1/2W L1-3 15cd SP1-16 1/2W L1-4 30cd SP1-29 1/2W L1-7 15cd S,L S,L 1 SS S,L S,L SP2-15 1/4W SP2-1 1/4W SP2-2 1/4W SP2-6 1/4W SP2-7 1/4W SP2-8 1/4W SP2-10 1/4W SP2-11 1/4W SP2-12 1/4W SP2-13 1/4W SP2-14 1/4W SP2-3 1/2W L2-1 15cd SP2-4 1/4W L2-2 15cd SP2-5 1/2W L2-3 75cd SP2-9 1/2W L2-4 15cd EXISTING DEVICE(E) 1 SS SS C SP1-30 1/4W L1-8 15cd LEVEL 2 LEVEL 1 *HATCH DENOTES AREA OUT OF SCOPE SCOPE OF WORK SCOPE OF WORKLEVEL 1 LEVEL 2 FACU LOCATION