Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 22-00213
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
Pg 1 Free text Larry Beesley : Building Open 1 SD CO
Pg 1 Free text Larry Beesley : Building Open 1 SD
Pg 1 Free text Larry Beesley : Building Open 1 SMOKE DETECTOR REQUIRED
Pg 1 Free text Larry Beesley : Building Open 1 The floor will also need insulation between the joist to try to
get and R 30 in the floor.
Pg 1 Free text Larry Beesley : Building Open 1 Any of the foundation that is above the floor must be
insulated also.
Pg 1 Rectangle Larry Beesley : Building Open 1
Pg 1 Free text Larry Beesley : Building Open 1 Fan
Pg 1 Line Larry Beesley : Building Open 1
Pg 1 Stamp Larry Beesley : Building Open 1 Prescriptive Insulation
Pg 1 Stamp Larry Beesley : Building Open 1 Approved - Building Inspector
Pg 1 Free text Larry Beesley : Building Open 1 What type of heat will be installed for use until the furnace is
installed?
Single Family - Remodel
Approval of plans does not constitute approval of variance from code
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
Pg 1 Rectangle Larry Beesley : Building Open 1
Pg 1 Free text Alex Owens : Electrical Open 1 All electrical work to be installed in accordance with the 2017
NEC (each bedroom circuit including smoke detectors needs to
have AFCI protection at the panel, receptacles in bedroom and
living room need installed on every 2 feet of open wall space,
within 6 feet of a doorway and a maximum 12 feet apart.
Ensure bathroom receptacle is within 3 feet of washbasin, is
GFCI protected, and is on a separate 20 amp circuit).
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
SD CO
SD
SMOKE DETECTOR REQUIRED
All electrical work to be installed in accordance
with the 2017 NEC (each bedroom circuit
including smoke detectors needs to have AFCI
protection at the panel, receptacles in bedroom
and living room need installed on every 2 feet of
open wall space, within 6 feet of a doorway and
a maximum 12 feet apart. Ensure bathroom
receptacle is within 3 feet of washbasin, is GFCI
protected, and is on a separate 20 amp circuit).
The floor will also need
insulation between the joist to try
to get and R 30 in the floor.
Any of the foundation that is
above the floor must be
insulated also.
Fan
What type of heat will be
installed for use until the
furnace is installed?