HomeMy WebLinkAboutAPPROVED PLANS - 22-00063 - 744 Hillside Dr - New SFRAuthor Name Author Email Author Phone No.: Larry Beesley Larry.Beesley@rexburg.org 208-372-2176 Kyle Baldwin Kyle.Baldwin@rexburg.org 208-372-2164 Description : 744 Hillside Dr - New SFR Address : Record Type : New Single Family Residence Document Filename : Hegsted Stamped Structural 12-21-21.pdf Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Approved # 22-00063 Page Reference Annotation Type Author : Department Status Page Review Comments Applicant Response Comments T1 Stamp Larry Beesley : Building Open 1 Approved - Building Inspector A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 New Single Family Residence As this house is nearing completion there can not be any personal item stored or placed in the house. All final inspections must be completed and a Certificate of Occupancy be issued before the home can be occupied. Approval of plans does not constitute approval of variance from code Page Reference Annotation Type Author : Department Status Page Review Comments Applicant Response Comments A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Ellipse Larry Beesley : Building Open 4 A1 Free text Larry Beesley : Building Open 4 SD A1 Free text Larry Beesley : Building Open 4 SD CO A1 Free text Larry Beesley : Building Open 4 SD A1 Free text Larry Beesley : Building Open 4 SD A1 Free text Larry Beesley : Building Open 4 SD A1 Stamp Larry Beesley : Building Open 4 Approved - Building Inspector A2 Stamp Larry Beesley : Building Open 5 Prescriptive Insulation A2 Stamp Larry Beesley : Building Open 5 Approved - Building Inspector A3 Free text Larry Beesley : Building Open 6 SD A3 Free text Larry Beesley : Building Open 6 SD CO A3 Free text Larry Beesley : Building Open 6 SD A3 Free text Larry Beesley : Building Open 6 Attic Access 22"x30" minimum access where attic clear height exceeds 30" (R807) A3 Stamp Larry Beesley : Building Open 6 Approved - Building Inspector A4 Stamp Larry Beesley : Building Open 7 Approved - Building Inspector A5 Free text Larry Beesley : Building Open 8 Minimum Frost Depth Ground Surface to Bottom of Footing 36" A5 Free text Larry Beesley : Building Open 8 Street Number Displayed on House A5 Free text Larry Beesley : Building Open 8 Ground Surface to Slope away from Foundation a minimum of 6" within first 10 ft. A5 Stamp Larry Beesley : Building Open 8 Approved - Building Inspector A6 Stamp Larry Beesley : Building Open 9 Approved - Building Inspector A7 Stamp Larry Beesley : Building Open 10 Approved - Building Inspector A8 Stamp Larry Beesley : Building Open 11 Prescriptive Insulation A8 Stamp Larry Beesley : Building Open 11 Approved - Building Inspector A9 Stamp Larry Beesley : Building Open 12 Prescriptive Insulation Approval of plans does not constitute approval of variance from code Page Reference Annotation Type Author : Department Status Page Review Comments Applicant Response Comments A9 Stamp Larry Beesley : Building Open 12 Approved - Building Inspector A10 Free text Larry Beesley : Building Open 13 CM A10 Stamp Larry Beesley : Building Open 13 Approved - Building Inspector A11 Line Larry Beesley : Building Open 14 A11 Free text Larry Beesley : Building Open 14 3' from end of fan blades A11 Free text Larry Beesley : Building Open 14 Fan A11 Free text Larry Beesley : Building Open 14 3' A11 Stamp Larry Beesley : Building Open 14 Approved - Building Inspector A12 Stamp Larry Beesley : Building Open 15 Approved - Building Inspector ST1 Stamp Larry Beesley : Building Open 16 Approved - Building Inspector ST2 Stamp Larry Beesley : Building Open 17 Approved - Building Inspector ST3 Stamp Larry Beesley : Building Open 18 Approved - Building Inspector ST4 Rectangle Larry Beesley : Building Open 19 ST4 Stamp Larry Beesley : Building Open 19 Approved - Building Inspector S1 Callout Kyle Baldwin : P&Z Open 2 Please show sidewalk location and street name. S1 Stamp Kyle Baldwin : P&Z Open 2 Corrections Required Approval of plans does not constitute approval of variance from code Powered by TCPDF (www.tcpdf.org) 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O T1 TI T L E S H E E T 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O S1 SI T E P L A N , N O T E S & D W G . S C H E D U L E LOT 4A Please show sidewalk location and street name. 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O S2 SW P P P L A N LOT 4A 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O 12/21/2021 SD SD CO SD SD SD 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O A2 CO N S T R U C T I O N N O T E S A N D D E T A I L S 2018 IRC 12/21/2021 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O A3 CO N S T R U C T I O N N O T E S A N D D E T A I L S ° 12/21/2021 SD CO Attic Access 22"x30" minimum access where attic clear height exceeds 30" (R807) SD SD 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O UP P E R F L O O R P L A N A4 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O A5 EX T E R I O R E L E V A T I O N S 5 1 1 1 1 2 33 3 3 4 5 6 7 8 88 9 10 10 11 11 12 12 12 12 13 14 14 ELEVATION NOTES 1 2 4 3 5 6 7 8 9 11 10 12 13 14 Minimum Frost Depth Ground Surface to Bottom of Footing 36" Street Number Displayed on House Ground Surface to Slope away from Foundation a minimum of 6" within first 10 ft. 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O A6 FR A M I N G P L A N S , T R U S S E S & B M . S C H E D . ELEVATION NOTES 1 2 4 3 5 6 7 8 9 11 10 12 13 14 1 1 3 3 4 4 5 5 6 6 7 7 8 88 9 9 11 11 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O A7 FR A M I N G S E C T I O N S 12/21/2021 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O A8 FR A M I N G S E C T I O N S 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O A9 FR A M I N G S E C T I O N S 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O A10 EL E C T R I C A L , M E C H . , A N D P L U M B I N G P L A N CM 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O A11 EL E C T R I C A L , M E C H . , A N D P L U M B I N G P L A N 3' from end of fan blades 3' Fan 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O A12 EL E C T R I C A L , M E C H . , A N D P L U M B I N G P L A N 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O 12/21/2021 15 SD1 ∅ ≤ > 12" 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O 12/21/2021 ≤ ∅ Ø Ø Ø 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O 12/21/2021 ∅ ∅ ∅ ∅ ∅ ∅ ∅ 1 SD2 2 SD2 4 SD2 ∅ ∅ ∅ ∅ ≤ GENERAL STRUCTURAL NOTES 1.CONTRACTOR (INCLUDING SUB-CONTRACTORS) SHALL FOLLOW ALL REQUIREMENTS STATED IN THESE DOCUMENTS AND ALL APPLICABLE BUILDING CODES AND STANDARDS AND SHALL BE QUALIFIED TO PERFORM AND EXPERIENCED IN PERFORMING THE WORK REQUIRED FOR THE PROJECT. 2.CONTRACTOR SHALL FOLLOW ALL REQUIREMENTS STATED IN ALL OTHER DOCUMENTS APPLICABLE TO THE PROJECT. IF ANY DISCREPANCIES OCCUR BETWEEN THE STRUCTURAL DOCUMENTS AND OTHER PROJECT DOCUMENTS, NOTIFY YORK ENGINEERING OF THE DISCREPANCY PRIOR TO CONSTRUCTION. 3.CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, ELEVATIONS, ETC., PRIOR TO CONSTRUCTION. 4.THE CONTRACTOR SHALL BE RESPONSIBLE FOR MEANS AND METHODS OF CONSTRUCTION AND SHALL PROVIDE SHORING AND BRACING AS REQUIRED TO PROVIDE STRUCTURAL STABILITY AT ALL TIMES DURING CONSTRUCTION. 5.IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ADEQUATE CORROSION PROTECTION OF ALL STRUCTURAL ELEMENTS. 6.ALL MATERIALS/PRODUCTS SHALL BE INSTALLED PER THE MANUFACTURER'S REQUIREMENTS. 7.SPECIFIC NOTES AND DETAILS SHALL GOVERN OVER TYPICAL NOTES AND DETAILS. 8.TYPICAL NOTES AND DETAILS APPLY WHERE SPECIFIC NOTES AND DETAILS ARE NOT INDICATED. 9.MATERIALS SHALL BE PLACED ON THE STRUCTURE SUCH THAT THE DESIGN LOADS STATED IN THE DESIGN CRITERIA TABLE ARE NOT EXCEEDED AND THE LOAD BEARING CAPACITY OF TEMPORARY SHORING AND BRACING IS NOT EXCEEDED. 10.EACH PIECE OF STRUCTURAL LUMBER (AND SHEATHING) SHALL BE MARKED BY A COMPETENT AND RELIABLE ORGANIZATION WHOSE REGULAR BUSINESS IS TO ESTABLISH LUMBER GRADES. THE ORGANIZATION, GRADING AND GRADE MARKINGS SHALL BE SUBJECT TO APPROVAL BY THE ENGINEER. 11.THE SIZING AND SURFACING OF ALL LUMBER SHALL BE MILL SIZED AND SURFACED ON ALL 4 SIDES U.N.O., SEE PLAN. ALL LUMBER SHALL BE FREE OF HEART CENTER. SPLICES SHALL NOT BE PERMITTED EXCEPT WHERE NOTED OR APPROVED BY THE ENGINEER. 12.ALL FRAMING HARDWARE SHALL BE SIMPSON STRONG-TIE OR APPROVED EQUAL U.N.O. AND SHALL BE INSTALLED PER THE MANUFACTURER'S REQUIREMENTS. USE THE MAXIMUM NUMBER AND SIZE OF FASTENERS SPECIFIED BY THE MANUFACTURER U.N.O., SEE PLAN. 13.WHERE A SPECIFIC CONNECTOR TYPE/MODEL IS NOT INDICATED, PROVIDE A CONNECTOR SIZED TO FIT THE MEMBERS BEING CONNECTED. 14.SAWN LUMBER SHALL BE DOUG FIR #2 OR BETTER U.N.O., SEE PLAN. POSTS AND TIMBERS SHALL BE DOUG FIR #1 OR BETTER. 15.INSTALL SOLID FULL HEIGHT BLOCKING BETWEEN TRUSSES/JOISTS AT ALL BEARING POINTS U.N.O, SEE PLAN. 16.WEB FILLERS SHALL BE PROVIDED ON WEBS OF WOOD I-JOISTS PER THE JOIST MANUFACTURER'S REQUIREMENTS AND PER THE HARDWARE MANUFACTURER'S REQUIREMENTS WHERE HARDWARE ATTACHES TO THE I-JOIST. 17.PRE-MANUFACTURED TRUSSES AND JOISTS SHALL BE BRACED PER THE MANUFACTURER'S REQUIREMENTS. MULTI-PLY MEMBERS SHALL BE ATTACHED TOGETHER PER THE MANUFACTURER'S REQUIREMENTS. 18.PRE-MANUFACTURED PRODUCTS SUCH AS WOOD TRUSSES AND I-JOISTS SHALL ONLY BE ALTERED WITH THE APPROVAL OF THE MANUFACTURER AND SHALL BE REPAIRED (WHEN REQUIRED) PER THE MANUFACTURER'S REQUIREMENTS. 19.BOLTS/LAGS AT ALL WOOD TO WOOD, WOOD TO STEEL AND WOOD TO CONCRETE CONNECTIONS SHALL BE A307 U.N.O., SEE PLAN. 20.BOLTS IN WOOD SHALL BE INSTALLED IN HOLES 1/16” IN DIAMETER LARGER THAN THE BOLT DIAMETER AND SHALL HAVE WASHERS BETWEEN HEAD/NUT AND WOOD MEMBER. 21.LAGS SHALL BE INSTALLED IN HOLES PRE-DRILLED AT SAME DIAMETER AS LAG SHAFT FOR UNTHREADED SHAFT PORTION OF HOLE AND 40%-70% OF SHAFT DIAMETER FOR THREADED PORTION. 22.ALL WOOD IN CONTACT WITH MASONRY OR CONCRETE OR EXPOSED TO WEATHER SHALL BE PRESSURE TREATED U.N.O, SEE PLAN. 23.ALL FASTENERS AND CONNECTORS (NAILS, SCREWS, BOLTS, NUTS, WASHERS, ETC.) IN CONTACT WITH PRESERVATIVE TREATED AND FIRE RETARDANT TREATED WOOD SHALL MEET THE REQUIREMENTS OF IBC 2304.10.5. 24.DO NOT COUNTER SINK BOLT/LAG HEADS INTO WOOD MEMBERS UNLESS SPECIFICALLY NOTED ON PLANS OR APPROVED BY THE ENGINEER. 25.ALL NAILING SHALL BE PER IBC TABLE 2304.10.1 U.N.O., SEE PLAN. ATTACH 2X4 STUDS TO WALL TOP AND BOTT. PLATES WITH (2) 16d NAILS, USE (3) 16d NAILS FOR 2X6 STUDS. BUILT-UP 2X POSTS SHALL BE FACE NAILED TOGETHER WITH (2) 16d AT 9” O.C. 26.PROVIDE POSTS TO MATCH WIDTH OF SUPPORTED BEAMS/HEADERS U.N.O., SEE PLAN. CONTINUE POSTS TO FOUNDATION INCLUDING SQUASH BLOCKING IN FLOORS. MATCH SQUASH BLOCKING SIZE TO POST SIZE. 27.WHERE JOISTS/TRUSSES RUN PARALLEL TO INTERIOR BEARING WALLS, ALIGN JOIST/TRUSS UNDER WALL BOTT. PLATE OR PROVIDE FULL HEIGHT BLOCKING AT 16” O.C. IN FLOOR PERPENDICULAR TO WALL AND BLOCKING ALIGNED UNDER WALL. PROVIDE DBL JOIST/TRUSS UNDER DBL SIDED SHEAR WALLS, SEE INTERIOR SHEAR WALL AT WOOD FLOOR DETAIL. 28.WOOD WALLS SHALL BE BALLOON FRAMED FROM FOUNDATION TO ROOF EXCEPT WHERE FLOORS BREAK WALL STUDS PER FLOOR JOIST AT WOOD WALL DETAIL. 29.SHEATHING SHALL BE PROVIDED ON RIM BOARDS AND NAILED PER REQUIREMENTS OF SHEAR WALL ABOVE. 30.EXCEPT WHERE NOTED OTHERWISE, PROVIDE METAL FRAMING CONNECTOR (HANGER, CLIP, CAP, ETC.) AT ALL WOOD TO CONCRETE, WOOD TO STEEL AND WOOD TO WOOD CONNECTIONS. 31.ATTACH BRICK VENEERS TO FRAMING PER IRC R703.8. 32.PROVIDE 6” X 3 1/2” X 5/16” STEEL ANGLE TO SUPPORT BRICK VENEERS. ATTACH ANGLE WITH (2) 7/16” X 4” LAGS AT 16” O.C., USE (1) ½” X 4 ½” TITEN HD BOLT AT 16” O.C. FOR ATTACHMENT TO CONCRETE OR MASONRY. 33.WOOD NAILERS ON STEEL BEAMS SHALL BE 2X WITH ½” DIAM. THREADED STUDS AT 32” O.C. U.N.O, SEE PLAN. NAILERS ON STEEL FRAME BEAMS SHALL BE 3X WITH ¾” DIAM. STUDS AT 24” O.C. U.N.O, SEE PLAN. 34.¼” WEB STIFFENERS SHALL BE PROVIDED EACH SIDE OF STEEL BEAMS AT ALL BEARING POINTS. 35.USE ¾” DIAM. A325 BOLTS AT ALL STEEL TO STEEL CONNECTIONS U.N.O., SEE PLAN. 36.GROUT BELOW STEEL BASE PLATES (IF USED) SHALL BE 5000 PSI NON-SHRINK GROUT. 37.ALL WELDING SHALL BE DONE PER AISC AND AWS SPECIFICATIONS. WELDERS SHALL BE AWS CERTIFIED. 38.WELD MATERIAL SHALL BE 70 KSI MIN. 39.RIM BOARD TO BE 1 1/8" MIN. U.N.O., SEE PLAN. 40.YORK ENGINEERING LIABILITY IS LIMITED TO FIVE TIMES THE FEE COLLECTED FOR SERVICES. THE CONTRACTOR(S) MUST READ, UNDERSTAND AND ACCEPT ALL YORK ENGINEERING DOCUMENTS APPLICABLE TO THIS DESIGN PRIOR TO UTILIZING THE DESIGN. BY USING THIS DESIGN, THE OWNER/CONTRACTOR ACCEPTS THE DESIGN, ASSUMED LOADS AND LIMITS ON LIABILITY STATED. 41.PERIODIC SPECIAL INSPECTIONS REQUIRED ON TRUSS BRACING AT TRUSSES OVER 5'-0" TALL UNLESS WAIVED BY BUILDING OFFICIAL. 42.PRE-FABRICATED TRUSS LAYOUT PLAN AND CALCULATIONS MUST BE PROVIDED TO YORK ENGINEERING FOR REVIEW AND APPROVAL PRIOR TO CONSTRUCTION. ∅ 12 - 1 3 - 2 1 4A 74 4 H I L S I D E D R RE X B U R D I D A H O 12/21/2021