HomeMy WebLinkAboutREVIEW CORRECTIONS - 21-00709 - Clair & Dees Point S Tires - Remodel Permit # 21-00709 Corrections Rest rooms need to be ADA compliant Please refer to sheet 4.1 for standards. Any window within 2’ arc of either side of door needs to be tempered Reference updated sheet A2.2 Signage for doors… All exits and ADA bathroom will be signed. Building a repair garage? (Yes) Comply with section 406.8 Will need a portable fire extinguisher according to section 906. Section 406.8 requires gas detection systems for repair garages that deal with Odorless gas systems. This garage does not work on such systems. 406.8 also requires a sprinkler system according to the requirements of 903.9.1. 903.9.1 requires an automatic sprinkler system if any of the conditions are met. The conditions of the building is: fire area 4,150 Sq ft. The allowable square footage of a repair garage is 5,000 sq ft before a Automatic sprinkler system is required. Fire barrier for the foam insulation See data sheet attached.