HomeMy WebLinkAboutCOMCHECK ELECTRICAL - 23-00172 - Connections TherapyCOMcheck Software Version 4.1.5.3
Interior Lighting Compliance Certificate
Project Title:
2018 IECC
Project Type:New Construction
Construction Site:Owner/Agent:Designer/Contractor:
Project Information
Energy Code:
Credits: 1.0 Required 0.0 Proposed
Additional Efficiency Package(s)
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-Event Center (Convention Center:Audience/Seating Area)2859 0.82 2344
2-Gym (Gymnasium/Fitness Center:Playing Area)3630 0.82 2977
3-Entrance Lobby/ Reception (Common Space Types:Lobby - General)2086 1.00 2086
4-Restrooms (Common Space Types:Restrooms)1416 0.85 1204
5-Storage (Common Space Types:Storage >=50 - <=1000 sq.ft.)1758 0.46 809
6-Hallways (Common Space Types:Corridor/Transition <8 ft wide)3317 0.66 2189
7-Offices/Treatment Rooms (Common Space Types:Office - Enclosed)8310 0.93 7728
8-Lounge & Breakrooms (Common Space Types:Lounge/Breakroom)2388 0.62 1481
9-Food Prep/Kitchen (Common Space Types:Food Preparation)1231 1.06 1305
10-Contruction/Craft Zones (Common Space Types:Classroom/Lecture/Training)1217 0.96 1168
11-3rd Floor Elevator Lobby (Common Space Types:Lobby For Elevator)125 0.68 85
23376Total Allowed Watts =
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
1-Event Center (Convention Center:Audience/Seating Area)
F6: F6: Decorative Pendant: LED Other Fixture Unit 40W:1 42 40 1680
2-Gym (Gymnasium/Fitness Center:Playing Area)
F3: F3: High Bay: LED Other Fixture Unit 125W:1 20 109 2180
F2: F2: Linear Up/Down: LED Other Fixture Unit 36W:1 16 33 525
F4: F4: Downlights: LED Other Fixture Unit 25W:1 14 21 294
3-Entrance Lobby/ Reception (Common Space Types:Lobby - General)
F4: F4: Downlights: LED Other Fixture Unit 25W:1 24 21 504
F6: F6: Decorative Pendant: LED Other Fixture Unit 40W:1 30 40 1200
F10: F10: Wallwash Downlight: LED Other Fixture Unit 25W:1 1 21 21
F8: F8: Decorative Pendant: LED Other Fixture Unit 25W:1 11 24 264
F12: F12: Decorative Pendant: LED Other Fixture Unit 25W:1 2 21 42
F1: F1: Lay In Volumetric: LED Other Fixture Unit 46W:1 6 41 244
Project Title:
Data filename:Z:\Projects\J22\J22253.00\Electrical\Calculations\J23012.00 - COMcheck.cck
03/14/23Report date:
81 ofPage
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
4-Restrooms (Common Space Types:Restrooms)
F4: F4: Downlights: LED Other Fixture Unit 25W:1 49 21 1029
F9: F9: Strip Light: LED Other Fixture Unit 36W:1 18 29 522
5-Storage (Common Space Types:Storage >=50 - <=1000 sq.ft.)
F2: F2: Linear Up/Down: LED Other Fixture Unit 36W:1 2 33 66
F1: F1: Lay In Volumetric: LED Other Fixture Unit 46W:1 25 41 1015
6-Hallways (Common Space Types:Corridor/Transition <8 ft wide)
F2: F2: Linear Up/Down: LED Other Fixture Unit 36W:1 88 33 2886
F1: F1: Lay In Volumetric: LED Other Fixture Unit 46W:1 7 41 284
F4: F4: Downlights: LED Other Fixture Unit 25W:1 2 21 42
F10: F10: Wallwash Downlight: LED Other Fixture Unit 25W:1 1 21 21
7-Offices/Treatment Rooms (Common Space Types:Office - Enclosed)
F1: F1: Lay In Volumetric: LED Other Fixture Unit 46W:1 94 41 3816
F2: F2: Linear Up/Down: LED Other Fixture Unit 36W:1 21 33 689
8-Lounge & Breakrooms (Common Space Types:Lounge/Breakroom)
F6: F6: Decorative Pendant: LED Other Fixture Unit 40W:1 21 40 840
F4: F4: Downlights: LED Other Fixture Unit 25W:1 2 21 42
F10: F10: Wallwash Downlight: LED Other Fixture Unit 25W:1 1 21 21
F2: F2: Linear Up/Down: LED Other Fixture Unit 36W:1 29 33 951
F18: F18: Cylinder Pendant: LED Other Fixture Unit 25W:1 18 25 450
9-Food Prep/Kitchen (Common Space Types:Food Preparation)
F2: F2: Linear Up/Down: LED Other Fixture Unit 36W:1 17 33 558
F1: F1: Lay In Volumetric: LED Other Fixture Unit 46W:1 4 41 162
F4: F4: Downlights: LED Other Fixture Unit 25W:1 1 21 21
10-Contruction/Craft Zones (Common Space Types:Classroom/Lecture/Training)
F2: F2: Linear Up/Down: LED Other Fixture Unit 36W:1 34 33 1115
11-3rd Floor Elevator Lobby (Common Space Types:Lobby For Elevator)
F2: F2: Linear Up/Down: LED Other Fixture Unit 36W:1 8 33 262
21746Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.3 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting PASSES: Design 7% better than code
Project Title:
Data filename:Z:\Projects\J22\J22253.00\Electrical\Calculations\J23012.00 - COMcheck.cck
03/14/23Report date:
82 ofPage
COMcheck Software Version 4.1.5.3
Exterior Lighting Compliance Certificate
Project Title:
2018 IECC
Project Type:New Construction
Construction Site:Owner/Agent:Designer/Contractor:
Project Information
Energy Code:
2 (Neighborhood business district (LZ2))Exterior Lighting Zone
Allowed Exterior Lighting Power
A
Area/Surface Category
B
Quantity
C
Allowed
Watts / Unit
D
Tradable
Wattage
E
Allowed Watts
(B X C)
Parking Lot (Parking area)35921 ft2 0.04 Yes 1437
Exterior of Building Area (Illuminated area of facade wall or surface)11850 ft2 0.07 No 889
Entrances (Pedestrian and vehicular entrances and exits)39 ft of door 14 Yes 546
Total Tradable Watts (a) =
Total Allowed Watts =
Total Allowed Supplemental Watts (b) =
2061
2950
400
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 400 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Parking Lot ( Parking area 35921 ft2): Tradable Wattage
LED 1: SF1: Parking Lot: LED Roadway-Parking Unit 67W:1 5 59 295
Exterior of Building Area ( Illuminated area of facade wall or surface 11850 ft2): Non-tradable Wattage
F15: F15: Wall Sconce: LED Other Fixture Unit 25W:1 30 25 750
F16: F16: Wall Pack: LED Other Fixture Unit 25W:1 6 21 126
Entrances ( Pedestrian and vehicular entrances and exits 39 ft of door width): Tradable Wattage
F4: F4: Downlights: LED Other Fixture Unit 25W:1 6 21 126
F4: F4: Downlights: LED Other Fixture Unit 25W:1 22 21 462
Outdoor Patio ( Plaza area 781 ft2): Tradable Wattage
883Total Tradable Proposed Watts =
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.3 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Exterior Lighting PASSES: Design 64% better than code
Project Title:
Data filename:Z:\Projects\J22\J22253.00\Electrical\Calculations\J23012.00 - COMcheck.cck
03/14/23Report date:
83 ofPage
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.5.3
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2018 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the interior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
C103.2
[PR8]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the exterior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:Z:\Projects\J22\J22253.00\Electrical\Calculations\J23012.00 - COMcheck.cck
03/14/23Report date:
84 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.2.2.
2
[EL22]1
Spaces required to have light-
reduction controls have a manual
control that allows the occupant to
reduce the connected lighting load in
a reasonably uniform illumination
pattern >= 50 percent.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1,
C405.2.1.
1
[EL18]1
Occupancy sensors installed in
classrooms/lecture/training rooms,
conference/meeting/multipurpose
rooms, copy/print rooms,
lounges/breakrooms, enclosed offices,
open plan office areas, restrooms,
storage rooms, locker rooms,
warehouse storage areas, and other
spaces <= 300 sqft that are enclosed
by floor-to-ceiling height partitions.
Reference section language
C405.2.1.2 for control function in
warehouses and section C405.2.1.3
for open plan office spaces.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1.
2
[EL19]1
Occupancy sensors control function in
warehouses: In warehouses, the
lighting in aisleways and open areas is
controlled with occupant sensors that
automatically reduce lighting power
by 50% or more when the areas are
unoccupied. The occupant sensors
control lighting in each aisleway
independently and do not control
lighting beyond the aisleway being
controlled by the sensor.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1.
3
[EL20]1
Occupant sensor control function in
open plan office areas: Occupant
sensor controls in open office spaces
>= 300 sq.ft. have controls 1)
configured so that general lighting can
be controlled separately in control
zones with floor areas <= 600 sq.ft.
within the space, 2) automatically turn
off general lighting in all control zones
within 20 minutes after all occupants
have left the space, 3) are configured
so that general lighting power in each
control zone is reduced by >= 80% of
the full zone general lighting power
within 20 minutes of all occupants
leaving that control zone, and 4) are
configured such that any daylight
responsive control will activate space
general lighting or control zone
general lighting only when occupancy
for the same area is detected.
Complies
Does Not
Not Observable
Not Applicable
C405.2.2,
C405.2.2.
1,
C405.2.2.
2
[EL21]2
Each area not served by occupancy
sensors (per C405.2.1) have time-
switch controls and functions detailed
in sections C405.2.2.1 and C405.2.2.2.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:Z:\Projects\J22\J22253.00\Electrical\Calculations\J23012.00 - COMcheck.cck
03/14/23Report date:
85 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.2.3,
C405.2.3.
1,
C405.2.3.
2
[EL23]2
Daylight zones provided with
individual controls that control the
lights independent of general area
lighting. See code section C405.2.3
Daylight-responsive controls for
applicable spaces, C405.2.3.1 Daylight
responsive control function and
section C405.2.3.2 Sidelit zone.
Complies
Does Not
Not Observable
Not Applicable
C405.2.4
[EL26]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
C405.2.4
[EL27]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
Complies
Does Not
Not Observable
Not Applicable
C405.2.5
[EL28]null
Automatic lighting controls for exterior
lighting installed. Controls will be
daylight controlled, set based on
business operation time-of-day, or
reduce connected lighting > 30%.
Complies
Does Not
Not Observable
Not Applicable
C405.3
[EL6]1
Exit signs do not exceed 5 watts per
face.
Complies
Does Not
Not Observable
Not Applicable
C405.6
[EL26]2
Low-voltage dry-type distribution
electric transformers meet the
minimum efficiency requirements of
Table C405.6.
Complies
Does Not
Not Observable
Not Applicable
C405.7
[EL27]2
Electric motors meet the minimum
efficiency requirements of Tables
C405.7(1) through C405.7(4).
Efficiency verified through certification
under an approved certification
program or the equipment efficiency
ratings shall be provided by motor
manufacturer (where certification
programs do not exist).
Complies
Does Not
Not Observable
Not Applicable
C405.8.2,
C405.8.2.
1
[EL28]2
Escalators and moving walks comply
with ASME A17.1/CSA B44 and have
automatic controls configured to
reduce speed to the minimum
permitted speed in accordance with
ASME A17.1/CSA B44 or applicable
local code when not conveying
passengers.
Complies
Does Not
Not Observable
Not Applicable
C405.9
[EL29]2
Total voltage drop across the
combination of feeders and branch
circuits <= 5%.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:Z:\Projects\J22\J22253.00\Electrical\Calculations\J23012.00 - COMcheck.cck
03/14/23Report date:
86 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C303.3,
C408.2.5.
2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
C405.4.1
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
C405.5.1
[FI19]1
Exterior lighting power is consistent
with what is shown on the approved
lighting plans, demonstrating
proposed watts are less than or equal
to allowed watts.
Complies
Does Not
Not Observable
Not Applicable
See the Exterior Lighting fixture schedule for values.
C408.1.1
[FI57]1
Building operations and maintenance
documents will be provided to the
owner. Documents will cover
manufacturers' information,
specifications, programming
procedures and means of illustrating
to owner how building, equipment and
systems are intended to be installed,
maintained, and operated.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
1
[FI16]3
Furnished as-built drawings for
electric power systems within 90 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.3
[FI33]1
Lighting systems have been tested to
ensure proper calibration, adjustment,
programming, and operation.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:Z:\Projects\J22\J22253.00\Electrical\Calculations\J23012.00 - COMcheck.cck
03/14/23Report date:
87 ofPage
Project Title:
Data filename:Z:\Projects\J22\J22253.00\Electrical\Calculations\J23012.00 - COMcheck.cck
03/14/23Report date:
88 ofPage