Envelope Compliance Certificate
Project Title:
2018 IECC
Project Type:New Construction
Vertical Glazing / Wall Area:18%
Location:Rexburg, Idaho
Climate Zone:6b
Construction Site:
Lot 13&14 First American Cir.
Rexburg, ID 83440
Owner/Agent:
Michelle Dahlberg
Dahlberg Group, LLC
1460 Elk Creek Dr.
Idaho Falls, ID 83404
208-535-1286
Designer/Contractor:
Troy Anderson
Clarity Design Group
5525 South 900 East
Murray, UT 84117
385-247-8570
Project Information
Energy Code:
Connection Therapy
Credits: 1.0 Required 1.0 Proposed
High Performance SWH, 1.0 credit
Additional Efficiency Package(s)
Building Area Floor Area
1-Office : Nonresidential 31122
Envelope Assemblies
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
Roof: Insulation Entirely Above Deck, [Bldg. Use 1 - Office]14452 ---36.0 0.027 0.032
Floor: Slab-On-Grade:Unheated, Vertical 2 ft., [Bldg. Use 1 - Office] (c)547 ---12.0 0.532 0.540
NORTH
North-12" Masonry: Concrete Block:12", Partially Grouted, Cells Empty,
Light Density, Furring: None, [Bldg. Use 1 - Office]
57 ---0.0 0.380 0.080
Window: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
4 ------0.290 0.360
Door: Glass (> 50% glazing):Metal Frame, Entrance Door, Perf. Specs.:
Product ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
9 ------0.290 0.770
North-8" Masonry- Metal siding CI: Concrete Block:8", Partially Grouted,
Cells Empty, Light Density, Furring: None, [Bldg. Use 1 - Office]
822 ---6.0 0.115 0.080
Window: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
165 ------0.290 0.360
Door: Glass (> 50% glazing):Metal Frame, Entrance Door, Perf. Specs.:
Product ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
17 ------0.290 0.770
North-8" Masonry-EIFS-Furring: Concrete Block:8", Partially Grouted,
Cells Empty, Light Density, Furring: Metal, [Bldg. Use 1 - Office]
517 13.0 5.0 0.077 0.080
Door: Insulated Metal, Swinging, [Bldg. Use 1 - Office]26 ------0.600 0.370
North-Wood: Wood-Framed, 16" o.c., [Bldg. Use 1 - Office]741 19.0 0.0 0.067 0.051
Window: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
109 ------0.290 0.360
North-12" Masonry- Furring: Concrete Block:12", Partially Grouted,
Cells Empty, Light Density, Furring: Metal, [Bldg. Use 1 - Office]
57 13.0 0.0 0.120 0.080
Project Title:
Data filename:
Connection Therapy
C:\Users\asoes\Clarity Design Group\Clarity Design Group - Documents\01 - Current Project
Files\Connections\Rexburg\Documentation\COMCheck\Rexburg.cck
04/12/23Report date:
121 ofPage
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
North-Wood-EIFS: Wood-Framed, 16" o.c., [Bldg. Use 1 - Office]3717 19.0 5.0 0.048 0.051
Window: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
654 ------0.290 0.360
Window: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID na, SHGC 0.38, PF 1.00, [Bldg. Use 1 - Office] (b)
63 ------0.290 0.360
Door: Glass (> 50% glazing):Metal Frame, Entrance Door, Perf. Specs.:
Product ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
48 ------0.290 0.770
Door: Insulated Metal, Swinging, [Bldg. Use 1 - Office]24 ------0.600 0.370
EAST
East-8" Masonry-GYM: Concrete Block:8", Partially Grouted, Cells
Empty, Light Density, Furring: Metal, [Bldg. Use 1 - Office]
641 19.0 0.0 0.115 0.080
East-8" Masonry-EIFS-Furring: Concrete Block:8", Partially Grouted,
Cells Empty, Light Density, Furring: Metal, [Bldg. Use 1 - Office]
1269 13.0 5.0 0.077 0.080
Window: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
27 ------0.290 0.360
Sliding Glass Wall: Glass (> 50% glazing):Metal Frame, Non-Entrance
Door, Perf. Specs.: Product ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
89 ------0.290 0.430
Door: Insulated Metal, Swinging, [Bldg. Use 1 - Office]19 ------0.600 0.370
East-8" Masonry-Furring: Concrete Block:8", Partially Grouted, Cells
Empty, Light Density, Furring: Metal, [Bldg. Use 1 - Office]
50 13.0 0.0 0.126 0.080
East-12" Masonry- Furring: Concrete Block:12", Partially Grouted, Cells
Empty, Light Density, Furring: Metal, [Bldg. Use 1 - Office]
165 13.0 0.0 0.120 0.080
Door: Insulated Metal, Swinging, [Bldg. Use 1 - Office]11 ------0.600 0.370
Sliding Glass Wall: Glass (> 50% glazing):Metal Frame, Non-Entrance
Door, Perf. Specs.: Product ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
37 ------0.290 0.430
East-Wood-EIFS: Wood-Framed, 16" o.c., [Bldg. Use 1 - Office]1103 19.0 5.0 0.048 0.051
Window no overhange: Metal Frame with Thermal Break:Fixed, Perf.
Specs.: Product ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
133 ------0.290 0.360
Window Entrance: Metal Frame with Thermal Break:Fixed, Perf.
Specs.: Product ID na, SHGC 0.38, PF 1.00, [Bldg. Use 1 - Office] (b)
80 ------0.290 0.360
Window overhange: Metal Frame with Thermal Break:Fixed, Perf.
Specs.: Product ID na, SHGC 0.38, PF 0.44, [Bldg. Use 1 - Office] (b)
133 ------0.290 0.360
Door Entrance: Glass (> 50% glazing):Metal Frame, Entrance Door,
Perf. Specs.: Product ID na, SHGC 0.38, PF 1.00, [Bldg. Use 1 -
Office] (b)
48 ------0.290 0.770
East-Wood: Wood-Framed, 16" o.c., [Bldg. Use 1 - Office]1132 19.0 0.0 0.067 0.051
Window no overhange: Metal Frame with Thermal Break:Fixed, Perf.
Specs.: Product ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
274 ------0.290 0.360
SOUTH
South-8" Masonry-GYM: Concrete Block:8", Partially Grouted, Cells
Empty, Light Density, Furring: Metal, [Bldg. Use 1 - Office]
1969 19.0 0.0 0.115 0.080
Window: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
179 ------0.290 0.360
Door: Insulated Metal, Swinging, [Bldg. Use 1 - Office]30 ------0.600 0.370
South-8" Masonry-EIFS-Furring: Concrete Block:8", Partially Grouted,
Cells Empty, Light Density, Furring: Metal, [Bldg. Use 1 - Office]
2538 13.0 5.0 0.077 0.080
Window: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
285 ------0.290 0.360
Door: Glass (> 50% glazing):Metal Frame, Entrance Door, Perf. Specs.:
Product ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
64 ------0.290 0.770
Door OHD Countertop: Insulated Metal, Non-Swinging, [Bldg. Use 1 -
Office]
26 ------0.600 0.179
South-12" Masonry- Furring: Concrete Block:12", Partially Grouted,
Cells Empty, Light Density, Furring: Metal, [Bldg. Use 1 - Office]
131 13.0 0.0 0.120 0.080
Window: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
21 ------0.290 0.360
Door: Glass (> 50% glazing):Metal Frame, Entrance Door, Perf. Specs.:32 ------0.290 0.770
Project Title:
Data filename:
Connection Therapy
C:\Users\asoes\Clarity Design Group\Clarity Design Group - Documents\01 - Current Project
Files\Connections\Rexburg\Documentation\COMCheck\Rexburg.cck
04/12/23Report date:
122 ofPage
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
Product ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
South-Wood-EIFS: Wood-Framed, 16" o.c., [Bldg. Use 1 - Office]1197 19.0 5.0 0.048 0.051
Window: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
258 ------0.290 0.360
South-Wood: Wood-Framed, 16" o.c., [Bldg. Use 1 - Office]107 19.0 0.0 0.067 0.051
WEST
West-8" Masonry-GYM: Concrete Block:8", Partially Grouted, Cells
Empty, Light Density, Furring: Metal, [Bldg. Use 1 - Office]
1506 19.0 0.0 0.115 0.080
Window: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
214 ------0.290 0.360
Door: Glass (> 50% glazing):Metal Frame, Entrance Door, Perf. Specs.:
Product ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
24 ------0.290 0.770
Door OHD: Glass (> 50% glazing):Metal Frame, Non-Entrance Door,
Perf. Specs.: Product ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
120 ------0.290 0.430
West-12" Masonry: Concrete Block:12", Partially Grouted, Cells Empty,
Light Density, Furring: None, [Bldg. Use 1 - Office]
28 ---0.0 0.380 0.080
West-12" Masonry- Furring: Concrete Block:12", Partially Grouted, Cells
Empty, Light Density, Furring: Metal, [Bldg. Use 1 - Office]
22 13.0 0.0 0.120 0.080
Window: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
12 ------0.290 0.360
West-8" Masonry- Metal siding CI: Concrete Block:8", Partially Grouted,
Cells Empty, Light Density, Furring: None, [Bldg. Use 1 - Office]
710 ---6.0 0.115 0.080
Window no overhange: Metal Frame with Thermal Break:Fixed, Perf.
Specs.: Product ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
120 ------0.290 0.360
West-Wood-EIFS: Wood-Framed, 16" o.c., [Bldg. Use 1 - Office]1298 19.0 5.0 0.048 0.051
Window: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
260 ------0.290 0.360
Door: Glass (> 50% glazing):Metal Frame, Entrance Door, Perf. Specs.:
Product ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
76 ------0.290 0.770
West-Wood: Wood-Framed, 16" o.c., [Bldg. Use 1 - Office]479 19.0 0.0 0.067 0.051
Window: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
84 ------0.290 0.360
Door: Glass (> 50% glazing):Metal Frame, Entrance Door, Perf. Specs.:
Product ID na, SHGC 0.38, [Bldg. Use 1 - Office] (b)
25 ------0.290 0.770
(a)Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
(b)Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
(c)Slab-On-Grade proposed and budget U-factors shown in table are F-factors.
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed envelope systems have been
designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.5 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Envelope PASSES: Design 7% better than code
Project Title:
Data filename:
Connection Therapy
C:\Users\asoes\Clarity Design Group\Clarity Design Group - Documents\01 - Current Project
Files\Connections\Rexburg\Documentation\COMCheck\Rexburg.cck
04/12/23Report date:
123 ofPage
Aaron Oesterle 04/12/2023
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.5.5
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2018 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR1]1
Plans and/or specifications provide all
information with which compliance
can be determined for the building
envelope and document where
exceptions to the standard are
claimed.
Complies
Does Not
Not Observable
Not Applicable
C402.4.1
[PR10]1
The vertical fenestration area <= 30
percent of the gross above-grade wall
area.
Complies
Does Not
Not Observable
Not Applicable
C402.4.1
[PR11]1
The skylight area <= 3 percent of the
gross roof area.
Complies
Does Not
Not Observable
Not Applicable
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Connection Therapy
C:\Users\asoes\Clarity Design Group\Clarity Design Group - Documents\01 - Current Project
Files\Connections\Rexburg\Documentation\COMCheck\Rexburg.cck
04/12/23Report date:
124 ofPage
Section
#
& Req.ID
Footing / Foundation Inspection Complies?Comments/Assumptions
C303.2
[FO4]2
Slab edge insulation installed per
manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
C303.2.1
[FO6]1
Exterior insulation protected against
damage, sunlight, moisture, wind,
landscaping and equipment
maintenance activities.
Complies
Does Not
Not Observable
Not Applicable
C105
[FO3]2
Installed slab-on-grade insulation type
and R-value consistent with insulation
specifications reported in plans and
COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.4
[FO7]2
Slab edge insulation depth/length.
Slab insulation extending away from
building is covered by pavement or
>= 10 inches of soil.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Connection Therapy
C:\Users\asoes\Clarity Design Group\Clarity Design Group - Documents\01 - Current Project
Files\Connections\Rexburg\Documentation\COMCheck\Rexburg.cck
04/12/23Report date:
125 ofPage
Section
#
& Req.ID
Framing / Rough-In Inspection Complies?Comments/Assumptions
C303.1.3
[FR12]2
Fenestration products rated in
accordance with NFRC.
Complies
Does Not
Not Observable
Not Applicable
C303.1.3
[FR13]1
Fenestration products are certified as
to performance labels or certificates
provided.
Complies
Does Not
Not Observable
Not Applicable
C402.4.3
[FR10]1
Vertical fenestration SHGC value.Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.4.3,
C402.4.3.
4
[FR8]1
Installed vertical fenestration U-factor
and SHGC consistent with label
specifications and as reported in plans
and COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.5.1.
2.1
[FR19]1
The building envelope contains a
continuous air barrier that is sealed in
an approved manner and material
permeability <= 0.004 dfm/ft2. Air
barrier penetrations are sealed in an
approved manner.
Complies
Does Not
Not Observable
Not Applicable
C402.5.2,
C402.5.4
[FR18]3
Factory-built fenestration and doors
are labeled as meeting air leakage
requirements.
Complies
Does Not
Not Observable
Not Applicable
C402.5.7
[FR17]3
Vestibules are installed on all building
entrances. Doors have self-closing
devices.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Connection Therapy
C:\Users\asoes\Clarity Design Group\Clarity Design Group - Documents\01 - Current Project
Files\Connections\Rexburg\Documentation\COMCheck\Rexburg.cck
04/12/23Report date:
126 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C402.5.5,
C403.2.4.
3
[ME3]3
Stair and elevator shaft vents have
motorized dampers that automatically
close. Refernece section C403.7.7 for
operational details.
Complies
Does Not
Not Observable
Not Applicable
C403.7.7
[ME58]3
Outdoor air and exhaust systems have
motorized dampers that automatically
shut when not in use and meet
maximum leakage rates. Check
gravity dampers where allowed.
Reference section language for
operational details.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Connection Therapy
C:\Users\asoes\Clarity Design Group\Clarity Design Group - Documents\01 - Current Project
Files\Connections\Rexburg\Documentation\COMCheck\Rexburg.cck
04/12/23Report date:
127 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.6
[EL26]2
Low-voltage dry-type distribution
electric transformers meet the
minimum efficiency requirements of
Table C405.6.
Complies
Does Not
Not Observable
Not Applicable
C405.7
[EL27]2
Electric motors meet the minimum
efficiency requirements of Tables
C405.7(1) through C405.7(4).
Efficiency verified through certification
under an approved certification
program or the equipment efficiency
ratings shall be provided by motor
manufacturer (where certification
programs do not exist).
Complies
Does Not
Not Observable
Not Applicable
C405.8.2,
C405.8.2.
1
[EL28]2
Escalators and moving walks comply
with ASME A17.1/CSA B44 and have
automatic controls configured to
reduce speed to the minimum
permitted speed in accordance with
ASME A17.1/CSA B44 or applicable
local code when not conveying
passengers.
Complies
Does Not
Not Observable
Not Applicable
C405.9
[EL29]2
Total voltage drop across the
combination of feeders and branch
circuits <= 5%.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Connection Therapy
C:\Users\asoes\Clarity Design Group\Clarity Design Group - Documents\01 - Current Project
Files\Connections\Rexburg\Documentation\COMCheck\Rexburg.cck
04/12/23Report date:
128 ofPage
Section
#
& Req.ID
Insulation Inspection Complies?Comments/Assumptions
C303.1
[IN3]1
Roof insulation installed per
manufacturer’s instructions. Blown or
poured loose-fill insulation is installed
only where the roof slope is <=3 in
12.
Complies
Does Not
Not Observable
Not Applicable
C402.2.1
[IN20]1
Insulation installed on a suspended
ceiling having ceiling tiles is not being
specified for roor/ceiling assemblies.
Continuous insulation board installed
in 2 or more layers with edge joints
offset between layers.
Complies
Does Not
Not Observable
Not Applicable
C303.1
[IN10]2
Building envelope insulation is labeled
with R-value or insulation certificate
providing R-value and other relevant
data.
Complies
Does Not
Not Observable
Not Applicable
C303.2
[IN7]1
Above-grade wall insulation installed
per manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
C303.2.1
[IN14]2
Exterior insulation is protected from
damage with a protective material.
Verification for exposed foundation
insulation may need to occur during
Foundation Inspection.
Complies
Does Not
Not Observable
Not Applicable
C402.1.3
[IN19]3
Non-swinging opaque doors have R-
4.75 insulation.
Complies
Does Not
Not Observable
Not Applicable
C105
[IN6]1
Installed above-grade wall insulation
type and R-value consistent with
insulation specifications reported in
plans and COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.3
[IN8]2
Installed floor insulation type and R-
value consistent with insulation
specifications reported in plans and
COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.6
[IN18]3
Radiant panels and associated
components, designed for heat
transfer from the panel surfaces to the
occupants or indoor space are
insulated with a minimum of R-3.5.
Complies
Does Not
Not Observable
Not Applicable
C105
[IN2]1
Installed roof insulation type and R-
value consistent with insulation
specifications reported in plans and
COMcheck reports. For some ceiling
systems, verification may need to
occur during Framing Inspection.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.5.1.
1
[IN1]1
All sources of air leakage in the
building thermal envelope are sealed,
caulked, gasketed, weather stripped
or wrapped with moisture vapor-
permeable wrapping material to
minimize air leakage.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Connection Therapy
C:\Users\asoes\Clarity Design Group\Clarity Design Group - Documents\01 - Current Project
Files\Connections\Rexburg\Documentation\COMCheck\Rexburg.cck
04/12/23Report date:
129 ofPage
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Connection Therapy
C:\Users\asoes\Clarity Design Group\Clarity Design Group - Documents\01 - Current Project
Files\Connections\Rexburg\Documentation\COMCheck\Rexburg.cck
04/12/23Report date:
1210 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C402.5.6
[FI37]1
Weatherseals installed on all loading
dock cargo door openings and provide
direct contact along the top and sides
of vehicles parked in the doorway.
Complies
Does Not
Not Observable
Not Applicable
C402.5.8
[FI26]3
Recessed luminaires in thermal
envelope to limit infiltration and be IC
rated and labeled. Seal between
interior finish and luminaire housing.
Complies
Does Not
Not Observable
Not Applicable
C406.7,
C406.7.1
[FI53]1
Enhanced Service Water Heat System
efficiency package. One of the
following SWH system enhancements
must satisfy 60 percent of buildings
annual hot water requirements, or 100
percent if the building requirements
otherwise complies with heat recovery
per Section C403.9.5: Waste heat
recovery (from SWH, process
equipment, OR on-site renewable
water-heating.
Complies
Does Not
Not Observable
Not Applicable
C408.1.1
[FI57]1
Building operations and maintenance
documents will be provided to the
owner. Documents will cover
manufacturers' information,
specifications, programming
procedures and means of illustrating
to owner how building, equipment and
systems are intended to be installed,
maintained, and operated.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Connection Therapy
C:\Users\asoes\Clarity Design Group\Clarity Design Group - Documents\01 - Current Project
Files\Connections\Rexburg\Documentation\COMCheck\Rexburg.cck
04/12/23Report date:
1211 ofPage
Project Title:
Data filename:
Connection Therapy
C:\Users\asoes\Clarity Design Group\Clarity Design Group - Documents\01 - Current Project
Files\Connections\Rexburg\Documentation\COMCheck\Rexburg.cck
04/12/23Report date:
1212 ofPage