Loading...
HomeMy WebLinkAboutFS PLAN REVIEW - 22-00007 - 253 W 2nd S - Sundance Bldg CSundance Apartments Building C – Rexburg 1 of 1 STATE FIRE MARSHAL IDAHO DEPARTMENT OF INSURANCE 700 W. State Street, 3rd Floor P.O. Box 83720 Boise, ID 83720-0043 (208) 334-4370 | www.doi.idaho.gov/sfm PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS PLANS RECEIVED: June 10, 2022 APPROVED: July 11, 2022 REVIEWED BY: Joe Schimanski, ISFM Fire Plan Reviewer PROJECT: Sundance Apartments Building C STREET ADDRESS: 266 W. 3rd St. CITY: Rexburg AHJ: Madison Fire Department SPRINKLER CONTRACTOR: 3-D Fire Protection 6312 S. Burgraff Way Idaho Falls, ID 83401 IDAHO LICENSE: FPSC-008 CONTACT NAME: Sean Small sean.small@3dfire.us PHONE NO: (208) 881-5414 SYSTEM DESIGNED BY: Sean Small sean.small@3dfire.us PHONE NO: (208) 881-5414 TYPE OF SYSTEM: NFPA 13R/Wet HEAD COUNT: 520 TOTAL SYSTEMS: 3 OCCUPANCY CLASSIFICATION: Residential CONSTRUCTION TYPE: Wood AREA SQUARE FOOTAGE: 46,720 SCOPE OF WORK: Apartment C wood construction. 520 sprinkler heads for the building. Design is done with four heads flowing using 16x16 max spacing for each remote area. There is no attic protection per NFPA 13R. PLAN REVIEW COMMENTS:Approved Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or Rules, International Fire Code, NFPA Standards or any other applicable criteria. It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s Office and its personnel does not take any responsibility for the back flow device.