HomeMy WebLinkAboutFS PLAN REVIEW - 20-00508 - Sugar Salem Jr High - FA - FS Sugar-Salem Junior High School – Sugar City 1 of 1
STATE FIRE MARSHAL
IDAHO DEPARTMENT OF INSURANCE
700 W. State Street, 3rd Floor
P.O. Box 83720
Boise, ID 83720-0043
(208) 334-4370 | www.doi.idaho.gov/sfm
PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS
PLANS RECEIVED: August 17, 2020 APPROVED: September 9,
2020
REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer
PROJECT: Sugar-Salem Junior High School
STREET ADDRESS: Teton Ave. and E 3rd N CITY: Sugar City
AHJ: Madison Fire Department
SPRINKLER CONTRACTOR: Viking Automatic Sprinkler Company
2022 N. Elder Street
Nampa, ID 83687
IDAHO LICENSE: FPSC-003
CONTACT NAME: Katerina Spencer
katerina.spencer@vikingsprinkler.net
PHONE NO: (208) 888-2762
SYSTEM DESIGNED BY: Katerina Spencer
katerina.spencer@vikingsprinkler.net
PHONE NO: (208) 888-2762
TYPE OF SYSTEM: NFPA 13/Wet/Dry HEAD COUNT: 889
TOTAL SYSTEMS: 3 OCCUPANCY CLASSIFICATION: Light Hazard
CONSTRUCTION TYPE: Mixed AREA SQUARE FOOTAGE: 72,000
SCOPE OF WORK: Install 5' out underground and protect new building.
PLAN REVIEW COMMENTS: Approved with the following comments:
1. Drains shall discharge outside or to a drain connection capable of handling the flow
of the drain. (NFPA 13, 8.16.2.4.4)
2. Provide owner a copy of NFPA 25. (NFPA 13, 25.4(2))
Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or
Rules, International Fire Code, NFPA Standards or any other applicable criteria.
It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s
Office and its personnel does not take any responsibility for the back flow device.