Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
T1.1 Free text Cody Jones : Building Open 1 Ground snow load 50
Roof snow load 35
T1.1 Free text Cody Jones : Building Open 1 If located in flood zone, we will need flood certificate.
T1.1 Free text Cody Jones : Building Open 1 Risk category?
A1.1 Free text Cody Jones : Building Open 2 2% max cross slope.
A1.1 Free text Cody Jones : Building Open 2 As per table 602, Fire resistance rating on exterior walls is 1
hour due to separation distance.
A2.1 Free text Cody Jones : Building Open 3 Penetrations shall comply with IBC Section 714 for rated
assemblies.
A2.1 Comment Cody Jones : Building Open 3 Concealed spaces are fireblocked/draftstopped per Section
718
A2.1 Free text Cody Jones : Building Open 3 Guards to comply with Section 1015.
A2.1 Free text Cody Jones : Building Open 3 Handrails to comply with section 1014.
A2.2 Free text Cody Jones : Building Open 4 Safety glazing required any window within a 2' arch of the
edge of door.
Glass and glazing shall comply with chapter 24.
# 21-00814
Madison County - Commercial
Report Date: 10.20.2021
Approval of plans does not constitute approval of variance from code
Page 1 of 2
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
A2.2 Free text Cody Jones : Building Open 4 Roof and roof fire classification B?
A2.2 Free text Cody Jones : Building Open 4 Where fire wall intersects exterior wall one of the following
conditions in Section 706.5.1 shall apply.
A6.1 Free text Cody Jones : Building Open 6 7" max riser. Stairways to comply with sections 1011 and 1019.
A8.1 Free text Cody Jones : Building Open 7 36"
A8.1 Free text Cody Jones : Building Open 7 Damp proofing/water proofing to comply with section 1805.
E1.1 Free text Cody Jones : Building Open 17 Exit lighting and exit signs shall comply with IBC section 1008
and 1013.
A1.1 Callout Stan Crittenden : Fire Open 2 Is this intended for fire department access to the back of the
property? If so min. width needs to be 20' drivable surface.
Report Date: 10.20.2021
Approval of plans does not constitute approval of variance from code
Page 2 of 2