Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
T1.1 Free text Cody Jones : Building Open 1 Ground snow load 50
Roof snow load 35
T1.1 Free text Cody Jones : Building Open 1 If located in flood zone, we will need flood certificate.
T1.1 Free text Cody Jones : Building Open 1 Risk category?
A1.1 Free text Cody Jones : Building Open 2 2% max cross slope.
A1.1 Free text Cody Jones : Building Open 2 As per table 602, Fire resistance rating on exterior walls is 1
hour due to separation distance.
A2.1 Free text Cody Jones : Building Open 3 Penetrations shall comply with IBC Section 714 for rated
assemblies.
A2.1 Comment Cody Jones : Building Open 3 Concealed spaces are fireblocked/draftstopped per Section
718
A2.1 Free text Cody Jones : Building Open 3 Guards to comply with Section 1015.
A2.1 Free text Cody Jones : Building Open 3 Handrails to comply with section 1014.
A2.2 Free text Cody Jones : Building Open 4 Safety glazing required any window within a 2' arch of the
edge of door.
Glass and glazing shall comply with chapter 24.
# 21-00814
Madison County - Commercial
Report Date: 10.20.2021
Approval of plans does not constitute approval of variance from code
Page 1 of 2
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
A2.2 Free text Cody Jones : Building Open 4 Roof and roof fire classification B?
A2.2 Free text Cody Jones : Building Open 4 Where fire wall intersects exterior wall one of the following
conditions in Section 706.5.1 shall apply.
A6.1 Free text Cody Jones : Building Open 6 7" max riser. Stairways to comply with sections 1011 and 1019.
A8.1 Free text Cody Jones : Building Open 7 36"
A8.1 Free text Cody Jones : Building Open 7 Damp proofing/water proofing to comply with section 1805.
E1.1 Free text Cody Jones : Building Open 17 Exit lighting and exit signs shall comply with IBC section 1008
and 1013.
A1.1 Callout Stan Crittenden : Fire Open 2 Is this intended for fire department access to the back of the
property? If so min. width needs to be 20' drivable surface.
Report Date: 10.20.2021
Approval of plans does not constitute approval of variance from code
Page 2 of 2
Powered by TCPDF (www.tcpdf.org)
Ground snow load 50
Roof snow load 35
If located in flood zone, we will need flood
certificate.
Risk category?
2% max cross slope.
8
.
0
0
f
t
9
.
0
1
f
t
As per table 602, Fire resistance rating on exterior
walls is 1 hour due to separation distance.
Is this intended for fire
department access to the
back of the property? If so
min. width needs to be 20'
drivable surface.
Penetrations shall comply with IBC
Section 714 for rated assemblies.
Guards to comply with Section 1015.
Handrails to comply with section 1014.
1
.
5
8
f
t
Safety glazing required
any window within a 2'
arch of the edge of door.
Glass and glazing shall
comply with chapter 24.
Roof and roof fire classification B?
Where fire wall intersects exterior wall one of the following
conditions in Section 706.5.1 shall apply.
7" max riser. Stairways to comply
with sections 1011 and 1019.
36" Damp proofing/water proofing to
comply with section 1805.
Exit lighting and exit signs shall comply with IBC section 1008
and 1013.