HomeMy WebLinkAboutAPPROVED ELECTRICAL PLAN - 22-00059 - Java EspressAuthor Name Author Email Author Phone No.: Alex Owens Alex.Owens@rexburg.org 208-372-2330 Description : Java Espress Address : 565 N 2nd E Record Type : New Commercial Building Document Filename : 22-02-10_Java Espress-Rexburg_E30 City Comments.pdf Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Approved # 22-00059 Page Reference Annotation Type Author : Department Status Page Review Comments Applicant Response Comments E3.0 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector New Commercial Building Approval of plans does not constitute approval of variance from code Powered by TCPDF (www.tcpdf.org) J J J J J J J M PANEL 'A'METERING EQUIP. PER LOCAL UTILITY CO. 320A, NEMA 3R 240/120V,1P,3W, 22k AIC UNDERGROUND SECONDARY CONDUIT & TRENCHING BY E.C. CONDUCTORS BY UTILITY CO. COORDINATE WITH LOCAL UTILITY CO. GROUND ELECTRODE SYSTEM (A/E3.0) (2) 2"C.,EA. W/3#3/0+1#3G 2 MAIN SERVICE DISC. 400A, NEMA 3R 400A FUSES (2) 2"C.,EA. W/3#3/0 FAULT CURRENT CALULATIONS WERE BASED ON INFINITE BUS, WITH AN ESTIMATED 75KVA TRANSFORMER WITH A 2.0%Z. *18,491A *18,491A *18,491A 1 1 BLDG. STEEL WATER MAIN GROUND BAR AT MAIN TTB GRND RODS STAND-OFF GROUND BAR LOCATED NEXT TO SERVICE EQUIP. GROUND BAR SHALL BE ERICO #B543A010 OR EQUAL. PROVIDE AND INSTALL ALL REQ'D LUGS & TERMINALS. MAIN SERVICE EQUIPMENT G N NEUTRAL TO GND BOND AT THIS POINT ONLY #1/0 Cu #6 C u CONCRETE ENCASED ELECTRODE 3/ 4 " C . , 1 # 6 C u #1 / 0 C u #1 / 0 C u #4 C u 1 ENTRANCE CONDUIT(S) 4" SQUARE BOX RAISED RING TO SUIT WALL RECEPTACLE - 20AMP RATED - SEE SPECIFICATIONS. NORMAL POWER COLOR - (SEE SPEC'S) COVER PLATE - STYLE & COLOR TO BE AS PER SPECIFICATIONS. CIRCUIT NUMBER TO BE WRITTEN ON BACK OF COVER W/FELT-TIP MARKER GREEN INSULATED GROUND CONDUCTOR 3/4" C., 1#6 B.C. GRND. CONNECT TO BLDG. GROUND SYSTEM FINISH FLOOR 2'X4'X3/4" PLYWOOD PRIME & PAINT W/TWO COATS GREY ENAMEL (INSTALL ON WALLS AS INDICATED ON PLANS) ANCHOR SECURELY TO WALL W/ CONST. ADHESIVE. RECEPTACLES PER PLANS PULL CORD INCOMING UTILITY SERVICE CONDUIT(S) WITH INSULATED BUSHING. SEE SITE PLAN FOR SIZE, QUANTITY, ETC. GROUND BAR (SQ. D #PK27GTA) WALL MOUNTED RACK WITH DATA, SOUND, CCTV AND SECURITY EQUIPMENT PER OWNER (TYP) INSTALL INSULATED BUSHING ON ALL CONDUIT ENDS. (TYP) FI E L D V E R I F Y LV CONDUITS/CABLING OUT TO DEVICES WP1 WP A-52,54 1"C.-2#6+1#10G RTU-1 240 V/1P42.3 A (TYP)F7 (TYP)F7 (TYP)F7 (TYP)F7 (TYP)F7 (TYP)F7 3 3 3 A-8 A-10 4 4 E-27b E-27a A-20 A-20 60 A/NEMA 3R 5 A-4 4 5 A-4 4 5 A-4 4 5 A-4 4 13053 ST ATE O F I D A HOSHAWNA.M E A D O R R E G I S TEREDRP O F E S S I O N AL ENGIN E E R Engineering Inc. Consulting Engineers 1823 E. Center Pocatello, Idaho 83201 tel (208) 232-4439 fax (208) 232-1435 www.payneengineeringinc.com 11 1 9 E . S t a t e S t r e e t , S u i t e 1 2 0 - E a g l e I D 8 3 6 1 6 20 8 . 5 1 4 . 2 7 1 3 THIS DRAWING CONTAINS INFORMATION WHICH IS PROPRIETARY PROPERTY OF ALC ARCHITECTURE NO UNAUTHORIZED REUSE OR DUPLICATION OF THESE PLANS OR ANY INFORMATION CONTAINED HEREIN, WITHOUT THE EXPRESS WRITTEN CONSENT OF ALC ARCHITECTURE. THIS DRAWING IS NOT TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT. COPYRIGHT © ALC ARCHITECTURE DRAWN BY : CHECKED BY: DATE : JOB # BRP SAM P.E. JOB #21121 PR O J E C T F O R : RE X B U R G , I D A H O 8 3 4 4 0 NO . RE V I S I O N S DA T E 12/23/21 12/23/2021 18117 ROOF PLAN, RISER, SCH. & DETAILS JA V A E S P R E S S RE X B U R G , I D A H O 56 5 N . 2 N D E E3.0 SCALE: NONE2POWER RISER DIAGRAM SCALE: NONEABLDG GROUNDING ELECTRODE SYSTEM DETAIL SCALE: NONEBRECEPTACLE MOUNTING DETAIL SCALE: NONECTELEPHONE TERMINAL BOARD (TTB) DETAIL SCALE: 1/4" = 1'-0"1 ELECTRICAL ROOF PLAN A. REFER TO SYMBOL SCHEDULES FOR GENERAL NOTES ASSOCIATED WITH THE INSTALLATION OF EACH SYSTEM; LIGHTING, POWER, FIRE ALARM, SPECIAL SYSTEMS, ETC. GENERAL NOTES: KEY NOTES:# 1 RECEPTACLE MOUNTED TO HVAC UNIT, COORDINATE MOUNTING WITH M.C. PRIOR TO ROUGH-IN. 2 ELECT. CONTRACTOR SHALL REQUEST FROM THE LOCAL UTILITY CO. THE MAXIMUM AVAILABLE FAULT-CURRENT AT THE TRANSFORMER. ALL EQUIPMENT DOWN-STREAM FROM THE TRANSFORMER SHALL HAVE AN 'AIC' RATING EXCEEDING THE MAXIMUM AVAILABLE FAULT-CURRENT, FOR ADDITIONAL ASSISTANCE CONTACT ENGINEER. 3 ELECTRICAL CIRCUIT FOR COLOR-CHANGING LED SOFFIT LIGHTING; E.C. SHALL PROVIDE REQUIRED CONNECTIONS TO LOW VOLTAGE POWER SUPPLIES AS REQUIRED. FIELD LOCATE IN ACCESSIBLE SPACE INSIDE BUILDING, MAINTAIN CIRCUIT LENGTHS PER MFG. PROVIDE REQUIRED CONDUCTORS AND CONNECTIONS FROM LIGHTING TO DMX CONTROLLER. LOCATE DMX PER OWNER PRIOR TO INSTALLATION. 4 ROUTE CIRCUIT THROUGH LIGHTING CONTROL PANEL "LCP". PROGRAM ON/OFF TIMES PER OWNERS DIRECTION. 5 CONNECTION TO BUILDING MOUNTED SIGNAGE; FIELD VERIFY EXACT LOCATION, MTG HEIGHT AND CONNECTION REQUIREMENTS WITH SIGN INSTALLER PRIOR TO ROUGH-IN. 8'4'0" SPECIAL NOTES: A. THESE PLANS HAVE BEEN PREPARED WITHOUT UTILITY COMPANY COMMENTS. THE E.C. SHALL VERIFY THE EXACT REQUIREMENTS FOR THE ELECTRIC AND TELEPHONE SERVICES WITH THE UTILITY COMPANY REPRESENTATIVES AND PROVIDE ALL WORK AND PAY ALL COSTS FOR A COMPLETE AND OPERATING SYSTEM, AS DIRECTED BY THE GOVERNING UTILITIES. S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL BRK NOTES: Receptacle 8100 VA 100.00% 8100 VA Other 1600 VA 100.00% 1600 VA TOTAL EST. DEMAND AMPS:237 A Motor 85 VA 125.00% 106 VA TOTAL CONN. AMPS.:318 A Lighting 2706 VA 100.00% 2706 VA TOTAL EST. DEMAND:56815 VA Kitchen Equipment - Non-Dwelling Unit 55680 VA 65.00%36192 VA TOTAL CONN. LOAD:76284 VA HVAC 8122 VA 100.00% 8122 VA LOAD CLASSIFICATION CONNECTED... DEMAND FACTOR EST. DEMAND PANEL TOTALS PANEL SUMMARY TOTAL AMPS:337 A 299 A TOTAL LOAD:40.5 kVA 35.8 kVA 83 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 84 81 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 82 79 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 80 77 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 78 75 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 76 73 PREPARED SPACE -- -- 1 -- -- 1 -- -- PREPARED SPACE 74 71 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 72 69 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 70 67 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 68 65 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 66 63 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 64 61 SPARE -- 20 A 1 0 2400 -- -- -- --62 59 SPARE -- 20 A 1 0 2400 2 30 A G Frozen Beverage Freezer (E-24a) 60 57 Nugget Ice Mach. G 20 A 1 1440 2400 -- -- -- --58 55 Microwave 20 A 1 960 2400 2 30 A G Frozen Beverage Freezer (E-24b) 56 53 ---- -- -- 2760 4061 -- -- -- --54 51 Espressor Machine G 30 A 2 2760 4061 2 60 A HVAC - Rooftop Unit 52 49 ---- -- -- 2760 2760 -- -- -- --50 47 Espressor Machine G 30 A 2 2760 2760 2 30 A G Coffee Brewer 48 45 ---- -- -- 840 1020 -- -- -- --46 43 Cooler Cond. 20 A 2 840 1020 2 20 A Freezer Cond. 44 41 Cooler Coil & Recpt. 20 A 1 1716 912 -- -- -- --42 39 Cooler/Freezer Lights/ Door Htr 20 A 1 600 912 2 20 A Freezer Coil 40 37 Coffee Grinder 20 A 1 960 720 1 20 A Juicer 38 35 Coffee Grinder 20 A 1 960 1560 1 20 A G Blender 36 33 Coffee Grinder 20 A 1 960 1560 1 20 A G Blender 34 31 Ice Maker G 20 A 1 1200 1560 1 20 A G Blender 32 29 Soda Equipment G 20 A 1 1200 1560 1 20 A G Blender 30 27 Soda Equipment G 20 A 1 1200 1476 1 20 A G Ice Cream Freezer 28 25 Soda Mach./Dipper Well G 20 A 1 1200 684 1 20 A G Under Counter Fridge 26 23 Receptacle 20 A 1 180 864 1 20 A G Under Counter Fridge 24 21 Receptacle 20 A 1 540 1596 1 20 A Toaster 22 19 Receptacle 20 A 1 360 360 1 20 A Receptacle - Rooftop 20 17 Receptacle 20 A 1 720 0 1 20 A -- SPARE 18 15 Receptacle - Signs 20 A 1 720 0 1 20 A -- SPARE 16 13 Receptacle 20 A 1 720 0 1 20 A -- SPARE 14 11 Receptacle G 20 A 1 720 715 1 20 A Lighting 12 9 Receptacle 20 A 1 540 1200 1 20 A LCP Lighting - Exterior 10 7 Receptacle 20 A 1 360 600 1 20 A LCP Lighting - Exterior 8 5 Receptacle 20 A 1 1080 268 1 20 A LCP Lighting - Exterior 6 3 Receptacle 20 A 1 720 800 1 20 A LCP Bldg signage 4 1 Receptacle 20 A 1 1080 800 1 20 A LCP Bldg signage 2 CKT CIRCUIT DESCRIPTION NOTE AMPS P A B P AMPS NOTE CIRCUIT DESCRIPTION CKT PANEL SHALL BE A SINGLE SECTION PANEL. NOTES: MFGR/MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.75"D x 68"H FEED:BOTTOM ENCLOSURE:NEMA 1 BUSSING:SEE SPEC'S MBR AMPS:N/A MOUNTING:FLUSH WIRES:3 PANEL AMPS:400 A ---- FED FROM: PHASES:1 PANEL TYPE:MLO JAVA ESPRESS REXBURG, IDAHO PANEL LOCATION: VOLTAGE:120/240 Single A.I.C. RATING:22k PROJECT NAME: PANEL: A PAYNE ENGINEERING 1 R e v i s i o n 2 0 2 /1 0 /2 0 2 2