HomeMy WebLinkAboutFA PLANS FA1-FA2 - 21-00766 - Yellowstone Heights Condos - Bldg 1 - 12 PlexN N N N FACP BATTERY BATTERY + + - - + - - - - POWER SUPPLY BATTERY BATTERY + + -- + - - - - FPS-1 FIRE ALARM AC / C H A R G E R NA C T R O U B L E BA T T E R Y GR O U N D F A U L T AC F1 15A 30V FACP Battery Calculation PROJECT NAME: 4/8/2022 Required Standby Time: Required Alarm Time: Yellowstone Heights 24 Hours 5 Minutes Regulated Load in Standby Number Device Type NFW-50X Main Board Smoke Detector Pull Station Dual Input Module TOTAL STANDBY LOAD Regulated Load in ALARM Number Device Type NFW-50X Main Board Smoke Detector Pull Station Dual Input Module TOTAL ALARM LOAD Standby Load Current (Amps) Alarm Load Current (Amps) Total Ampere Hours (before derating factor) Derating Factor TOTAL AMPERE HOURS REQUIRED BATTERIES (2 - 12v) 0.85700 X Battery Requirements 0.14235 X Required Standby Time in Hours 24.00000 = Required Alarm Time in Hours 0.08333 = X = of Devices 1 1 1 1 X X X X Current (Amps) 0.25700 = 0.20000 = 0.20000 = 0.20000 = of Devices 1 1 1 1 X X X X Current (Amps) 0.14100 = 0.00030 = 0.00030 = 0.00075 = Total Current (Amps) 0.14100 0.00030 0.00030 0.00075 0.14235 Total Current (Amps) 0.25700 0.20000 0.20000 0.20000 0.85700 3.41640 0.07142 3.48782 10% 3.83660 7 Ah Point to Point NAC Voltage Drop Calculation 4/8/2022 Project Name Circuit Number Nominal System Voltage Minimum Device Voltage Distance from source to 1st device Wire Gauge for balance of circuit Max Output Current Total Circuit Current End of Line Voltage Circuit is within limits Device Current Device 1 Device 2 Device 3 Device 4 Device 5 Device 6 Device 7 Device 8 Device 9 Device 10 Device 11 Device 12 Totals 0.108 0.108 0.108 0.108 0.108 0.108 0.108 0.108 0.108 0.108 0.108 0.108 1.296 228 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Yellowstone Heights FPS1-1 20.4 volts 16.0 volts 17 feet 2.50 amps 1.296 amps 19.42 volts Distance previous Voltage at Drop from Percent device Device 34 3 29 3 19 37 20 3 27 3 33 20.26 20.02 20.00 19.82 19.81 19.72 19.57 19.51 19.50 19.44 19.44 19.42 source 0.135 0.383 0.403 0.576 0.592 0.680 0.828 0.894 0.902 0.956 0.960 0.981 Drop 0.66% 1.88% 1.98% 2.82% 2.90% 3.34% 4.06% 4.38% 4.42% 4.68% 4.70% 4.81% Wire Gauge 14 14 Resistance Per 1000 3.07 3.07 Point to Point NAC Voltage Drop Calculation 4/8/2022 Project Name Circuit Number Nominal System Voltage Minimum Device Voltage Distance from source to 1st device Wire Gauge for balance of circuit Max Output Current Total Circuit Current End of Line Voltage Circuit is within limits Device Current Device 1 Device 2 Device 3 Device 4 Device 5 Device 6 Device 7 Device 8 Device 9 Device 10 Device 11 Device 12 Totals 0.108 0.108 0.108 0.108 0.108 0.108 0.108 0.108 0.108 0.108 0.108 0.108 1.296 228 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Yellowstone Heights FPS1-2 20.4 volts 16.0 volts 17 feet 2.50 amps 1.296 amps 19.42 volts Distance previous Voltage at Drop from Percent device Device 34 3 29 3 19 37 20 3 27 3 33 20.26 20.02 20.00 19.82 19.81 19.72 19.57 19.51 19.50 19.44 19.44 19.42 source 0.135 0.383 0.403 0.576 0.592 0.680 0.828 0.894 0.902 0.956 0.960 0.981 Drop 0.66% 1.88% 1.98% 2.82% 2.90% 3.34% 4.06% 4.38% 4.42% 4.68% 4.70% 4.81% Wire Gauge 14 14 Resistance Per 1000 3.07 3.07 Point to Point NAC Voltage Drop Calculation 4/8/2022 Project Name Circuit Number Nominal System Voltage Minimum Device Voltage Distance from source to 1st device Wire Gauge for balance of circuit Max Output Current Total Circuit Current End of Line Voltage Circuit is within limits Device Current Device 1 Device 2 Device 3 Device 4 Device 5 Device 6 Device 7 Device 8 Device 9 Device 10 Device 11 Device 12 Totals 0.108 0.108 0.108 0.108 0.108 0.108 0.108 0.108 0.108 0.108 0.108 0.108 1.296 228 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Yellowstone Heights FPS1-3 20.4 volts 16.0 volts 17 feet 2.50 amps 1.296 amps 19.42 volts Distance previous Voltage at Drop from Percent device Device 34 3 29 3 19 37 20 3 27 3 33 20.26 20.02 20.00 19.82 19.81 19.72 19.57 19.51 19.50 19.44 19.44 19.42 source 0.135 0.383 0.403 0.576 0.592 0.680 0.828 0.894 0.902 0.956 0.960 0.981 Drop 0.66% 1.88% 1.98% 2.82% 2.90% 3.34% 4.06% 4.38% 4.42% 4.68% 4.70% 4.81% Wire Gauge 14 14 Resistance Per 1000 3.07 3.07 Point to Point NAC Voltage Drop Calculation 4/8/2022 Project Name Circuit Number Nominal System Voltage Minimum Device Voltage Distance from source to 1st device Wire Gauge for balance of circuit Max Output Current Total Circuit Current End of Line Voltage Circuit is within limits Device Current Device 1 Totals 0.194 0.194 8 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Yellowstone Heights FPS1-4 20.4 volts 16.0 volts 8 feet 2.50 amps 0.194 amps 20.39 volts Distance previous Voltage at Drop from Percent device Device 20.39 source 0.010 Drop 0.05% Wire Gauge 14 14 Resistance Per 1000 3.07 3.07 MATRIX OPERATIONS FPS1 Battery Calculation PROJECT NAME: Required Standby Time: Required Alarm Time: Yellowstone Heights 24 Hours 5 Minutes Regulated Load in Standby Number Device Type FPS MAINBOARD TOTAL STANDBY LOAD Regulated Load in ALARM Number Device Type FPS MAINBOARD FPS1-1 (See Voltage Drop Calculations) FPS1-2 (See Voltage Drop Calculations) FPS1-3 (See Voltage Drop Calculations) FPS1-4 (See Voltage Drop Calculations) TOTAL ALARM LOAD Standby Load Current (Amps) Alarm Load Current (Amps) Total Ampere Hours (before derating factor) Derating Factor TOTAL AMPERE HOURS REQUIRED BATTERIES TO BE PROVIDED (2 - 12v) 4.22100 X Battery Requirements 0.15700 X of Devices 1 1 1 1 1 X X X X X Current (Amps) 0.13900 = 1.29600 = 1.29600 = 1.29600 = 0.19400 = of Devices 1 X Current (Amps) 0.15700 = Total Current (Amps) 0.15700 0.15700 Total Current (Amps) 0.13900 1.29600 1.29600 1.29600 0.19400 4.22100 Required Standby Time in Hours 24.00000 = Required Alarm Time in Hours 0.08333 = X = 3.76800 0.35175 4.11975 1.2 4.94370 7 AH 4/20/2022