FACP Battery Calculation
PROJECT NAME:
4/8/2022
Required Standby Time:
Required Alarm Time:
Yellowstone Heights
24 Hours
5 Minutes
Regulated Load in Standby
Number
Device Type
NFW-50X Main Board
Smoke Detector
Pull Station
Dual Input Module
TOTAL STANDBY LOAD
Regulated Load in ALARM
Number
Device Type
NFW-50X Main Board
Smoke Detector
Pull Station
Dual Input Module
TOTAL ALARM LOAD
Standby Load
Current (Amps)
Alarm Load
Current (Amps)
Total Ampere Hours (before derating factor)
Derating Factor
TOTAL AMPERE HOURS REQUIRED
BATTERIES (2 - 12v)
0.85700 X
Battery Requirements
0.14235 X
Required Standby Time in Hours
24.00000 =
Required Alarm Time in Hours
0.08333 =
X
=
of Devices
1
1
1
1
X
X
X
X
Current
(Amps)
0.25700 =
0.20000 =
0.20000 =
0.20000 =
of Devices
1
1
1
1
X
X
X
X
Current
(Amps)
0.14100 =
0.00030 =
0.00030 =
0.00075 =
Total Current
(Amps)
0.14100
0.00030
0.00030
0.00075
0.14235
Total Current
(Amps)
0.25700
0.20000
0.20000
0.20000
0.85700
3.41640
0.07142
3.48782
10%
3.83660
7 Ah
Point to Point NAC Voltage Drop Calculation 4/8/2022
Project Name
Circuit Number
Nominal System Voltage
Minimum Device Voltage
Distance from source to 1st device
Wire Gauge for balance of circuit
Max Output Current
Total Circuit Current
End of Line Voltage
Circuit is within limits
Device
Current
Device 1
Device 2
Device 3
Device 4
Device 5
Device 6
Device 7
Device 8
Device 9
Device 10
Device 11
Device 12
Totals
0.108
0.108
0.108
0.108
0.108
0.108
0.108
0.108
0.108
0.108
0.108
0.108
1.296 228
Notes:
Wire resistance is doubled in the calculations for two wires (Positive and Negative).
The voltage calculated to the last device must not be lower than the manufactures listed
minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)).
Yellowstone Heights
FPS1-1
20.4 volts
16.0 volts
17 feet
2.50 amps
1.296 amps
19.42 volts
Distance
previous Voltage at Drop from Percent
device Device
34
3
29
3
19
37
20
3
27
3
33
20.26
20.02
20.00
19.82
19.81
19.72
19.57
19.51
19.50
19.44
19.44
19.42
source
0.135
0.383
0.403
0.576
0.592
0.680
0.828
0.894
0.902
0.956
0.960
0.981
Drop
0.66%
1.88%
1.98%
2.82%
2.90%
3.34%
4.06%
4.38%
4.42%
4.68%
4.70%
4.81%
Wire
Gauge
14
14
Resistance
Per 1000
3.07
3.07
Point to Point NAC Voltage Drop Calculation 4/8/2022
Project Name
Circuit Number
Nominal System Voltage
Minimum Device Voltage
Distance from source to 1st device
Wire Gauge for balance of circuit
Max Output Current
Total Circuit Current
End of Line Voltage
Circuit is within limits
Device
Current
Device 1
Device 2
Device 3
Device 4
Device 5
Device 6
Device 7
Device 8
Device 9
Device 10
Device 11
Device 12
Totals
0.108
0.108
0.108
0.108
0.108
0.108
0.108
0.108
0.108
0.108
0.108
0.108
1.296 228
Notes:
Wire resistance is doubled in the calculations for two wires (Positive and Negative).
The voltage calculated to the last device must not be lower than the manufactures listed
minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)).
Yellowstone Heights
FPS1-2
20.4 volts
16.0 volts
17 feet
2.50 amps
1.296 amps
19.42 volts
Distance
previous Voltage at Drop from Percent
device Device
34
3
29
3
19
37
20
3
27
3
33
20.26
20.02
20.00
19.82
19.81
19.72
19.57
19.51
19.50
19.44
19.44
19.42
source
0.135
0.383
0.403
0.576
0.592
0.680
0.828
0.894
0.902
0.956
0.960
0.981
Drop
0.66%
1.88%
1.98%
2.82%
2.90%
3.34%
4.06%
4.38%
4.42%
4.68%
4.70%
4.81%
Wire
Gauge
14
14
Resistance
Per 1000
3.07
3.07
Point to Point NAC Voltage Drop Calculation 4/8/2022
Project Name
Circuit Number
Nominal System Voltage
Minimum Device Voltage
Distance from source to 1st device
Wire Gauge for balance of circuit
Max Output Current
Total Circuit Current
End of Line Voltage
Circuit is within limits
Device
Current
Device 1
Device 2
Device 3
Device 4
Device 5
Device 6
Device 7
Device 8
Device 9
Device 10
Device 11
Device 12
Totals
0.108
0.108
0.108
0.108
0.108
0.108
0.108
0.108
0.108
0.108
0.108
0.108
1.296 228
Notes:
Wire resistance is doubled in the calculations for two wires (Positive and Negative).
The voltage calculated to the last device must not be lower than the manufactures listed
minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)).
Yellowstone Heights
FPS1-3
20.4 volts
16.0 volts
17 feet
2.50 amps
1.296 amps
19.42 volts
Distance
previous Voltage at Drop from Percent
device Device
34
3
29
3
19
37
20
3
27
3
33
20.26
20.02
20.00
19.82
19.81
19.72
19.57
19.51
19.50
19.44
19.44
19.42
source
0.135
0.383
0.403
0.576
0.592
0.680
0.828
0.894
0.902
0.956
0.960
0.981
Drop
0.66%
1.88%
1.98%
2.82%
2.90%
3.34%
4.06%
4.38%
4.42%
4.68%
4.70%
4.81%
Wire
Gauge
14
14
Resistance
Per 1000
3.07
3.07
Point to Point NAC Voltage Drop Calculation 4/8/2022
Project Name
Circuit Number
Nominal System Voltage
Minimum Device Voltage
Distance from source to 1st device
Wire Gauge for balance of circuit
Max Output Current
Total Circuit Current
End of Line Voltage
Circuit is within limits
Device
Current
Device 1
Totals
0.194
0.194 8
Notes:
Wire resistance is doubled in the calculations for two wires (Positive and Negative).
The voltage calculated to the last device must not be lower than the manufactures listed
minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)).
Yellowstone Heights
FPS1-4
20.4 volts
16.0 volts
8 feet
2.50 amps
0.194 amps
20.39 volts
Distance
previous Voltage at Drop from Percent
device Device
20.39
source
0.010
Drop
0.05%
Wire
Gauge
14
14
Resistance
Per 1000
3.07
3.07
MATRIX
OPERATIONS
FPS1 Battery Calculation
PROJECT NAME:
Required Standby Time:
Required Alarm Time:
Yellowstone Heights
24 Hours
5 Minutes
Regulated Load in Standby
Number
Device Type
FPS MAINBOARD
TOTAL STANDBY LOAD
Regulated Load in ALARM
Number
Device Type
FPS MAINBOARD
FPS1-1 (See Voltage Drop Calculations)
FPS1-2 (See Voltage Drop Calculations)
FPS1-3 (See Voltage Drop Calculations)
FPS1-4 (See Voltage Drop Calculations)
TOTAL ALARM LOAD
Standby Load
Current (Amps)
Alarm Load
Current (Amps)
Total Ampere Hours (before derating factor)
Derating Factor
TOTAL AMPERE HOURS REQUIRED
BATTERIES TO BE PROVIDED (2 - 12v)
4.22100 X
Battery Requirements
0.15700 X
of Devices
1
1
1
1
1
X
X
X
X
X
Current
(Amps)
0.13900 =
1.29600 =
1.29600 =
1.29600 =
0.19400 =
of Devices
1 X
Current
(Amps)
0.15700 =
Total Current
(Amps)
0.15700
0.15700
Total Current
(Amps)
0.13900
1.29600
1.29600
1.29600
0.19400
4.22100
Required Standby Time in Hours
24.00000 =
Required Alarm Time in Hours
0.08333 =
X
=
3.76800
0.35175
4.11975
1.2
4.94370
7 AH
4/20/2022