Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
A1.1 Free text Cody Jones : Building Open 1 Need to have envelope COMM check or prescriptive insulation
formed signed.
Need engineered truss plans reviewed and approved by
building engineer.
Buildings or structures in flood areas need to have flood
certificates.
A1.1 Free text Cody Jones : Building Open 1 Egress Balcony to comply with section 1021.
A1.1 Comment Cody Jones : Building Open 1 Exterior Exit Stairs & Ramps comply with IBC Section 1027
A1.1 Free text Cody Jones : Building Open 1 Exterior walls less then 10 feet from adjacent building or lot
line needs to have a minimum of one hour protection.
A2.1 Free text Cody Jones : Building Open 2 Please make sure dog house is large enough for required
access and equipment.
A6.1 Free text Cody Jones : Building Open 5 2 layers required.
A6.1 Free text Cody Jones : Building Open 5 Fire partitions and horizontal assemblies need to be identified
and listed assembly from the GA-600 Fire resistance design
manual noted on plans.
A2.1 Free text Alex Owens : Electrical Open 10 Available fault current calculation needed for plan review.
# 22-00260
New Multi-Family Residence
Report Date: 05.04.2022
Approval of plans does not constitute approval of variance from code
Page 1 of 2
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
A2.1 Free text Alex Owens : Electrical Open 10 Notes:
All electrical work and wiring methods to comply with 2017
NEC. A concrete encased electrode ("UFFER" ground) is
required on all buildings that have a foundation. Receptacle
locations/spacing to comply with requirements of 210.52.
Report Date: 05.04.2022
Approval of plans does not constitute approval of variance from code
Page 2 of 2
Powered by TCPDF (www.tcpdf.org)
Need to have envelope COMM check or prescriptive insulation formed signed.
Need engineered truss plans reviewed and approved by building engineer.
Buildings or structures in flood areas need to have flood certificates.
Egress Balcony to comply with section 1021.
Exterior walls less then 10 feet from adjacent building or lot line needs to have a
minimum of one hour protection.
Please make sure dog house is large enough for required
access and equipment.
2 layers required.
Fire partitions and
horizontal assemblies need
to be identified and listed
assembly from the GA-600
Fire resistance design
manual noted on plans.
Available fault
current calculation
needed for plan
review.
Notes:
All electrical work and wiring
methods to comply with 2017 NEC.
A concrete encased electrode
("UFFER" ground) is required on all
buildings that have a foundation.
Receptacle locations/spacing to
comply with requirements of 210.52.