Compressive Strength of Concrete Test Specimens
Project Number:
22-212
Cumulative Test Load Amount:
15.0
Ticket #:
07006
Project Name:
Rexburg Denny's
Test Location:
Rexburg Denny’s foundation walls
Client:
EcoCon
Admixtures:
MSAC 534, P 997
Required 28 day Strength
(psi):
3,000.0
Contractor:
KC Concrete
Supplier:
Walters ready mix
Mix Number:
1710
Date:
04/15/2022
Start Time
01:00 PM
End Time
03:30 PM
Testing:
Set #:Time
Tested:
Ticket #:Test
Location:
Ambient
Temp.
(°F):
Unit Weight
(PCF):
Entrained
Air (%):
Entrained
Air
Spec.
(%):
Concrete
Temp.
(°F):
Slump
(in):
Slump
Spec.
(in):
1 02:15
PM
07006 Rexburg
Denny’s
foundation
walls
47 143.13 1.20 2 63 6.25 6 max
Observations/Remarks:
I arrived at 1:20 pm, and inspected the rebar and forms. I was able to get my work station setup while the pump
truck was setting up.
The trucks began to arrive around 2:00 pm and I was able to get my sample and begin my testing. The results
were received and reported, the air was low but they decided to continue.
I cleaned up and observed the remainder of the pour. The crew utilized knocking on the forms for consolidation
as they went. I returned to my truck and finished my report.
I left the job site at 3:00 pm.
Tested By:
M.Mansfield
Signature:
Reviewed By:
E. Vail
Signature:
File Name
22212C04152022MM
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
8B2B9B16-2D71-4216-A25E-9DBCFE018E1E 2
Date:
04/16/2022
Inspection Images
File Name:
22212FB04202022CJH
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
51824609-16B3-40D7-BA36-B8A136AB32AF 1
4103 E 605 N Suite 1 Rigby, ID 83442 208.881.0081 www.connectengr.com
Compressive Strength of Concrete Test Specimens
Project Number:
22-212
Cumulative Test Load Amount:
8.0
Project Name:
Rexburg Denny's
Test Location:
Western continuous footing
Client:
EcoCon
Admixtures:
NC, P997, MS AC 534
Ticket Number:
6979
Contractor:
J&M Concrete
Supplier:
Walter's
Mix Number:
1700
Pour Date:
4/13/2022
Cylinder Log #:
115
Field Test Results:
Set #:
1
Slump
(inches):
5.0
Slump
Maximum
(in):
Entrained Air
(%):
1.50
Entrained Air
Spec. (%):
2.00
Concrete
Temperature
(°F):
65
Ambient
Temperature
(°F):
33
Unit Weight
(PCF):
143.13
Tested By:
C. Carlson
Date:
4/13/2022
Time Tested:
2:30 PM
Picked Up By:
Mark Mansfield
Date:
4/14/2022
Time:
1:00 PM
Max, Min Temperature
55,70
Initial Break Results:
Cylinder
#:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Break
Type:
Required
28 day
Strength
(psi):
A 7 4/20/2022 12.56 40,335.0 3211.39 Type 5 3,000.0
Date:
04/20/2022
Reviewed By:
E. Vail
Signature:
File Name:
22212FB04222022EV
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
057AE1B1-9D78-489E-BF48-62FB6EE78869 1
4103 E 605 N Suite 1 Rigby, ID 83442 208.881.0081 www.connectengr.com
Compressive Strength of Concrete Test Specimens
Project Number:
22-212
Cumulative Test Load Amount:
15.0
Project Name:
Rexburg Denny's
Test Location:
Rexburg Dennys foundation walls
Client:
EcoCon
Admixtures:
MSAC 534, P 997
Ticket Number:
7006
Contractor:
KC Concrete
Supplier:
Walters ready mix
Mix Number:
1710
Pour Date:
4/15/2022
Cylinder Log #:
121
Field Test Results:
Set #:
1
Slump
(inches):
6.2
Slump
Maximum
(in):
Entrained Air
(%):
1.20
Entrained Air
Spec. (%):
2.00
Concrete
Temperature
(°F):
63
Ambient
Temperature
(°F):
47
Unit Weight
(PCF):
143.13
Tested By:
M. Mansfield
Date:
4/15/2022
Time Tested:
2:15 PM
Picked Up By:
E. Vail
Date:
4/18/2022
Time:
10:30 AM
Max, Min Temperature
84, 61
Initial Break Results:
Cylinder
#:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Break
Type:
Required
28 day
Strength
(psi):
A 7 4/22/2022 12.56 46,495.0 3701.83 Type 2 3,000.0
Date:
04/25/2022
Reviewed By:
E. Vail
Signature:
File name:
22212SB05112022LC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
DF5EF5C7-A38E-4E75-B396-90B376F6FB60 1
4103 E 605 N Suite 1 Rigby, ID 83442 208.881.0081 www.connectengr.com
Compressive Strength of Concrete Test Specimens
Project Number:
22-212
Cumulative Test Load Amount:
8.0
Project Name:
Rexburg Denny's
Test Location:
Western continuous footing
Client:
EcoCon
Admixtures:
NC, P997, MS AC 534
Ticket Number:
6979
Contractor:
J&M Concrete
Supplier:
Walter's
Mix Number:
1700
Date:
4/13/2022
Cylinder Log #:
115
Field Test Results:
Set #:
1
Slump
(inches):
5.0
Slump
Maximum
(in):
Entrained Air
(%):
1.50
Entrained Air
Spec. (%):
2.00
Concrete
Temperature
(°F):
65
Ambient
Temperature
(°F):
33
Unit Weight
(PCF):
143.13
Tested By:
C. Carlson
Date:
4/13/2022
Picked Up By:
Mark Mansfield
Date:
4/14/2022
Time:
1:00 PM
Max, Min Temperature
55,70
Previous Test Results:
Cylinder
ID:
Break Age:Break
Date:
Area (in^2:Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 4/20/2022 12.56 40335 3211.39 3,000.00 Type 5
File name:
22212SB05112022LC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
DF5EF5C7-A38E-4E75-B396-90B376F6FB60 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 5/11/2022 4.00 12.6 54,600.0 4333.3 3,000.0 Type 5
C 28 5/11/2022 4.00 12.6 55,870.0 4434.1 3,000.0 Type 3
D 28 5/11/2022 4.00 12.6 54,160.0 4298.4 3,000.0 Type 5
Second Break Average:
4355
Date:
05/11/2022
Reviewed By:
E. Vail
Signature:
File name:
22212SB05132022LSH
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A7F4BE43-26ED-4970-B8D1-F4D2F7C68A8F 1
4103 E 605 N Suite 1 Rigby, ID 83442 208.881.0081 www.connectengr.com
Compressive Strength of Concrete Test Specimens
Project Number:
22-212
Cumulative Test Load Amount:
15.0
Project Name:
Rexburg Denny's
Test Location:
Rexburg Dennys foundation walls
Client:
EcoCon
Admixtures:
MSAC 534, P 997
Ticket Number:
7006
Contractor:
KC Concrete
Supplier:
Walters ready mix
Mix Number:
1710
Date:
4/15/2022
Cylinder Log #:
121
Field Test Results:
Set #:
1
Slump
(inches):
6.2
Slump
Maximum
(in):
Entrained Air
(%):
1.20
Entrained Air
Spec. (%):
2.00
Concrete
Temperature
(°F):
63
Ambient
Temperature
(°F):
47
Unit Weight
(PCF):
143.13
Tested By:
M. Mansfield
Date:
4/15/2022
Picked Up By:
E. Vail
Date:
4/18/2022
Time:
10:30 AM
Max, Min Temperature
84, 61
Previous Test Results:
Cylinder
ID:
Break Age:Break
Date:
Area (in^2:Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 4/22/2022 12.56 46495 3701.83 3,000.00 Type 2
File name:
22212SB05132022LSH
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A7F4BE43-26ED-4970-B8D1-F4D2F7C68A8F 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 5/13/2022 4.00 12.6 59,155.0 4694.8 3,000.0 Type 2
C 28 5/13/2022 4.00 12.6 63,850.0 5067.5 3,000.0 Type 1
D 28 5/13/2022 4.00 12.6 59,925.0 4756.0 3,000.0 Type 6
Second Break Average:
4839
Date:
05/16/2022
Reviewed By:
E. Vail
Signature:
File Name
22212C06152022COP
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
AEB7039C-EF2C-48A5-8AAD-FD7AF7212419 1
4103 E 605 N Suite 1 Rigby, ID 83442 208.881.0081 www.connectengr.com
Compressive Strength of Concrete Test Specimens
Project Number:
22-212
Cumulative Test Load Amount:
11.0
Ticket #:
08797
Project Name:
Rexburg Denny's
Test Location:
Interior slab of building
Client:
EcoCon
Admixtures:
MS AC 534, MP 322
Required 28 day Strength
(psi):
4,000.0
Contractor:
K&C Concrete
Supplier:
Walters Ready Mix, Inc.
Mix Number:
142I
Date:
06/15/2022
Start Time
04:45 AM
End Time
08:15 AM
Testing:
Set #:Time
Tested:
Ticket #:Test
Location:
Ambient
Temp.
(°F):
Unit Weight
(PCF):
Entrained
Air (%):
Entrained
Air
Spec.
(%):
Concrete
Temp.
(°F):
Slump
(in):
Slump
Spec.
(in):
1 05:50
AM
08797 Interior
slab of
building
39 144.3 1.7 2 64 6 max
2 06:45
AM
08803 Interior
slab of
building
41 145.3 1.4 2 57 6 max
Observations/Remarks:
I arrived on site and prepared my gear. I noted a pump truck was to be used to place the concrete. At
approximately 5:30 am, the first truck arrived. After approximately two cubic yards had been poured, I sampled
from the truck and began my tests. I found these tests to be within the given specifications. I then sampled from
the fifth truck, and performed the required tests. I found the tests to be within the given specifications, except
for the slump test. The specification for slump was 6 in and I tested 6 3/4 in. I informed the contractor of my
results. After performing my tests, I observed the remainder of the pour. I then returned to the lab.
Tested By:
C. Price
Signature:
Reviewed By:
Luke Hammar
Signature:
File Name
22212C06152022COP
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
AEB7039C-EF2C-48A5-8AAD-FD7AF7212419 2
Date:
06/15/2022
Inspection Images
File Name
22212C06152022COP
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
AEB7039C-EF2C-48A5-8AAD-FD7AF7212419 3
File Name:
22212FB06132022JPC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
8AF6B181-24C3-4DC6-9630-D0840F9275E3 1
4103 E 605 N Suite 1 Rigby, ID 83442 208.881.0081 www.connectengr.com
Compressive Strength of Concrete Test Specimens
Project Number:
22-212
Cumulative Test Load Amount:
11
Project Name:
Rexburg Denny's
Test Location:
Interior slab of building
Client:
EcoCon
Admixtures:
MS AC 534, MP 322
Ticket Number:
8797
Contractor:
KC Concrete
Supplier:
Walters Ready Mix, Inc.
Mix Number:
142I
Pour Date:
6/15/2022
Cylinder Log #:
271
Field Test Results:
Set #:
1
Slump
Maximum
(in):
Entrained Air
(%):
1.7
Entrained Air
Spec. (%):
2.0
Concrete
Temperature
(°F):
64
Ambient
Temperature
(°F):
39
Unit Weight
(PCF):
144.3
Tested By:
C. Price
Date:
6/15/2022
Time Tested:
271
Picked Up By:
K. Drake
Date:
6/15/2022
Time:
12:00 PM
Max, Min Temperature
55,70
Initial Break Results:
Cylinder
#:
Break
Age:
Break
Date:
Area (in^2):Maximum
Load (lbs):
Compressive
Strength
(psi):
Break
Type:
Required
28 day
Strength
(psi):
A 7 6/22/2022 12.56 5344 Type 4
Date:
06/22/2022
Reviewed By:
Luke Hammar
Signature:
File Name:
22212FB06132022JPC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
6ECB3ED2-04E1-4C3E-842E-A28652EFFBF9 1
4103 E 605 N Suite 1 Rigby, ID 83442 208.881.0081 www.connectengr.com
Compressive Strength of Concrete Test Specimens
Project Number:
22-212
Cumulative Test Load Amount:
55
Project Name:
Rexburg Denny's
Test Location:
Interior slab of building
Client:
EcoCon
Admixtures:
MS AC 534, MP 322
Ticket Number:
8803
Contractor:
KC Concrete
Supplier:
Walters Ready Mix, Inc.
Mix Number:
142I
Pour Date:
6/15/2022
Cylinder Log #:
272
Field Test Results:
Set #:
2
Slump
Maximum
(in):
Entrained Air
(%):
1.4
Entrained Air
Spec. (%):
2.0
Concrete
Temperature
(°F):
57
Ambient
Temperature
(°F):
41
Unit Weight
(PCF):
145.3
Tested By:
C. Price
Date:
6/15/2022
Time Tested:
272
Picked Up By:
K. Drake
Date:
6/15/2022
Time:
12:04 PM
Max, Min Temperature
55,70
Initial Break Results:
Cylinder
#:
Break
Age:
Break
Date:
Area (in^2):Maximum
Load (lbs):
Compressive
Strength
(psi):
Break
Type:
Required
28 day
Strength
(psi):
A 7 6/22/2022 12.56 4781 Type 3
Date:
06/22/2022
Reviewed By:
Luke Hammar
Signature:
File name:
22212SB06152022JPC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
AE3EF741-3AB7-4BF1-A030-C1874B8CA3D6 1
4103 E 605 N Suite 1 Rigby, ID 83442 208.881.0081 www.connectengr.com
Compressive Strength of Concrete Test Specimens
Project Number:
22-212
Cumulative Test Load Amount:
55
Project Name:
Rexburg Denny's
Test Location:
Interior slab of building
Client:
EcoCon
Admixtures:
MS AC 534, MP 322
Ticket Number:
8803
Contractor:
KC Concrete
Supplier:
Walters Ready Mix, Inc.
Mix Number:
142I
Date:
6/15/2022
Cylinder Log #:
272
Field Test Results:
Set #:
2
Slump
Maximum
(in):
Entrained Air
(%):
1.4
Entrained Air
Spec. (%):
2.0
Concrete
Temperature
(°F):
57
Ambient
Temperature
(°F):
41
Unit Weight
(PCF):
145.3
Tested By:
C. Price
Date:
6/15/2022
Picked Up By:
K. Drake
Date:
6/15/2022
Time:
12:04 PM
Max, Min Temperature
55,70
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 6/22/2022 12.56 60055 4781 4,000.00 272
File name:
22212SB06152022JPC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
AE3EF741-3AB7-4BF1-A030-C1874B8CA3D6 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 7/13/2022 4.000 12.56 72,900.0 5804 4,000.0 Type 2
C 28 7/13/2022 4.000 12.56 72,040.0 5736 4,000.0 Type 1
D 28 7/13/2022 4.000 12.56 74,200.0 5908 4,000.0 Type 1
Second Break Average:
5816
Date:
07/14/2022
Reviewed By:
Luke Hammar
Signature:
File name:
22212SB06152022JPC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
3330DB78-E757-4CBE-AFC0-B6AB4D05C2A6 1
4103 E 605 N Suite 1 Rigby, ID 83442 208.881.0081 www.connectengr.com
Compressive Strength of Concrete Test Specimens
Project Number:
22-212
Cumulative Test Load Amount:
11
Project Name:
Rexburg Denny's
Test Location:
Interior slab of building
Client:
EcoCon
Admixtures:
MS AC 534, MP 322
Ticket Number:
8797
Contractor:
KC Concrete
Supplier:
Walters Ready Mix, Inc.
Mix Number:
142I
Date:
6/15/2022
Cylinder Log #:
271
Field Test Results:
Set #:
1
Slump
Maximum
(in):
Entrained Air
(%):
1.7
Entrained Air
Spec. (%):
2.0
Concrete
Temperature
(°F):
64
Ambient
Temperature
(°F):
39
Unit Weight
(PCF):
144.3
Tested By:
C. Price
Date:
6/15/2022
Picked Up By:
K. Drake
Date:
6/15/2022
Time:
12:00 PM
Max, Min Temperature
55,70
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 6/22/2022 12.56 67125 5344 4,000.00 271
File name:
22212SB06152022JPC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
3330DB78-E757-4CBE-AFC0-B6AB4D05C2A6 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 7/13/2022 4.000 12.56 82,445.0 6564 4,000.0 Type 2
C 28 7/13/2022 4.000 12.56 80,720.0 6427 4,000.0 Type 3
D 28 7/13/2022 4.000 12.56 81,660.0 6502 4,000.0 Type 2
Second Break Average:
6498
Date:
07/14/2022
Reviewed By:
Luke Hammar
Signature:
File Name
22212C04132022CRC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
7ca1bb41ba298523-1649879948832 1
4103 E 605 N Suite 1 Rigby, ID 83442 208.881.0081 www.connectengr.com
Compressive Strength of Concrete Test Specimens
Project Number:
22-212
Cumulative Test Load Amount:
8.0
Ticket #:
06979
Project Name:
Rexburg Denny's
Test Location:
Western continuous footing
Client:
EcoCon
Admixtures:
NC, P997, MS AC 534
Required 28 day Strength
(psi):
3,000.0
Contractor:
J&M Concrete
Supplier:
Walter's
Mix Number:
1700
Date:
04/13/2022
Start Time
01:00 PM
End Time
04:15 PM
Testing:
Set #:Time
Tested:
Ticket #:Test
Location:
Ambient
Temp.
(°F):
Unit Weight
(PCF):
Entrained
Air (%):
Entrained
Air
Spec.
(%):
Concrete
Temp.
(°F):
Slump
(in):
Slump
Spec.
(in):
1 02:30
PM
06979 Western
continuous
footing
33 143.13 1.50 2 65 5.00 6 max
Observations/Remarks:
The rebar was inspected, and photos placed into this report.
A Walter's Concrete truck arrived a half hour later than scheduled. The concrete was placed via pump truck
(Brundage Bone). After approximately 10% of the truckload was offloaded, a sample was collected and tested for
temperature, unit weight, air, and slump. Compressive strength cylinder specimens were casted and stored in a
thermal container for initial set.
Results were reported to K&C Concrete, as well as Walter's mixer driver.
Two trucks total (16 Yds) were placed. The entire pour consisted of the continuous footing around the perimeter
of the building.
Tested By:
C. Carlson
Signature:
Reviewed By:
E. Vail
Signature:
File Name
22212C04132022CRC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its