Loading...
HomeMy WebLinkAboutLOAD SHORT FORM - 23-00106 - 2205 W 640 S - New SFRCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Mar-07 12:27:54 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N SF8B15Job:Load Short Form Date:Entire House Vince ByramBy: fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody Puzey, Karthcner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) Semi-tightConstruction quality7570Inside db (°F) 0Fireplaces1476Design TD (°F) H-Daily range 5050Inside humidity (%) -3162Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Lennox Make Lennox Trade LENNOX Trade LENNOX Model ML195UH045XP24B-*Cond 13ACXN018-230A** AHRI ref 4805337 Coil C35-18/24B*++TDR AHRI ref 201757243 Efficiency 95 AFUE Efficiency 10.7 EER, 13 SEER Heating input Btuh44000 Sensible cooling Btuh17500 Heating output Btuh41000 Latent cooling Btuh0 Temperature rise °F63 Total cooling Btuh17500 Actual air flow cfm700 Actual air flow cfm700 Air flow factor cfm/Btuh0.020 Air flow factor cfm/Btuh0.045 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Room1 253 3293 1763 65 79 Room3 109 1828 476 36 21 Room4 814 10126 5939 199 267 Room6 36 448 33 9 1 Room7 144 2197 1012 43 46 Room8 78 762 56 15 3 Room9 146 2381 1001 47 45 Room10 204 3910 691 77 31 Room11 544 4019 1432 79 64 Room12 53 81 39 2 2 Room14 138 1319 301 26 14 Room15 40 443 61 9 3 Room16 149 2322 1367 46 62 Room17 151 2335 1370 46 62 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Mar-07 12:27:54 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 2 ...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N Room5 51 226 12 4 1 Entire House d 2910 35691 15552 700 700 Other equip loads 7358 1355 Equip. @ 0.94 RSM 15893 Latent cooling 0 TOTALS 2910 43049 15893 700 700 2023-Mar-07 12:27:54 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N SF8B15Job:Building Analysis Date:Entire House Vince ByramBy: fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody Puzey, Karthcner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) Semi-tightConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing DoorsCeilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 31.5135674.9Walls 20.1863223.9Glazing 2.292622.0Doors 6.126311.5Ceilings 7.431891.81.8Floors 15.767452.1Infiltration 00Ducts 00Piping 00Humidification 17.17358Ventilation0Adjustments 100.043049Total Cooling Walls Glazing Other Ceilings Infiltration Ventilation % of loadBtuhBtuh/ft²Component 7.713030.5Walls 70.71194833.0Glazing 1.32255.4Doors 8.614540.8Ceilings 000Floors 3.76210.2Infiltration 00Ducts 8.01355Ventilation 00Internal gains 00Blower 0Adjustments 100.016907Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 57 Btuh/ft²-°F Data entries checked. 2023-Mar-07 12:27:55 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N SF8B15Job:Component Constructions Date:Entire House Vince ByramBy: fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody Puzey, Karthcner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) Semi-tightConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 3390.4735274.9422.00.065714n 3360.4734984.9422.00.065708e 3450.4735964.9422.00.065728s 2830.4729474.9422.00.065597w 13030.47135674.9422.00.0652746all Partitions (none) Windows 61C: 61C; 6.67 ft head ht 16010.638825.800.34015n 160433.8122725.800.34048e 28118.738825.800.34015s 168833.8129225.800.34050w 373329.3329525.800.340128all 61C: 61C; NFRC rated (SHGC=0.33); 6.67 ft head ht 0.30051n 53510.5116522.80 122835.179822.800.30035e 30519.036522.800.30016s 463135.1301022.800.300132w 669828.6533722.800.300234all Doors 11P0: Door, mtl pur core type 1135.3646322.010.50.29021e 1135.3646322.010.50.29021s 2255.3692622.010.50.29042all Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 14540.8426311.5250.00.0201731 Floors 21A-32c: Bg floor, heavy dry or light damp soil, 8' depth, carpet flr fnsh 022571.5200.0201485 0 2023-Mar-07 12:27:55 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 2 ...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N 22B-10cpm: Bg floor, heavy dry or light damp soil, on grade depth, r-10 edge ins, carpet flr fnsh 0093227.010.00.35535 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Mar-07 12:27:55 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N SF8B15Job:Project Summary Date:Entire House Vince ByramBy: fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody Puzey, Karthcner HomesFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F14Daily range H Relative humidity %50Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh35691 Structure Btuh15552 Ducts Btuh0 Ducts Btuh0Central vent (105 cfm)7358 Btuh Central vent (105 cfm)Btuh1355 Outside air Outside airHumidificationBtuh0Blower Btuh0 Piping Btuh0Equipment load Btuh43049 Use manufacturer's data n Rate/swing multiplier 0.94InfiltrationEquipment sensible load Btuh15893 Method Latent Cooling Equipment Load SizingSimplified Construction quality Semi-tight0Fireplaces Structure Btuh-864 Ducts Btuh0Central vent (105 cfm)Btuh-1884 CoolingHeating Outside air29102910Area (ft²)Equipment latent load Btuh0 2619226192Volume (ft³)Air changes/hour 0.110.22 Equipment Total Load (Sen+Lat)Btuh15893 Equiv. AVF (cfm)4896 Req. total capacity at 1.00 SHR ton1.3 Heating Equipment Summary Cooling Equipment Summary Make Lennox Make LennoxTradeLENNOXTradeLENNOX Model ML195UH045XP24B-*Cond 13ACXN018-230A**AHRI ref 4805337 Coil C35-18/24B*++TDR AHRI ref 201757243Efficiency95 AFUE Efficiency 10.7 EER, 13 SEER Heating input Btuh44000 Sensible cooling Btuh17500Heating output Btuh41000 Latent cooling Btuh0 Temperature rise °F63 Total cooling Btuh17500Actual air flow cfm700 Actual air flow cfm700 Air flow factor cfm/Btuh0.020 Air flow factor cfm/Btuh0.045Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 2023-Mar-07 12:27:55 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N SF8B15Job:AED Assessment Date:Entire House Vince ByramBy: fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody Puzey, Karthcner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) )H(34-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limitGlazing load (Btuh)Hour of Day 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 46.4%. House does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 1518 Btuh (PFG - 1.3*AFG) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Mar-07 12:27:55Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N SF8B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Entire House Room1 2 Exposed wall 350.0 ft 31.3 ft 3 Room height 9.0 dft 9.0 heat/coolft 4 Room dimensions ft252.6x1.0 5 Room area 2910.2 f t²252.6 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 780 714 3527 339 0 0 0 0 .GG 61C61C 0.3400.340 nn 25.8425.84 10.6510.65 15 0 388 160 0 0 0 0 .GG 61C61C 0.3000.300 nn 22.8022.80 10.4710.47 51 0 1165 535 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 812 708 3498 336 0 0 0 0 1 1 GG 61C61C 0.3400.340 ee 25.8425.84 33.7733.77 48 0 1227 1604 0 0 0 0 GG 61C61C 0.3000.300 ee 22.8022.80 35.0835.08 35 0 798 1228 0 0 0 0 DD 11P011P0 0.2900.290 ee 22.0422.04 5.365.36 21 21 463 113 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 780 728 3596 345 128 128 630 60 GG 61C61C 0.3400.340 ss 25.8425.84 18.7118.71 15 0 388 281 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 19.0519.05 16 0 365 305 0 0 0 0 DD 11P011P0 0.2900.290 ss 22.0422.04 5.365.36 21 21 463 113 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 779 597 2947 283 155 125 615 59 GG 61C61C 0.3400.340 ww 25.8425.84 33.7733.77 50 0 1292 1688 0 0 0 0 GG 61C61C 0.3000.300 ww 22.8022.80 35.0835.08 132 0 3010 4631 30 0 684 1052 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 1731 1731 2631 1454 247 247 376 208 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 1485 1485 2257 0 253 253 384 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 291 35 932 0 0 0 0 0 6 c) AED excursion 1518 327 Envelope loss/gain 28945 14931 2689 1707 12 a)Infiltration 6745 621 604 56 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)35691 15552 3293 1763 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 35691 15552 3293 1763 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 35691 15552 3293 1763 Air required (cfm)Air required (cfm)700 700 65 79 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Mar-07 12:27:55Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 2...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N SF8B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room3 Room4 2 Exposed wall 21.0 ft 81.8 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft9.5x11.5 ft814.3x1.0 5 Room area 109.3 f t²814.3 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 275 223 1104 106 .GG 61C61C 0.3400.340 nn 25.8425.84 10.6510.65 0 0 0 0 0 0 0 0 .GG 61C61C 0.3000.300 nn 22.8022.80 10.4710.47 0 0 0 0 51 0 1165 535 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 104 104 511 49 90 59 291 28 1 1 GG 61C61C 0.3400.340 ee 25.8425.84 33.7733.77 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ee 22.8022.80 35.0835.08 0 0 0 0 10 0 228 351 DD 11P011P0 0.2900.290 ee 22.0422.04 5.365.36 0 0 0 0 21 21 463 113 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 86 70 343 33 120 99 489 47 GG 61C61C 0.3400.340 ss 25.8425.84 18.7118.71 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 19.0519.05 16 0 365 305 0 0 0 0 DD 11P011P0 0.2900.290 ss 22.0422.04 5.365.36 0 0 0 0 21 21 463 113 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 252 150 741 71 GG 61C61C 0.3400.340 ww 25.8425.84 33.7733.77 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ww 22.8022.80 35.0835.08 0 0 0 0 102 0 2326 3578 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 25 25 38 21 28 28 42 23 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 109 109 166 0 814 814 1238 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 31 829 Envelope loss/gain 1423 438 8549 5794 12 a)Infiltration 405 37 1577 145 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1828 476 10126 5939 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1828 476 10126 5939 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1828 476 10126 5939 Air required (cfm)Air required (cfm)36 21 199 267 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Mar-07 12:27:55Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 3...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N SF8B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room6 Room7 2 Exposed wall 6.2 ft 24.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft6.2x5.8 ft12.7x11.3 5 Room area 36.0 f t²143.6 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 114 114 563 54 .GG 61C61C 0.3400.340 nn 25.8425.84 10.6510.65 0 0 0 0 0 0 0 0 .GG 61C61C 0.3000.300 nn 22.8022.80 10.4710.47 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 102 77 380 37 1 1 GG 61C61C 0.3400.340 ee 25.8425.84 33.7733.77 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ee 22.8022.80 35.0835.08 0 0 0 0 25 0 570 877 DD 11P011P0 0.2900.290 ee 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 56 56 274 26 0 0 0 0 GG 61C61C 0.3400.340 ss 25.8425.84 18.7118.71 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 19.0519.05 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 ss 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3400.340 ww 25.8425.84 33.7733.77 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ww 22.8022.80 35.0835.08 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 2 2 3 2 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 36 36 55 0 144 144 218 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -5 0 Envelope loss/gain 329 22 1735 969 12 a)Infiltration 119 11 463 43 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)448 33 2197 1012 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 448 33 2197 1012 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 448 33 2197 1012 Air required (cfm)Air required (cfm)9 1 43 46 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Mar-07 12:27:55Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 4...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N SF8B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room8 Room9 2 Exposed wall 10.0 ft 26.5 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft7.8x10.0 ft12.7x11.5 5 Room area 78.3 f t²145.7 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 114 114 563 54 .GG 61C61C 0.3400.340 nn 25.8425.84 10.6510.65 0 0 0 0 0 0 0 0 .GG 61C61C 0.3000.300 nn 22.8022.80 10.4710.47 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 90 90 445 43 104 81 400 38 1 1 GG 61C61C 0.3400.340 ee 25.8425.84 33.7733.77 0 0 0 0 23 0 581 760 GG 61C61C 0.3000.300 ee 22.8022.80 35.0835.08 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 ee 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 21 21 104 10 GG 61C61C 0.3400.340 ss 25.8425.84 18.7118.71 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 19.0519.05 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 ss 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3400.340 ww 25.8425.84 33.7733.77 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ww 22.8022.80 35.0835.08 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 4 4 6 3 146 146 221 122 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 78 78 119 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -8 -31 Envelope loss/gain 570 38 1870 954 12 a)Infiltration 193 18 511 47 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)762 56 2381 1001 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 762 56 2381 1001 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 762 56 2381 1001 Air required (cfm)Air required (cfm)15 3 47 45 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Mar-07 12:27:55Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 5...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N SF8B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room10 Room11 2 Exposed wall 42.2 ft 36.7 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft15.5x13.2 ft544.2x1.0 5 Room area 204.1 f t²544.2 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 3 3 15 1 66 66 326 31 .GG 61C61C 0.3400.340 nn 25.8425.84 10.6510.65 0 0 0 0 0 0 0 0 .GG 61C61C 0.3000.300 nn 22.8022.80 10.4710.47 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 119 119 585 56 183 158 781 75 1 1 GG 61C61C 0.3400.340 ee 25.8425.84 33.7733.77 0 0 0 0 25 0 646 844 GG 61C61C 0.3000.300 ee 22.8022.80 35.0835.08 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 ee 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 140 125 615 59 81 81 400 38 GG 61C61C 0.3400.340 ss 25.8425.84 18.7118.71 15 0 388 281 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 19.0519.05 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 ss 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 119 119 585 56 0 0 0 0 GG 61C61C 0.3400.340 ww 25.8425.84 33.7733.77 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ww 22.8022.80 35.0835.08 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 204 204 310 171 544 544 827 457 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 108 22 599 0 183 12 333 0 6 c) AED excursion -9 -79 Envelope loss/gain 3098 616 3313 1367 12 a)Infiltration 813 75 707 65 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3910 691 4019 1432 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 3910 691 4019 1432 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3910 691 4019 1432 Air required (cfm)Air required (cfm)77 31 79 64 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Mar-07 12:27:55Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 6...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N SF8B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room12 Room14 2 Exposed wall 0 ft 12.5 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft6.7x8.0 ft12.5x11.0 5 Room area 53.3 f t²137.5 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 113 98 482 46 .GG 61C61C 0.3400.340 nn 25.8425.84 10.6510.65 0 0 0 0 15 0 388 160 .GG 61C61C 0.3000.300 nn 22.8022.80 10.4710.47 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0 1 1 GG 61C61C 0.3400.340 ee 25.8425.84 33.7733.77 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ee 22.8022.80 35.0835.08 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 ee 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3400.340 ss 25.8425.84 18.7118.71 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 19.0519.05 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 ss 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3400.340 ww 25.8425.84 33.7733.77 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ww 22.8022.80 35.0835.08 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 53 53 81 45 138 138 209 115 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -6 -43 Envelope loss/gain 81 39 1078 279 12 a)Infiltration 0 0 241 22 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)81 39 1319 301 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 81 39 1319 301 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 81 39 1319 301 Air required (cfm)Air required (cfm)2 2 26 14 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Mar-07 12:27:55Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 7...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N SF8B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room15 Room16 2 Exposed wall 6.0 ft 24.7 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft6.0x6.7 ft10.7x14.0 5 Room area 40.0 f t²149.3 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3400.340 nn 25.8425.84 10.6510.65 0 0 0 0 0 0 0 0 .GG 61C61C 0.3000.300 nn 22.8022.80 10.4710.47 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0 1 1 GG 61C61C 0.3400.340 ee 25.8425.84 33.7733.77 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ee 22.8022.80 35.0835.08 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 ee 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 54 54 267 26 96 96 474 46 GG 61C61C 0.3400.340 ss 25.8425.84 18.7118.71 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 19.0519.05 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 ss 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 0 0 0 0 126 101 499 48 GG 61C61C 0.3400.340 ww 25.8425.84 33.7733.77 0 0 0 0 25 0 646 844 GG 61C61C 0.3000.300 ww 22.8022.80 35.0835.08 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 40 40 61 34 149 149 227 125 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -9 261 Envelope loss/gain 328 51 1846 1324 12 a)Infiltration 116 11 475 44 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)443 61 2322 1367 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 443 61 2322 1367 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 443 61 2322 1367 Air required (cfm)Air required (cfm)9 3 46 62 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Mar-07 12:27:55Right-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 8...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N SF8B15Job:Right-J® W or ksheet Date:Entire House Vince ByramBy:fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com 1 Room name Room17 Room5 2 Exposed wall 24.8 ft 2.3 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft10.7x14.2 ft7.8x6.5 5 Room area 151.1 f t²50.9 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 4.944.94 0.470.47 96 96 474 46 0 0 0 0 .GG 61C61C 0.3400.340 nn 25.8425.84 10.6510.65 0 0 0 0 0 0 0 0 .GG 61C61C 0.3000.300 nn 22.8022.80 10.4710.47 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 4.944.94 0.470.47 0 0 0 0 21 21 104 10 1 1 GG 61C61C 0.3400.340 ee 25.8425.84 33.7733.77 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ee 22.8022.80 35.0835.08 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 ee 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3400.340 ss 25.8425.84 18.7118.71 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 19.0519.05 0 0 0 0 0 0 0 0 DD 11P011P0 0.2900.290 ss 22.0422.04 5.365.36 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 4.944.94 0.470.47 128 103 506 49 0 0 0 0 GG 61C61C 0.3400.340 ww 25.8425.84 33.7733.77 25 0 646 844 0 0 0 0 GG 61C61C 0.3000.300 ww 22.8022.80 35.0835.08 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 151 151 230 127 0 0 0 0 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 0 0 0 0 51 51 77 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 260 -2 Envelope loss/gain 1856 1326 181 8 12 a)Infiltration 479 44 45 4 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2335 1370 226 12 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2335 1370 226 12 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2335 1370 226 12 Air required (cfm)Air required (cfm)46 62 4 1 Job #: SF8B15 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Modern Plumbing Heating and Electric 3939 E 240 N Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Vince@modernphe.com Scale: 1 : 90 Page 1 Rig h t-S ui t e ® Un i v ersal 2 02 2 22.0.05 RSU20477 2023-Mar-07 12:29:05 ...oft Program\SF8B15 magnolia.rup N main Room1 Room3 Room4 Room5 Room6 Room7 Room8 6" mechanical fresh air damper 40 cfm 205 cfm 67 cfm 101 cfm 67 cfm40 cfm 112 cfm 67 cfm 36 cfm 67 cfm 4 cfm 9 cfm 46 cfm 15 cfm 14x3.25 12 x 8 14x3.25 6 " 12 x 8 14x3.25 12 x 8 12 x 8 14x3.25 14x3.25 6 "14x3.25 6 " 14x3.25 6 " 6 " 6 " 6 " 6 "6 " 6 " 6 " 6 " 6 " 6 " 12 x 8 6 " 6 " 12 x 8 6 " 12 x 8 6 " 14x3.25 6 " 12 x 8 6 " 14x3.25 6 " 12 x 8 Job #: SF8B15 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Modern Plumbing Heating and Electric 3939 E 240 N Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Vince@modernphe.com Scale: 1 : 90 Page 2 R ig h t-S ui t e ® Un i v ersal 2 02 2 22.0.05 RSU20477 2023-Mar-07 12:29:05 ...oft Program\SF8B15 magnolia.rup N 2nd story Room9 Room10 Room11 Room12Room13 Room14 Room15 Room16 Room17 65 cfm 62 cfm38 cfm 84 cfm 38 cfm 39 cfm 2 cfm 47 cfm 26 cfm 9 cfm 38 cfm 50 cfm 39 cfm 62 cfm 62 cfm 47 cfm 2023-Mar-07 12:27:56 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 1 ...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N SF8B15Job:Duct System Summary Date:Entire House Vince ByramBy: fairviewPlan:Modern Plumbing Heating and Electric 3939 E 240 N, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: Vince@modernphe.com Project Information Cody Puzey, Karthcner HomesFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0.34in H2O0.34 Available static pressure in H2O0.36in H2O0.36 Supply / return available pressure 0.208 / 0.152 in H2O in H2O0.208 / 0.152 Lowest friction rate in/100ft0.056in/100ft0.056 Actual air flow cfm700cfm700 Total effective length (TEL)ft649 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st2150.022.0ShMt0x06.00.1214032881cRoom1 st2185.033.0ShMt0x06.00.0954032881cRoom1-A st2A230.019.0ShMt0x06.00.08316381955hRoom10 st2185.029.0ShMt0x06.00.09716381955hRoom10-A st1270.030.5ShMt0x06.00.06932392010hRoom11 95.020.5ShMt0x06.00.18032392010hRoom11-A st1295.011.0ShMt0x06.00.0682239cRoom12 st1B345.029.0ShMt0x06.00.05614261319hRoom14 st1225.08.0ShMt0x06.00.08939443hRoom15 st1305.020.0ShMt0x06.00.06462461367cRoom16 st1260.035.5ShMt0x06.00.07062461370cRoom17 st2195.019.5ShMt0x06.00.09721361828hRoom3 st1305.019.8ShMt0x06.00.06467501485cRoom4 st1B335.028.0ShMt0x06.00.05767501485cRoom4-A st1A280.037.5ShMt0x06.00.06567501485cRoom4-B st1290.030.0ShMt0x06.00.06567501485cRoom4-C st1160.03.5ShMt0x06.00.12714226hRoom5 st1280.024.0ShMt0x06.00.06819448hRoom6 st1A280.044.5ShMt0x06.00.06446431012cRoom7 st2150.07.5ShMt0x06.00.132315762hRoom8 st1A290.043.5ShMt0x06.00.06245472381hRoom9 2023-Mar-07 12:27:56 Rig ht-Su ite® U niv er sal 20 22 22 .0.05 RSU2 0477 Page 2 ...Country\Wrightsoft Program\SF8B15 magnolia.rup Calc = MJ8 Front Door faces: N Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 469 533 0.056 800 12.3 12x8 ShtMetl st1A Peak AVF 215 238 0.056 357 9.1 12x8 ShtMetl st1 st2A Peak AVF 38 16 0.083 58 4.2 12x8 ShtMetl st2 st2 Peak AVF 192 134 0.083 288 7.7 12x8 ShtMetl st1B Peak AVF 76 80 0.056 121 6.0 12x8 ShtMetl st1A Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb9 0x 930 112 274.5 0.056 356 6.9 3.25x14 10x9 SJSp rt1A rb3 0x 470 45 150.2 0.101 148 4.4 3.25x14 10x9 SJSp rt1 rb6 0x 380 16 109.0 0.140 121 3.8 3.25x14 10x9 SJSp rt1 rb5 0x 460 62 120.3 0.127 195 4.6 3.25x14 10x9 SJSp rt1 rb2 0x 500 37 90.0 0.169 157 4.0 3.25x14 10x9 SJSp rt1 rb4 0x 650 46 156.7 0.097 207 5.0 3.25x14 10x9 SJSp rt1A rb7 0x 840 77 229.0 0.067 265 5.9 3.25x14 10x9 SJSp rt2A rb8 0x 1000 101 131.0 0.116 319 5.7 3.25x14 10x9 SJSp rt2 rb10 0x 1770 205 62.3 0.244 649 6.4 3.25x14 10x9 SJSp Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1A Peak AVF 158 158 0.056 237 7.8 12x8 ShtMetl rt1 rt1 Peak AVF 339 317 0.056 508 10.3 12x8 ShtMetl rt2A Peak AVF 84 77 0.067 126 5.9 12x8 ShtMetl rt2 rt2 Peak AVF 184 178 0.067 276 7.9 12x8 ShtMetl