Loading...
HomeMy WebLinkAboutFS PLANS - 22-00694 - U-Haul Bldg B - New Commercial.pdf8 150'-0±8TO CITY LOOP8TO CITY LOOP24,700 FT² OPEN WAREHOUSE REMOTE FDC FIRE PUMP ROOM PLANRISER DETAIL SECTION VIEW Sprinkler LegendSymbolManufacturerSINModelQuantityK-FactorTypeSizeResponseFinishTemperatureGenericR602P25ESFR32425.2Pendent1QuickBrass200 °FReliableRA1435F1FR5615.6Sidewall½QuickWhite Polyester200 °FTotal = 325RISER DETAIL 1. 8" SUPPLY FROM FIRE PUMP DISCHARGE. 2. PIPE STAND. 3. 8" BUTTERFLY CONTROL VALVE. 4. RISER CHECK VALVE WITH MAIN DRAIN OUTLET AND GAUGES. TYCO CV-1FR. 5. 2" ANGLE VALVE FOR MAIN DRAIN TO OUTSIDE. 6. WATERFLOW SWITCH. 7. AGF MODEL 3011 INSPECTOR'S TEST VALVE WITH 1/2" ORIFICE AND BUILT IN PRESSURE RELIEF VALVE. EXTEND TO 2" MAIN DRAIN. 8. SPARE SPRINKLER CABINET PER NFPA 13. 9. HYDRAULIC DESIGN INFORMATION SIGN. 10. GENERAL INFORMATION SIGN. 11. 8" SUPPLY TO ESFR FIRE SPRINKLER SYSTEM PROTECTING BUILDING B. 328 N. 2nd E. Rexburg, ID 83440U-HaulPRINT DATE 3-D Fire Sprinkler Layout1 2 3 4 DESCRIPTIONNO.DATE FOR APPROVAL REVISIONS OWNERSHIP OF DOCUMENTS ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT OF 3-D FORTHIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF 3-D WHETHER THE PROJECT IS COMPLETEDOR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE, BY THE OWNER OR EXTENSIONS OF THE PROJECT WITHOUT WRITTEN PERMISSION OF 3-D SHALLBE AT THE OWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY, AND HOLD HARMLESS 3-D FROM ALL CLAIMS, DAMAGES, AND EXPENSESINCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THE INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGHTHE OWNER DRAWN BY 4C0103 Travis Capson 3-D FIRE PROJECT NUMBER NORTH 814 SCALE 1/8" = 1'-0" 0 FREEZING CONDITIONS IN LOCATIONS SUBJECT TO FREEZING CONDITIONS, IT IS THE OWNERS RESPONSIBILITY TO PROVIDE HEAT AND ADEQUATEINSULATION THROUGHOUT WET PIPE SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY PIPE AND OTHER TYPES OF VALVES CONTROLLINGWATER SUPPLIES TO SPRINKLER SYSTEMS. Signature AS-BUILT Date of Review Nicet Name SUBMITTAL NICET Level II OTHER FP01 Idaho State Licence: FPSC-8 Tel. 208-881-5436 Travis.Capson@3Dfire.us Idaho Falls, ID 6312 Burggraf Way I have reviewed these plans and certify that they comply with the adopted NFPA standards. 02/01/23 02/01/23 FIRE SERVICE ENTRANCE NO SCALE - BUILDING STRUCTURE AND CONSTRUCTION CONSISTS OF: -CONCRETE FOUNDATION/FLOOR -STEEL BEAMS -STEEL PERLINS - TOTAL SQUARE FOOTAGE: -MAIN LEVEL: 24,700 FT² - BUILDING CODE CLASSIFICATION STORAGE - CONSTRUCTION TYPE - STEEL, CONCRETE THIS AUTOMATIC SPRINKLER SYSTEM IS SIZED BASED ON HYDRAULIC CALCULATIONS IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 13 2019 EDITION. FIRE SPRINKLER SYSTEM IN AREA OF WORK IS DESIGNED CLASS I-IV AT 40 FT MAX STORAGE AND CARTONED, UNEXPANDED PLASTICS IN A 45 FT TALL BUILDING. CITY WATER SUPPLY DATA: STATIC PRESSURE: 86 RESIDUAL PRESSURE: 74 FLOW: 1475 DATE: 09/28/22 SOURCE: 3-D FIRE PROTECTION PUMP DATA: CHURN: 112.5 PSI @ 0.00 GPM RATED: 90 PSI @ 1500 GPM 150% FLOWING: 58.5 PSI @ 1875 GPM TOTAL SYSTEM PROTECTION AREA: 24,700 FT² HYDRAULIC CALCULATION REFERENCE POINT: DESIGN AND INSTALL A SINGLE ZONE WET AUTOMATIC ESFR FIRE SPRINKLER SYSTEM FOR THE NEW BUILDING LOCATED AT 328 N. 2ND E. REXBURG, ID 83440. SYSTEM TO BE SUPPLIED BY A NEW 8" UNDERGROUND LEAD IN TESTED AND FLUSHED BY 3-D FIRE PROTECTION. SYSTEM SCOPE OF WORK STARTS 5' STUB OUT OF THE BUILDING. SYSTEM DESIGN SHALL BE IN ACCORDANCE WITH NFPA 13 2019 AND LOCAL AUTHORITY. DESIGNED BY: TRAVIS CAPSON NICET LEVEL II #71005462 208-881-5438 - OFFICE 6312 S. BURGRAFF WAY IDAHO FALLS, ID 83402 AUTHORITY HAVING JURISDICTION: MADISON FIRE DEPARTMENT 26 N. CENTER ST. REXBURG, ID 208-359-3010 GENERAL CONTRACTOR: BATEMAN HALL 1405 FOOTE DR. IDAHO FALLS, ID 208-523-2681 1. SYSTEM DESIGN, INSTALLATION AND TESTING SHALL BE IN ACCORDANCE WITH NFPA 13 (2019 EDITION) AND LOCAL FIRE AUTHORITY. 2. ALL MATERIAL AND DEVICES TO BE U.L. LISTED AND/OR F.M. APPROVED FOR FIRE SPRINKLER USE. 3. ALL 1" SYSTEM PIPING SHALL BE SCHEDULE 40 BLACK PIPE WITH THREADED CI FITTINGS. 4. ALL SYSTEM PIPING 1¼" AND LARGER SHALL BE SCHEDULE 10 BLACK PIPE WITH GROOVED FITTINGS & GROOVED RIGID COUPLINGS. 5. PIPE SHALL BE MANUFACTURED TO MEET ASTM A135 STANDARDS. CRR VALUE = 1.0 OR GREATER 6. ALL HANGERS SHALL BE DESIGNED, SPACED AND INSTALLED AS PER NFPA-13, 2019 EDITION, CHAPTER-18. MAX LENGTH OF UNSUPPORTED ARMOVERS SHALL BE 24" (PRESSURE LESS THAN 100 PSI). 7. SPRINKLERS LOCATED IN ACOUSTICAL GRID CEILINGS SHALL BE INSTALLED CENTER OF TILE OR QUARTER POINTS. 8. ALL ALARM SYSTEM WIRING AND INSTALLATION IS BY OTHERS. 24 HOUR SUPERVISION TO BE PROVIDED BY OTHERS. 9. OTHER CONTRACTORS TO PROVIDE PAINTING, WIRING, FIRE EXTINGUISHERS, HYDRANTS, THRUST BLOCKING, CITY WATER CONNECTION, EXCAVATION, BACKFILLING AND SYSTEM MONITORING. 10. FLUSHING AND TESTING OF UNDERGROUND PIPING SHALL BE COMPLETED BY THE INSTALLING CONTRACTOR BEFORE CONNECTION TO THE FIRE SPRINKLER SYSTEM. 11. ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE FIRE STOPPED. FIRE STOPPING MATERIAL SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTION BY OTHERS. 12. HYDRAULIC PLACARD SHALL BE POSTED ON RISER. 13. BUILDING OWNER SHALL BE RESPONSIBLE FOR ADEQUATE HEAT (40ºF AND ABOVE) IN ALL WET PIPE AREAS TO PREVENT SPRINKLER SYSTEM FROM FREEZING. 14. 3-D FIRE PROTECTION WILL NOT BE RESPONSIBLE SHOULD THE MINIMUM WATER FLOW VALUES NOT BE SUPPLIED AT THE POINT OF CONNECTION OF THE HYDRAULIC SOURCE NODE. ESFR SYSTEM DESIGN NOTES 40 FEET HIGH STORAGE OF CLASS I-IV COMMODITIES AND CARTONED, UNEXPANDED PLASTICS IN A 45 FT TALL BUILDING. PROTECTED WITH K-25.2 ESFR FIRE SPRINKLERS PER NFPA 13 TABLE 23.5.1. MINIMUM 40 PSI AT HYDRAULICALLY MOST REMOTE SPRINKLER WITH 12 SPRINKLERS FLOWING AND 250 GPM HOSE ALLOWANCE. SYSTEM REQUIRES 43.2 PSI (WITH BOOST FROM 90 PSI AT 1500 GPM FIRE PUMP) WITH 1475 GPM FLOWING AT POINT OF CONNECTION TO PUBLIC WATER SYSTEM. E.S.F.R. SYSTEMS REQUIRE SPECIAL CONSIDERATION REGARDING PLACEMENT OF LIGHTING, DUCT WORK, PROCESS PIPING, ELECTRICAL CONDUIT RUNS, ETC. HYDRAULIC FLOWS AND HEAD PLACEMENTS ARE VERY CRITICAL AND ARE ASSUMED TO TAKE PRECEDENCE. PIPING CAN NOT BE ROUTED AROUND OBSTRUCTIONS DUE TO INCREASED FRICTION LOSSES OR LOWERED FROM ROOF STRUCTURE DUE TO PENDENT DESIGN ONLY AND REQUIRED 12" DEFLECTOR DISTANCE FROM ROOF DECK. IT IS UNDERSTOOD THAT REQUIRED COORDINATION WITH ROOF STRUCTURE, JOIST PANEL POINTS, ROOF DUCTING, LIGHTING. AND OTHER PIPING WILL BE ACCOMPLISHED TO ACCOMMODATE REQUIRED SPRINKLER SPACING. PROPER SPACING MUST ALSO BE MADE BETWEEN E.S.F.R. SPRINKLERS BY THIS EQUIPMENT TO MEET REQUIRED CODES. ESFR SYSTEM NOTE ESFR SYSTEM OBSTRUCTIONS ESFR SPRINKLERS SHALL BE POSITIONED A MINIMUM OF 1 FT HORIZONTALLY FROM THE NEAREST EDGE TO ANY BOTTOM CORD OF A BAR JOIST OR OPEN TRUSS PER NFPA 13 2019, 14.2.11.3.2. ADDITIONAL SPRINKLERS SHALL NOT BE REQUIRED WHERE THE OBSTRUCTION IS 2 IN OR LESS IN WIDTH AND IS LOCATED A MINIMUM OF 2 FT BELOW THE ELEVATION OF THE SPRINKLER DEFLECTOR OR IS POSITIONED A MINIMUM OF 1 FT HORIZONTALLY FROM THE SPRINKLER PER NFPA 13 2019, 14.2.11.3.1. ADDITIONAL SPRINKLERS SHALL NOT BE REQUIRED WHERE THE OBSTRUCTION IS 1 FT OR LESS IN WIDTH AND LOCATED A MINIMUM OF 1 FT HORIZONTALLY FROM THE SPRINKLER PER NFPA 13 2019, 14.2.11.3.1. ADDITIONAL SPRINKLERS SHALL NOT BE REQUIRED WHERE THE OBSTRUCTION IS 2 FT OR LESS IN WIDTH AND LOCATED A MINIMUM OF 2 FT HORIZONTALLY FROM THE SPRINKLER PER NFPA 13 2013, 14.2.11.3.1. INVERTED BEAM CLAMP PIPE ALL THREAD ROD SWIVEL RING I-BEAM BEAM CLAMP ( W/ RETAINER STRAP) RETAINER STRAP PITCH REMOTE INSPECTORS TEST BRANCHLINE 1" GLOBE VALVE 1" UNION 1" GALV. 45º w/ ½" ORIFICE 1" SCH.40 PIPE ADJUSTABLE PIPE STAND 2" SCH.40 PIPE 1½" SCH.40 PIPE 1½" ADJUSTABLE NUT 2" THREADED FLANGE (BOLT TO GROUND) PIPE SADDLE WELDED CONNECTION SPRINKLER PIPE SLOPED BEAM HANGER DETAIL 3/8" ROD BRANCHLINE PIPE SWIVEL RING CLAMP 3/8" BEAM STEEL I-BEAM TOLCO SWIVEL (FIG 75) STEEL BEAM / JOIST LONGITUDINAL BRACE DETAIL TOLCO FIG 828 TOLCO FIG 980 1" SCH.40 PIPE 45º - 60º BRACE ANGLE TOLCO FIG 4L SPRINKLER PIPE TRAPEZE HANGER DETAIL PIPE ALL THREAD ROD TOP BEAM CLAMP SWIVEL RING BEAM / JOIST BEAM CLAMP PIPE ALL THREAD ROD STEEL BEAM / JOIST LATERAL BRACE DETAIL TOLCO FIG 828 TOLCO FIG 980 TOLCO FIG 1000 "FAST CLAMP"SPRINKLER PIPE 1" SCH.40 PIPE 45º - 60º BRACE ANGLE ZEE PURLIN PIPE STEEL SAMMY SIDEWINDER SAMMY SIDEWINDER ALL THREAD ROD SWIVEL RING BRANCHLINE RESTRAINT 3/8" ROD 3/8" ROD BRANCHLINE PIPE SWIVEL RING TOLCO SWIVEL (FIG 75) CLAMP 3/8" BEAM (STEEL BEAM) 45° STEEL BEAM / JOIST BRANCHLINE 1/2" PLUG WET SYSTEM AIR VENT 1/2" BALL VALVE 1/2" X 0-3 NIPPLE 1/2" X 0-3 NIPPLE 1/2" 90º ELBOW NOTE: A SINGLE AIR VENT SHALL BE LOCATED NEAR A HIGH POINT IN THE SYSTEM. GARAGE DOOR SPRINKLER DETAIL BRANCHLINE PIPING OVERHEAD GARAGE DOOR 1" SCH.40 DROP HSW SPRINKLER 1" SCH.40 NIPPLE 1" 90º ELBOW 4"-6"ESFR PENDENT SPRINKLER BRANCHLINE PIPING WELDED OUTLET ESFR PENDENT SPRINKLER DETAIL INSTALL SPRINKLER 6"-18" BELOW DECK SCOPE OF WORK SYSTEM DESIGN NOTES BUILDING DETAILS GENERAL NOTES SURGE RESTRAINT 3/4" ALL THR. ROD "J" BOLT HEX NUT & WASHER THRUST BLOCK (PER NFPA 24) U.G. PIPING GROUND LEVEL D.I.P. RISER M.J. X FL. ADAPTER STEEL RISER 4 3 1 2 5 19 18 17 Travis Capson 71005462 02/01/23 NORTH 1. ALL MATERIALS & INSTALLATIONS TO BE U.L. LISTED & SHALL CONFORM TO NFPA 13 & NFPA 24 2. THRUST BLOCKS & RODDING SHALL CONFORM TO NFPA 24 3. MINIMUM BURY SHALL BE 6'-0" 4. ALL WATER LINES FOR FIRE SPRINKLER SYSTEMS SHALL BE TESTED AT 200 psi FOR TWO HOURS MINIMUM. 5. DUCTILE IRON PIPE SHALL BE USED WHEN PIPE PASSES UNDER BUILDING FOUNDATION OR FOOTING. 6. ALL EXTERIOR MATERIALS SHALL BE PROPERLY PROTECTED AGAINST EXPOSURE. 7. UNDERGROUND PIPING SHALL BE FLUSHED PER NFPA 24 BEFORE CONNECTING TO THE OVERHEAD FIRE SPRINKLER SYSTEM PIPING. 8. REFER TO ANY LOCAL REQUIREMENTS BEFORE INSTALLING OR MAKING A CONNECTION TO THE FIRE SERVICE CONNECTION. UNDERGROUND PIPING GENERAL NOTES SITE PLAN AREA OF WORK FDC LEGEND 1. 4" Butterfly (Sup. Closed) 2. 4" Check Valve 3. 4" Tee for Forward Flow Loop 4. 4 x 2½ x 2½ Remote FDC 5. Connect to 6" Near Main NO SCALE NO SCALE NO SCALENO SCALE SCALE: 1/8" = 1'-0" NORTH NFPA 13, 16.12.5.7 Fire department connections shall be located at the nearest point of fire department apparatus accessibility or at a location approved by the authority having jurisdiction IDAHO STATE FIRE MARSHAL'S OFFICE FIRE SPRINKLER PLAN REVIEW ACCEPTED 02/22/2023WITH COMMEN T S Sprinkler LegendSymbolManufacturerSINModelQuantityK-FactorTypeSizeResponseFinishTemperatureGenericR602P25ESFR32425.2Pendent1QuickBrass200 °FReliableRA1435F1FR5615.6Sidewall½QuickWhite Polyester200 °FTotal = 325328 N. 2nd E. Rexburg, ID 83440U-HaulPRINT DATE 3-D Fire Sprinkler Layout1 2 3 4 DESCRIPTIONNO.DATE FOR APPROVAL REVISIONS OWNERSHIP OF DOCUMENTS ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT OF 3-D FORTHIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF 3-D WHETHER THE PROJECT IS COMPLETEDOR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE, BY THE OWNER OR EXTENSIONS OF THE PROJECT WITHOUT WRITTEN PERMISSION OF 3-D SHALLBE AT THE OWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY, AND HOLD HARMLESS 3-D FROM ALL CLAIMS, DAMAGES, AND EXPENSESINCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THE INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGHTHE OWNER DRAWN BY 4C0103 Travis Capson 3-D FIRE PROJECT NUMBER NORTH 814 SCALE 1/8" = 1'-0" 0 FREEZING CONDITIONS IN LOCATIONS SUBJECT TO FREEZING CONDITIONS, IT IS THE OWNERS RESPONSIBILITY TO PROVIDE HEAT AND ADEQUATEINSULATION THROUGHOUT WET PIPE SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY PIPE AND OTHER TYPES OF VALVES CONTROLLINGWATER SUPPLIES TO SPRINKLER SYSTEMS. Signature AS-BUILT Date of Review Nicet Name SUBMITTAL NICET Level II OTHER FP02 Idaho State Licence: FPSC-8 Tel. 208-881-5436 Travis.Capson@3Dfire.us Idaho Falls, ID 6312 Burggraf Way I have reviewed these plans and certify that they comply with the adopted NFPA standards. 02/01/23 02/01/23 Travis Capson 71005462 02/01/23 SCALE 1/8" = 1'-0" MAIN FLOOR PLAN IDAHO STATE FIRE MARSHAL'S OFFICE FIRE SPRINKLER PLAN REVIEW ACCEPTED 02/22/2023WITH COMMEN T S NFPA 13, 16.12.5.7 Fire department connections shall be located at the nearest point of fire department apparatus accessibility or at a location approved by the authority having jurisdiction