Loading...
HomeMy WebLinkAboutSEWER & WATER DESIGN REPORT - 23-00085 - Founders Square Phase 3 - Plat THE DYER GROUP, LLC • 343 E 4th NORTH, SUITE 108 • REXBURG, ID 83440 - 6001 208.390.9700 (VOICE AND TEXT) • wdyer@thedyergroup.com M E M O R A N D U M To: Carlin Feisthamel, PE - DEQ From: Winston R. Dyer, PE – Project Manager Date: December 30, 2022 Re: Sewer and Water Design Report for Founder’s Square Subdivision, Phase 3 – Rexburg, Idaho The following is submitted as an Engineering Report addressing design capacity and design flow demands associated with this Phase of the proposed single-family residential subdivision development. A previous engineering report dated March 7, 2008 was submitted to DEQ and the City for the entire Founder’s Square subdivision, which was subsequently approved by both entities. This report focuses strictly on the Phase 3 area of the subdivision. Sewer Demand Demand: equivalent population = 15 homes x 3.4 persons/home = 51 persons 51 persons x 65 gpcd = 3,315 gal/day Flow Rate: (3,315 gpd / 1440 minutes per day) x 4.0 peaking factor = 9 gpm Flow Capacity: 8” line @ 0.32% slope = 399 gpm Flow Capacity Used: 9 gpm / 399 gpm = 2% (maximum) ok New Treatment Demand: 3,315 gpd Available Treatment Capacity (Rexburg): 5,500,000 gpd Treatment Capacity Commitment: 3,315 gpd / 5,500,000 gpd = 0.1% ok Providing 8” gravity sewer service in the subdivision will be adequate, and generated wastewater flow will have negligible effect on the existing wastewater collection and treatment facilities. Water Demand Peak Daily Demand: 51 persons x 0.45 gpm / person = 23 gpm 2 Supply Capacity: 3,840 gpm (14” DI from upper reservoir @ 8 fps recommended max velocity for peak) Capacity Used: 23 gpm / 3,840 gpm = 0.6 % in peak day ok Peak Hour Demand: 3 gpm / connection x 15 connections = 45 gpm Pipeline Capacity: 3,840 gpm (14” DI @ 8 fps recommended max velocity for peak) Capacity Used: 45 gpm / 3,840 gpm = 1% in peak hour ok Minimum System Pressure: (5310 wtr surface in elevated reservoir – 10 ft operating range – 5130 max ground elevation in SE corner) x 0.433 psi/ft wtr = 74 psi > 40 psi ok (dynamic losses in the 14” and 12” supply lines to this area are negligible). Fire Flow Demand: 1,125 gpm (IFC B105 for Type V, residential occupancy < 3600 ft.²) Pipeline Capacity: 8” DI @ 10 fps = 1,575 gpm Capacity Used: 1,125 gpm / 1,575 gpm = 71% for fire flow ok Fire Pressure Loss: 12” DI @ 1,125 gpm = 0.0014 psi/ft x 1,260’ = 2 psi (from 2nd East to Founder’s Square along Sunrise / Washington streets) 8” DI @ 1,125 gpm = 0.0098 psi/ft x 760’ = 8 psi (from Founder’s Square to NE corner of Phase along Jefferson / Paul Revere streets) Minimum Fire Pressure: 74 psi min in SE corner – (2 + 8) psi loss = 64 psi > 20 psi ok Providing water service and required fire flow to this proposed subdivision Phase is within the capacity of the existing water supply and distribution facilities and exceeds minimum system requirements for the pipe sizes indicated. -- End of Design Report --