HomeMy WebLinkAboutCOMCHECK - 22-00630 - Bodifi - AdditionCOMcheck Software Version 4.1.5.4
Envelope Compliance Certificate
Project Title:
2018 IECC
Project Type:Addition
Vertical Glazing / Wall Area:3%
Location:Rexburg, Idaho
Climate Zone:6b
Construction Site:Owner/Agent:Designer/Contractor:
Project Information
Energy Code:
Building Area Floor Area
1-Exercise Center : Nonresidential 11718
Envelope Assemblies
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
Roof 1: Metal Building, Screw Down, Liner System without Thermal
Blocks, [Bldg. Use 1 - Exercise Center]
11718 0.0 35.0 0.028 0.031
Floor 1: Slab-On-Grade:Unheated Fully insulated (uniform R-value
across perimeter + under entire slab), [Bldg. Use 1 - Exercise
Center] (c)
340 ---10.0 0.360 0.540
NORTH
Exterior Wall 1: Solid Concrete:10" Thickness, Normal Density, Furring:
None, [Bldg. Use 1 - Exercise Center]
100 ---2.0 0.255 0.080
Exterior Wall 4: Metal Building Wall, Single Layer Mineral Fiber (in
cavity, thermal block at girt), [Bldg. Use 1 - Exercise Center]
2163 30.0 0.0 0.052 0.052
Door_North_Man: Insulated Metal, Swinging, [Bldg. Use 1 - Exercise
Center]
21 ------0.340 0.370
Door_North_Overhead: Insulated Metal, Garage door 14% glazing,
[Bldg. Use 1 - Exercise Center]
70 ------0.340 0.310
EAST
Exterior Wall 2: Solid Concrete:10" Thickness, Normal Density, Furring:
None, [Bldg. Use 1 - Exercise Center]
120 ---2.0 0.255 0.080
Exterior Wall 5: Metal Building Wall, Single Layer Mineral Fiber (in
cavity, thermal block at girt), [Bldg. Use 1 - Exercise Center]
2694 30.0 0.0 0.052 0.052
WEST
Exterior Wall 3: Solid Concrete:10" Thickness, Normal Density, Furring:
None, [Bldg. Use 1 - Exercise Center]
120 ---2.0 0.255 0.080
Exterior Wall 6: Metal Building Wall, Single Layer Mineral Fiber (in
cavity, thermal block at girt), [Bldg. Use 1 - Exercise Center]
2345 30.0 0.0 0.052 0.052
Window: Metal Frame with Thermal Break:Fixed, Perf. Specs.: Product
ID 550, SHGC 0.33, [Bldg. Use 1 - Exercise Center] (b)
240 ------0.340 0.360
Door_East_Man: Insulated Metal, Swinging, [Bldg. Use 1 - Exercise
Center]
21 ------0.340 0.370
Door_West_Man: Insulated Metal, Swinging, [Bldg. Use 1 - Exercise
Center]
21 ------0.340 0.370
Project Title:
Data filename:S:\Drawings\893 Bodifi Addition Rexburg\ComCheck.cck
09/28/22Report date:
101 ofPage
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
(a)Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
(b)Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
(c)Slab-On-Grade proposed and budget U-factors shown in table are F-factors.
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed envelope systems have been
designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.4 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Envelope PASSES: Design 4% better than code
Project Title:
Data filename:S:\Drawings\893 Bodifi Addition Rexburg\ComCheck.cck
09/28/22Report date:
102 ofPage