MANUAL J - 23-00074 - 3023 Olympic Ct - New SFR Mechanical
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00 Right-Suite® Universal 2022 22.0.04 RSU28163 Page 1 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Load Short Form 01/06/2023Date:Entire House Gene MillerBy: L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Summett ServicesFor: Design Information InfiltrationClgHtg SimplifiedMethod90-13Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1583Design TD (°F) H-Daily range 5030Inside humidity (%) -2936Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Day & Night Make Day & Night Trade DAY & NIGHT Trade 13 SEER N SERIES R410A AC Model G96VTN1202422A Cond N4A348GKG1 AHRI ref 0 Coil END4X60L24A1++TDR AHRI ref 0 Efficiency 96 AFUE Efficiency 10.5 EER, 13 SEER Heating input Btuh120000 Sensible cooling Btuh41395 Heating output Btuh94770 Latent cooling Btuh0 Temperature rise °F84 Total cooling Btuh41395 Actual air flow cfm1225 Actual air flow cfm1645 Air flow factor cfm/Btuh0.016 Air flow factor cfm/Btuh0.046 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Main Floor Zone 4766 44781 23492 727 1071 2nd Floor Zone 1415 30652 19934 498 909 Entire House 6181 75433 34657 1225 1645 Other equip loads 9891 1738 Equip. @ 0.95 RSM 34430 Latent cooling 0 TOTALS 6181 85324 34430 1225 1645 No Condenser will be installed at this time Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00 Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 2 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Load Short Form 01/06/2023Date:2nd Floor Zone Gene MillerBy: L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Summett ServicesFor: Design Information InfiltrationClgHtg SimplifiedMethod90-13Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1583Design TD (°F) H-Daily range 5030Inside humidity (%) -2936Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Storage 268 5070 3399 82 155 Bedroom 4 173 3642 4122 59 188 Vanity 45 1112 214 18 10 Bath 36 1088 365 18 17 Bedroom 5 182 4831 1727 78 79 Loft 210 0 0 0 0 Bonus 284 7632 5583 124 255 Office 216 7276 4524 118 206 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00 Right-Suite® Universal 2022 22.0.04 RSU28163 Page 3 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N 2nd Floor Zone 1415 30652 19934 498 909 Other equip loads 0 0 Equip. @ 0.95 RSM 18858 Latent cooling 0 TOTALS 1415 30652 18858 498 909 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00 Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 4 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Load Short Form 01/06/2023Date:Main Floor Zone Gene MillerBy: L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Summett ServicesFor: Design Information InfiltrationClgHtg SimplifiedMethod90-13Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1583Design TD (°F) H-Daily range 5030Inside humidity (%) -2936Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Mech 26 0 0 0 0 Cond Crawl 2370 9089 0 148 0 M TR 25 1193 156 19 7 M Bath 118 3033 1925 49 88 M WIC 88 732 63 12 3 Master 411 5127 3977 83 181 Laundry 118 965 673 16 31 Living 132 1495 407 24 19 Bedroom 2 147 2735 941 44 43 WIC 2 32 925 103 15 5 J-J Vanity 56 0 0 0 0 J - J Bath 39 859 767 14 35 WIC 3 29 879 96 14 4 Bedroom 3 143 2344 2075 38 95 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00 Right-Suite® Universal 2022 22.0.04 RSU28163 Page 5 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N Kit/Din/Great Rm 995 14902 12151 242 554 Pwdr 38 503 158 8 7 Main Floor Zone 4766 44781 23492 727 1071 Other equip loads 0 0 Equip. @ 0.95 RSM 22223 Latent cooling 0 TOTALS 4766 44781 22223 727 1071 2023-Jan-07 11:44:00 Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 1 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Building Analysis 01/06/2023Date:Entire House Gene MillerBy: L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Summett ServicesFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls Rgnl, ID, US 1583Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude:Outdoor:-29.436.4Moisture difference (gr/lb)CoolingHeating Infiltration:90-13Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality61-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors CeilingsFloors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 29.4250444.9Walls 14.21214124.9Glazing 5.3453732.4Doors 5.748561.7Ceilings 7.160812.12.1Floors 16.2138483.2Infiltration 10.58926Ducts 00Piping 00Humidification 11.69891Ventilation0Adjustments 100.085324Total Cooling Walls Glazing Doors CeilingsOtherInfiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 5.018070.4Walls 42.31539331.6Glazing 2.810167.3Doors 6.824600.8Ceilings 0.1360.0Floors 3.613030.3Infiltration 18.36662Ducts 4.81738Ventilation 16.45980Internal gains 00Blower 0Adjustments 100.036395Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 55 Btuh/ft²-°F Data entries checked. 2023-Jan-07 11:44:00 Right-Suite® Universal 2022 22.0.04 RSU28163 Page 2 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Building Analysis 01/06/2023Date:2nd Floor Zone Gene MillerBy: L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Summett ServicesFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1583Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude:Outdoor:-29.436.4Moisture difference (gr/lb)CoolingHeating Infiltration:90-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 27.684635.4Walls 12.9396424.9Glazing 000Doors 7.723511.7Ceilings 4.914962.82.8Floors 17.854523.2Infiltration 29.18926Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.030652Total Cooling Walls Glazing Ceilings OtherInfiltration Ducts Internal Gains % of loadBtuhBtuh/ft²Component 3.87540.5Walls 40.2801750.4Glazing 000Doors 6.011910.8Ceilings 0.2360.1Floors 2.65130.3Infiltration 38.97764Ducts 00Ventilation 8.31660Internal gains 00Blower 0Adjustments 100.019934Total Latent Cooling Load = 0 Btuh Overall U-value = 0.053 Btuh/ft²-°F Data entries checked. 2023-Jan-07 11:44:00 Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 3 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Building Analysis 01/06/2023Date:Main Floor Zone Gene MillerBy: L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Summett ServicesFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls Rgnl, ID, US 1583Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude:Outdoor:-29.436.4Moisture difference (gr/lb)CoolingHeating Infiltration:90-13Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality61-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Floors Infiltration % of loadBtuhBtuh/ft²Component 37.0165814.7Walls 18.3817724.9Glazing 10.1453732.4Doors 5.625051.7Ceilings 10.245861.91.9Floors 18.783953.2Infiltration 00Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.044781Total Cooling Walls Glazing Doors Ceilings Inf iltration Internal Gains % of loadBtuhBtuh/ft²Component 4.510530.3Walls 64.01504445.9Glazing 4.310167.3Doors 5.412690.8Ceilings 000Floors 3.47900.3Infiltration 00Ducts 00Ventilation 18.44320Internal gains 00Blower 0Adjustments 100.023492Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 55 Btuh/ft²-°F Data entries checked. 2023-Jan-07 11:44:00 Right-Suite® Universal 2022 22.0.04 RSU28163 Page 1 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Component Constructions 01/06/2023Date:Entire House Gene MillerBy: L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Summett ServicesFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1583Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-29.436.4Moisture difference (gr/lb)CoolingHeating Infiltration:90-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² 0014893.5719.00.043417n 008893.5719.00.043249e 0014893.5719.00.043417s 008893.5719.00.043249w 0047563.5719.00.0431331all 4540.4850945.4022.00.065943n 4990.4855995.4022.00.0651037e 4200.4847165.4022.00.065873s 4350.4848805.4022.00.065904w 18070.48202885.4022.00.0653756all 112511.0254324.900.300102n 56647.129924.900.30012e 686930.1568424.900.300228s 683447.1361524.900.300145w 1539331.61214124.900.300487all 7117.25317632.400.39098n 3057.25136132.400.39042s 10167.25453732.400.390140all 24600.8448561.6650.00.0202922 Construction descriptions Walls 15B19-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud Partitions (none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.35); foreground = new concrete (0.32); 6.67 ft head ht Doors 11D0: Door, wd sc type Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh Floors 20P-30v: Flr floor, frm flr, 12" thkns, vinyl flr fnsh, r-30 cav ins, gar ovr 360.0714402.9130.00.035495 2023-Jan-07 11:44:00 Right-Suite® Universal 2022 22.0.04 RSU28163 Page 2 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N 21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.0222370 0043321.83 00561.8300.02230 0043881.8300.0222400all 22B-10vpl: Bg floor, light dry soil, on grade depth, r-10 edge ins, vinyl flr fnsh 0025317.510.00.21015 2023-Jan-07 11:44:00 Right-Suite® Universal 2022 22.0.04 RSU28163 Page 3 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Component Constructions 01/06/2023Date:Main Floor Zone Gene MillerBy: L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Summett ServicesFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1583Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-29.436.4Moisture difference (gr/lb)CoolingHeating Infiltration:90-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² 0014893.5719.00.043417n 008893.5719.00.043249e 0014893.5719.00.043417s 008893.5719.00.043249w 0047563.5719.00.0431331all 2500.4828135.4022.00.065521n 2780.4831195.4022.00.065578e 3390.4838085.4022.00.065705s 1860.4820855.4022.00.065386w 10530.48118255.4022.00.0652189all 69511.0157124.900.30063n 56647.129924.900.30012e 596530.1493624.900.300198s 259247.1137124.900.30055w 981729.9817724.900.300328all 7117.25317632.400.39098n 3057.25136132.400.39042s 10167.25453732.400.390140all 12690.8425051.6650.00.0201507 00.0222370 0043321.83 Construction descriptions Walls 15B19-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud Partitions (none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.35); foreground = new concrete (0.32); 6.67 ft head ht Doors 11D0: Door, wd sc type Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh Floors 21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 22B-10vpl: Bg floor, light dry soil, on grade depth, r-10 edge ins, vinyl flr fnsh 0025317.510.00.21015 2023-Jan-07 11:44:00 Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 4 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N 2023-Jan-07 11:44:00 Right-Suite® Universal 2022 22.0.04 RSU28163 Page 5 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Component Constructions 01/06/2023Date:2nd Floor Zone Gene MillerBy: L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Summett ServicesFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1583Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-29.436.4Moisture difference (gr/lb)CoolingHeating Infiltration:90-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² 2030.4822815.4022.00.065422n 2210.4824795.4022.00.065459e 810.489075.4022.00.065168s 2490.4827955.4022.00.065518w 7540.4884635.4022.00.0651567all 43011.097224.900.30039n 90430.174824.900.30030s 424247.1224424.900.30090w 557635.1396424.900.300159all 11910.8423511.6650.00.0201415 360.0714402.9130.00.035495 Construction descriptions Walls Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud Partitions (none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.35); foreground = new concrete (0.32); 6.67 ft head ht Doors (none) Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh Floors 20P-30v: Flr floor, frm flr, 12" thkns, vinyl flr fnsh, r-30 cav ins, gar ovr 21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.02230 00561.83 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00 Right-Suite® Universal 2022 22.0.04 RSU28163 Page 1 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Project Summary 01/06/2023Date:Entire House Gene MillerBy: L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information For:Summett Services INFORMATION CONTAINED WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. OVERSIZED EQUIPMENT IS AT THE OWNERS REQUEST. Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-13 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F83 Design TD °F15Daily range H Relative humidity %50Moisture difference gr/lb-29 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh66507 Structure Btuh27995 Ducts Btuh8926 Ducts Btuh6662Central vent (129 cfm)9891 Btuh Central vent (129 cfm)Btuh1738 Outside air Outside airHumidificationBtuh0Blower Btuh0 Piping Btuh0Equipment load Btuh85324 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh34430 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh-420 Ducts Btuh-93Central vent (129 cfm)Btuh-2161 CoolingHeating Outside air61816181Area (ft²)Equipment latent load Btuh0 3864338643Volume (ft³)Air changes/hour 0.150.28 Equipment Total Load (Sen+Lat)Btuh34430 Equiv. AVF (cfm)97180 Req. total capacity at 1.00 SHR ton2.9 Heating Equipment Summary Cooling Equipment Summary Make Day & Night Make Day & NightTradeDAY & NIGHT Trade 13 SEER N SERIES R410A AC Model G96VTN1202422A Cond N4A348GKG1AHRI ref 0 Coil END4X60L24A1++TDR AHRI ref 0Efficiency96 AFUE Efficiency 10.5 EER, 13 SEER Heating input Btuh120000 Sensible cooling Btuh41395Heating output Btuh94770 Latent cooling Btuh0 Temperature rise °F84 Total cooling Btuh41395Actual air flow cfm1225 Actual air flow cfm1645 Air flow factor cfm/Btuh0.016 Air flow factor cfm/Btuh0.046Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00 Right-Suite® Universal 2022 22.0.04 RSU28163 Page 2 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Project Summary 01/06/2023Date:2nd Floor Zone Gene MillerBy: L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information For:Summett Services INFORMATION CONTAINED WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. OVERSIZED EQUIPMENT IS AT THE OWNERS REQUEST. Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-13 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F83 Design TD °F15Daily range H Relative humidity %50Moisture difference gr/lb-29 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh21726 Structure Btuh12171 Ducts Btuh8926 Ducts Btuh7764Central vent (29 cfm)0 Btuh Central vent (29 cfm)Btuh0 Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh30652 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh18858 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh-238 Ducts Btuh-93Central vent (29 cfm)Btuh0 CoolingHeating14151415Area (ft²)Equipment latent load Btuh0 1273112731Volume (ft³)Air changes/hour 0.180.33 Equipment Total Load (Sen+Lat)Btuh18858 Equiv. AVF (cfm)3871 Req. total capacity at 0.70 SHR ton2.2 Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/aTraden/a Trade n/a Model n/a Cond n/aAHRI ref n/a Coil n/a AHRI ref n/aEfficiencyn/a Efficiency n/a Heating input Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00 Right-Suite® Universal 2022 22.0.04 RSU28163 Page 3 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Project Summary 01/06/2023Date:Main Floor Zone Gene MillerBy: L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information For:Summett Services INFORMATION CONTAINED WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. OVERSIZED EQUIPMENT IS AT THE OWNERS REQUEST. Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-13 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F83 Design TD °F15Daily range H Relative humidity %50Moisture difference gr/lb-29 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh44781 Structure Btuh23492 Ducts Btuh0 Ducts Btuh0Central vent (99 cfm)0 Btuh Central vent (99 cfm)Btuh0 Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh44781 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh22223 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh-182 Ducts Btuh0Central vent (99 cfm)Btuh0 CoolingHeating47664766Area (ft²)Equipment latent load Btuh0 2591225912Volume (ft³)Air changes/hour 0.140.25 Equipment Total Load (Sen+Lat)Btuh22223 Equiv. AVF (cfm)59109 Req. total capacity at 0.70 SHR ton2.6 Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/aTraden/a Trade n/a Model n/a Cond n/aAHRI ref n/a Coil n/a AHRI ref n/aEfficiencyn/a Efficiency n/a Heating input Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 1...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:Entire House Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Entire House Main Floor Zone 2 Exposed wall 683.2 ft 491.4 ft 3 Room height 8.4 ft 8.2 ft 4 Room dimensions 5 Room area 6180.8 f t²4766.3 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.573.57 0.000.00 417 417 1489 0 417 417 1489 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 5.405.40 0.480.48 1143 943 5094 454 682 521 2813 250 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 24.9324.93 11.0311.03 102 0 2543 1125 63 0 1571 695 .DD 11D011D0 0.3900.390 nn 32.4132.41 7.257.25 98 98 3176 711 98 98 3176 711 1 1 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.573.57 0.000.00 249 249 889 0 249 249 889 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 5.405.40 0.480.48 1049 1037 5599 499 590 578 3119 278 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 24.9324.93 47.1347.13 12 0 299 566 12 0 299 566 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.573.57 0.000.00 417 417 1489 0 417 417 1489 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 5.405.40 0.480.48 1143 873 4716 420 945 705 3808 339 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 24.9324.93 30.1330.13 228 0 5684 6869 198 0 4936 5965 DD 11D011D0 0.3900.390 ss 32.4132.41 7.257.25 42 42 1361 305 42 42 1361 305 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.573.57 0.000.00 249 249 889 0 249 249 889 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 5.405.40 0.480.48 1049 904 4880 435 441 386 2085 186 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 24.9324.93 47.1347.13 145 0 3615 6834 55 0 1371 2592 CC 16B-50ad16B-50ad 0.0200.020 --1.661.66 0.840.84 2922 2922 4856 2460 1507 1507 2505 1269 FF 20P-30v20P-30v 0.0350.035 --2.912.91 0.070.07 495 495 1440 36 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.831.83 0.000.00 2370 2370 4332 0 2370 2370 4332 0 FF 21A-28v21A-28v 0.0220.022 --1.831.83 0.000.00 30 30 56 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --17.4517.45 0.000.00 26 15 253 0 26 15 253 0 6 c) AED excursion 0 5227 Envelope loss/gain 52659 20711 36386 18382 12 a)Infiltration 13848 1303 8395 790 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 6 1380 4 920 Appliances/other 4600 3400 Subtotal (lines 6 to 13)66507 27995 44781 23492 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 66507 27995 44781 23492 15 Duct loads 13%25%8926 6662 0%0%0 0 Total room load 75433 34657 44781 23492 Air required (cfm)Air required (cfm)1225 1645 727 1071 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 2...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:Entire House Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name 2nd Floor Zone 2 Exposed wall 191.8 ft 3 Room height 9.0 ft 4 Room dimensions 5 Room area 1414.5 f t² Ty Construction U-value Or HTM Area (f t²)Load Area Load number (Bt uh/f t²-°F)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 15B19-0wc-6 0.069 n 3.57 0.00 0 0 0 0 .W Frm wall, vnl ext, 3 0.065 n 5.40 0.48 461 422 2281 203 .G 2 glazing, clr low-e 0.300 n 24.93 11.03 39 0 972 430 .D 11D0 0.390 n 32.41 7.25 0 0 0 0 1 1 W 15B19-0wc-6 0.069 e 3.57 0.00 0 0 0 0 W Frm wall, vnl ext, 3 0.065 e 5.40 0.48 459 459 2479 221 G 2 glazing, clr low-e 0.300 e 24.93 47.13 0 0 0 0 W 15B19-0wc-6 0.069 s 3.57 0.00 0 0 0 0 W Frm wall, vnl ext, 3 0.065 s 5.40 0.48 198 168 907 81 G 2 glazing, clr low-e 0.300 s 24.93 30.13 30 0 748 904 D 11D0 0.390 s 32.41 7.25 0 0 0 0 W 15B19-0wc-6 0.069 w 3.57 0.00 0 0 0 0 W Frm wall, vnl ext, 3 0.065 w 5.40 0.48 608 518 2795 249 G 2 glazing, clr low-e 0.300 w 24.93 47.13 90 0 2244 4242 C 16B-50ad 0.020 -1.66 0.84 1415 1415 2351 1191 F 20P-30v 0.035 -2.91 0.07 495 495 1440 36 F 21A-28v 0.022 -1.83 0.00 0 0 0 0 F 21A-28v 0.022 -1.83 0.00 30 30 56 0 F 22B-10vpl 0.210 -17.45 0.00 0 0 0 0 6 c) AED excursion 2441 Envelope loss/gain 16273 9998 12 a)Infiltration 5452 513 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 2 460 Appliances/other 1200 Subtotal (lines 6 to 13)21726 12171 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 21726 12171 15 Duct loads 41%64%8926 7764 Total room load 30652 19934 Air required (cfm)498 909 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 3...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:2nd Floor Zone Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name 2nd Floor Zone Storage 2 Exposed wall 191.8 ft 32.8 ft 3 Room height 9.0 ft 9.0 heat/coolft 4 Room dimensions ft16.5x16.3 5 Room area 1414.5 f t²268.1 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 5.405.40 0.480.48 461 422 2281 203 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 24.9324.93 11.0311.03 39 0 972 430 0 0 0 0 .DD 11D011D0 0.3900.390 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 1 1 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 5.405.40 0.480.48 459 459 2479 221 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 5.405.40 0.480.48 198 168 907 81 146 116 628 56 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 24.9324.93 30.1330.13 30 0 748 904 30 0 748 904 DD 11D011D0 0.3900.390 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 5.405.40 0.480.48 608 518 2795 249 149 149 802 71 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 24.9324.93 47.1347.13 90 0 2244 4242 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.661.66 0.840.84 1415 1415 2351 1191 268 268 446 226 FF 20P-30v20P-30v 0.0350.035 --2.912.91 0.070.07 495 495 1440 36 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.831.83 0.000.00 30 30 56 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 2441 716 Envelope loss/gain 16273 9998 2624 1973 12 a)Infiltration 5452 513 931 88 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 2 460 0 0 Appliances/other 1200 0 Subtotal (lines 6 to 13)21726 12171 3555 2061 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 39 14 14 Subtotal 21726 12171 3594 2075 15 Duct loads 41%64%8926 7764 41%64%1477 1324 Total room load 30652 19934 5070 3399 Air required (cfm)Air required (cfm)498 909 82 155 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 4...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:2nd Floor Zone Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Bedroom 4 Vanity 2 Exposed wall 20.5 ft 7.8 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft14.8x11.8 ft5.8x7.8 5 Room area 173.3 f t²44.6 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 5.405.40 0.480.48 52 52 280 25 70 70 377 34 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 24.9324.93 11.0311.03 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 1 1 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 5.405.40 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 5.405.40 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 24.9324.93 30.1330.13 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 5.405.40 0.480.48 133 103 555 49 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 24.9324.93 47.1347.13 30 0 748 1414 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.661.66 0.840.84 173 173 288 146 45 45 74 38 FF 20P-30v20P-30v 0.0350.035 --2.912.91 0.070.07 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.831.83 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 551 -4 Envelope loss/gain 1870 2185 451 67 12 a)Infiltration 583 55 220 21 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2453 2470 671 88 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 128 47 117 43 14 Subtotal 2581 2517 788 131 15 Duct loads 41%64%1061 1605 41%64%324 83 Total room load 3642 4122 1112 214 Air required (cfm)Air required (cfm)59 188 18 10 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 5...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:2nd Floor Zone Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Bath Bedroom 5 2 Exposed wall 6.3 ft 30.8 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft5.8x6.3 ft182.4x1.0 5 Room area 35.9 f t²182.4 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 5.405.40 0.480.48 56 47 255 23 122 92 494 44 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 24.9324.93 11.0311.03 9 0 224 99 30 0 748 331 .DD 11D011D0 0.3900.390 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 1 1 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 5.405.40 0.480.48 0 0 0 0 135 135 729 65 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 5.405.40 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 24.9324.93 30.1330.13 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 5.405.40 0.480.48 0 0 0 0 20 20 109 10 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 24.9324.93 47.1347.13 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.661.66 0.840.84 36 36 60 30 182 182 303 154 FF 20P-30v20P-30v 0.0350.035 --2.912.91 0.070.07 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.831.83 0.000.00 0 0 0 0 30 30 56 0 FF 22B-10vpl22B-10vpl 0.2100.210 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 34 99 Envelope loss/gain 539 186 2439 702 12 a)Infiltration 178 17 874 82 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13)717 203 3314 1014 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 54 20 111 40 14 Subtotal 771 223 3424 1055 15 Duct loads 41%64%317 142 41%64%1407 673 Total room load 1088 365 4831 1727 Air required (cfm)Air required (cfm)18 17 78 79 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 6...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:2nd Floor Zone Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Loft Bonus 2 Exposed wall 2.0 ft 45.3 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft210.3x1.0 ft283.6x1.0 5 Room area 210.3 f t²283.6 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 5.405.40 0.480.48 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 24.9324.93 11.0311.03 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 1 1 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 5.405.40 0.480.48 18 18 97 9 178 178 960 85 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 5.405.40 0.480.48 0 0 0 0 52 52 280 25 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 24.9324.93 30.1330.13 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 5.405.40 0.480.48 0 0 0 0 178 148 798 71 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 24.9324.93 47.1347.13 0 0 0 0 30 0 748 1414 CC 16B-50ad16B-50ad 0.0200.020 --1.661.66 0.840.84 210 210 350 177 284 284 471 239 FF 20P-30v20P-30v 0.0350.035 --2.912.91 0.070.07 0 0 0 0 279 279 811 21 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.831.83 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -8 513 Envelope loss/gain 447 178 4068 2368 12 a)Infiltration 57 5 1287 121 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 900 Subtotal (lines 6 to 13)504 183 5355 3389 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -504 -183 54 20 14 Subtotal 0 0 5409 3409 15 Duct loads 41%64%0 0 41%64%2222 2174 Total room load 0 0 7632 5583 Air required (cfm)Air required (cfm)0 0 124 255 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 7...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:2nd Floor Zone Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Office 2 Exposed wall 46.5 ft 3 Room height 9.0 heat/coolft 4 Room dimensions ft216.3x1.0 5 Room area 216.3 f t² Ty Construction U-value Or HTM Area (f t²)Load Area Load number (Bt uh/f t²-°F)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 15B19-0wc-6 0.069 n 0.00 0.00 0 0 0 0 .W Frm wall, vnl ext, 3 0.065 n 5.40 0.48 162 162 875 78 .G 2 glazing, clr low-e 0.300 n 24.93 11.03 0 0 0 0 .D 11D0 0.390 n 0.00 0.00 0 0 0 0 1 1 W 15B19-0wc-6 0.069 e 0.00 0.00 0 0 0 0 W Frm wall, vnl ext, 3 0.065 e 5.40 0.48 128 128 693 62 G 2 glazing, clr low-e 0.300 e 0.00 0.00 0 0 0 0 W 15B19-0wc-6 0.069 s 0.00 0.00 0 0 0 0 W Frm wall, vnl ext, 3 0.065 s 5.40 0.48 0 0 0 0 G 2 glazing, clr low-e 0.300 s 24.93 30.13 0 0 0 0 D 11D0 0.390 s 0.00 0.00 0 0 0 0 W 15B19-0wc-6 0.069 w 0.00 0.00 0 0 0 0 W Frm wall, vnl ext, 3 0.065 w 5.40 0.48 128 98 531 47 G 2 glazing, clr low-e 0.300 w 24.93 47.13 30 0 748 1414 C 16B-50ad 0.020 -1.66 0.84 216 216 359 182 F 20P-30v 0.035 -2.91 0.07 216 216 629 16 F 21A-28v 0.022 -0.00 0.00 0 0 0 0 F 21A-28v 0.022 -1.83 0.00 0 0 0 0 F 22B-10vpl 0.210 -0.00 0.00 0 0 0 0 6 c) AED excursion 539 Envelope loss/gain 3835 2338 12 a)Infiltration 1322 124 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 300 Subtotal (lines 6 to 13)5157 2762 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 5157 2762 15 Duct loads 41%64%2119 1762 Total room load 7276 4524 Air required (cfm)118 206 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 8...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:Main Floor Zone Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Main Floor Zone Mech 2 Exposed wall 491.4 ft 14.5 ft 3 Room height 8.2 ft 9.0 heat/coolft 4 Room dimensions ft3.8x7.0 5 Room area 4766.3 f t²26.3 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.573.57 0.000.00 417 417 1489 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 5.405.40 0.480.48 682 521 2813 250 63 28 151 13 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 24.9324.93 11.0311.03 63 0 1571 695 0 0 0 0 .DD 11D011D0 0.3900.390 nn 32.4132.41 7.257.25 98 98 3176 711 35 35 1134 254 1 1 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.573.57 0.000.00 249 249 889 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 5.405.40 0.480.48 590 578 3119 278 34 34 182 16 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 24.9324.93 47.1347.13 12 0 299 566 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.573.57 0.000.00 417 417 1489 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 5.405.40 0.480.48 945 705 3808 339 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 24.9324.93 30.1330.13 198 0 4936 5965 0 0 0 0 DD 11D011D0 0.3900.390 ss 32.4132.41 7.257.25 42 42 1361 305 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.573.57 0.000.00 249 249 889 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 5.405.40 0.480.48 441 386 2085 186 34 34 182 16 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 24.9324.93 47.1347.13 55 0 1371 2592 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.661.66 0.840.84 1507 1507 2505 1269 22 22 36 18 FF 20P-30v20P-30v 0.0350.035 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.831.83 0.000.00 2370 2370 4332 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --17.4517.45 0.000.00 26 15 253 0 26 15 253 0 6 c) AED excursion 5227 -18 Envelope loss/gain 36386 18382 1939 300 12 a)Infiltration 8395 790 412 39 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 4 920 0 0 Appliances/other 3400 0 Subtotal (lines 6 to 13)44781 23492 2351 338 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 -2351 -338 14 Subtotal 44781 23492 0 0 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 44781 23492 0 0 Air required (cfm)Air required (cfm)727 1071 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 9...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:Main Floor Zone Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Cond Crawl M TR 2 Exposed wall 242.0 ft 3.5 ft 3 Room height 5.5 heat/coolft 9.0 heat/coolft 4 Room dimensions ft2369.8x1.0 ft4.0x6.3 5 Room area 2369.8 f t²25.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.573.57 0.000.00 417 417 1489 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 5.405.40 0.480.48 0 0 0 0 32 32 170 15 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 24.9324.93 11.0311.03 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 32.4132.41 7.257.25 0 0 0 0 0 0 0 0 1 1 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.573.57 0.000.00 249 249 889 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 5.405.40 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 24.9324.93 47.1347.13 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.573.57 0.000.00 417 417 1489 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 5.405.40 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 24.9324.93 30.1330.13 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 32.4132.41 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.573.57 0.000.00 249 249 889 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 5.405.40 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 24.9324.93 47.1347.13 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.661.66 0.840.84 0 0 0 0 0 0 0 0 FF 20P-30v20P-30v 0.0350.035 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.831.83 0.000.00 2370 2370 4332 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --17.4517.45 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 0 -1 Envelope loss/gain 9089 0 170 14 12 a)Infiltration 0 0 100 9 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)9089 0 270 23 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 924 133 14 Subtotal 9089 0 1193 156 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 9089 0 1193 156 Air required (cfm)Air required (cfm)148 0 19 7 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 10...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:Main Floor Zone Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name M Bath M WIC 2 Exposed wall 14.5 ft 9.5 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft118.3x1.0 ft87.8x1.0 5 Room area 118.3 f t²87.8 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.573.57 0.000.00 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 5.405.40 0.480.48 0 0 0 0 68 68 365 32 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 24.9324.93 11.0311.03 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 32.4132.41 7.257.25 0 0 0 0 0 0 0 0 1 1 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 5.405.40 0.480.48 0 0 0 0 18 18 97 9 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 24.9324.93 47.1347.13 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 5.405.40 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 24.9324.93 30.1330.13 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 32.4132.41 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 5.405.40 0.480.48 131 106 570 51 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 24.9324.93 47.1347.13 25 0 623 1178 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.661.66 0.840.84 0 0 0 0 0 0 0 0 FF 20P-30v20P-30v 0.0350.035 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.831.83 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --17.4517.45 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 452 -3 Envelope loss/gain 1193 1681 462 38 12 a)Infiltration 412 39 270 25 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1605 1720 732 63 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 1428 205 0 0 14 Subtotal 3033 1925 732 63 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3033 1925 732 63 Air required (cfm)Air required (cfm)49 88 12 3 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 11...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:Main Floor Zone Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Master Laundry 2 Exposed wall 49.0 ft 10.3 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft411.1x1.0 ft117.6x1.0 5 Room area 411.1 f t²117.6 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.573.57 0.000.00 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 5.405.40 0.480.48 0 0 0 0 92 83 450 40 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 24.9324.93 11.0311.03 0 0 0 0 9 0 224 99 .DD 11D011D0 0.3900.390 nn 32.4132.41 7.257.25 0 0 0 0 0 0 0 0 1 1 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 5.405.40 0.480.48 72 72 389 35 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 24.9324.93 47.1347.13 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 5.405.40 0.480.48 146 116 628 56 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 24.9324.93 30.1330.13 30 0 748 904 0 0 0 0 DD 11D011D0 0.3900.390 ss 32.4132.41 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 5.405.40 0.480.48 223 193 1041 93 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 24.9324.93 47.1347.13 30 0 748 1414 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.661.66 0.840.84 108 108 179 91 0 0 0 0 FF 20P-30v20P-30v 0.0350.035 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.831.83 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --17.4517.45 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 794 6 Envelope loss/gain 3733 3386 674 145 12 a)Infiltration 1393 131 291 27 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 2 460 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)5127 3977 965 673 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 5127 3977 965 673 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 5127 3977 965 673 Air required (cfm)Air required (cfm)83 181 16 31 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 12...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:Main Floor Zone Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Living Bedroom 2 2 Exposed wall 12.8 ft 24.5 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft132.2x1.0 ft12.3x12.0 5 Room area 132.2 f t²147.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.573.57 0.000.00 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 5.405.40 0.480.48 115 100 539 48 108 78 421 38 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 24.9324.93 11.0311.03 15 0 374 165 30 0 748 331 .DD 11D011D0 0.3900.390 nn 32.4132.41 7.257.25 0 0 0 0 0 0 0 0 1 1 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 5.405.40 0.480.48 0 0 0 0 77 77 413 37 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 24.9324.93 47.1347.13 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 5.405.40 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 24.9324.93 30.1330.13 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 32.4132.41 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 5.405.40 0.480.48 0 0 0 0 36 36 194 17 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 24.9324.93 47.1347.13 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.661.66 0.840.84 132 132 220 111 147 147 244 124 FF 20P-30v20P-30v 0.0350.035 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.831.83 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --17.4517.45 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 48 91 Envelope loss/gain 1132 373 2021 637 12 a)Infiltration 363 34 697 66 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13)1495 407 2718 932 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 17 8 14 Subtotal 1495 407 2735 941 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1495 407 2735 941 Air required (cfm)Air required (cfm)24 19 44 43 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 13...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:Main Floor Zone Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name WIC 2 J-J Vanity 2 Exposed wall 11.3 ft 0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft5.8x5.5 ft9.8x5.8 5 Room area 31.6 f t²56.1 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.573.57 0.000.00 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 5.405.40 0.480.48 50 50 267 24 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 24.9324.93 11.0311.03 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 32.4132.41 7.257.25 0 0 0 0 0 0 0 0 1 1 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 5.405.40 0.480.48 52 52 280 25 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 24.9324.93 47.1347.13 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 5.405.40 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 24.9324.93 30.1330.13 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 32.4132.41 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 5.405.40 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 24.9324.93 47.1347.13 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.661.66 0.840.84 32 32 53 27 56 56 93 47 FF 20P-30v20P-30v 0.0350.035 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.831.83 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --17.4517.45 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -5 -2 Envelope loss/gain 599 70 93 45 12 a)Infiltration 320 30 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)919 100 93 45 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 6 3 -93 -45 14 Subtotal 925 103 0 0 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 925 103 0 0 Air required (cfm)Air required (cfm)15 5 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 14...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:Main Floor Zone Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name J - J Bath WIC 3 2 Exposed wall 7.0 ft 10.8 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft7.0x5.5 ft5.3x5.5 5 Room area 38.5 f t²28.9 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.573.57 0.000.00 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 5.405.40 0.480.48 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 24.9324.93 11.0311.03 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 32.4132.41 7.257.25 0 0 0 0 0 0 0 0 1 1 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 5.405.40 0.480.48 63 51 275 25 47 47 255 23 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 24.9324.93 47.1347.13 12 0 299 566 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 5.405.40 0.480.48 0 0 0 0 50 50 267 24 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 24.9324.93 30.1330.13 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 32.4132.41 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 5.405.40 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 24.9324.93 47.1347.13 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.661.66 0.840.84 39 39 64 32 29 29 48 24 FF 20P-30v20P-30v 0.0350.035 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.831.83 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --17.4517.45 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 115 -5 Envelope loss/gain 639 738 571 66 12 a)Infiltration 199 19 306 29 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)838 757 876 94 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 21 10 2 1 14 Subtotal 859 767 879 96 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 859 767 879 96 Air required (cfm)Air required (cfm)14 35 14 4 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 15...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:Main Floor Zone Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Bedroom 3 Kit/Din/Great Rm 2 Exposed wall 19.5 ft 58.2 ft 3 Room height 9.0 heat/coolft 13.4 heat/coolft 4 Room dimensions ft11.3x12.8 ft994.7x1.0 5 Room area 143.4 f t²994.7 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.573.57 0.000.00 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nn 5.405.40 0.480.48 0 0 0 0 117 54 292 26 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 24.9324.93 11.0311.03 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 32.4132.41 7.257.25 0 0 0 0 63 63 2042 457 1 1 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ee 5.405.40 0.480.48 61 61 328 29 167 167 899 80 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 24.9324.93 47.1347.13 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ss 5.405.40 0.480.48 115 85 458 41 635 455 2455 219 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 24.9324.93 30.1330.13 30 0 748 904 138 0 3440 4157 DD 11D011D0 0.3900.390 ss 32.4132.41 7.257.25 0 0 0 0 42 42 1361 305 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.573.57 0.000.00 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 ww 5.405.40 0.480.48 0 0 0 0 18 18 97 9 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 24.9324.93 47.1347.13 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.661.66 0.840.84 143 143 238 121 800 800 1329 673 FF 20P-30v20P-30v 0.0350.035 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.831.83 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10vpl22B-10vpl 0.2100.210 --17.4517.45 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 690 3032 Envelope loss/gain 1772 1785 11916 8958 12 a)Infiltration 554 52 2957 278 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 0 2900 Subtotal (lines 6 to 13)2327 2067 14873 12137 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 17 8 29 14 14 Subtotal 2344 2075 14902 12151 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2344 2075 14902 12151 Air required (cfm)Air required (cfm)38 95 242 554 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2023-Jan-07 11:44:00Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 16...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Right-J® W or ksheet 01/06/2023Date:Main Floor Zone Gene MillerBy:L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Pwdr 2 Exposed wall 4.3 ft 3 Room height 9.0 heat/coolft 4 Room dimensions ft9.0x4.3 5 Room area 38.3 f t² Ty Construction U-value Or HTM Area (f t²)Load Area Load number (Bt uh/f t²-°F)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 15B19-0wc-6 0.069 n 3.57 0.00 0 0 0 0 .W Frm wall, vnl ext, 3 0.065 n 5.40 0.48 38 29 158 14 .G 2 glazing, clr low-e 0.300 n 24.93 11.03 9 0 224 99 .D 11D0 0.390 n 32.41 7.25 0 0 0 0 1 1 W 15B19-0wc-6 0.069 e 3.57 0.00 0 0 0 0 W Frm wall, vnl ext, 3 0.065 e 5.40 0.48 0 0 0 0 G 2 glazing, clr low-e 0.300 e 24.93 47.13 0 0 0 0 W 15B19-0wc-6 0.069 s 3.57 0.00 0 0 0 0 W Frm wall, vnl ext, 3 0.065 s 5.40 0.48 0 0 0 0 G 2 glazing, clr low-e 0.300 s 24.93 30.13 0 0 0 0 D 11D0 0.390 s 32.41 7.25 0 0 0 0 W 15B19-0wc-6 0.069 w 3.57 0.00 0 0 0 0 W Frm wall, vnl ext, 3 0.065 w 5.40 0.48 0 0 0 0 G 2 glazing, clr low-e 0.300 w 24.93 47.13 0 0 0 0 C 16B-50ad 0.020 -1.66 0.84 0 0 0 0 F 20P-30v 0.035 -0.00 0.00 0 0 0 0 F 21A-28v 0.022 -1.83 0.00 0 0 0 0 F 21A-28v 0.022 -0.00 0.00 0 0 0 0 F 22B-10vpl 0.210 -17.45 0.00 0 0 0 0 6 c) AED excursion 34 Envelope loss/gain 382 147 12 a)Infiltration 121 11 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)503 158 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 503 158 15 Duct loads -0%0%0 0 Total room load 503 158 Air required (cfm)8 7 Job #: Neese Performed by Gene Miller for: Summett Services Mechanical Compliance Solutions 4181 Aschli lane Idaho Falls, ID 83406 Phone: 208-881-3243 gene.mechcompliancesolutions@gmail.com Scale: 1 : 130 Page 1 Ri ght-Sui te ® Uni ve rsal 202 2 22.0.04 RSU28163 2023-Jan-07 11:44:26 ...Services Astorga\Neese\Neese.rup N Main Mech M TR M Bath M WIC Master LaundryLiving Bedroom 2 WIC 2 J-J VanityJ - J Bath WIC 3 Bedroom 3 Kit/Din/Great Rm Pwdr 12 cfm 88 cfm 19 cfm92 cfm 8 cfm 24 cfm 44 cfm 15 cfm 35 cfm 91 cfm 91 cfm 92 cfm 92 cfm 92 cfm 611 cfm 95 cfm 14 cfm 31 cfm 83 cfm 279 cfm 92 cfm 92 cfm Sup Riser 14 " Ret Riser 16 " 99 cfm Job #: Neese Performed by Gene Miller for: Summett Services Mechanical Compliance Solutions 4181 Aschli lane Idaho Falls, ID 83406 Phone: 208-881-3243 gene.mechcompliancesolutions@gmail.com Scale: 1 : 130 Page 2 Ri ght-Sui te ® Uni ve rsal 202 2 22.0.04 RSU28163 2023-Jan-07 11:44:27 ...Services Astorga\Neese\Neese.rup N 2nd floor Open To Below Storage Bedroom 4 VanityBath Bedroom 5 Loft Bonus Office 78 cfm 78 cfm 79 cfm 18 cfm 94 cfm 94 cfm 127 cfm 127 cfm 103 cfm 103 cfm 50 cfm 155 cfm 188 cfm 152 cfm 18 cfm 255 cfm 206 cfm Sup Riser 14 " Ret Riser 16 " 10 " 6 " 6 " 8 " 10 " 8 " 8 " 6 " 8 " 8 " 8 " 8 " 6 " 6 "16 " 10 " 12 " 8 " 10 " 8 " 10 " 6 " Job #: Neese Performed by Gene Miller for: Summett Services Mechanical Compliance Solutions 4181 Aschli lane Idaho Falls, ID 83406 Phone: 208-881-3243 gene.mechcompliancesolutions@gmail.com Scale: 1 : 130 Page 3 Ri ght-Sui te ® Uni ve rsal 202 2 22.0.04 RSU28163 2023-Jan-07 11:44:27 ...Services Astorga\Neese\Neese.rup N Conditioned Crawl Cond Crawl 74 cfm 74 cfm Sup Riser 14 " Ret Riser 16 " 6 " 6 "6 " 6 " 6 "6 " 6 " 6 " 6 " 6 " 6 " 16 " 6 " 6 " 14 " 6 " 14 "28 x 8 10 " 14 " 6 "6 " 10 " 6 "6 "6 "6 " 6 " 6 " 6 "12 " 8 "10 " 20 x 8 10 x 8 Fresh air will be supplied with a pipe and damper 2023-Jan-07 11:44:02 Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 1 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N NeeseJob:Duct System Summary 01/06/2023Date:Entire House Gene MillerBy: L 65 Olympic Court Rex.Plan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Summett ServicesFor: CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0.41in H2O0.41 Available static pressure in H2O0.59in H2O0.59 Supply / return available pressure 0.306 / 0.284 in H2O in H2O0.306 / 0.284 Lowest friction rate in/100ft0.099in/100ft0.099 Actual air flow cfm1645cfm1225 Total effective length (TEL)ft594 2023-Jan-07 11:44:02 Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 2 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st4235.050.1VlFx0x06.00.10717181088hBath st2C200.060.8ShMt0x06.00.11743442735hBedroom 2 st2B155.071.5ShMt0x06.00.13595382075cBedroom 3 st5245.037.8VlFx0x08.00.10894302061cBedroom 4 st5235.042.8VlFx0x08.00.11094302061cBedroom 4-A st4225.057.9VlFx0x06.00.10879781727cBedroom 5 st5225.044.8VlFx0x08.00.113127622791cBonus st5A245.062.6VlFx0x08.00.099127622791cBonus-A st2C185.073.5ShMt0x06.00.1180744544hCond Crawl st1130.020.3ShMt0x06.00.2030744544hCond Crawl-A st2C195.064.8ShMt0x06.00.1183514767cJ - J Bath st2A155.030.5ShMt0x06.00.16592402025cKit/Din/Great Rm st2B175.061.5ShMt0x06.00.12992402025cKit/Din/Great Rm-A st2145.027.0ShMt0x06.00.17892402025cKit/Din/Great Rm-B st2A145.051.5ShMt0x06.00.15692402025cKit/Din/Great Rm-C st2A175.044.8ShMt0x06.00.13992402025cKit/Din/Great Rm-D st2A180.033.8ShMt0x06.00.14392402025cKit/Din/Great Rm-E st2135.012.0ShMt0x06.00.2083116673cLaundry st2B165.045.3ShMt0x06.00.14519241495hLiving st1160.04.8ShMt0x06.00.18688491925cM Bath st1150.012.5ShMt0x06.00.1887191193hM TR st2180.09.5ShMt0x06.00.161312732hM WIC st1165.029.5ShMt0x06.00.15791421989cMaster st1140.037.0ShMt0x06.00.17391421989cMaster-A st5A235.069.6VlFx0x08.00.100103592262cOffice st5A235.068.3VlFx0x08.00.101103592262cOffice-A st2A165.024.3ShMt0x06.00.16278503hPwdr st3190.041.7VlFx0x06.00.13278411699cStorage st3190.038.9VlFx0x06.00.13478411699cStorage-A st4245.040.6VlFx0x06.00.10710181112hVanity st2C165.062.5ShMt0x06.00.134515925hWIC 2 st2C175.074.8ShMt0x06.00.122414879hWIC 3 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 114 105 0.107 209 10.0 0x0 ShtMetl st3 st2B Peak AVF 264 293 0.117 536 10.0 0x0 ShtMetl st2A st2A Peak AVF 434 669 0.117 852 12.0 0x0 ShtMetl st2 st2 Peak AVF 502 795 0.117 744 14.0 0x0 ShtMetl st1 Peak AVF 226 276 0.157 507 10.0 0x0 ShtMetl st5 Peak AVF 301 649 0.099 826 12.0 0x0 ShtMetl st3 st2C Peak AVF 161 87 0.117 463 8.0 0x0 ShtMetl st2B st5A Peak AVF 180 334 0.099 612 10.0 0x0 ShtMetl st5 st3 Peak AVF 498 909 0.099 850 14.0 0x0 ShtMetl 2023-Jan-07 11:44:02 Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 8163 Page 3 ...tloss's\Summit Services Astorga\Neese\Neese.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb3 0x 1640 279 90.3 0.315 512 10.0 x0 0 ShMt rt1 rb1 0x 2900 611 204.0 0.139 571 14.0 x0 0 ShMt rt1A rb2 0x 500 26 201.0 0.141 257 6.0 x0 0 ShMt rt2A rb4 0x 730 83 286.0 0.099 421 6.0 x0 0 ShMt rt1B rb5 0x 520 99 242.0 0.117 504 6.0 x0 0 ShMt rt1B rb6 0x 970 155 220.1 0.129 444 8.0 x0 0 VlFx rt2A rb7 0x 740 188 126.1 0.225 539 8.0 x0 0 VlFx rt2 rb8 0x 1520 79 282.4 0.101 436 8.0 x0 0 VlFx rt2A rb9 0x 1390 255 172.3 0.165 467 10.0 x0 0 VlFx rt2 rb10 0x 1330 206 151.5 0.188 378 10.0 x0 0 VlFx rt2 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt2A Peak AVF 300 260 0.101 550 10.0 0x0 ShtMetl rt2 rt1 Peak AVF 580 1071 0.099 689 14.1 28x8 ShtMetl rt1A Peak AVF 416 792 0.099 713 12.4 20x8 ShtMetl rt1 rt1B Peak AVF 126 182 0.099 327 12.4 10x8 ShtMetl rt1A rt2 Peak AVF 645 909 0.101 651 16.0 0x0 ShtMetl