HomeMy WebLinkAboutANALYSIS REPORT - 23-00033 - 110 S 12th St - Cell TowerMaser Consulting 2000 Midlantic Drive Suite 100 Mt. Laurel, NJ 08054 856.797.0412 matthew.graubart@collierseng.com Post-Modification Antenna Mount Analysis Report and PMI Requirements Mount Fix SMART Tool Project #: 10172561 Maser Consulting Project #: 22995453A October 20, 2022 Site Information Site ID:273696-VZW / ERICKSON - Alt 1 Site Name:ERICKSON - Alt 1 Carrier Name:Verizon Wireless Address:110 South 12th Street Rexburg, Idaho 83460 Jefferson County Latitude:43.82345416° Longitude:-111.8207283° Structure Information Tower Type:Monopole Mount Type:12.50-Ft Platform FUZE ID # 16932340 Analysis Results Platform:85.9 % Pass w/ Modifications* *Antennas and equipment to be installed in compliance with PMI Requirements of this mount analysis. ***Contractor PMI Requirements: Included at the end of this MA report Available & Submitted via portal at https://pmi.vzwsmart.com For additional questions and support, please reach out to: pmisupport@colliersengineering.com Report Prepared By: David Anuka Mount Post-Modification Analysis Report (1) 12.50-Ft Platform October 20, 2022 Site ID: 273696-VZW / ERICKSON - Alt 1 Page | 2 Executive Summary: The objective of this report is to summarize the analysis results of the antenna support mount including the proposed modifications at the subject facility for the final wireless telecommunications configuration, per the applicable codes and standards. This analysis is inclusive of the mount structure only and does not address the structural capacity of the supporting structure. This mounting frame was not analyzed as an anchor attachment point for fall protection. All climbing activities are required to have a fall protection plan completed by a competent person. Sources of Information: Document Type Remarks Radio Frequency Data Sheet (RFDS)Verizon RFDS, Site ID: 3098879, dated August 11, 2022 Mount Mapping Report RKS Design & Engineering, LLC, Site #: VZW: 273696, dated September 4, 2022 Previous Mount Analysis Maser Consulting, Project #: 22995453A, dated October 6, 2022 Mount Modification Drawings Maser Consulting, Project #: 22995453A, dated October 20, 2022 Analysis Criteria: Codes and Standards:ANSI/TIA-222-H Wind Parameters:Basic Wind Speed (Ultimate 3-sec. Gust), VULT:105 mph Ice Wind Speed (3-sec. Gust):50 mph Design Ice Thickness:0.25 in Risk Category:II Exposure Category:C Topographic Category:1 Topographic Feature Considered:N/A Topographic Method:N/A Ground Elevation Factor, Ke:0.839 Seismic Parameters:SS:0.358 g S1:0.140 g Maintenance Parameters:Wind Speed (3-sec. Gust): 30 mph Maintenance Live Load, Lv:250 lbs. Maintenance Live Load, Lm:500 lbs. Analysis Software:RISA-3D (V17) Mount Post-Modification Analysis Report (1) 12.50-Ft Platform October 20, 2022 Site ID: 273696-VZW / ERICKSON - Alt 1 Page | 3 Final Loading Configuration: The following equipment has been considered for the analysis of the mount: Mount Elevation (ft) Equipment Elevation (ft) Quantity Manufacturer Model Status 3 Ericsson AIR 6449 6 JMA Wireless MX06FRO860-02 3 Ericsson 4449 3 Ericsson 8843 Added94.00 96.00 2 Raycap RHSDC-3315-PF-48 Retained It is acceptable to install up to any three (3) of the OVP model numbers listed below as required at any location other than the mount face without affecting the structural capacity of the mount. If OVP units are installed on the mount face, a mount re-analysis may be required unless replacing an existing OVP. Model Number Ports AKA RxxDC-3315-PF-48 6 OVP-6 RC3DC-3300-PF-48 6 OVP-6 DB-B1-6C-12AB-0Z 6 OVP-6 RxxDC-6627-PF-48 12 OVP-12 RCMDC-6627-PF-48 12 OVP-12 RVZDC-6627-PF-48 12 OVP-12 RRODC-6627-PF-48 12 OVP-12 Standard Conditions: 1. All engineering services are performed on the basis that the information provided to Maser Consulting and used in this analysis is current and correct. The existing equipment loading has been applied at locations determined from the supplied documentation. Any deviation from the loading locations specified in this report shall be communicated to Maser Consulting to verify deviation will not adversely impact the analysis. 2. Mounts are assumed to have been properly fabricated, installed and maintained in good condition, twist free and plumb in accordance with its original design and manufacturer’s specifications. Obvious safety and structural issues/deficiencies noticed at the time of the mount mapping and reported in the Mount Mapping Report are assumed to be corrected and documented as part of the PMI process and are not considered in the mount analysis. The mount analysis and the mount mapping are not a condition assessment of the mount. Proper maintenance and condition assessments are still required post analysis. 3. For mount analyses completed from other data sources (including new replacement mounts) and not specifically mapped in accordance with the NSTD-446 Standard, the mounts are assumed to have been properly fabricated, installed and maintained in good condition, twist free and plumb in accordance with its original design and manufacturer’s specifications. 4. All member connections are assumed to have been designed to meet or exceed the load carrying capacity of the connected member unless otherwise specified in this report. 5. The mount was checked up to, and including, the bolts that fasten it to the mount collar/attachment and threaded rod connections in collar members if applicable. Local deformation and interaction between the mount collar/attachment and the supporting tower structure are outside the scope of this analysis. Mount Post-Modification Analysis Report (1) 12.50-Ft Platform October 20, 2022 Site ID: 273696-VZW / ERICKSON - Alt 1 Page | 4 6. All services are performed, results obtained, and recommendations made in accordance with generally accepted engineering principles and practices. Maser Consulting is not responsible for the conclusion, opinions, and recommendations made by others based on the information supplied. 7. Structural Steel Grades have been assumed as follows, if applicable, unless otherwise noted in this analysis: o Channel, Solid Round, Angle, Plate ASTM A36 (Gr. 36) o HSS (Rectangular) ASTM 500 (Gr. B-46) o Pipe ASTM A53 (Gr. B-35) o Threaded Rod F1554 (Gr. 36) o Bolts ASTM A325 8. Any mount modifications listed under Sources of Information are assumed to have been installed per the design specifications. Discrepancies between in-field conditions and the assumptions listed above may render this analysis invalid unless explicitly approved by Maser Consulting. Analysis Results: Component Utilization %Pass/Fail Standoff Horizontal 30.4 %Pass Connector Plate 39.0 %Pass Middle Face Horizontal 45.4 %Pass Face Horizontal 85.9 %Pass Support Rail 33.0 %Pass Bottom Corner Plate 59.5 %Pass Cross Brace 30.9 %Pass Mount Pipe 16.9 %Pass MOD Support Rail Brace 8.6 %Pass Connection Check 81.0 %Pass Structure Rating – (Controlling Utilization of all Components)85.9% Mount Steel (EPA)a per ANSI/TIA-222-H Section 2.6.11.2: Mount Pipes Excluded Mount Pipes Included Ice Thickness (In) Front (EPA)a (Sq. Ft.) Side (EPA)a (Sq. Ft.) Front (EPA)a (Sq. Ft.) Side (EPA)a (Sq. Ft.) 0 25.3 25.2 46.5 46.5 0.5 33.8 33.8 64.1 64.1 1 41.6 41.6 80.9 80.9 Notes: - (EPA)a values listed above may be used in the absence of more precise information - (EPA)a values in the table above include 3 sector(s). - Ka factors included in (EPA)a calculations Mount Post-Modification Analysis Report (1) 12.50-Ft Platform October 20, 2022 Site ID: 273696-VZW / ERICKSON - Alt 1 Page | 5 Requirements: The existing mount will be SUFFICIENT for the final loading configuration (Attachment 2) after the modifications detailed in Attachment 3 are successfully completed. ANSI/ASSP rigging plan review services compliant with the requirements of ANSI/TIA 322 are available for a Construction Class IV site or other, if required. Separate review fees will apply. Attachments: 1.Contractor Required PMI Report Deliverables 2. Antenna Placement Diagrams 3. Mount Modification Drawings 4. Mount Photos 5. Mount Mapping Report (for reference only) 6. Analysis Calculations Mount Desktop – Post Modification Inspection (PMI) Report Requirements Documents & Photos Required from Contractor – Mount Modification Electronic pdf version of this can be downloaded at https://pmi.vzwsmart.com For additional questions and support, please reach out to pmisupport@colliersengineering.com __________________________________________________________________________________________________________________________________________________________________________________________________________ PSLC #: 273696 SMART Project #: 10172561 Fuze Project ID: 16932340 Purpose – to upload the proper documentation to the SMART Tool in order to allow the SMART Tool engineering vendor to complete the required Mount Desktop review of the Post Modification Inspection Report. Contractor is responsible for making certain the photos provided as noted below provide confirmation that the modification was completed in accordance with the modification drawings. Contractor shall relay any data that can impact the performance of the mount or the mount modification, this includes safety issues. Base Requirements: If installation of the modification will cause damage to the structure, the climbing facility, or safety climb if present or any installed system, SMART Tool vendor to be notified prior to install. Any special photos outside of the standard requirements will be indicated on the drawings. Provide “as built drawings” showing contractor’s name, preparer’s signature, and date. Any deviations from the drawings (proposed modification) shall be shown. NOTE: If loading is different than what is conveyed in the post-modification passing mount analysis (MA) contact the SMART Tool vendor immediately. Each photo shall be time and date stamped. Photos should be high resolution. Contractor shall ensure that the safety climb wire rope is not adversely impacted by the install of the modification components. This may involve the install of wire rope guides, or other items to protect the wire rope. If there is conflict, contact the SMART Tool engineer for recommendations. The PMI can be accessed at the following portal: https://pmi.vzwsmart.com Photo Requirements: Photos taken at ground level o Photo of Gate Signs showing the tower owner, site name, and number. o Overall tower structure after installation of the modifications. o Photos of the mount after installation of the modifications; if the mounts are at different rad elevations, pictures must be provided for all elevations that the modifications were installed Photos taken at Mount Elevation o Photos showing the safety climb wire rope above and below the mount prior to modification. o Photos showing the climbing facility and safety climb if present. o Photos showing each individual sector after installation of modifications. Each entire sector must be in one photo to show the interconnection of members. These photos shall also certify that the placement and geometry of the equipment on the mount is as depicted in the antenna placement diagram in this form. o Photos that show the model number of each antenna and piece of equipment installed per sector. o Photos of each installed modification per the modification drawings; pictures shall also include connection hardware (U-bolts, bolts, nuts, all-threaded rods, etc.) o Photos showing the distances (relative distance between collars) of the installed modifications from the appropriate reference locations shown in the modification drawings. o Photos showing the installed modifications onto the tower (i.e. ring/collar mounts, tie- backs, V-bracing kits, etc.); if the existing mount elevation needs to be changed according to the modification drawings, an elevation measurement shall be provided before the elevation change. Material Certification: Materials utilized must be as per specification on the drawings or the equivalent as validated by the SMART Tool vendor. o If the materials are as specified on the drawings The contractor shall provide the packing list, or the materials certifications for the materials utilized to perform the mount modification Commscope, Metrosite, Perfect Vision, Sabre, and Site Pro have all agreed to support Verizon vendors with the necessary material certifications o If seeking permission to use an equivalent It is required that the SMART Tool engineering vendor approval of such is included in the contractor submission package. There may be an additional charge for approval if the equivalent submission doesn’t meet specifications as prescribed in the drawings. ☐ All hardware has been properly installed, and the existing hardware was inspected. ☐ The material utilized was as specified on the SMART Tool engineering vendor Mount Modification Drawings and included in the material certification folder is a packing list or invoice for these materials. OR ☐ The material utilized was approved by a SMART Tool engineering vendor as an “equivalent” and this approval is included as part of the contractor submission. Antenna & Equipment Placement and Geometry Confirmation: ☐ The contractor certifies that the photos support and the equipment on the mount is as depicted on the sketch and table included in this form and with the mount analysis provided. OR ☐ The contractor notes that the equipment on the mount is not in accordance with the sketch and has noted the differences below and provided photo documentation of any alterations. Comments: Was the mount modification completed in conjunction with the equipment change / installation? ☐ Yes ☐ No Special Instructions / Validation as required from the MA or Mod Drawings: Issue: Contractor shall inspect safety climb, reattach and re-tension the rope as necessary. Contractor shall provide photos of final safety guide climb condition as part of PMI documents. Contact EOR if additional guidance is required. Response: Special Instruction Confirmation: ☐ The contractor has read and acknowledges the above special instructions. Comments: Contractor certifies that the climbing facility / safety climb was not damaged prior to starting work: ☐ Yes ☐ No Contractor certifies no new damage created during the current installation: ☐ Yes ☐ No Contractor to certify the condition of the safety climb and verify no damage when leaving the site: ☐ Safety Climb in Good Condition ☐ Safety Climb Damaged Comments: Certifying Individual: Company: Employee Name: Contact Phone: Email: Date: Structure: 273696-VZW - ERICKSON - Alt 1 Sector: Structure Type: Mount Elev: A Monopole 10172561 94.00 10/18/2022 Page: 1 Plan View Front View - Looking at Structure Copyright 2019 by Tower Engineering Solutions, LLC. All Rights Reserved 12345 A2 A2 R3 R4 A5 A1 Structure Height Width H Dist Pipe Pipe Ant C. Ant Ant Ref#Model (in)(in)Frm L.#Pos V Pos Frm T.H Off Status Validation A2 MX06FRO860-02 95.9 15.4 97 2 a Front 48 -9 Added A2 MX06FRO860-02 95.9 15.4 97 2 b Front 48 9 Added R3 4449 15 13.2 97 2 a Behind 12 -8 Added R4 8843 15 13.2 97 2 a Behind 12 8 Added A5 RHSDC-3315-PF-48 29.5 16.5 76 3 a Behind 6 0 Retained 09/04/2022 A1 AIR 6449 30.8 16.1 12.25 5 a Front 48 0 Added Structure: 273696-VZW - ERICKSON - Alt 1 Sector: Structure Type: Mount Elev: B Monopole 10172561 94.00 10/18/2022 Page: 2 Plan View Front View - Looking at Structure Copyright 2019 by Tower Engineering Solutions, LLC. All Rights Reserved 12345 A2 A2 R3 R4 A5 A1 Structure Height Width H Dist Pipe Pipe Ant C. Ant Ant Ref#Model (in)(in)Frm L.#Pos V Pos Frm T.H Off Status Validation A2 MX06FRO860-02 95.9 15.4 97 2 a Front 48 -9 Added A2 MX06FRO860-02 95.9 15.4 97 2 b Front 48 9 Added R3 4449 15 13.2 97 2 a Behind 12 -8 Added R4 8843 15 13.2 97 2 a Behind 12 8 Added A5 RHSDC-3315-PF-48 29.5 16.5 76 3 a Behind 6 0 Retained 09/04/2022 A1 AIR 6449 30.8 16.1 12.25 5 a Front 48 0 Added Structure: 273696-VZW - ERICKSON - Alt 1 Sector: Structure Type: Mount Elev: C Monopole 10172561 94.00 10/18/2022 Page: 3 Plan View Front View - Looking at Structure Copyright 2019 by Tower Engineering Solutions, LLC. All Rights Reserved 12345 A2 A2 R3 R4 A1 Structure Height Width H Dist Pipe Pipe Ant C. Ant Ant Ref#Model (in)(in)Frm L.#Pos V Pos Frm T.H Off Status Validation A2 MX06FRO860-02 95.9 15.4 97 2 a Front 48 -9 Added A2 MX06FRO860-02 95.9 15.4 97 2 b Front 48 9 Added R3 4449 15 13.2 97 2 a Behind 12 -8 Added R4 8843 15 13.2 97 2 a Behind 12 8 Added A1 AIR 6449 30.8 16.1 12.25 5 a Front 48 0 Added I . D . C . O . A . # : 4 1 5 4 A L L S T A T E S R E Q U I R E N O T I F I C A T I O N O F E X C A V A T O R S , D E S I G N E R S , O R A N Y P E R S O N P R E P A R I N G T O D I S T U R B T H E E A R T H ' S S U R F A C E A N Y W H E R E I N A N Y S T A T E S I T E N A M E : N O T E : D O N O T S C A L E D R A W I N G S F O R C O N S T R U C T I O N . I AM RESPONSIBLE FOR DETERMINING THAT THE ARCHITECTURALDESIGN INCLUDED IN THIS APPLICATION ARE IN COMPLIANCE WITHALL LAWS AND REGULATIONS OF THE DISTRICT OF COLUMBIA. I HAVEPERSONALLY PREPARED, OR DIRECTLY SUPERVISED THE DEVELOPMENTOF THE ENGINEERING DESIGNS INCLUDED IN THIS APPLICATION. S C A L E : K n o w w h a t ' s b e l o w . b e f o r e y o u d i g . C a l l R S H E E T T I T L E : D R A W N B Y P R O T E C T Y O U R S E L F I T I S A V I O L A T I O N O F L A W F O R A N Y P E R S O N , U N L E S S T H E Y A R E A C T I N G U N D E R T H E D I R E C T I O N O F T H E R E S P O N S I B L E L I C E N S E D P R O F E S S I O N A L E N G I N E E R , T O A L T E R T H I S D O C U M E N T . S H E E T N U M B E R : \AcPublish_21556\Template.Mount MOD.dwg\ST-1 By: DAVID.ANUKA R E V D A T E D E S C R I P T I O N C H E C K E D B Y F O R S T A T E S P E C I F I C D I R E C T P H O N E N U M B E R S V I S I T : W W W . C A L L 8 1 1 . C O M J O B N U M B E R : C o p y r i g h t © 2 0 2 2 . C o l l i e r s E n g i n e e r i n g & D e s i g n A l l R i g h t s R e s e r v e d . T h i s d r a w i n g a n d a l l t h e i n f o r m a t i o n c o n t a i n e d h e r e i n i s a u t h o r i z e d f o r u s e o n l y b y t h e p a r t y f o r w h o m t h e s e r v i c e s w e r e c o n t r a c t e d o r t o w h o m i t i s c e r t i f i e d . T h i s d r a w i n g m a y n o t b e c o p i e d , r e u s e d , d i s c l o s e d , d i s t r i b u t e d o r r e l i e d u p o n f o r a n y o t h e r p u r p o s e w i t h o u t t h e e x p r e s s w r i t t e n c o n s e n t o f C o l l i e r s E n g i n e e r i n g & D e s i g n . w w w . c o l l i e r s e n g i n e e r i n g . c o m C O N S U L T I N G E n g i n e e r i n g & D e s i g n E n g i n e e r i n g & D e s i g n P h o n e : E R I C K S O N - A L T 1 2 7 3 6 9 6 A S S H O W N 0 . . .. M T . L A U R E L 2 0 0 0 M i d l a n t i c D r i v e , S u i t e 1 0 0 M t . L a u r e l , N J 0 8 0 5 4 8 5 6 . 7 9 7 . 0 4 1 2 C O L L I E R S E N G I N E E R I N G & D E S I G N , I N C . D O I N G B U S I N E S S A S M A S E R C O N S U L T I N G 2 2 9 9 5 4 5 3 A . . . ... 1 1 0 S O U T H 1 2 T H S T R E E T R E X B U R G , I D 8 3 4 6 0 J E F F E R S O N C O U N T Y I S S U E D F O R C O N S T R U C T I O N D A . . . . . ...... 1 0 / 2 0 / 2 2 J P L . . . . . ......... _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ D o i n g B u s i n e s s a s C O L L I E R S E N G I N E E R I N G & D E S I G N , I N C . COPYRIGHT ©COLLIERS ENGINEERING & DESIGNALL RIGHTS RESERVEDTHIS DRAWING AND ALL THE INFORMATION CONTAINED HEREIN ISAUTHORIZED FOR USE ONLY BY THE PARTY FOR WHOM THE WORKWAS CONTRACTED OR TO WHOM IT IS CERTIFIED. THIS DRAWINGMAY NOT BE COPIED, REUSED, DISCLOSED, DISTRIBUTED OR RELIEDUPON FOR ANY OTHER PURPOSE WITHOUT THE EXPRESS WRITTENCONSENT OF COLLIERS ENGINEERING & DESIGN.MO U N T M O D I F I C A T I O N D R A W I N G S E X I S T I N G 1 2 . 5 0 ' P L A T F O R M T I T L E S H E E T S T - 1 2022 TOW E R O W N E R : V E R I Z O N W I R E L E S S TOWER O W N E R S I T E N U M B E R : I D 6 E R I C K S O N CARRI E R S I T E N A M E : E R I C K S O N - A L T 1 C A R R I E R S I T E N U M B E R : 2 7 3 6 9 6 F U Z E I D : 1 6 9 3 2 3 4 0 1 1 0 S O U T H 1 2 T H S T R E E T R E X B U R G , I D 8 3 4 6 0 J E F F E R S O N C O U N T Y L A T I T U D E : 4 3 . 8 2 3 4 5 4 1 6 ° N L O N G I T U D E : 1 1 1 . 8 2 0 7 2 8 3 ° W C O N T R A C T O R P M I R E Q U I R E M E N T S P M I L O C A T I O N : H T T P S : / / P M I . V Z W S M A R T . C O M S M A R T T O O L P R O J E C T # : 1 0 1 7 2 5 6 1 V Z W L O C A T I O N C O D E ( P S L C ) : 2 7 3 6 9 6 A N A L Y S I S D A T E : 1 0 / 2 0 / 2 0 2 2 P M I R E Q U I R E M E N T S E M B E D D E D W I T H I N M O U N T M O D I F I C A T I O N R E P O R T D E S I G N C R I T E R I A WIND LOAD S BASIC WIND S P E E D ( 3 S E C O N D G U S T ) , V = 1 0 5 M P H EXPOSURE CA T E G O R Y C TOPOGRAPHI C C O N S I D E R E D N O MEAN BASE EL E V A T I O N ( A M S L ) = 4 8 5 3 . 3 3 ' ICE LOADSICE WIND SPE E D ( 3 S E C O N D G U S T ) , V = 5 0 M P H ICE THICKNES S = 0 . 2 5 I N SEISMIC LOA D S SEISMIC DESIG N C A T E G O R Y D SHORT TERM M C E R G R O U N D M O T I O N , S S = . 3 5 8 LONG TERM M C E R G R O U N D M O T I O N , S 1 = . 1 4 0 S H E E T I N D E X S H E E T D E S C R I P T I O N S T - 1 T I T L E S H E E T S B O M - 1 B I L L O F M A T E R I A L S S G N - 1 G E N E R A L N O T E S S C F - 1 S S - 1 M O D I F I C A T I O N D E T A I L S S S - 2 C L I M B I N G F A C I L I T Y D E T A I L M O U N T P H O T O S S P E C I F I C A T I O N S H E E T S P R O J E C T I N F O R M A T I O N A P P L I C A N T / L E S S E E C O M P A N Y : V E R I Z O N W I R E L E S S C L I E N T R E P R E S E N T A T I V E C O M P A N Y : V E R I Z O N W I R E L E S S P R O J E C T M A N A G E R C O M P A N Y : C O L L I E R S E N G I N E E R I N G & D E S I G N C O N T A C T : M A T T H E W G R A U B A R T P H O N E : 8 5 6 . 7 9 7 . 0 4 1 2 E - M A I L : M A T T H E W . G R A U B A R T @ C O L L I E R S E N G I N E E R I N G . C O M I . D . C . O . A . # : 4 1 5 4 A L L S T A T E S R E Q U I R E N O T I F I C A T I O N O F E X C A V A T O R S , D E S I G N E R S , O R A N Y P E R S O N P R E P A R I N G T O D I S T U R B T H E E A R T H ' S S U R F A C E A N Y W H E R E I N A N Y S T A T E S I T E N A M E : I AM RESPONSIBLE FOR DETERMINING THAT THE ARCHITECTURALDESIGN INCLUDED IN THIS APPLICATION ARE IN COMPLIANCE WITHALL LAWS AND REGULATIONS OF THE DISTRICT OF COLUMBIA. I HAVEPERSONALLY PREPARED, OR DIRECTLY SUPERVISED THE DEVELOPMENTOF THE ENGINEERING DESIGNS INCLUDED IN THIS APPLICATION. S C A L E : K n o w w h a t ' s b e l o w . b e f o r e y o u d i g . C a l l R S H E E T T I T L E : D R A W N B Y P R O T E C T Y O U R S E L F I T I S A V I O L A T I O N O F L A W F O R A N Y P E R S O N , U N L E S S T H E Y A R E A C T I N G U N D E R T H E D I R E C T I O N O F T H E R E S P O N S I B L E L I C E N S E D P R O F E S S I O N A L E N G I N E E R , T O A L T E R T H I S D O C U M E N T . S H E E T N U M B E R : \AcPublish_21556\Template.Mount MOD.dwg\SBOM-1 By: DAVID.ANUKA R E V D A T E D E S C R I P T I O N C H E C K E D B Y F O R S T A T E S P E C I F I C D I R E C T P H O N E N U M B E R S V I S I T : W W W . C A L L 8 1 1 . C O M J O B N U M B E R : C o p y r i g h t © 2 0 2 2 . C o l l i e r s E n g i n e e r i n g & D e s i g n A l l R i g h t s R e s e r v e d . T h i s d r a w i n g a n d a l l t h e i n f o r m a t i o n c o n t a i n e d h e r e i n i s a u t h o r i z e d f o r u s e o n l y b y t h e p a r t y f o r w h o m t h e s e r v i c e s w e r e c o n t r a c t e d o r t o w h o m i t i s c e r t i f i e d . T h i s d r a w i n g m a y n o t b e c o p i e d , r e u s e d , d i s c l o s e d , d i s t r i b u t e d o r r e l i e d u p o n f o r a n y o t h e r p u r p o s e w i t h o u t t h e e x p r e s s w r i t t e n c o n s e n t o f C o l l i e r s E n g i n e e r i n g & D e s i g n . w w w . c o l l i e r s e n g i n e e r i n g . c o m C O N S U L T I N G E n g i n e e r i n g & D e s i g n E n g i n e e r i n g & D e s i g n P h o n e : E R I C K S O N - A L T 1 2 7 3 6 9 6 A S S H O W N 0 . . .. M T . L A U R E L 2 0 0 0 M i d l a n t i c D r i v e , S u i t e 1 0 0 M t . L a u r e l , N J 0 8 0 5 4 8 5 6 . 7 9 7 . 0 4 1 2 C O L L I E R S E N G I N E E R I N G & D E S I G N , I N C . D O I N G B U S I N E S S A S M A S E R C O N S U L T I N G 2 2 9 9 5 4 5 3 A . . . ... 1 1 0 S O U T H 1 2 T H S T R E E T R E X B U R G , I D 8 3 4 6 0 J E F F E R S O N C O U N T Y I S S U E D F O R C O N S T R U C T I O N D A . . . . . ...... 1 0 / 2 0 / 2 2 J P L . . . . . ......... _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ D o i n g B u s i n e s s a s C O L L I E R S E N G I N E E R I N G & D E S I G N , I N C . S B O M - 1 B I L L O F M A T E R I A L S NOTES:1.THE MANUFACTURERS LISTED ARE THE APPROVED VENDORS FOR THE VZW MOUNT KITS.EACH MANUFACTURER WILL BE AWARE OF WHICH KITS HAVE BEEN THROUGH THE VZWAPPROVAL PROCESS AND THEY ARE IN TURN APPROVED TO SELL. PLEASE NOTE THAT THEMATERIAL UTILIZED ON THE MOUNT MODIFICATIONS WILL BE REVIEWED AS A PART OF THEDESKTOP PMI COMPLETED BY THE SMART TOOL VENDOR. IT WILL BE REQUIRED THAT THEVZW KITS SPECIFIED ARE UTILIZED IN THE MODIFICATIONS.2.ALL MATERIALS REQUIRED FOR THE DESIGNED MODIFICATIONS BUT NOT LISTED IN THISSHEET ARE ASSUMED TO BE PROVIDED BY THE CONTRACTOR.COMMSCOPECONTACTSALVADOR ANGUIANOPHONE(817) 304-7492EMAILSALVADOR.ANGUIANO@COMMSCOPE.COMWEBSITEWWW.COMMSCOPE.COMMETROSITE FABRICATORS, LLCCONTACTKENT RAMEYPHONE(706) 335-7045 (O), (706) 982-9788 (M)EMAILKENT@METROSITELLC.COMWEBSITEMETROSITEFABRICATORS.COM PERFECTV I S I O N CONTACTWIRELESS SALESPHONE(844) 887-6723EMAILWWW.PERFECT- V I S I O N . C O M WEBSITEWIRELESSSALES@ P E R F E C T - V I S I O N . C O M SABRE INDUST R I E S , I N C . CONTACTANGIE WELCHPHONE(866) 428-6937EMAILAKWELCH@SAB R E I N D U S T R I E S . C O M WEBSITEWWW.SABRESITE S O L U T I O N S . C O M S I T E P R O 1 C O N T A C T P A U L A B O S W E L L P H O N E ( 9 7 2 ) 2 3 6 - 9 8 4 3 E M A I L P A U L A . B O S W E L L @ V A L M O N T . C O M W E B S I T E W W W . S I T E P R O 1 . C O M N E W A V E C O N T A C T N E W A V E S A L E S T E A M P H O N E ( 9 7 1 ) 2 3 9 - 4 7 6 2 E M A I L S A L E S @ N E W A V E T C . C O M W E B S I T E W W W . N E W A V E T C . C O M B E T T E R M E T A L , L L C C O N T A C T D A V I D S T A N S B E R R Y P H O N E ( 6 1 5 ) 5 3 5 - 0 9 9 0 ( O ) , ( 6 1 5 ) 6 3 1 - 2 5 2 0 ( M ) E M A I L D L S @ B E T T E R M E T A L . C O M W E B S I T E W W W . B E T T E R M E T A L . C O M B I L L O F M A T E R I A L S S E C T I O N 1 - V Z W S M A R T K I T S QUANTITYMANUFACTURERPART NUMBERDESCRIPTIO N N O T E S U N I T W E I G H T ( L B S . ) W E I G H T ( L B S . ) 3VZWSMARTVZWSMART-PLK10SUPPORT RAIL BRAC I N G K I T C O N T R A C T O R T O V E R I F Y T H E L E N G T H R E Q U I R E D A N D T R I M A S N E C E S S A R Y I N A C C O R D A N C E W I T H T H E ' S T R U C T U R A L S T E E L ' N O T E S O N S H E E T S G N - 1 . 1 1 6 3 4 8                                                                                 S E C T I O N 2 - O T H E R R E Q U I R E D P A R T S QUANTITYMANUFACTURERPART NUMBERDESCRIPTIO N N O T E S U N I T W E I G H T ( L B S . ) W E I G H T ( L B S . )                                                                                                                          V Z W S M A R T K I T S - A P P R O V E D V E N D O R S S E C T I O N 3 - R E Q U I R E D S A F E T Y C L I M B P A R T S QUANTITYMANUFACTURERPART NUMBERDESCRIPTIO N N O T E S U N I T W E I G H T ( L B S . ) W E I G H T ( L B S . ) T O T A L : 3 4 8 I . D . C . O . A . # : 4 1 5 4 A L L S T A T E S R E Q U I R E N O T I F I C A T I O N O F E X C A V A T O R S , D E S I G N E R S , O R A N Y P E R S O N P R E P A R I N G T O D I S T U R B T H E E A R T H ' S S U R F A C E A N Y W H E R E I N A N Y S T A T E S I T E N A M E : N O T E : D O N O T S C A L E D R A W I N G S F O R C O N S T R U C T I O N . I AM RESPONSIBLE FOR DETERMINING THAT THE ARCHITECTURALDESIGN INCLUDED IN THIS APPLICATION ARE IN COMPLIANCE WITHALL LAWS AND REGULATIONS OF THE DISTRICT OF COLUMBIA. I HAVEPERSONALLY PREPARED, OR DIRECTLY SUPERVISED THE DEVELOPMENTOF THE ENGINEERING DESIGNS INCLUDED IN THIS APPLICATION. S C A L E : K n o w w h a t ' s b e l o w . b e f o r e y o u d i g . C a l l R S H E E T T I T L E : D R A W N B Y P R O T E C T Y O U R S E L F I T I S A V I O L A T I O N O F L A W F O R A N Y P E R S O N , U N L E S S T H E Y A R E A C T I N G U N D E R T H E D I R E C T I O N O F T H E R E S P O N S I B L E L I C E N S E D P R O F E S S I O N A L E N G I N E E R , T O A L T E R T H I S D O C U M E N T . S H E E T N U M B E R : \AcPublish_21556\Template.Mount MOD.dwg\SGN-1 By: DAVID.ANUKA R E V D A T E D E S C R I P T I O N C H E C K E D B Y F O R S T A T E S P E C I F I C D I R E C T P H O N E N U M B E R S V I S I T : W W W . C A L L 8 1 1 . C O M J O B N U M B E R : C o p y r i g h t © 2 0 2 2 . C o l l i e r s E n g i n e e r i n g & D e s i g n A l l R i g h t s R e s e r v e d . T h i s d r a w i n g a n d a l l t h e i n f o r m a t i o n c o n t a i n e d h e r e i n i s a u t h o r i z e d f o r u s e o n l y b y t h e p a r t y f o r w h o m t h e s e r v i c e s w e r e c o n t r a c t e d o r t o w h o m i t i s c e r t i f i e d . T h i s d r a w i n g m a y n o t b e c o p i e d , r e u s e d , d i s c l o s e d , d i s t r i b u t e d o r r e l i e d u p o n f o r a n y o t h e r p u r p o s e w i t h o u t t h e e x p r e s s w r i t t e n c o n s e n t o f C o l l i e r s E n g i n e e r i n g & D e s i g n . w w w . c o l l i e r s e n g i n e e r i n g . c o m C O N S U L T I N G E n g i n e e r i n g & D e s i g n E n g i n e e r i n g & D e s i g n P h o n e : E R I C K S O N - A L T 1 2 7 3 6 9 6 A S S H O W N 0 . . .. M T . L A U R E L 2 0 0 0 M i d l a n t i c D r i v e , S u i t e 1 0 0 M t . L a u r e l , N J 0 8 0 5 4 8 5 6 . 7 9 7 . 0 4 1 2 C O L L I E R S E N G I N E E R I N G & D E S I G N , I N C . D O I N G B U S I N E S S A S M A S E R C O N S U L T I N G 2 2 9 9 5 4 5 3 A . . . ... 1 1 0 S O U T H 1 2 T H S T R E E T R E X B U R G , I D 8 3 4 6 0 J E F F E R S O N C O U N T Y I S S U E D F O R C O N S T R U C T I O N D A . . . . . ...... 1 0 / 2 0 / 2 2 J P L . . . . . ......... _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ D o i n g B u s i n e s s a s C O L L I E R S E N G I N E E R I N G & D E S I G N , I N C . S G N - 1 M O D I F I C A T I O N N O T E S GENERAL NOTES1.THESE MODIFICATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH THEGOVERNING PROVISIONS OF THE TELECOMMUNICATIONS INDUSTRYSTANDARD TIA-222-H. MATERIALS AND SERVICES PROVIDED BY THECONTRACTOR SHALL CONFORM TO THE ABOVE MENTIONED CODES.2.CONTRACTOR SHALL TAKE ALL PRECAUTIONS NECESSARY TO PREVENTDAMAGE TO EXISTING STRUCTURES. ANY DAMAGE TO EXISTINGSTRUCTURES AS A RESULT OF THE CONTRACTOR'S WORK OR FROMDAMAGE DUE TO OTHER CAUSES SHALL BE REPAIRED AT THECONTRACTOR'S EXPENSE TO THE SATISFACTION OF THE OWNER.3.CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONSBEFORE BEGINNING WORK, ORDERING MATERIAL, AND PREPARING OF SHOPDRAWINGS. ANY DISCREPANCIES BETWEEN FIELD CONDITIONS AND THECONTRACT DOCUMENTS SHALL BE BROUGHT TO THE IMMEDIATEATTENTION OF THE ENGINEER. IF THE CONTRACTOR DISCOVERS ANYEXISTING CONDITIONS THAT ARE NOT REPRESENTED ON THESE DRAWINGS,OR ANY CONDITIONS THAT WOULD INTERFERE WITH THE INSTALLATIONOF THE MODIFICATIONS, NOTIFY THE ENGINEER IMMEDIATELY.4.IT IS ASSUMED THAT ANY STRUCTURAL MODIFICATION WORK SPECIFIED ONTHESE PLANS WILL BE ACCOMPLISHED BY KNOWLEDGEABLE WORKMENWITH TOWER CONSTRUCTION EXPERIENCE.5.THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND SHALL BESOLELY RESPONSIBLE FOR ALL CONSTRUCTION METHODS, MEANS,TECHNIQUES, SEQUENCES, AND PROCEDURES.6.ALL CONSTRUCTION MEANS AND METHODS; INCLUDING BUT NOT LIMITEDTO, ERECTION PLANS, RIGGING PLANS, CLIMBING PLANS, AND RESCUE PLANSSHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR RESPONSIBLEFOR THE EXECUTION OF THE WORK CONTAINED HEREIN AND SHALL MEETANSI/TIA-322 (LATEST EDITION), OSHA, AND GENERAL INDUSTRYSTANDARDS.  ALL RIGGING PLANS SHALL ADHERE TO ANSI/TIA-322 (LATESTEDITION) INCLUDING THE REQUIRED INVOLVEMENT OF A QUALIFIEDENGINEER FOR CLASS IV CONSTRUCTION.7.THE CONTRACTOR IS SOLELY RESPONSIBLE FOR INITIATING, MAINTAINING,AND SUPERVISING ALL SAFETY PROGRAMS IN ACCORDANCE WITHAPPLICABLE SAFETY CODES.8.WORK SHALL ONLY BE PERFORMED DURING CALM DRY DAYS (WINDS LESSTHAN 30-MPH). THE STRUCTURE SHOWN ON THE DRAWINGS ISSTRUCTURALLY SOUND ONLY IN THE COMPLETED FORM. THECONTRACTOR SHALL BE RESPONSIBLE FOR THE STRENGTH AND STABILITYOF THE STRUCTURE DURING ERECTION. CONTRACTOR SHALL PROVIDETEMPORARY SUPPORT, SHORING, BRACING AND ANY OTHER STRUCTURALSYSTEMS AS REQUIRED TO RESIST ALL FORCES THAT MAY OCCUR DURINGHANDLING AND ERECTION UNTIL THE STRUCTURE IS FULLY COMPLETED.TEMPORARY SUPPORTS, BRACING AND OTHER STRUCTURAL SYSTEMSREQUIRED DURING CONSTRUCTION SHALL REMAIN THE CONTRACTOR'SPROPERTY AFTER THEIR USE.9.ALL INSTALLATIONS PERFORMED ON THIS STRUCTURE SHALL BE COMPLETEDIN ACCORDANCE WITH THE GOVERNING PROVISIONS OF THE STANDARDFOR INSTALLATION, ALTERATION AND MAINTENANCE OF ANTENNASUPPORTING STRUCTURES AND ANTENNAS, ANSI/TIA-322.10.CONTRACTOR SHALL SECURE SITE BACK TO EXISTING CONDITION UNDERSUPERVISION OF OWNER. ALL FENCE, STONE, GEOFABRIC, GROUNDING,AND SURROUNDING GRADE SHALL BE REPLACED AND REPAIRED ASREQUIRED TO ACHIEVE OWNER APPROVAL. POSITIVE DRAINAGE AWAYFROM TOWER SITE SHALL BE MAINTAINED.11.CONNECTIONS BETWEEN ITEMS SUPPORTED BY THE STRUCTURE AND THESTRUCTURE NOT SPECIFICALLY DETAILED IN THE CONTRACT DOCUMENTSARE THE RESPONSIBILITY OF THE CONTRACTOR. SUCH CONNECTIONSSHALL BE DESIGNED, COORDINATED AND INSPECTED BY A PROFESSIONALSTRUCTURAL ENGINEER LICENSED IN THE STATE OF THE PROJECT. SUBMITSIGNED AND SEALED CALCULATIONS DURING SHOP DRAWING REVIEW.12. DO NOT SCALE DRAWINGS.13. DO NOT USE THESE DRAWINGS FOR ANY OTHER SITE.14.ALL MATERIAL UTILIZED FOR THIS PROJECT MUST BE NEW AND FREE OF ANYDEFECTS. ANY MATERIAL SUBSTITUTIONS, INCLUDING BUT NOT LIMITED TOALTERED SIZE AND/OR STRENGTHS, MUST BE APPROVED BY THE OWNERAND ENGINEER IN WRITING.15.THE MOUNT UNDER NO CIRCUMSTANCES SHOULD BE USED AS A TIE OFFPOINT.STRUCTURAL ST E E L 1.DESIGN, DETAILING, FABRICATION AND ERECTIO N O F S T R U C T U R A L S T E E L SHALL CONFORM TO THE FOLLOWING PUBLICAT I O N S E X C E P T A S SPECIFICALLY INDICATED IN THE CONTRACT DO C U M E N T S . a.AMERICAN INSTITUTE OF STEEL CONSTRUC T I O N ( A I S C ) M A N U A L O F STEEL CONSTRUCTION (15TH EDITION)b.SPECIFICATION FOR STRUCTURAL JOINTS US I N G A S T M A 3 2 5 O R A 4 9 0 BOLTSc.AISC CODE OF STANDARD PRACTICE2.STRUCTURAL STEEL SHALL CONFORM TO THE FO L L O W I N G U N L E S S OTHERWISE SHOWN:CHANNELS, ANGLES, PLATES, ETC.ASTM A36 (GR 3 6 ) STEEL PIPEASTM A53 (GR 3 5 ) BOLTSASTM A325NUTSASTM A563LOCK WASHERSLOCKING STR U C T U R A L G R A D E 3.ALL SUBSTITUTIONS PROPOSED BY THE CONTRA C T O R S H A L L B E A P P R O V E D IN WRITING BY THE ENGINEER. CONTRACTOR SH A L L P R O V I D E DOCUMENTATION TO ENGINEER FOR VERIFYING T H E S U B S T I T U T E I S SUITABLE FOR USE AND MEETS ORIGINAL DESIGN C R I T E R I A . D I F F E R E N C E S FROM THE ORIGINAL DESIGN, INCLUDING MAINT E N A N C E , R E P A I R A N D REPLACEMENT, SHALL BE NOTED. ESTIMATES OF C O S T S / C R E D I T S A S S O C I A T E D WITH THE SUBSTITUTION (INCLUDING RE-DESIG N C O S T S A N D C O S T S T O SUB-CONTRACTORS) SHALL BE PROVIDED TO TH E E N G I N E E R . C O N T R A C T O R SHALL PROVIDE ADDITIONAL DOCUMENTATION A N D / O R S P E C I F I C A T I O N S TO THE ENGINEER AS REQUESTED.4.PROVIDE STRUCTURAL STEEL SHOP DRAWINGS T O E N G I N E E R F O R APPROVAL PRIOR TO FABRICATION.a.SUBMIT SHOP DRAWINGS TOMATTHEW.GRAUBART@COLLIERSEN G I N E E R I N G . C O M b.PROVIDE MASER CONSULTING PROJECT # A N D M A S E R C O N S U L T I N G PROJECT ENGINEER CONTACT IN THE BODY O F T H E E M A I L . 5.DRILL NO HOLES IN ANY NEW OR EXISTING STRU C T U R A L S T E E L M E M B E R S OTHER THAN THOSE SHOWN ON STRUCTURAL D R A W I N G S W I T H O U T T H E APPROVAL OF THE ENGINEER OF RECORD.6.GALVANIZED ASTM A325 BOLTS SHALL NOT BE RE U S E D . 7.ALL NEW STEEL SHALL BE HOT BE DIPPED GALVA N I Z E D F O R F U L L W E A T H E R PROTECTION. IN ADDITION ALL NEW STEEL SHAL L B E P A I N T E D T O M A T C H EXISTING STEEL. CONTRACTOR SHALL OBTAIN W R I T T E N P E R M I S S I O N T O PROTECT STEEL BY ANY OTHER MEANS.8.ALL BOLT ASSEMBLIES FOR STRUCTURAL MEMBERS R E P R E S E N T E D I N T H I S DRAWING REQUIRE LOCKING DEVICES TO BE INS T A L L E D I N A C C O R D A N C E WITH TIA-222-H SECTION 4.9.2 REQUIREMENTS.9.WHERE CONNECTIONS ARE NOT FULLY DETAILE D O N T H E S E D R A W I N G S , FABRICATOR SHALL DESIGN CONNECTIONS TO R E S I S T L O A D S A N D F O R C E S WHERE SHOWN ON DRAWINGS AND AS OUTLIN E D I N S P E C I F I C A T I O N S . 10.FOR MEMBERS BEING REPLACED, PROVIDE NEW B O L T S A N D M A T C H E X I S T I N G SIZE AND GRADE. MAINTAIN AISC REQUIREMENTS F O R M I N I M U M B O L T DISTANCE AND SPACING.11.ALL PROPOSED AND/OR REPLACED BOLTS SHALL B E O F S U F F I C I E N T L E N G T H SUCH THAT THE END OF THE BOLT IS AT LEAST F L U S H W I T H T H E F A C E O F THE NUT. IT IS NOT PERMITTED FOR THE BOLT E N D T O B E B E L O W T H E F A C E OF THE NUT AFTER TIGHTENING IS COMPLETED.12.GALVANIZED ASTM A325 BOLTS SHALL NOT BE RE U S E D . 13.ALL NEW STEEL SHALL BE HOT BE DIPPED GALVA N I Z E D F O R F U L L W E A T H E R PROTECTION. CONTRACTOR SHALL OBTAIN WRI T T E N P E R M I S S I O N T O PROTECT STEEL BY ANY OTHER MEANS.14.ALL EXISTING PAINTED/GALVANIZED SURFACES D A M A G E D D U R I N G R E H A B INCLUDING AREAS UNDER STIFFENER PLATES SHA L L B E W I R E B R U S H E D CLEAN, REPAIRED BY COLD GALVANIZING (ZING A O R Z I N C C O T E ) , A N D REPAINTED TO MATCH THE EXISTING FINISH (IF A P P L I C A B L E ) . 15.ALL HOLES IN STEEL MEMBERS SHALL BE SIZED 1/1 6 ” L A R G E R T H A N T H E B O L T DIAMETER. STANDARD HOLES SHALL BE USED UN L E S S N O T E D O T H E R W I S E . E D G E S P A C I N G GAGE L I M I T O F A L L O W A B L E C O P E W I T H O U T P R I O R E O R A P P R O V A L G A G E A L L O W A B L E C O P I N G 30° W O R K A B L E G A G E S ( I N . ) L E G G A G E 4 2 1 / 2 3 1 / 2 2 3 1 3 / 4 2 1 / 2 1 3 / 8 2 1 1 / 8 B O L T S C H E D U L E ( I N . ) B O L T D I A M E T E R S T A N D A R D H O L E S H O R T S L O T M I N . E D G E D I S T A N C E S P A C I N G 1 / 2 9 / 1 6 9 / 1 6 x 1 1 / 1 6 7 / 8 1 1 / 2 5 / 8 1 1 / 1 6 1 1 / 1 6 x 7 / 8 1 1 / 8 1 7 / 8 3 / 4 1 3 / 1 6 1 3 / 1 6 x 1 1 1 / 4 2 1 / 4 7 / 8 1 5 / 1 6 1 5 / 1 6 x 1 1 / 8 1 1 / 2 2 5 / 8 1 1 1 / 1 6 1 1 / 1 6 x 1 5 / 1 6 1 3 / 4 3 T Y P . B O L T A S S E M B L Y B O L T N U T L O C K W A S H E R N O T E S : 1 . A L L D I M E N S I O N S R E P R E S E N T E D I N T H E A B O V E T A B L E S A R E A I S C M I N I M U M R E Q U I R E M E N T S . C O N T R A C T O R S H A L L V E R I F Y E X I S T I N G C O N D I T I O N S I N F I E L D A N D N O T I F Y E N G I N E E R I F D I S T A N C E S A R E L E S S T H A N T H O S E P R O V I D E D . 2 . T H E D I M E N S I O N S P R O V I D E D A R E M I N I M U M R E Q U I R E M E N T S . A C T U A L D I M E N S I O N S O F P R O P O S E D M E M B E R S W I T H I N T H E S E D R A W I N G S M A Y V A R Y F R O M T H E A I S C M I N I M U M R E Q U I R E M E N T S . 3 . S H O R T S L O T H O L E S S H A L L O N L Y B E U S E D W H E N D E P I C T E D I N T H E D R A W I N G S 4 . M A T C H E X I S T I N G G A G E S W H E N A P P L I C A B L E , U N L E S S M I N I M U M E D G E D I S T A N C E S A R E C O M P R O M I S E D . I . D . C . O . A . # : 4 1 5 4 A L L S T A T E S R E Q U I R E N O T I F I C A T I O N O F E X C A V A T O R S , D E S I G N E R S , O R A N Y P E R S O N P R E P A R I N G T O D I S T U R B T H E E A R T H ' S S U R F A C E A N Y W H E R E I N A N Y S T A T E S I T E N A M E : I AM RESPONSIBLE FOR DETERMINING THAT THE ARCHITECTURALDESIGN INCLUDED IN THIS APPLICATION ARE IN COMPLIANCE WITHALL LAWS AND REGULATIONS OF THE DISTRICT OF COLUMBIA. I HAVEPERSONALLY PREPARED, OR DIRECTLY SUPERVISED THE DEVELOPMENTOF THE ENGINEERING DESIGNS INCLUDED IN THIS APPLICATION. S C A L E : K n o w w h a t ' s b e l o w . b e f o r e y o u d i g . C a l l R S H E E T T I T L E : D R A W N B Y P R O T E C T Y O U R S E L F I T I S A V I O L A T I O N O F L A W F O R A N Y P E R S O N , U N L E S S T H E Y A R E A C T I N G U N D E R T H E D I R E C T I O N O F T H E R E S P O N S I B L E L I C E N S E D P R O F E S S I O N A L E N G I N E E R , T O A L T E R T H I S D O C U M E N T . S H E E T N U M B E R : \AcPublish_21556\Template.Mount MOD.dwg\SCF-1 By: DAVID.ANUKA R E V D A T E D E S C R I P T I O N C H E C K E D B Y F O R S T A T E S P E C I F I C D I R E C T P H O N E N U M B E R S V I S I T : W W W . C A L L 8 1 1 . C O M J O B N U M B E R : C o p y r i g h t © 2 0 2 2 . C o l l i e r s E n g i n e e r i n g & D e s i g n A l l R i g h t s R e s e r v e d . T h i s d r a w i n g a n d a l l t h e i n f o r m a t i o n c o n t a i n e d h e r e i n i s a u t h o r i z e d f o r u s e o n l y b y t h e p a r t y f o r w h o m t h e s e r v i c e s w e r e c o n t r a c t e d o r t o w h o m i t i s c e r t i f i e d . T h i s d r a w i n g m a y n o t b e c o p i e d , r e u s e d , d i s c l o s e d , d i s t r i b u t e d o r r e l i e d u p o n f o r a n y o t h e r p u r p o s e w i t h o u t t h e e x p r e s s w r i t t e n c o n s e n t o f C o l l i e r s E n g i n e e r i n g & D e s i g n . w w w . c o l l i e r s e n g i n e e r i n g . c o m C O N S U L T I N G E n g i n e e r i n g & D e s i g n E n g i n e e r i n g & D e s i g n P h o n e : E R I C K S O N - A L T 1 2 7 3 6 9 6 A S S H O W N 0 . . .. M T . L A U R E L 2 0 0 0 M i d l a n t i c D r i v e , S u i t e 1 0 0 M t . L a u r e l , N J 0 8 0 5 4 8 5 6 . 7 9 7 . 0 4 1 2 C O L L I E R S E N G I N E E R I N G & D E S I G N , I N C . D O I N G B U S I N E S S A S M A S E R C O N S U L T I N G 2 2 9 9 5 4 5 3 A . . . ... 1 1 0 S O U T H 1 2 T H S T R E E T R E X B U R G , I D 8 3 4 6 0 J E F F E R S O N C O U N T Y I S S U E D F O R C O N S T R U C T I O N D A . . . . . ...... 1 0 / 2 0 / 2 2 J P L . . . . . ......... _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ D o i n g B u s i n e s s a s C O L L I E R S E N G I N E E R I N G & D E S I G N , I N C . S C F - 1 C L I M B I N G F A C I L I T Y D E T A I L SCALE : N.T.S.CLIMBING FACILITY LOCATION1 C L I M B I N G F A C I L I T Y P H O T O BETA SECTOR GAMMA SECTORSTRUCTURAL NOTES:1.PER THE MOUNT MAPPING COMPLETED BY RKS DESIGN & ENGINEERING, LLC ON9/4/2022, THE SAFETY CLIMB AND CLIMBING FACILITIES UP TO THE VERIZONMOUNT ELEVATION (94'-0") IS IN POOR CONDITION. COLLIERS ENGINEERING &DESIGN DOES NOT WARRANT THIS INFORMATION.2.INSTALL SHALL NOT CAUSE HARM TO THE STRUCTURE, CLIMBING FACILITY,SAFETY CLIMB, OR ANY SYSTEM INSTALLED ON THE STRUCTURE. TIMELY NOTICEAND DOCUMENTATION SHALL BE PROVIDED BY CONTRACTORS TO THE EOR(OF STRUCTURAL DESIGN) IF AN OBSTRUCTION WAS REQUIRED TO MEET THE RFSYSTEM DESIGN REQUIREMENTS AND PERFORMANCES. A L P H A S E C T O R I . D . C . O . A . # : 4 1 5 4 A L L S T A T E S R E Q U I R E N O T I F I C A T I O N O F E X C A V A T O R S , D E S I G N E R S , O R A N Y P E R S O N P R E P A R I N G T O D I S T U R B T H E E A R T H ' S S U R F A C E A N Y W H E R E I N A N Y S T A T E S I T E N A M E : I AM RESPONSIBLE FOR DETERMINING THAT THE ARCHITECTURALDESIGN INCLUDED IN THIS APPLICATION ARE IN COMPLIANCE WITHALL LAWS AND REGULATIONS OF THE DISTRICT OF COLUMBIA. I HAVEPERSONALLY PREPARED, OR DIRECTLY SUPERVISED THE DEVELOPMENTOF THE ENGINEERING DESIGNS INCLUDED IN THIS APPLICATION. S C A L E : K n o w w h a t ' s b e l o w . b e f o r e y o u d i g . C a l l R S H E E T T I T L E : D R A W N B Y P R O T E C T Y O U R S E L F I T I S A V I O L A T I O N O F L A W F O R A N Y P E R S O N , U N L E S S T H E Y A R E A C T I N G U N D E R T H E D I R E C T I O N O F T H E R E S P O N S I B L E L I C E N S E D P R O F E S S I O N A L E N G I N E E R , T O A L T E R T H I S D O C U M E N T . S H E E T N U M B E R : \AcPublish_21556\Template.Mount MOD.dwg\SS-1 By: DAVID.ANUKA R E V D A T E D E S C R I P T I O N C H E C K E D B Y F O R S T A T E S P E C I F I C D I R E C T P H O N E N U M B E R S V I S I T : W W W . C A L L 8 1 1 . C O M J O B N U M B E R : C o p y r i g h t © 2 0 2 2 . C o l l i e r s E n g i n e e r i n g & D e s i g n A l l R i g h t s R e s e r v e d . T h i s d r a w i n g a n d a l l t h e i n f o r m a t i o n c o n t a i n e d h e r e i n i s a u t h o r i z e d f o r u s e o n l y b y t h e p a r t y f o r w h o m t h e s e r v i c e s w e r e c o n t r a c t e d o r t o w h o m i t i s c e r t i f i e d . T h i s d r a w i n g m a y n o t b e c o p i e d , r e u s e d , d i s c l o s e d , d i s t r i b u t e d o r r e l i e d u p o n f o r a n y o t h e r p u r p o s e w i t h o u t t h e e x p r e s s w r i t t e n c o n s e n t o f C o l l i e r s E n g i n e e r i n g & D e s i g n . w w w . c o l l i e r s e n g i n e e r i n g . c o m C O N S U L T I N G E n g i n e e r i n g & D e s i g n E n g i n e e r i n g & D e s i g n P h o n e : E R I C K S O N - A L T 1 2 7 3 6 9 6 A S S H O W N 0 . . .. M T . L A U R E L 2 0 0 0 M i d l a n t i c D r i v e , S u i t e 1 0 0 M t . L a u r e l , N J 0 8 0 5 4 8 5 6 . 7 9 7 . 0 4 1 2 C O L L I E R S E N G I N E E R I N G & D E S I G N , I N C . D O I N G B U S I N E S S A S M A S E R C O N S U L T I N G 2 2 9 9 5 4 5 3 A . . . ... 1 1 0 S O U T H 1 2 T H S T R E E T R E X B U R G , I D 8 3 4 6 0 J E F F E R S O N C O U N T Y I S S U E D F O R C O N S T R U C T I O N D A . . . . . ...... 1 0 / 2 0 / 2 2 J P L . . . . . ......... _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ D o i n g B u s i n e s s a s C O L L I E R S E N G I N E E R I N G & D E S I G N , I N C . S S - 1 M O D I F I C A T I O N D E T A I L S SCALE : N.T.S.1 S C A L E : N . T . S . PROPOSED ISOMETRIC VIEW 2 P R O P O S E D P L A N V I E W LEGEND:PROPOSEDRELOCATEDEXISTING M O U N T M O D I F I C A T I O N S C H E D U L E N O . E L E V A T I O N Q U A N T I T Y D E S C R I P T I O N N O T E S 1 9 4 ' - 0 " 3 P R O P O S E D S U P P O R T R A I L B R A C I N G K I T ( P A R T # : V Z W S M A R T - P L K 1 0 ) C O N T R A C T O R T O V E R I F Y T H E L E N G T H R E Q U I R E D A N D T R I M A S N E C E S S A R Y I N A C C O R D A N C E W I T H T H E ' S T R U C T U R A L S T E E L ' N O T E S O N S H E E T S G N - 1 . S E E G E N E R A L N O T E A 2   3   R E L O C A T E D M O U N T P I P E S R E C O N N E C T S H I F T E D P I P E S T O M O U N T H O R I Z O N T A L S U S I N G E X I S T I N G C O N N E C T I O N C R O S S O V E R P L A T E S , E T C . W I T H N E W B O L T I N G H A R D W A R E . D O N O T R E U S E E X I S T I N G B O L T S . G E N E R A L N O T E S : A . T H R E A D E D R O D F R O M P R O P O S E D K I T S S H A L L B E T R I M M E D T O E X T E N D N O M O R E T H A N 3 " B E Y O N D T H E L O C K N U T . T R E A T A L L C U T E N D S W I T H ( 2 ) C O A T S O F C O L D G A L V A N I Z A T I O N ( Z I N G A O R Z I N C K O T E ) . B. M O U N T M E M B E R S N O T S H O W N F O R C L A R I T Y U . N . O . 3'-6"±3" (TYP.)6'-0"±3" (TYP.) 1 ' - 2 " ± 3 " ( T Y P . ) 2'-0"±3" (TYP.)2'-0"±3" (TYP.) 1 1 2 I . D . C . O . A . # : 4 1 5 4 A L L S T A T E S R E Q U I R E N O T I F I C A T I O N O F E X C A V A T O R S , D E S I G N E R S , O R A N Y P E R S O N P R E P A R I N G T O D I S T U R B T H E E A R T H ' S S U R F A C E A N Y W H E R E I N A N Y S T A T E S I T E N A M E : I AM RESPONSIBLE FOR DETERMINING THAT THE ARCHITECTURALDESIGN INCLUDED IN THIS APPLICATION ARE IN COMPLIANCE WITHALL LAWS AND REGULATIONS OF THE DISTRICT OF COLUMBIA. I HAVEPERSONALLY PREPARED, OR DIRECTLY SUPERVISED THE DEVELOPMENTOF THE ENGINEERING DESIGNS INCLUDED IN THIS APPLICATION. S C A L E : K n o w w h a t ' s b e l o w . b e f o r e y o u d i g . C a l l R S H E E T T I T L E : D R A W N B Y P R O T E C T Y O U R S E L F I T I S A V I O L A T I O N O F L A W F O R A N Y P E R S O N , U N L E S S T H E Y A R E A C T I N G U N D E R T H E D I R E C T I O N O F T H E R E S P O N S I B L E L I C E N S E D P R O F E S S I O N A L E N G I N E E R , T O A L T E R T H I S D O C U M E N T . S H E E T N U M B E R : \AcPublish_21556\Template.Mount MOD.dwg\SS-2 By: DAVID.ANUKA R E V D A T E D E S C R I P T I O N C H E C K E D B Y F O R S T A T E S P E C I F I C D I R E C T P H O N E N U M B E R S V I S I T : W W W . C A L L 8 1 1 . C O M J O B N U M B E R : C o p y r i g h t © 2 0 2 2 . C o l l i e r s E n g i n e e r i n g & D e s i g n A l l R i g h t s R e s e r v e d . T h i s d r a w i n g a n d a l l t h e i n f o r m a t i o n c o n t a i n e d h e r e i n i s a u t h o r i z e d f o r u s e o n l y b y t h e p a r t y f o r w h o m t h e s e r v i c e s w e r e c o n t r a c t e d o r t o w h o m i t i s c e r t i f i e d . T h i s d r a w i n g m a y n o t b e c o p i e d , r e u s e d , d i s c l o s e d , d i s t r i b u t e d o r r e l i e d u p o n f o r a n y o t h e r p u r p o s e w i t h o u t t h e e x p r e s s w r i t t e n c o n s e n t o f C o l l i e r s E n g i n e e r i n g & D e s i g n . w w w . c o l l i e r s e n g i n e e r i n g . c o m C O N S U L T I N G E n g i n e e r i n g & D e s i g n E n g i n e e r i n g & D e s i g n P h o n e : E R I C K S O N - A L T 1 2 7 3 6 9 6 A S S H O W N 0 . . .. M T . L A U R E L 2 0 0 0 M i d l a n t i c D r i v e , S u i t e 1 0 0 M t . L a u r e l , N J 0 8 0 5 4 8 5 6 . 7 9 7 . 0 4 1 2 C O L L I E R S E N G I N E E R I N G & D E S I G N , I N C . D O I N G B U S I N E S S A S M A S E R C O N S U L T I N G 2 2 9 9 5 4 5 3 A . . . ... 1 1 0 S O U T H 1 2 T H S T R E E T R E X B U R G , I D 8 3 4 6 0 J E F F E R S O N C O U N T Y I S S U E D F O R C O N S T R U C T I O N D A . . . . . ...... 1 0 / 2 0 / 2 2 J P L . . . . . ......... _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ D o i n g B u s i n e s s a s C O L L I E R S E N G I N E E R I N G & D E S I G N , I N C . S S - 2 M O U N T P H O T O S MOUNT PHOTO 1 M O U N T P H O T O 2 MOUNT PHOTO 3 M O U N T P H O T O 4 2 V4.1 Updated on 12-17-2021 FCC # UNKNOWN RKS Design & Engineering, LLC Sector / Position Vertical Offset Dimension "u" Horizontal Offset "C1, C2, C3, etc." Sector / Position Vertical Offset Dimension "u" Horizontal Offset "C1, C2, C3, etc." A1 71.50 12.00 C1 71.50 12.00 A2 47.75 41.50 C2 47.75 41.50 A3 32.25 21.00 C3 32.25 21.00 A4 47.75 21.50 C4 47.75 21.50 A5 71.50 42.25 C5 71.50 42.25 A6 C6 B1 71.50 12.00 D1 B2 47.75 41.50 D2 B3 32.25 21.00 D3 B4 47.75 21.50 D4 B5 71.50 42.25 D5 B6 D6 16.48 Photos of antennas Antenna Mount Mapping Form (PATENT PENDING) VZW Mapping Date:9/4/2022 VZW: ERICKSON - ALT 1 Tower Type:Monopole VZW: 273696 Tower Height (Ft.):150 Mount Elevation (Ft.):96.5 PIPE 2.38"Ø X 0.15" X 120.5" LONG PIPE 2.38"Ø X 0.15" X 96" LONG PIPE 2.37"Ø X 0.14" X 48" LONG Mount Pipe Configuration and Geometries [Unit = Inches] Mount Pipe Size & Length PIPE 2.38"Ø X 0.15" X 120.5" LONG PIPE 2.38"Ø X 0.15" X 96" LONG PIPE 2.37"Ø X 0.14" X 48" LONG PIPE 2.38"Ø X 0.15" X 96" LONG PIPE 2.38"Ø X 0.15" X 120.5" LONG Mount Pipe Size & Length PIPE 2.38"Ø X 0.15" X 120.5" LONG PIPE 2.38"Ø X 0.15" X 96" LONG PIPE 2.38"Ø X 0.15" X 48" LONG PIPE 2.38"Ø X 0.15" X 96" LONG PIPE 2.38"Ø X 0.15" X 120.5" LONG Distance from top of bottom support rail to lowest tip of ant./eqpt. of Carrier above. (N/A if > 10 ft.) : Distance from top of bottom support rail to highest tip of ant./eqpt. of Carrier below. (N/A if > 10 ft.) : Please enter additional infomation or comments below. Please insert the sketches of the antenna mount from the "Sketches" tab with dimensions and members here. Tower Owner: Site Name: Site Number or ID: Mapping Contractor: This antenna mapping form is the property of TES and under PATENT PENDING. The formation contained herein is considered confidential in nature and is to be used only for the specific customer it was intended for. Reproduction, transmission, publication, modification or disclosure by any method is prohibited except by express written permission of TES. All means and methods are the responsibility of the contractor and the work shall be compliant with ANSI/ASSE A 10.48, OSHA, FCC, FAA and other safety requirements that may apply. TES is not warrantying the usability of the safety climb as it must be assessed prior to each use in compliance with OSHA requirements. PIPE 2.38"Ø X 0.15" X 96" LONG PIPE 2.38"Ø X 0.15" X 120.5" LONG Tower Face Width at Mount Elev. (ft.): Mounting Locations [Units are inches and degrees]Enter antenna model. If not labeled, enter "Unknown". Tower Leg Size or Pole Shaft Diameter at Mount Elev. (in.): An t s . I t e m s Antenna Models if Known Width (in.) Depth (in.) Height (in.) Coax Size and Qty Antenna Center- line (Ft.) Vertical Distances"b1a, b2a, b3a, b1b…." (Inches) Horiz. Offset "h" (Use "-" if Ant. is behind) Antenna Azimuth (Degrees) Photo Numbers Ant1a B66A RRH 4X45 11.80 7.20 25.80 99.2083 39.00 -6.50 209 Ant1b HEX658CW0000G 12.00 7.10 98.70 98.5625 46.75 9.00 40.00 20, 209 Ant1c Ant2a Ant2b Ant2c Ant3a RHSDC-3315-PF-48 15.73 10.25 25.66 98.1458 12.50 211 Ant3b Ant3c Ant4a Ant4b Ant4c Ant5a B13 RRH4X30 11.80 7.50 20.90 99.5833 34.50 -6.75 214 Ant5b HEX658CW0000G 12.00 7.10 98.70 98.5625 46.75 9.00 40.00 20, 215 Ant5c Ant on Standoff Ant on Standoff Ant on Tower Ant on TowerAntenna Layout (Looking Out From Tower) Sector A Ant1a B66A RRH 4X45 11.80 7.20 25.80 99.2083 39.00 -6.50 217 Sector A:40.00 Deg Leg A: Deg Ant1b HEX658CW0000G 12.00 7.10 98.70 98.5625 46.75 9.00 160.00 26, 217 Sector B:160.00 Deg Leg B: Deg Ant1c Sector C:280.00 Deg Leg C: Deg Ant2a Sector D: Deg Leg D: Deg Ant2b Ant2c Location: 160.00 Ant3a RHSDC-3315-PF-48 15.73 10.25 25.66 98.1458 12.50 219 Ant3b Ant3c Ant4a Ant4b Ant4c Ant5a B13 RRH4X30 11.80 7.50 20.90 99.5833 34.50 -6.75 226 Ant5b HEX658CW0000G 12.00 7.10 98.70 98.5625 46.75 9.00 160.00 26, 226 Ant5c Ant on Standoff Ant on Standoff Ant on Tower Ant on Tower Ant1a B66A RRH 4X45 11.80 7.20 25.80 99.2083 39.00 -6.50 228 Ant1b HEX658CW0000G 12.00 7.10 98.70 98.5625 46.75 9.00 280.00 32, 228 Ant1c Ant2a Ant2b Ant2c Ant3a Ant3b Ant3c Ant4a Ant4b Ant4c Ant5a B13 RRH4X30 11.80 7.50 20.90 99.5833 34.50 -6.75 234 Ant5b HEX658CW0000G 12.00 7.10 98.70 98.5625 46.75 9.00 280.00 32, 234 Ant5c Ant on Standoff Ant on Standoff Ant on Tower Ant on Tower Ant1a Ant1b Ant1c Ant2a Ant2b Ant2c Ant3a Ant3b Ant3c Ant4a Ant4b Ant4c Ant5a Ant5b Ant5c Ant on Standoff Ant on Standoff Ant on Tower Ant on Tower Sector BMount Azimuth (Degree) for Each Sector Tower Leg Azimuth (Degree) for Each Sector Climbing Facility Corrosion Type: Access: Condition: Sector C Sector D Deg N/A N/A Climbing path was unobstructed. Loose hardware. Climbing Facility Information Issue #Photo # 1 129 2 4 3 4 5 6 7 8 Mapping Notes 1. Please report any visible structural or safety issues observed on the antenna mounts (Damaged members, loose connections, tilting mounts, safety climb issues, etc.) Description of Issue COAX TOTAL (1): (1) 1.55"Ø HYBRID Standard Conditions 1. Obvious safety and structural issues/deficiencies noticed at the time of the mount mapping are to be reported in this mapping. However, this mount mapping is not a condition assessment of the mount. 6. Please measure and report the size and length of all existing antenna mounting pipes. 8. Don't delete or rearrange any sheet or contents of any sheet from this mapping form. 7. Please measure and report the antenna information for all sectors. Observed Safety and Structural Issues During the Mount Mapping 2. If the thickness of the existing pipes or tubing can't be obtained from a general tool (such as Caliper), please use an ultrasonic measurement tool (thickness gauge) to measure the thickness. 3. Please create all required detail sketches of the mounts and insert them into the "Sketches" tab. 4. Please measure and enter the bolt sizes and types under the Members Box in the spreadsheet of the mount type. 5. Take and label the photos of the tower, mounts, connections, antennas and all measurements. Minimum 50 photos are required. SAFETY CABLE AT BOTTOM OF TOWER NOT CONNECTED V4.1 Updated on 12-17-2021 FCC # UNKNOWN Tower Owner: Site Name: Site Number or ID: Mapping Contractor: This antenna mapping form is the property of TES and under PATENT PENDING. The formation contained herein is considered confidential in nature and is to be used only for the specific customer it was intended for. Reproduction, transmission, publication, modification or disclosure by any method is prohibited except by express written permission of TES. All means and methods are the responsibility of the contractor and the work shall be compliant with ANSI/ASSE A 10.48, OSHA, FCC, FAA and other safety requirements that may apply. TES is not warrantying the usability of the safety climb as it must be assessed prior to each use in compliance with OSHA requirements. Antenna Mount Mapping Form (PATENT PENDING) VZW Mapping Date:9/4/2022 VZW: ERICKSON - ALT 1 Tower Type:Monopole VZW: 273696 Tower Height (Ft.):150 RKS Design & Engineering, LLC Mount Elevation (Ft.):96.5 Please Insert Sketches of the Antenna Mount Please Insert Sketches of the Antenna Mount, cont'd Please Insert Sketches of the Antenna Mount, cont'd Client:Verizon Wireless Date:10/18/2022 Site Name:ERICKSON - Alt 1 PSLC #: 273696 Fuze ID #:16932340 Page:1 Version 1.01 I. Mount-to-Tower Connection Check Custom Orientation Required No Tower Connection Bolt Checks Yes Bolt Orientation Parallel Bolt Quantity per Reaction:4 dx (in) (Delta X of typ. bolt config. sketch):9 dy (in) (Delta Y of typ. bolt config. sketch):9 Bolt Type:A325N Bolt Diameter (in):0.625 Required Tensile Strength / bolt (kips):4.3 Required Shear Strength / bolt (kips):0.5 Tensile Capacity / bolt (kips):20.7 Shear Capacity / bolt (kips):12.4 Bolt Overall Utilization:20.5% Tower Connection Baseplate Checks Yes Connecting Standoff Member Shape:Rect Tube Weld Stiffener Configuration:No Stiffeners Plate Width, Dx (in):11.5 Plate Height, Dy (in):11.5 W1(in):6 W2 (in):3 Member Thickness (in):0.375 Stiffener location a1 (in): Stiffener location b1 (in): Stiffener location a2 (in): Stiffener location b2 (in): Fy (ksi, plate):36 Plate Thickness (in):0.5 Length of Yield Line, Ly (in):9.15 Bolt Eccentricity, e (in):3.53 Mu (kip-in):15.02 Phi*Mn (kip-in):18.54 Plate Bending Utilization:81.0% Client:Verizon Wireless Date:10/18/2022 Site Name:ERICKSON - Alt 1 PSLC #: 273696 Fuze ID #:16932340 Page:2 Version 1.01 Tower Connection Weld Checks Yes Weld Shape:Rectangle Weld Stiffener Configuration:None Stiffener Notch Length, n (in):None Weld Size (1/16 in):4 W1 (in):6 W2 (in):3 Weld Total Length (in):18.00 Zx (in3/in):21.00 Zy (in3/in):30.00 Jp (in4/in):121.50 cx (in)3.375 cy (in)1.875 Required combined strength (kip/in):2.42 Weld Capacity (kip/in):5.57 Weld Utilization:43.4%