HomeMy WebLinkAboutVERTICAL TURBINE PUMP ACCESSORIES - 23-00006 - Hibbard Elemenatry - Fire Sprinkler
SUBMITTAL DATA
VERTICAL TURBINE FIRE PUMP ACCESSORIES
500 GPM @ 95 PSI BOOST
PHOENIX FIRE PROTECTION
HIBBARD ELEMENTARY REXBURG, IDAHO
General ArrangementABCD4.002.008.502.50EFGHJ2.503.502.759.5011.00NOTES:1. Dimensions are in inches (mm) and may vary ±1/4 (6).2. Components shown are shipped loose for field installation and assembly.3. Manifold supply size “A” and the number of hose valves (“B”) meets or exceedsthe minimums specified by N.F.P.A. 20 for the pump ratings indicated.4. Manifolds for 3000 through 5000 GPM ratings consist of multiple sectionsandmay require support (by others).5. 1-1/2” Hose valves furnished with 1-1/2” National Standard Fire Hose Thread: 1.9900 (50.55) O.D. (max.), 6 threads per inch. 2-1/2” Hose valves are furnished with 2-1/2” National Standard Fire HoseThread: 3.0686 (77.94) O.D. (max.), 7-1/2 threads per inch. Refer to factory for other thread conventions or adaptors.Quote InformationCustomerNICKERSON COMPANY, INC. - UT (AuroraCustomer Quote0Job NameMarket-Quote Item001Quote Date22 Jul 2022Encompass 2.0 - 22.2.0
AURORA® FIRE PUMPS
OPTION 75 - TEST MANIFOLD
OPTION 76 - HOSE VALVES
OPTION 77 - BALL DRIP VALVE
Section 916 Page 203
Date September 2013
Supersedes Section 916 Page 203
Dated May 2004
VALVE
SIZE
”E“ ”F“ ”G“ ”H“ ”J“
1-1/2 2.25 2.00 6.50 7.50
(57) (51) (165) (191)
2-1/2 3.5 2.75 9.50 11.00
(89) (70) (241) (297)
NOTES:
1. Dimensions are in inches (mm) and may vary ±1/4 (6).
2. Components shown are shipped loose for field
installation and assembly.
3. Manifold supply size “A” and the number of hose
valves (“B”) meets or exceeds the minimums specified
by N.F.P.A. 20 for the pump ratings indicated.
4. Manifolds for 3000 through 5000 GPM ratings consist of
multiple sections and may require support (by others).
5. 1-1/2” Hose valves furnished with 1-1/2” National Standard
Fire Hose Thread: 1.9900 (50.55) O.D. (max.), 6 threads per
inch. 2-1/2” Hose valves are furnished with 2-1/2” National
Standard Fire Hose Thread: 3.0686 (77.94) O.D. (max.),
7-1/2 threads per inch. Refer to factory for other thread
conventions or adaptors.
STD. 125# ASA FLANGES OPT. 250# ASA FLANGES
OPTION 75 - TEST MANIFOLD
WITH CAPS AND CHAINS WITHOUT CAPS AND CHAINS
OPTION 76 - HOSE VALVE(S)
Designed to drain a branch line leading to an
outside test manifold where danger of freezing
exists. Opens at zero flow.
OPTION 77 - BALL DRIP VALVE
"E" NPT
"J"OPEN "H"CLOSED
"E" HOSE THREAD
(SEE NOTE 5)
"G"
"F"
LISTED APPROVED
FM
QTY "B" SIZE "D" PIPE
TAPS FOR HOSE VA LVES
A
C
2.56 (65)
1/2 NPT
100 400 1250
PUMP RATING 50 150 250 450 750 1000 1500 2500 3000 3500 4000 5000
G.P.M. 200 300 500 2000 4500
”A“ MANIFOLD
SUPPLY SIZE 1.5” 2.5” 3” 4” 6” 6” 8” 10” 10” 12” 12” 12”
”B“ 1 1 1 2 3 4 6 8 12 12 16 20
”C“ 1.00 1.13 1.31 8.50 10.62 10.62 11.75 12.50 25.63 31.63 31.63 43.75
(25) (29) (33) (216) (270) (270) (298) (318) (651) (803) (803) (1111)
”D“ 1-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2
Well Service Air Valves
MATERIALS OF CONSTRUCTION
COMPONENT STANDARD OPTIONAL
Body and Cover Cast Iron ASTM A126 Class B
Class 125 and 250
Ductile Iron ASTM A536 Grade 65-45-12
Stainless Steel ASTM A351 Grade CF8M
Trim Type 316 Stainless Steel (Air Valve)
Bronze ASTM B584 C83600 (Reg. Exh. Dev.)*-
Coating Universal Alkyd Primer (external)Non-Stick Fusion Bonded Epoxy (internal & external)
WELL SERVICE AIR VALVE SIZING
VALVE
SIZE
NO HEAD PUMP
CAPACITY, GPM
MODEL NUMBER
150 PSI MODEL 300 PSI MODEL
1/2”0 - 350 100ST
1”351 - 1,350 101ST
2”1,351 - 4,000 102ST
3”4,001 - 7,000 103ST
4”7,001 - 11,000 104SS 154SS
6”11,001 - 24,000 106SS 156SS
8”24,001 - 50,000 108SS 158SS
10”50,001 - 70,000 110FSS 160FSS
12”70,001 - 110,000 112FSS 162FSS
22
Operational Highlights:
• Regulates the exhaust of air on pump start-up
• Admits air to protect pump and mechanical seals
• Protects against air-related surges on pump start-up
• Fully complies with AWWA C512 and NSF 61
Product Features:
• Unconditionally guaranteed 316 stainless steel floats
• Inlets and outlets are equal to full nominal pipe area
• 1/2" - 3" equipped with Dual Port Throttling Device
• 4" and larger equipped with Regulated-Exhaust Device mounted on
the inlet
Dual Port Throttling Device:
• Adjustable discharge outlet provides regulated air exhaust
• Allows air to enter the system on pump shut down through an
unrestricted independent vacuum port
Regulated-Exhaust Device:
• Retrictor disc provides regulated exhaust to limit pump column surges
• Ability to adjust air exhaust for greater surge suppression
• Provides full vacuum flow port
1 - 3 inch
4 inch & larger
*(Reg. Exh. Dev.) = Regulated-Exhaust Device
Well Service Air Valve
with Dual Port Throttling Device
Inlet
Size
Outlet
Size
Model
Number
CWP
PSI
Dimensions
A B
1/2” NPT 1/2” NPT 100ST 300 6 1/8”11 3/4”
1” NPT 1” NPT 101ST 300 7”14 3/4”
2” NPT 2” NPT 102ST*300 9 1/2”20 1/8”
3” NPT 3” NPT 103ST*300 9 1/2”22 1/8”
Well Service Air Valve with Regulated-Exhaust Device
Inlet
Size
Outlet
Size
Model
Number
CWP
PSI
Dimensions
A B
4” 125lb Flg 4” NPT 104SS 150 11 1/2”22 3/4”
4” 250lb Flg 4” NPT 154SS 300 11 1/2”22 3/4”
6” 125lb Flg 6” NPT 106SS 150 14”28 1/2”
6” 250lb Flg 6” NPT 156SS 300 14”28 1/2”
8” 125lb Flg 8” NPT 108SS 150 17 1/4”35 5/16”
8” 250lb Flg 8” NPT 158SS 300 17 1/4”35 5/16”
10” 125lb Flg 10” 125lb Flg 110FSS 150 20 1/4”40 1/16”
10” 250lb Flg 10” 125lb Flg 160FSS 300 20 1/4”40 1/16”
12” 125lb Flg 12” 125lb Flg 112FSS 150 24”44 5/16”
12” 250lb Flg 12” 125lb Flg 162FSS 300 24”44 5/16”
*UL Listed for fire pump service
Installation Dimensions
A
B
100ST - 103ST
Well Service Air Valves with
Dual Port Throttling Device
104SS - 162FSS
Well Service Air Valves
with Regulated-Exhaust Device
A
B
23
Well Service Air Valves
3” Well Service Air Valve on Vertical Pump discharge.