HomeMy WebLinkAboutRELIABLE MODEL G CHECK VALVE - 23-00006 - Hibbard Elemenatry - Fire SprinklerFeatures
• Grooved end connections.
• Compact, lightweight design.
• Non–slamming, spring loaded clapper to minimize water
hammer.
• Approved for horizontal and vertical installation.
• Streamlined body design provides very low friction loss.
Product Description
Reliable Model G Swing Check Valves are low friction loss check
valves approved for use in fire protection systems. Typical applica-
tions include connections between public water supplies and pri-
vate fire systems, at the discharge from fire pumps, at gravity tank
connections and at fire department pumper connections. All Model
G Check Valves are provided with ½” NPT (R½) supply side and
discharge side connections (Item 12, Figure 1). Grooved end con-
nections provide fast and easy installation using listed or approved
mechanical grooved couplings. Rigid style grooved couplings can
be used for positive clamping to resist flexural and torsional loads.
Installation
The Model G Check Valve shall be installed in accordance with
NFPA 13, “Standard for the Installation of Sprinkler Systems,”
as well as the requirements of any authorities having jurisdic-
tion. When installed vertically, the direction of flow shall be up
through the valve (install with flow arrow pointed up). For hor-
izontal installations, the hinge pin must be located to the top.
Failure to follow installation instructions may void the warran-
ty and listing of the valve. Verify compatibility of the Model G
Check Valve materials with the water supply and the environ-
ment where the valve will be installed prior to installation. Do
not apply lubricants, sealants, or other chemicals to the clapper
seal or seat.
www.reliablesprinkler.com
Note: Model G Check Valves may be damaged by excessively turbu-
lent water flow. Model G Check Valves should be installed a reasonable
distance from pipe transitions, such as pumps, elbows, expanders, re-
ducers, or similar devices. Typical piping practices suggest a minimum
distance of five times the pipe diameter for general use.
Table ATechnical Data
Valve Size Pressure Rating Face-to-Face
Dimension Eq. Length C = 120 Eq. Length C = 100 Cv Factor Shipping Weight
1-1/2” (40 mm)300 psi (20.7 bar)6-1/4 “ (159 mm)6.7’ (2.0 m)4.8’ (1.5 m)36 5 lbs (2.3 kg)
2” (50 mm)6-1/2” (165 mm)9.6’ (2.9 m)6.8’ (2.1 m)67 6 lbs (2.7 kg)
2-1/2” (65 mm)
250 psi (17.3 bar)
7.12” (181 mm)6.0’ (1.8m)4.3’ (1.3m)212 9 lbs (4.1 kg)
76 mm 7.12” (181 mm)6.0’ (1.8m)4.3’ (1.3m)212 9 lbs. (4.1 kg)
3” (80 mm)7.62” (194 mm)5.3’ (1.6m)3.8’ (1.2m)376 11 lbs. (5.0 kg)
4” (100 mm)8.44” (214 mm)7.1’ (2.2m)5.0’ (1.5m)656 17 lbs. (7.7 kg)
6” (150 mm)10.25” (260 mm)13.7’ (4.2m)9.8’ (3.0m)1395 38 lbs. (17.2 kg)
165 mm 10.25” (260 mm)13.7’ (4.2m)9.8’ (3.0m)1395 38 lbs. (17.2 kg)
8” (200 mm)12.5” (318 mm)15.9’ (4.8m)11.3’ (3.4m)2818 63 lbs. (28.6 kg)
10” (250 mm)300 psi (20.7 bar)14.5” (368 mm)28.8’ (8.8m)20.6’ (6.3m)3928 102 lbs. (46.3 kg)
cULus Listed, FM Approved
Model G Swing Check Valve
1-1/2”, 2”, 2-1/2”, 3”, 4”, 6”, 8”, & 10” Sizes
Bulletin 807 May 2019
Reliable Model G Swing Check Valve (3”)
Figure 1Model G Swing Check Valve Components
Maintenance
The owner is responsible for maintaining the fire protection sys-
tem in proper operating condition. Any system maintenance or
testing that involves placing a system out of service may elim-
inate the fire protection that is provided by the fire protection
system. Notify any required authorities having jurisdiction and
implement appropriate precautions prior to proceeding.
The Reliable Model G Check Valve shall periodically be given
a thorough inspection and test. NFPA 25, “Inspection, Testing
and Maintenance of Water Based Fire Protection Systems,” pro-
vides minimum maintenance requirements. Inspect the interior
of the valve and all components for corrosion, damage, and
wear at least every five (5) years. Replace any components
found to be corroded, damaged, or worn. Increase the fre-
quency of inspections when the valve is exposed to corrosive
conditions or chemicals that could impact the valve materials.
Part Number
1-1/2”
(40 mm)
2”
(50 mm)
2½”
(65 mm)76 mm 3”
(80 mm)
4”
(100 mm)
6”
(150 mm)165 mm 8”
(200 mm)
10”
(250 mm)
6888000015 6888000020 6888040025 6888040025 6888040030 6888040040 6888040060 6888040060 6888040080 6888040090
Table CReplacement Seal Kit Part Numbers
Item
No.Part Name Material
1 Valve Body Gray Cast Iron Class 30
2 Seat Bronze C83600 or C93200
3 Clapper Stainless Steel 304 or 17-4
4 Facing Seal *EPDM Rubber
5 Clamping Ring Stainless Steel 304
6 Gasket *EPDM Rubber or PTFE
7 Spring Stainless Steel 302
8 Hinge Pin Stainless Steel 303
9 Bolt Stainless Steel 18-8
10 Locknut *Stainless Steel 18-8
11 Plug, 1/8” NPT Steel
12 Plug, ½” NPT Steel
13 Shoulder Eye Steel
* Part of Replacement Seal Kit
Table BValve Components (refer to Figure 1)
Guarantee
For Reliable Automatic Sprinkler Co., Inc. guarantee, terms,
and conditions, visit www.reliablesprinkler.com.
Ordering Information
Specify:
1. Model G Check Valve.
2. Size.P/N 9999970071Bulletin 807
May 2019
Page 2 of 2