Loading...
HomeMy WebLinkAbout4 WAY EQ CALC - 23-00006 - Hibbard Elemenatry - Fire Sprinkler1 Seismic Brace Report Project Name HIBBARD ELEMENTARY Date 12/22/2022 Address 2413 N 3000 W REXBURG, ID 83440 APPROVAL STAMP Approved Approved as Noted Not Approved Remarks: Standard NFPA 13-2019 BRACE SUMMARY Brace Name Drawing Reference Seismic Design Load Structure Brace Description Fastener Attachments 4 WAY FP2 62 lbf..035 ¹Lateral Orientation A, B, D, & E 30° - 59° 1 NPS Sch 40 1/2" LAG BOLT ¹AF700 - 1/2" AF001 - 2 1/2 NPS x 1 NPS NOTE: Per NFPA 13-2019, all load capacities listed for fasteners installed in cracked concrete have been reduced based on the prying factors listed for ASC's swivel attachments. Prying factors for NFPA fastener orientations “A” through “I” may be found in ASC's individual product submittal at asc-es.com NFPA 13-2016 Product loads incorporate a minimum safety factor of 1.5. NFPA 13-2019 FM Product loads have been reduced to include a safety factor of 2.2 unless noted in the applicable product submittal. ¹ This field entry has been defined by the end user. ASC Engineered Solutions has not verified it's load capacity for this application. 2 4 WAY - SEISMIC BRACE CALCULATIONS Seismic Project HIBBARD ELEMENTARY Standard NFPA 13-2019 Brace Type Riser / 4-Way Brace Assembly - Wall Condition Brace Name 4 WAY Drawing Reference FP2 Approval Agency UL Listed STRUCTURE INFORMATION Structure CMU ¹ Substrate .035 ¹ BRACE INFORMATION Brace Member 1 NPS Sch 40 Brace Length Max 10 ft 6 in Brace Angle 30° - 59° Least Radius of Gyration 0.421 in. l/r Ratio Max 300 Max Horizontal Load 412 lbf. FASTENER INFORMATION Fastener Name LAG BOLT ¹ Fastener Orientation A, B, D, & E Fastener Diameter 1/2 in. Max Horizontal Load 100 lbf. ¹ SEISMIC BRACE ATTACHMENTS Model Size Load Rating Swivel Att.AF700 1/2"942 lbf. Pipe Att.AF001 2 1/2 NPS x 1 NPS 340 lbf. See Appendix A for alternate seismic brace attachments. All seismic brace attachments manufactured by ASC Engineered Solutions. SPRINKLER SYSTEM LOAD CALCULATION (FPW = CP*WP) CP = 0.359 Qty Line Description Pipe Diameter/Type Length Weight per ft Weight 1 Main Braced Pipe 2 1/2 NPS Steel Sch 10 25.00 ft.5.89 lb/ft.147.25 lb. Weakest Main Size Spacing Max Fpw 2 1/2 NPS Steel Sch 10 25 ft.513 lbf. Total System Weight 147.25 lb. System Design Weight (Wp)170.00 lb. Horizontal Seismic Load (Fpw)62 lbf. ¹ This field entry has been defined by the end user. ASC Engineered Solutions has not verified it's load capacity for this application. 3 Appendix A - Alternate Seismic Brace Attachments 4 WAY Structural Attachment Structural Attach. Size Structural Attach. Capacity Swivel Pipe Attachment --------AF035 2 1/2 NPS x 1 NPS | 625 lbf. --------AF775 2 1/2 NPS x 1 NPS | 340 lbf. --------AF730 2 1/2 NPS | 545 lbf. 4 Appendix B - Enlarged Images 4 WAY 5 Appendix C - Cp Calculations BRACE CALCULATION DATA Brace Name Brace Ref Method Cp Ss Site Fa SDS Z H 4 WAY FP2 A 0.359 0.350 ---------- CALCULATION METHODS A Cp calculated per NFPA 13-2019 Table 18.5.9.3 B Cp entered by user C Cp calculated per ASCE/SEI 7-16 per NFPA 13-2019 Section 18.5.9.4 Per NFPA 13-2019, the following values are always assumed for ap, Rp, and Ip: ap Rp Ip 2.5 4.5 1.5 LEGEND Fpw Seismic Horizontal Design Force Cp Seismic Coefficient per NFPA Ss Short Period MCEr Spectral Response Acceleration Fa Site Coefficient. See Tables Below. SDS Short Period Spectral Acceleration ap Component Amplification Factor. Taken as 2.5 for Fire Sprinkler Applications Rp Component Response Modification Factor. Taken as 4.5 for Fire Sprinkler Applications Ip Component Importance Factor. Taken as 1.5 for Fire Sprinkler Applications Wp Component Operating Weight. Taken as the weight of the Fire Sprinkler System in the ZOI plus 15% z Height in the structure where the component attaches to the structure. Height is relative to the base of the structure and shall not be taken as less than 0 and shall not be larger than “H”. h Average roof height of the structure relative to the base EQUATIONS 6 SITE COEFFICIENT, FA PER ASCE/SEI 7-16 Ss ≤ 0.25 Ss = 0.5 Ss = 0.75 Ss = 1 Ss = 1.25 Ss ≥ 1.5 A 0.8 0.8 0.8 0.8 0.8 0.8 B 0.9 0.9 0.9 0.9 0.9 0.9 C 1.3 1.3 1.2 1.2 1.2 1.2 D 1.6 1.4 1.2 1.1 1 1 E 2.4 1.7 1.3 1.2 1.2 1.2 Use straight-line interpolation for intermediate values of Ss. SITE CLASSIFICATION PER ASCE/SEI 7-16 Site Class Ground Structure A Hard Rock B Rock C Very Dense Soil and Soft Rock D Stiff Soil E Soft Clay Soil 7 Appendix D - Bill of Materials Project Name HIBBARD ELEMENTARY Code Requirements NFPA 13-2019 Last Updated December 22, 2022 QUANTITY FIGURE NUMBER PRODUCT DESCRIPTION 1/2" LAG BOLT Fastener AF700 1/2" AF700 Universal Swivel Attachment AF700 - 1/2" AF001 2 1/2 NPS AF001 Q Brace Clamp AF001 - 2 1/2 NPS x 1 NPS